461 Interface Adaptor Card

INSTALLATION SHEET
461 Interface Adaptor Card
Description
The 461 Interface Adaptor Card is a mounting assembly that allows the connection of up to five DMP LX-Bus™
interface cards to the XR500, XR500N, XR500E or XR2500F Command Processor™ Panels. Use any combination of zone
expansion, printer, data network, and interface cards to maximize Command Processor panel capability.
Installing the 461 card
Follow these steps for trouble-free 461 Interface Adaptor Card installation:
1.Remove AC and battery power from the panel before installing the 461 card.
2.Align the 50 pin P6 connector on the 461 with the 50 pin J6 connector on the panel. Align the standoff
installed between slots A and B with the mounting hole in the panel.
3.Press the connectors together and the standoff into the panel mounting hole by applying even pressure to
both sides of the board.
4.Install up to five interface cards from left to right in the slots marked A to E.
461 Interface Adaptor Card
Slot A
Standoff
J6 Expansion Connector
A
B
D
C
E
J4
Tamper
J3
Phone Line
XR500 Series/
XR2500F Command
Processor™ Panel
J1
Ethernet
J21
J23
RS-232
R
L
X
J22
LX-Bus
Output 2
Output 1
J10
J2
Battery
Start
K6
Out2
Power LED
K7
AC
+B
-B
1
2
3
4
BELL GND RED YEL
5
6
7
8
GRN BLK
9
10
SMK GND
11
12
B
AC
J11
B
3
4
5
6
J8
PROG
Z1
GND
Z2
Z3
GND
Z4
Z5
GND
Z6
Z7
GND
Z8
13
14
15
16
17
18
19
20
21
22
23
24
Zone Expansion Connectors
Z9+ Z9- Z10+ Z10-
25
26
27
28
Up to 5 LX-Bus™ Interface Cards
Figure 1: 461 Interface Adaptor Card with Additional Interface Cards
J23 6-Pin Header
The panel supports RS-232, LX-Bus, and 1100 Series DMP Wireless operation. Only one operation can function at a
time. Install a jumper on one pair of J23 header pins to indicate how the panel is programmed to operate. Refer to
the table below when installing a jumper on J23. When a jumper is installed or moved on the 6-pin header, briefly
reset the panel using the J16 jumper to activate the selected operation.
J23 6-Pin Header
Letter
Operation
R
Standard RS-232
L
LX-Bus
X
1100 Series DMP Wireless
J21
J23
R
L
X
RS-232
J22
LX
LEDs
Xmit
Rec
Overcurrent
(OVC) LED
Figure 2: J23 6-Pin Header
The XR500 Series or XR2500F panels support up to 500 wireless bus zones and up to five LX-Bus circuits. Each
Interface card LX-Bus circuit provides 100 hardwire expansion zones. The maximum number of LX-Bus and wireless
zones available on a fully populated panel is 500.
LX-Bus, Wireless, and RS-232 Operation
LX-Bus Operation: Place a jumper on the two pins next to the letter “L” on the J23 6-Pin header. When using J22 as
an LX-Bus, connect a DMP Model 300 4-wire Harness to the J22 4-pin header labeled LX. This provides the first 100
LX-Bus zones numbered 500-599. No LX-Bus Interface Card is required. Refer to the following tables to identify zone
locations and numbers relative to J22 LX-Bus operation.
Note: Do NOT use shielded wire when using the J22 LX-Bus Header.
One Interface Card
AND
LX-Bus
2
Zone Numbers
600-699
One Interface Card
J22 LX-Bus
NOT Enabled
LX-Bus
1
Zone Numbers
500-599
(J23 set to
"X" or "R")
OR
461 Adaptor Card and
Multiple Interface Cards
LX-Bus Zone Numbers
1 (A)
500-599
2 (B)
600-699
3 (C)
700-799
4 (D)
800-899
5 (E)
900-999
Specifications
Current Draw
Compatibility
OR
461 Adaptor Card and
Multiple Interface Cards
LX-Bus Zone Numbers
2 (A)
600-699
3 (B)
700-799
4 (C)
800-899
5 (D)
900-999
7mA
XR500, XR500N, XR500E, and XR2500F
Command Processor™ panels.
Certifications
California State Fire Marshal (CSFM)
New York City (FDNY COA #6055)
UL 294 Access Control System Units
UL 365 Police Connected Burglar
UL 609 Local Burglar
UL 636 Holdup Alarm Units and Systems Accessory
800 - 641 - 4282
UL 1023
UL 1076
UL 1610
UL 1635
UL 985
UL 864
ULC 5545
ULC Subject-C1023
ULC/ORD-C1076
ULC S304
INTRUSION
•
Household Burglar
Proprietary Burglar
Central Station Burglar
Digital Burglar
Household Fire Warning
Fire Protective Signaling
Household Fire
Household Burglar
Proprietary Burglar
Central Station Burglar
FIRE
•
ACCESS
•
NETWORKS
www.dmp.com
2500 North Partnership Boulevard
Designed, Engineered and
Assembled in U.S.A.
S p r i n g fi e l d , M i s s o u r i 6 5 8 0 3 - 8 8 7 7
LT-0736 1.01 © 2016 Digital Monitoring Products, Inc.
16372
J22 LX-Bus Enabled
(Set J23 to "L")
LX-Bus Zone Numbers
1
500-599