Power System Testing and Commissioning EET 414/3 Laboratory Module EXPERIMENT 3 RELAY TESTING AND CALIBRATION 1. Objective 1. To familiarized with over-current and earth fault relay testing 2. To find the inverse time/ current characteristic curves for IDMT Relay. 2. Introductions The induction relay is used in the great majority of time-graded over-current protection schemes. It construction may vary but its characteristic and method of setting are common to all types. The basic requirement is that firstly, it has to have an inverse time/current characteristic ; that is it has a long operating time at low multiples of setting current and a shorter operating time at high multiples of setting current. Secondly, it must have the means of adjusting the current setting and the time of operation at a given multiple of setting. A protective relay which operates when the load current exceed a preset value, is called an over current relay. The value of the preset current above which the relay operates is known as its pick-up value. An Over Current Relay (OCR) is used in substation for the power equipment protection against short circuit of phase to phase and ground fault. Time current characteristics A wide variety of time current characteristics is available for over current relays. The name is assigned to an over current relay indicates its time-current characteristic as described below. i). Definite-time Over current Relay A definite-time OCR operates after a predetermined time when the current exceeds its pick-up value. Curve (a) of Figure 5.1. shows the time-current characteristics for this type of relay. The operating time is constant, irrespective of the magnitude of the current above pick-up value. UNIVERSITI MALAYSIA PERLIS – Exp3 1 Power System Testing and Commissioning EET 414/3 Laboratory Module ii). Instantaneous Over current Relay An instantaneous relay operates in a definite time when the current exceeds its pick up value. The operating time is constant, irrespective of the magnitude of the currents and there is no intentional time delay. It operates in 0.1s or less. Sometimes the term like high set or high speed is used for very fast relays having operating times les than 0.1s. iii). Inverse-time Over current Relay An inverse-time OCR operates when the current exceeds its pick up value. The operating time depends on the magnitude of operating current. The operating time decrease as the current increases. Curve (b) of Figure 5.1. shows the inverse time current characteristic of this type relay. iv). Inverse Definite Minimum Time Over current (IDMT) Relay. This type of relay gives an inverse-time current characteristic at lower values of the fault current and definite-time characteristic at higher values of the fault current. Generally, an inverse time characteristic is obtained if the value of the plug setting multiplier between 10 and 20, the characteristic tend to become a straight line, i.e. toward the definite time characteristic such as Figure 5.2. These relays are widely used for the protection of lines. v). Very Inverse-time Over current Relay A very inverse-time over current relay gives more inverse characteristic than previous ones. The very inverse characteristic gives better selectivity than the IDMT characteristic. Hence, it can be used where an IDMT extremely inverse relays are employed. I 3.5 relay fails in selectivity, Its time-current characteristic according to t = K. This relay is very suitable for the protection against overheating for machines, power transformers, grounding transformers, and expensive cables. UNIVERSITI MALAYSIA PERLIS – Exp3 2 Power System Testing and Commissioning EET 414/3 Laboratory Module Operating time INVERSE TIME CHARACTERISTIC DEFINITE TIME CHARACTERISTIC Pick Up Value Actuating Quantity Figure 5.1. Characteristic of Definite and Inverse time OCR Figure 5.2. Moderately, Very and Extremely inverse-time characteristics The time-current characteristic for relay that respective of the magnitude of the current in generally is given by t = K / (I n –1). The approximate expression is t = K / I n. For definite time characteristic, the value of n is equal to 0. According to the British Standard, the following are the important characteristic of over-current relays, UNIVERSITI MALAYSIA PERLIS – Exp3 3 Power System Testing and Commissioning EET 414/3 i). I.D.M.T t= 0.14 I 1 ii). Very inverse t = 13.5 I 1 iii). Extremely inverse t = 80 I 1 Laboratory Module 0.02 2 The time-current curves for induction relays can be approximated by the following equation A t = TD P B M 1 where, t : trip time (sec) M : multiple of pickup current (M>1) TD : time dial setting A,B,p : curve shaping constant such as in Table 5. Table 5. IEEE Standardized Relay Curve Equation Constant _____________________________________________________ A B C _______________ ______________________________________ Moderately inverse 0.0515 0.114 0.02 Very inverse 19.61 0.491 2.0 Extremely inverse 28.2 0.122 2.0 _____________________________________________________ 3. Equipment and Part 1. IDMT Relay 203 (Overcurrent) – 1 unit 2. IDMT Relay 202 (Earthfault) – 1 unit 3. SVERKER 760 Relay Test Unit – 1 unit 4. Digital Multimeter 10/20A – 1 unit 5. High Resistance Cable UNIVERSITI MALAYSIA PERLIS – Exp3 4 Power System Testing and Commissioning EET 414/3 Laboratory Module IDMT 203 Overcurrent Relay : 4. Procedure A) Overcurrent Relay characteristic test 1. Calculate the PSM at 80% of full load current. Take it as the 100% PSM setting of the relay. Record the value in your test certificate. 2. Connect the instrument as shown in Fig. 5.1(a) with the SVERKER 760 Relay Test Unit in the OFF position. (Always turn SVERKER 760 OFF before connecting) 4. For the connection to Overcurrent Relay (IDMT 203), make sure the connection follow the diagram as at the side of the Overcurrent Relay. (Refer the connection diagram). Ensure to connect the current injection set to correct terminal phase at the relay UNIVERSITI MALAYSIA PERLIS – Exp3 5 Power System Testing and Commissioning EET 414/3 Laboratory Module 5. Manually increase the current by turning the knob at 130% of PMS setting of the relay. You will observed the relay trips if the current injected is over 100% setting. 6. Press HOLD button to stop any current injection. Reset the secondary injection set and the relay being tested. 7. Now, activate the timer release. The current will now be injected automatically at 130% of PSM and will cause the relay to trip according to its characteristics. 8. Record the time displayed at the secondary injection set. Repeat the procedures at 200% and 300% of PSM setting. 9. Repeat the procedures for all other phases. 10. Record your reading in the Test certificate provided to you. 11. Plot a graph of time vs magnitude of current. B) Overcurrent Relay Stability Test 1. The connection and diagram for this testing are the same as procedure A 2. Set the PSM of the relay to 2. 3. Slowly, increase the current until the relay is trip. 4. Record the value of injected current displayed at the secondary injection set. 5. Repeat the procedures for every PSM setting. C) Earth Fault Relay characteristic Test. 1. For this experiment, use IDMT202 type of relay. 2. For earth fault setting, calculate 10% of from 5A. This will be 100% of PSM of the relay. 3. Connect the relay to the secondary injection test set as shown in Figure 2. Ensure Test set is OFF before making the connection. 4. Increase the current injected to the relay at 130%, 200% and 300% from the PSM. 5. Record the time for relay to trip as procedure of overcurrent relay. 6. Plot a graph of time vs current. UNIVERSITI MALAYSIA PERLIS – Exp3 6 Power System Testing and Commissioning EET 414/3 Laboratory Module D) Earth Fault Stability Test 1) Without disconnecting the wiring connection, conduct an experiment as per procedure B of over-current relay stability test. 2) Record your data in the test certificate. QUESTIONS 1) What can be concluded from the results obtained? 2) What is the time for the relay to trip if the fault current is 1500 Ampere? UNIVERSITI MALAYSIA PERLIS – Exp3 7 Power System Testing and Commissioning EET 414/3 Laboratory Module ADDITIONAL QUESTION 1. Explain how would you use an overcurrent characteristic to determine its time of operation, given the following information. (Draw the curves) Relay Specification : 1A, 3sec Plug Setting : 125% Time Multiplier Setting : 6 Current Transformer Ratio : 400/1 A Fault Current : 4000A DISCUSSION/CONCLUSION ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ________________________________________________________________ UNIVERSITI MALAYSIA PERLIS – Exp3 8 Power System Testing and Commissioning EET 414/3 UNIVERSITI MALAYSIA PERLIS – Exp3 Laboratory Module 9 Power System Testing and Commissioning EET 414/3 Laboratory Module KOLEJ UNIVERSITI KEJURUTERAAN UTARA MALAYSIA RELAY TEST CERTIFICATE Job Ref NO . Type of installation Client Cert no. Circuit Consultant/Contractor CB Detail Make Volt Rating Serial No. O/C Relay Detail Make/Type Serial No. CT Detail Ratio Class Burden Make Relay Setting P.M.S [O/C] T.M.S P.M.S [E/F] T.M.S E/F Relay Detail Make/Type Serial No. Tripping Time Test Test Setting Creep Amps. Is Injected (A) O/C O/C = T.M = O/C [R] Time (s) E/F O/C [Y] Time (s) E/F = T.M = O/C [B} Time (s) E/F Time (s) Reset Time Pickup Current Test Test Setting O/C = Test Setting (Amps) O/C E/F Trip Voltage 220 T.M = O/C [R] Shunt Trip Tested O/C [Y] E/F = Operating Value (Amps) O/C [ B] T.M = E/F Seal Remarks: @shukur modular_kukum UNIVERSITI MALAYSIA PERLIS – Exp3 10
© Copyright 2026 Paperzz