Information Guide Details of how OIML R 46 differs from NMI M 6-1 General Current Value Definitions New current definitions (see Table 1). Manufacturers can choose values provided they meet the minimum specified ratios (see Table 1 in OIML R 46-1). Table 1. Current value definitions. Standard Decreasing current ↓ OIML R 46 Maximum Current (Imax) [No name], but typically 10 Itr Transitional current (Itr) Minimum current (Imin) Starting current (Ist) NMI M6 Maximum Current (Imax) Basic current (Ib) or nominal current (In) [No name] 0.1 Ib, or 0.05 In (see NMI M 6-1, Tables 1 to 3) [No name] Value 0.05 Ib, or 0.01 In via NMI M 6-1, Tables 1 to 3. [No name] Corresponds to values in NMI M 6-1, Table 7. Temperature Ranges Manufacturer must select from a list temperature values. Note: Australia would adopt a minimum temperature range suitable for Australian conditions. Humidity Class Manufacturer must specify humidity classes to match the conditions, with associated testing depending on the class. Accuracy Class designations Different class designations using letters A, B, C & D are used where A is the least accurate and D is the most accurate (see Table 2). Class A is a lower accuracy class than class 1.5 of NMI M 6-1. OIML R 46 recommends class B or higher where consumption exceeds 5000 kWh per year. Table 2. Accuracy class designations. OIML R 46 Accuracy Class Minimum base MPE (%) NMI M 6-1 class correspondence A ±2.0 n/a B ±1.0 1 C ±0.5 0.5 D ±0.2 0.2 Interval and Multi-tariff Meters The meter must be able to measure and store data relevant for billing, with minimum storage capabilities determined by the national authority. Requirements for interval data and multi-tariff data to store sum correctly. Note: the internal clock requirements are interpreted to be the same as NMI M 6-1. Meter Markings A recommended list of markings is specified, with mandatory markings to be determined. Protection/Sealing Legally relevant software must be identified by software version or similar. Zeroing the total accumulation register is considered to be a metrological change. Protection and sealing requirement apply. Manufacturers may declare part(s) of the meter legally relevant – to be validated at approval. There are requirements for storage and transmission outside of the meter. This may have applications for Australia, but historically NMI has considered back office software and communications as outside the scope of approval. Requirements for software updates. Note: OIML R 46 provides for national authorities to establish levels of authorized access. NMI is proposing to develop a system of authorised access to address issues including battery replacement, and register zeroing without the need for verification. Indicating Device / Display Characters must be at least 4 mm high. Able to display all data relevant for billing. Automatic sequencing displays must display each register for at least 5 s. For multi-tariff meters, active tariff must be indicated, and each tariff register must be able to be read locally. Energy storage and display for 4000 h (at power P = UnomImaxn) applies to all billing relevant registers including positive and negative flow and tariff registers. For electronic registers, minimum retention time is 1 year for a disconnected meter. There shall also be a display test, all segments on and off to check all segments are working. Testability Manufacturer shall declare the necessary number of pulse to ensure a standard deviation of the measurement less than 0.1 base MPE at Imax, Itr and Imin. Requirements for radiated signal wavelength and strength. Pattern Approval (Type Approval) Documentation NMI provides information on documentation required for approval in documents and webpages separate from NMI M 6-1. The differences listed below are not differences with NMI M 6-1, but with NMI’s broad requirements. Limits of Error Class A Class A does not correspond to a class in NMI M 6-1, so the limits of error are new. The rest of this section only discusses differences for classes B, C and D. Base MPEs OIML R 46 uses the term “base maximum permissible errors” for the error limits for various current and power factor values, but with the meter otherwise operated at reference conditions. OIML R 46 allows greater flexibility in the selection of the current parameters. For example, for a class B (class 1) meter, with a maximum current of 100 A, the meter must be accurate to 1% (at unity pf) down to at least 2 A. The manufacturer may select a lower transitional current. In NMI M 6-1, the meter must be accurate to 1% (at unity power factor) down to 1 A. Aside from current parameterisation differences, there are the following MPE differences: For class B (class 1), the error limit is 1.8% at lower currents (power factor 0.5 inductive/0.8 capacitive) as opposed to 1.5%. Below Imin and down to Ist a formula is provided for the base MPE so that the MPE smoothly increases at lower currents. NMI M 6-1 is silent on MPEs below the specified test current range. In practice, it is worth noting that the actual test points specified in OIML R 46 do not extend below Imin except for the starting current test at Ist. Allowed Effects of Influence Quantities and Disturbances A list of influence and disturbance tests is list in Table 3 below. Note it does not list all criteria (allowed effects) and test procedures, but instead provides a summary of the key differences from NMI M 6-1. Table 3. Influence and disturbance tests. OIML R 46 Clause(s) Influence Quantity Tests Temperature 3.3.5:Table 3 coefficient / 6.3.2 Temperature Dependence Self-heating 3.3.5:Table 4 6.2.2 OIML R46 Test Load balance Voltage variation Frequency variation Harmonics in voltage and current circuit 3.3.5:Table 4 6.3.3 3.3.5:Table 4 6.3.4 3.3.5:Table 4 6.3.5 3.3.5:Table 4 6.3.6 NMI M 6-1 Test NMI M 6-1 Clause(s) Difference? Difference in allowed effects Difference in test procedure Temperature coefficient/Mean Temperature coefficient — 5.3:Table 6 A.2.3 Similar The limits of error are doubled for class D below -10 °C. Temperature intervals must be between 15 K and 23 K. Must include the reference temperature — New — Maximum Permissible Error Voltage variation 4.8:Table 3 Similar 5.1:Table 4 A.2.12 5.1:Table 4 A.2.13 5.1:Table 4 A.2.21 Same Error shift limits as opposed to MPEs. Same Same Same Different Error shift limits are tighter. — (This new test has the meter operating continuously at maximum current.) Same. (Clearer on mandatory test points.) Same. (Clearer on mandatory test points.) Same. (Clearer on mandatory test points.) Includes up to the 13th harmonic. 5.1:Table 4 Similar Error shift limits provided for classes A, B and C. Frequency variation Harmonic components in the current and voltage circuits Tilt at 3° in any direction from the vertical Tilt 3.3.5:Table 4 6.3.7 Severe voltage variations 3.3.5:Table 4 6.3.8 Voltage variation 5.1:Table 4 A.2.12 Similar Error shift limits are tighter. One or two phases interrupted Sub-harmonics in the AC current circuit 3.3.5:Table 4 6.3.9 Voltage unbalance 5.1:Table 4 Same Same Same. (Test remains only applicable for electromechanical meters and other meters influenced by working position.) Same test, but with mandatory test points and including either side of any distinct shut-down voltage. Same 3.3.5:Table 4 6.3.10 Sub-harmonics in the AC circuit 5.1:Table 4 A.2.17 Same Same Same. Test point is 10 Itr instead of 0.5 Ib or 0.5 In. OIML R46 Test Harmonics in the AC current circuit Reversed phase sequence Continuous (DC) magnetic induction of external origin Magnetic field (AC, power frequency) of external origin Radiated, RF, electromagnetic fields Conducted disturbances , induced by radio frequency fields DC in the AC current circuit OIML R 46 Clause(s) 3.3.5:Table 4 6.3.11 3.3.5:Table 4 6.3.12 3.3.5:Table 4 6.3.13 3.3.5:Table 4 6.3.14 NMI M 6-1 Test Odd harmonics in the AC current circuit Reversed phase sequence Continuous magnetic induction of external origin Magnetic induction of external origin 0.5 mT NMI M 6-1 Clause(s) 5.1:Table 4 A.2.18 Same Difference in allowed effects Same Same. Test point is 10 Itr instead of 0.5 Ib or 0.5 In. 5.1:Table 4 Same Same Same. Test point is 10 Itr instead of 0.1 Ib or 0.1 In. 5.1:Table 4 Different Error shift limits are tighter. Permanent magnet as opposed to electromagnet with different specifications. 5.1:Table 4 Similar Error shift limits are tighter. Similar test with new reference to IEC 61000-4-8. The limits of error are wider for class C (class 0.5) The limits of error are wider for class C (class 0.5) Frequency range extends up to 6000 MHz as opposed to 2400 MHz. Limits of error introduced for class C and D. — Same Difference? 3.3.5:Table 4 6.3.15.1 Electromagnetic RF fields 5.1:Table 4 A.2.9 Different 3.3.5:Table 4 6.3.15.2 Conducted RF Fields 5.1:Table 4 A.2.10 Similar 3.3.5:Table 4 6.3.16 DC component in the AC circuit 5.1:Table 4 Similar Difference in test procedure Same High-order 3.3.5:Table 4 — — New — harmonics 6.3.16 (New test: 15fnom to 40fnom) Disturbance Tests The allowed effects generally include “no significant fault” where changes in the registers and pulses of the test output are less that the critical change value. Magnetic field 3.3.6.2:Table 5 — — New — — (AC, power 6.4.2 (This new test is at 1000 A/m, 3 s, and references frequency) of IEC 61000-4-8) external origin Electrostatic 3.3.6.2:Table 5 Electrostatic A.2.11 Same Same Same discharges 6.4.3 discharge test OIML R46 Test Fast transients Voltage dips Voltage interruptions OIML R 46 Clause(s) 3.3.6.2:Table 5 6.4.4 3.3.6.2:Table 5 6.4.5 3.3.6.2:Table 5 6.4.5 NMI M 6-1 Clause(s) 5.1:Table 4 A.2.15 A.2.14 Similar Difference in allowed effects Same Different Same A.2.14 Different Same Radiated Electromagnetic (EM) Radiofrequency (RF) Fields — A.2.9 Different No significant fault (critical change value) instead of “not perturbed” — New — — (New test) 3.3.6.2:Table 5 6.4.8 — — New — — (New test) Same, but only with tests A (30 Imax for directconnected) and B (20 Imax for transformeroperated). In particular, the 7000 A test is not present in OIML R 46. Same procedure, but with different parameters, typically 10 kV and 10 J at standard rated system voltage of 230/240 V. NMI M 6-1 Test Fast transient bursts Voltage Dips and interruptions Voltage Dips and interruptions Difference? Radiated, RF, electromagnetic fields 3.3.6.2:Table 5 6.4.6 Surges on AC mains power lines Damped oscillatory waves immunity test Short-time overcurrent 3.3.6.2:Table 5 6.4.7 3.3.6.2:Table 5 6.4.9 Short-time Overcurrents 5.1:Table 4 A.2.16 Similar Same Impulse voltage 3.3.6.2:Table 5 6.4.10 Impulse voltage Test A.2.19 Similar Earth fault 3.3.6.2:Table 5 6.4.11 3.3.6.2:Table 5 6.4.12 3.3.6.2:Table 5 6.4.13.1 — — New No significant fault (critical change value) instead of error shift not greater than uncertainty of measurement. — Operation of accessories Vibration (Sinusoidal) Test 5.1:Table 4 Similar A.2.7 Different Operation of ancillary devices Vibration Error shift limits are different Error shift limits after the test Difference in test procedure Same, but with references to IEC 61000-4-1 and IEC 61000-4 -4. Three different voltage dip tests. References to IEC 61000-4-11, IEC 61000-6-1 and IEC 61000-6-2. One different voltage interruption test. References to IEC 61000-4-11, IEC 61000-6-1 and IEC 61000-6-2. Frequency range extends up to 6000 MHz as opposed to 2400 MHz. — (New test) Same test, but test points are Itr and Imax instead of other values such as 0.05 Ib. The vibration test references IEC 60068-2-47 and IEC 60068-2-64. OIML R46 Test Shock Protection against solar radiation OIML R 46 Clause(s) 3.3.6.2:Table 5 6.4.13.2 3.3.6.2:Table 5 6.4.14 NMI M 6-1 Test Shock / Mechanical shock Test Solar Radiation Test NMI M 6-1 Clause(s) 5.1:Table 4 A.2.8 5.5 A.2.5 Difference? Similar Different Difference in allowed effects Error shift limits after the test Same but with specific mention of metrological properties and sealing added. Same Protection against ingress of dust Dry Heat 3.3.6.2:Table 5 6.4.15 Dust Test 5.6 A.2.6 Same 3.3.6.2:Table 5 6.4.16.1 Dry Heat A.2.1 Similar Cold 3.3.6.2:Table 5 6.4.16.2 Cold A.2.2 Similar Damp Heat 3.3.6.2:Table 5 6.4.16.3 6.4.16.4 Damp Heat Cyclic Test A.2.4 Different Water 3.3.6.2:Table 5 6.4.16.5 6.4.17 — — New Error shift limits after the test instead of MPEs. No high temperature accuracy testing. Error shift limits after the test instead of MPEs. No low temperature accuracy testing. Error shift limits after the test instead of MPEs. No significant fault during the test. No insulation testing afterwards. — — — New — Durability Difference in test procedure Same as per mechanical shock test in NMI M 6 (A.2.8). A different 66 days test in a cycling rig with reference to ISO 4892-3. Same Same test but conducted at one standard step higher than the upper temperature limit specified for the meter. Same test but conducted at one standard step lower than the lower temperature limit specified for the meter. There are two separate Damp Heat tests selected by the humidity class of the meter: Steady State (IEC 60068-2-78, IEC 60068-3-4) for H1 meters, and cyclic IEC 60068-2-30, IEC 60068-3-4) for H2 and H3 meters. — (New test) — (New test)
© Copyright 2026 Paperzz