SWR (Single Wall Round) – Spiral Duct

1
SWR (Single Wall Round) – Spiral Duct
METU-STREIMER spiral duct is built for the most stringent applications! Standard offerings can be made
to meet or exceed SMACNA standards for ±10” wg!*
METU-STREIMER spiral duct is made to SMACNA lock seam standard RL-1.
METU-STREIMER spiral is constructed from narrow 5.394” – 5.906” wide strip, creating a consistent lock
seam that is both pleasing to the eye and inherently rigid. The METU-STREIMER lock seam has a leakage rate
less than that allowed by leakage class “3”, and fully complies with seal class “A”, making it an ideal choice to
lower energy use by ensuring that conditioned air reaches its intended destination.
“METU-STREIMER certifies that the Spiral Duct shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on tests and procedures performed in
accordance with AMCA Publication 511, and comply with the requirements of the AMCA
Certified Ratings Program.” See data on last page.
METU-STREIMER spiral duct is available in the following material grades:
•
•
•
•
•
•
Galvanized steel, lock forming quality, conforming to ASTM standards
A653 and A924.
304L-2B & 316L-2B stainless steel, conforming to ASTM-A240.
Aluminum T-3003, conforming to ASTM-B209.
Paint Grip.
PolyVinyl coated.
Perforated.
* - Stock pipe will be built to +10” wg / -2” wg as listed in “SMACNA HVAC Duct Construction
Standards, Metal & Flexible 3rd Edition – 2005”, Table 3-10.
METU-STREIMER Catalog, SWR – Spiral Duct, January 2011 – Rev. 08a
2
Spiral Duct – Ordering Details
METU-STREIMER STANDARD SPIRAL DUCT SPECIFICATIONS *
Catalog #
D1002-001
D1002-002
D1002-003
D1002-004
D1002-005
D1002-006
D1002-007
D1002-008
D1002-009
D1002-010
D1002-011
D1002-012
D1002-013
D1002-014
D1002-015
D1002-016
D1002-017
D1002-018
D1002-019
D1002-020
D1002-021
D1002-022
D1002-023
D1002-024
D1002-025
D1002-026
D1002-027
D1002-028
D1002-029
D1002-030
D1002-031
D1002-032
D1002-033
D1002-034
D1002-035
D1002-036
D1002-037
D1002-038
Description
SWR, Spiral Duct, 3" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 4" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 5" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 6" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 7" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 8" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 9" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 10" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 11" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 12" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 13" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 14" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 15" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 16" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 17" Ø x 24GA Galv, 120" Long
SWR, Spiral Duct, 18" Ø x 24GA Galv, 120" Long
SWR, Spiral Duct, 19" Ø x 24GA Galv, 120" Long
SWR, Spiral Duct, 20" Ø x 24GA Galv, 120" Long
SWR, Spiral Duct, 22" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 24" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 26" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 28" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 30" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 32" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 34" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 36" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 38" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 40" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 42" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 44" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 46" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 48" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 50" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 52" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 54" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 56" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 58" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 60" Ø x 20GA Galv, 120" Long
(D)
(L)
Units Diameter (in.)† Length (ft.)§
Each
3
10
Each
4
10
Each
5
10
Each
6
10
Each
7
10
Each
8
10
Each
9
10
Each
10
10
Each
11
10
Each
12
10
Each
13
10
Each
14
10
Each
15
10
Each
16
10
Each
17
10
Each
18
10
Each
19
10
Each
20
10
Each
22
10
Each
24
10
Each
26
10
Each
28
10
Each
30
10
Each
32
10
Each
34
10
Each
36
10
Each
38
10
Each
40
10
Each
42
10
Each
44
10
Each
46
10
Each
48
10
Each
50
10
Each
52
10
Each
54
10
Each
56
10
Each
58
10
Each
60
10
(G) Reinforcement Class
Gauge
-2" wg
26
NR
26
NR
26
NR
26
NR
26
NR
26
NR
26
NR
26
NR
26
NR
26
NR
26
NR
26
NR
26
NR
26
NR
24
NR
24
NR
24
NR
24
NR
22
NR
22
NR
22 **
A
22 **
A
22 **
A
22 **
A
22 **
A
22 **
A
22 **
A
22 **
C
22 **
C
20 **
C
20 **
C
20 **
C
20 **
C
20 **
C
20 **
C
20 **
C
20 **
C
20 **
C
* - Standard Duct is made from G90 galvanized steel.
† - Diameter = Outside Dimension
§ - 1' to 20' lengths available for an additional charge.
\\ - Gauge listed is for +10" / -2" wg per SMACNA HVAC Duct Construction Standards, Metal & Flexible 3rd Edition – 2005”, Table 3-10.
** - Reinforcement required. Duct > 24" Ø will be supplied with MF (METU FLANGE) flanged ends for reinforcement.
Note: Custom Lengths, gauges, & materials available upon request.
For pricing and ordering information, contact your METU-STREIMER sales support team.
METU-STREIMER Catalog, SWR – Spiral Duct, January 2011 – Rev. 08a
3
Spiral Duct Tolerances
METU-STREIMER STANDARD SPIRAL DUCT TOLERANCE
Description
SWR, Spiral Duct, 3" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 4" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 5" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 6" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 7" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 8" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 9" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 10" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 11" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 12" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 13" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 14" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 15" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 16" Ø x 26GA Galv, 120" Long
SWR, Spiral Duct, 17" Ø x 24GA Galv, 120" Long
SWR, Spiral Duct, 18" Ø x 24GA Galv, 120" Long
SWR, Spiral Duct, 19" Ø x 24GA Galv, 120" Long
SWR, Spiral Duct, 20" Ø x 24GA Galv, 120" Long
SWR, Spiral Duct, 22" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 24" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 26" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 28" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 30" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 32" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 34" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 36" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 38" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 40" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 42" Ø x 22GA Galv, 120" Long
SWR, Spiral Duct, 44" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 46" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 48" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 50" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 52" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 54" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 56" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 58" Ø x 20GA Galv, 120" Long
SWR, Spiral Duct, 60" Ø x 20GA Galv, 120" Long
(D)
Diameter (in.)
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
Length
Weight (Lbs
/ Ft) ¶
Ø Tolerance ‡ Tolerance (in.)
2.967 ± 0.03
± 1/4
0.8
3.967 ± 0.03
± 1/4
1.1
4.967 ± 0.03
± 1/4
1.4
5.967 ± 0.03
± 1/4
1.6
6.967 ± 0.03
± 1/4
1.9
7.967 ± 0.03
± 1/4
2.2
8.967 ± 0.03
± 1/4
2.5
9.967 ± 0.03
± 1/4
2.7
10.967 ± 0.03
± 1/4
3.0
11.967 ± 0.03
± 1/4
3.3
12.967 ± 0.03
± 1/4
3.6
13.967 ± 0.03
± 1/4
3.8
14.967 ± 0.03
± 1/4
4.1
15.967 ± 0.03
± 1/4
4.4
16.955 ± 0.03
± 1/2
5.9
17.955 ± 0.03
± 1/2
6.3
18.955 ± 0.03
± 1/2
6.6
19.955 ± 0.03
± 1/2
7.0
21.95 ± 0.04
± 1/2
9.3
23.95 ± 0.04
± 1/2
10.2
25.95 ± 0.04
± 1/2
11.0
27.938 ± 0.04
± 1/2
11.8
29.938 ± 0.04
± 1/2
12.7
31.938 ± 0.04
± 1/2
13.5
33.916 ± 0.04
± 3/4
14.4
35.916 ± 0.04
± 3/4
15.2
37.916 ± 0.04
± 3/4
16.1
39.916 ± 0.04
± 3/4
16.9
41.916 ± 0.04
± 3/4
17.8
43.898 ± 0.05
±1
22.4
45.898 ± 0.05
±1
23.4
47.898 ± 0.05
±1
24.4
49.898 ± 0.05
±1
25.4
51.898 ± 0.05
±1
26.4
53.898 ± 0.05
±1
27.5
55.898 ± 0.05
±1
28.5
57.898 ± 0.05
±1
29.5
59.898 ± 0.05
±1
30.5
‡ - Inner pipe dimensions. Tolerances may vary if non-standard material is selected.
¶ - Calculated weight, based on standard gauge G90 galv.
** - Reinforcement required. Duct > 24" Ø will be supplied with MF (METU FLANGE) flanged ends for reinforcement.
METU-STREIMER Catalog, SWR – Spiral Duct, January 2011 – Rev. 08a
(G)
Gauge
26
26
26
26
26
26
26
26
26
26
26
26
26
26
24
24
24
24
22
22
22 **
22 **
22 **
22 **
22 **
22 **
22 **
22 **
22 **
20 **
20 **
20 **
20 **
20 **
20 **
20 **
20 **
20 **
4
AMCA Licensed Ratings and Leakage Test Results
Duct Gauge
26
24
22
20
18
16
14
Test Pressure
Inch/wg
15
15
15
15
15
15
15
* Leakage Rate at
test pressure
0.003
0.010
0.022
0.022
0.014
0.006
0.004
* - Leakage rate measured as CFM per 100 ft2 of duct surface area. Listed measurements have
been converted from CFM to SCFM.
Standard cubic feet per minute (SCFM) is the volumetric flow rate of a gas corrected to
standardized conditions of temperature, pressure and relative humidity.
Tests are based on 24"Ø x 10' long spiral duct samples.
Maximum allowable leakage of a duct system per SMACNA Class 3 at 10 wg is 13.4 SCFM.
Air leakage is based on operation between 50° F to 104° F.
IMPORTANT!
METU-STREIMER spiral duct can be used with our revolutionary MF Flange connecting system!
METU-STREIMER Catalog, SWR – Spiral Duct, January 2011 – Rev. 08a