APPLICATION DATA PSS-00003A Specification for ModBus Communication Jan 2003 Supersedes: N/A Applicability: Turbocor TT300 compressor References: ModBus Application Specification V1.1 by ModBus.org. Introduction: This application data sheet defines the registers and functions implemented to monitor/control a Turbocor TT300 compressor. Implemented Functions: 03 (0x03) Read Holding Registers This function code is used to read the contents of a contiguous block of holding registers in a remote device. The register data in the response message are packed as two bytes per register, with the binary contents right justified within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits. 06 (0x06) Write Single Register This function code is used to write a single holding register in a remote device. The Request PDU specifies the address of the register to be written. Turbocor Inc. PSS-00003A REV. 1 1 OF 5 TT-300 Register Definition Register Address TT-300 Device TT-300 Parameter Access Translation Rule 40020 SoftStart 0: Status R Bit 0: NOK->0 / OK->1 1: SCRs R Bit 1: OFF->0 / ON->1 40021 3: Line 1-2 R 1:1 40022 4: Line 2-3 R 1:1 40023 5: Line 3-1 R 1:1 40024 6: DC Bus R 1:1 40025 8: UpTrip R 1:1 40026 9: Dn Trip R 1:1 40027 14: Version R Digits without dots. 40028 15: VoltDrop R 1:1 40029 16: RxxVolts R 1:1 0: Alarms R/W Writing a value different than 0 to this register will clear all error messages. Bit 0 I 0/1: Inverter Temperature Bit 1 A 0/1: Motor Current Bit 2 B 0/1: Bearing Current Bit 3 C 0/1: Shaft Cavity Temperature Bit 4 D 0/1: Discharge Pressure Bit 5 L 0/1: Leaving Chilled Water Temp Bit 6 P 0/1: Power Input Bit 7 S 0/1:Suction Pressure Bit 8 T 0/1: Discharge Pressure Bit 9 W 0/1: Winding Temperature Bit 10 X 0/1: External Interlock Bit 11 Y 0/1: Waiting for SoftStart Bit 12 Z 0/1: Motor Bearing Controller Bit 13 + 0/1: Watchdog Timer Bit 14 - 0/1: Compressor Rotating Bit 15 Fail->1 / OK->0 40030 Control 21: Interlok Turbocor Inc. PSS-00003A REV. 1 2 OF 5 Register Address TT-300 Device TT-300 Parameter Access Translation Rule 40031 1: Demand R/W 1:10 40032 1: Demand mode R/W M: 1 A: 2 N: 3 C: 4 40033 2: IGV R 1:10 40034 3: Suction R 1:10 Signed Value 40035 4: Interm P R 1:10 40036 5: Dischg P R 1:10 40037 6: Suction T R 1:10 Signed Value 40038 7: Interm T R 1:10 40039 8: Dischg T R 1:10 40040 9: Cavity T R 1:10 40041 10: Enter T R 1:10 40042 11: Leave T R 1:10 40043 19: Surge R 1:1 40044 20: Choke R 1:1 40045 22: Version R Digits without dots. 40046 23: Serial R 1:1 40047 24: Units R/W 0 -> Imperial / 1 -> Metric 40048 25: Suct SP R 1:1 Signed Value 40049 26: SPAlmDel R 1:1 0: MLL/SH State R 1:10 0/8: MLL/SH R/W 40050 EX Valve 40051 ALL/SH Mode Main Auxiliary Turbocor Inc. PSS-00003A REV. 1 Bits 0-3 %L -> 1 Bits 0-3 KS -> 2 Bits 0-3 FS -> 2 Bits 0-3 KM -> 3 Bits 0-3 FM -> 3 Bits 4-7 %L -> 1 Bits 4-7 KS -> 2 3 OF 5 Register Address TT-300 Device TT-300 Parameter Access Translation Rule Bits 4-7 FK -> 2 Bits 4-7 KM -> 3 Bits 4-7 FM -> 3 Writing 0 mode leaves the register unchanged. This allows the change of a single valve mode. E.g. if the value 0x11 is written both valves are set to mode A. If 0x10 is written, only he auxiliary mode is altered, leaving the main mode at its current value. 40052 1: MEXValve R 1:10 40053 2: MEXStart R 1:1 40054 3: MEXDelay R 1:1 40055 4: MEXSt Pt R 1:1 40056 5: MEX Int R 1:1 40057 6: MEX Prop R 1:1 40058 7: MEX Der R 1:1 40059 8: ALL/SH State R 1:10 40060 9: AEXValve R 1:10 40061 10: AEXStart R 1:1 40062 11: AEXDelay R 1:1 40063 12: AEXSt Pt R 1:1 40064 13: AEX Int R 1:1 40065 14: AEX Prop R 1:1 40066 15: AEX Der R 1:1 40067 16: Cooling R Full->2 / Half->1 / Off->0 0: Floating R OFF->0 / ON->1 40069 4: Ax Force R 1:100 40070 5: FX Force R 1:100 40071 6: FY Force R 1:100 40072 7: RX Force R 1:100 40073 8: RY Force R 1:100 40074 11: Version R Digits without dots. 40075 12: Fault # R Hexnumber 40076 13: Alarm # R Hexnumber 0: Act RPM R 1:1 40068 40077 Bearing Motor Turbocor Inc. PSS-00003A REV. 1 4 OF 5 Register Address TT-300 Device TT-300 Parameter Access Translation Rule 40078 1: Des RPM R 1:1 40079 2: MotorAmp R 1:10 40080 3: Pwr (kW) R 1:10 40081 4: Inv Temp R 1:10 always displayed in °C. 40082 8: Fault # R Hexnumber 40083 9: Alarm # R Hexnumber Turbocor Inc. PSS-00003A REV. 1 5 OF 5
© Copyright 2026 Paperzz