DGU Parameters

Parameterlist
Digital Governor System
DGS 8800 & DGS 8800e
for MAN B&W MC engines
AO-20064-A
1
Parameterlist
Document history
Rev. A
AOE-015794
The information contained in this document is subject to change without prior notice.
Kongsberg Maritime AS shall not be liable for errors contained herein or for incidental
or consequential damages in connection with the furnishing, performance, or use of this
document.
© 2003 Kongsberg Maritime AS. All rights reserved. No part of this work covered by
the copyright hereon may be reproduced or otherwise copied without prior permission
from Kongsberg Maritime AS.
Kongsberg Maritime AS
Bekkajordet
P.O.Box 1009
N-3194 Horten,
Norway
Telephone: +47 33 03 20 00
Telefax: +47 85 02 80 28
www.kongsberg.com
TABLE OF CONTENTS
Section
Page
DISPLAY OF OPCODES. .................................................................................................................................. 5
ADJUSTING OF OPCODES: .............................................................................................................................. 5
HARDWARE & SOFTWARE CONFIGURATION .................................................................................................. 6
PLANT INFORMATION ............................................................................ ERROR! BOOKMARK NOT DEFINED.
REGULATOR: USER PARAMETERS; ................................................................................................ 7
REGULATOR - OPCODE 0 - USER 1 PARAMETERS ........................................................................................... 7
REGULATOR - OPCODE 0 - USER 2 PARAMETERS .......................................................................................... 7
AO-20064-A
2
Parameterlist
REGULATOR: BASIC PARAMETERS; .............................................................................................. 8
REGULATOR - OPCODE 1 BASIC PARAMETERS .......................................................................................... 8
ENGINE DATA ................................................................................................................................................ 8
REGULATOR - OPCODE 1 BASIC PARAMETERS .......................................................................................... 9
FUEL START SETPOINT .................................................................................................................................... 9
SPEED START SETPOINT .................................................................................................................................. 9
SYSTEM SETTINGS ........................................................................................................................................... 9
ELECTRIC ACTUATOR ..................................................................................................................................... 9
REGULATOR - OPCODE 2 (I/O ADJUSTMENTS) BASIC PARAMETERS .......................................................... 10
REGULATOR: EXPERT PARAMETERS; ........................................................................................ 11
RPM COMMAND LIMITERS ........................................................................................................................... 12
RPM COMMAND ACCELERATION FILTER, DIAGRAM & PARAMETERS. ............................................................ 12
CRITICAL RPM AREAS (BARRED SPEED RANGE) ............................................................................................. 12
MEASURED RPM.......................................................................................................................................... 13
NOTCH FILTER ............................................................................................................................................. 13
START DETECTION SPEED (SULZER ONLY) ...................................................................................................... 13
D-GAIN........................................................................................................................................................ 14
REGULATOR CONTROL ................................................................................................................................. 14
P/I-GAIN...................................................................................................................................................... 14
LDG FUNCTION (LOAD DEPENDENT GAIN) .................................................................................................. 14
CPP SETTINGS (CONTROLLABLE PITCH PROPELLER) .................................................................................... 14
FUEL SETPOINT ADJUSTMENTS (REGULATOR BYPASS) ................................................................................... 15
FUEL LIMITERS ............................................................................................................................................ 15
TORQUE FUEL LIMIT (MAN B&W) ............................................................................................................... 15
SCAVENGE AIR FUEL LIMIT (MAN B&W) ..................................................................................................... 16
ACTUATOR TYPE........................................................................................................................................... 17
ELECTRIC ACTUATOR ................................................................................................................................... 17
LCDL FUNCTION (LOAD CHANGE DEPENDENT LUBRICATION )..................................................................... 17
VIT FUNCTION (VARIABLE INJECTION TIMING) ............................................................................................. 18
CONSTANT FUEL MODE................................................................................................................................ 19
MISCELLANEOUS .......................................................................................................................................... 19
K4 ALARM RELAY ......................................................................................................................................... 19
NON-LINEAR COMPENSATION, DUE TO FUEL PUMP POSITION ...................................................................... 20
SG FUNCTION (SHAFT GENERATOR) ............................................................................................................. 20
NON-LINEAR COMPENSATION, DUE TO LOW RPM ........................................................................................ 21
NON LINEAR PEAK ABILITY. ........................................................................................................................... 21
QPT FUNCTION (QUICK PASS THROUGH BARRED SPEED FOR CPP SYSTEMS) ................................................ 22
DISPLAY DECIMAL POINT POSITION. .............................................................................................................. 22
SELECTABLE OUTPUT SOURCE, FOR PPI PORT 2PC.................................................................................... 23
OUTPUT SOURCE, SELECTION TABLE (NR.0-31) FOR PPI PORT 2PC........................................................... 23
DIGITAL OUTPUT "OR" FUNCTION ................................................................................................................ 24
ANALOG OUTPUT PARAMETERS ..................................................................................................................... 25
CCO - CYLINDER CUT OUT FUNCTION ..................................................................................................... 28
SPECIAL TEST PARAMETERS........................................................................................................................... 29
SULZER ENGINE DATA .................................................................................................................................. 30
PNEUMATIC ACTUATOR TYPE B: LIST OF PARAMETERS ..................................................... 31
ELECTRIC ACTUATOR: USER PARAMETERS; ........................................................................... 33
ELECTRIC ACTUATOR: BASIC PARAMETERS; ......................................................................... 33
ELECTRIC ACTUATOR: EXPERT PARAMETERS; ..................................................................... 34
GERERAL INFORMATION, REGULATOR. ...................................................................................................... 37
GERERAL INFORMATION, ACTUATOR. ........................................................................................................ 37
SYSTEM IN TEST, REGULATOR. .................................................................................................................... 37
AO-20064-A
3
Parameterlist
ALARM CODES, REGULATOR. ...................................................................................................................... 38
ALARM CODES, ACTUATOR. ........................................................................................................................ 39
AO-20064-A
4
Parameterlist
Display of OpCodes.
OpCode 0
1
13
14
OpCode 1,3,4,5,6
1
USER
parameters
Par.
ch
BASIC
parameters
BASIC
BASIC
parameters
OpCode 2
Expert
parameters
Expert
parameters
1
I/O Basic par.
parameters
2
.
.
.
31
32
Adjusting of OpCodes:
1.
Set the Service-Code.
Switch "Change Lock Key" to Open and set "Service-code" to correct value.
2.
Change OpCode.
The OpCode will be displayed when the Change Lock Key is switched to Lock
position. Select OpCode as required. To adjust parameters switch "Change Lock
Key" to Open position.
3.
Reset Service-Code.
When all adjustments is ready, set the "Service-Code" to 0. Save adjusted values
by pushing the save push-button. Switch the "Change Lock Key" to closed and
remove the Key. (Keep the Key in the chief engineer office).
CAUTION !
Adjusting of values in OpCode 1 and 2 may cause damage to engine
and should be done by authorized personnel ONLY !
Parameter description is included in instruction manual
Note 1: To be able to display parameters with higher number than 10,
the Change Lock Key must be set in "OPEN" position.
AO-20064-A
5
Parameterlist
Hardware & Software Configuration
Electronic unit: DGU-8800
Hardware
Elact: 001
configuration: Actuator:
Serial No.: 2317
Regulator side: Version:
Software
configuration: Actuator side: Version:
SW-20112-B1. c
SW-20124-A8
Engine Maker:
Engine type:
AO-20064-A
Serial No.: 2307
HHI-EMD
6S50MC-C
6
Parameterlist
Параметры выделеные красным, реальные уставки сохраненные
в память!!!
Regulator: USER Parameters;
Regulator - OpCode 0 - USER 1 Parameters
Parameter name /
description:
OPEN PARAMETERS
Limits
Unit Default
Min/Max: type: setting:
06
Readable:
Readable:
Readable:
Readable:
Readable:
Manual RPM limit
Mode select
RPM command
Measured RPM on engine
General information, (selected on parameter 14).
Scavenge air pressure
RPM
0 - 280
103
120
07
Manual fuel limit
08
RPM deadband
09
10
Information:
Information:
Par.
no.:
01
02
03
04
05
0 - 150
0 - 15
Pump
index
RPM
Commission
setting:
100
80
2
2
Remarks/
reference:
1
0.0
0.0
See page 37
0.00
Auto-R
Auto-F
Other status.
Other alarm /Reset "old-alarm" with parameter 16 or 17.
Normal
Regulator - OpCode 0 - USER 2 Parameters
"CHANGE KEY" - PROTECTED - PARAMETERS
11
12
Readable:
Readable:
Alarm nr
Alarm Text
13
14
Adjustable
VIT OFFSET ADJUSTMENT :
18
Select data to (par.4)
See page 37
Readable
Information:
(no save)
Information:
(no save)
Readable
19
Readable
20
Set/Reset
(no save)
adjust
(no save)
15
16
17
21
Normal
Normal
nr.
0
1
Ref.
separate list
ID of Lowest Fuel Limiter
5
RPM detector fail", "Out data error" & "Low Voltage"
Reset with "UP" button " (ref. Instruction Manual. Chapter 3)
00
"In data error" (Analog inputs channels 19, 18, 19, 20 & 21)
Reset with "UP" button (ref. Instruction Manual, Chapter. 3)
00
Sw version,
20112-B1C
Information
"System In Test"
00
information
Fixed fuel Mode, (useful for taking diagrams on engine)
0
Auto reset outside 50-105% RpmMCR. 0=normal, 1=Fixed Fuel
Fixed fuel Level, (useful for taking diagrams on engine)
Intended for fine adjusting of fuel level.
0.0
Service Code
99
adjustable
AO-20064-A
Service Code :
“47”
7
Parameterlist
Regulator: BASIC Parameters;
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
BASIC Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Engine Data
1
Engine Maker
2
Number of teeth
on flywheel
3
Number of cylinders
4
6
Engine Power
at MCR
Engine Speed
at MCR
Inertia (total)
7
Pe, at MCR
8
PSC, at MCR
Scav. air pressure
Servo Actuator pos.
at MCR
Pump Index pos.
at (MCR)
Pump Index pos.
at Offset,
5
9
10
11
Sum of rotating masses
Mean effective pressure
AO-20064-A
MAN
B&W
text
MAN B&W
1 - 500
Pcs.
60
117
1 - 12
Pcs.
6
6
0.1 - 100
Mega
Watt
RPM
5.00
9.47
Hp * 736W
100.0
127
RPM at max
cont. rating
10 - 280
1 - 2000
1000
Kg m²
80.0
82.2
10 - 30
Bar
17.0
20
0.1 - 4
Bar
2.00
2.72
0 - 100.0
mm
100.0
86.5
0 - 150.0
Pump
Index
Pump
Index
100.0
73.0
0.0
13
0 - 50.0
8
Parameterlist
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
BASIC Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Fuel start setpoint
12
13
14
Normal start,
Fuel setpoint
Heavy start,
Fuel setpoint
Start extension time
0 - 100
0 - 100
0 -30
Pump
index
Pump
index
30
40
50
55
Sec.
10.0
10.0
Speed start setpoint
15
16
Speed start setpoint
Rpm level.
Speed start setpoint
Time delay
0 - 280
Rpm
62
45
0 - 10
Sec.
6
6
System Settings
17 и 61 неменять. Сбиваются настройки!!!
17
Set Rpm-Levels
from Engine Data
53
CPP VERSION
61
Set Fuel-Limiters
from Engine Data
rPMLIM /
Auto-r
CPP /
F-Reg
FUELIM /
Auto-F
text
rPMLIM
text
F-Reg
text
FUELIM
Auto setting of Speed Levels
Parameters marked “Auto-R”
Auto setting of fuel limiters.
Parameters marked “Auto-F”
Electric Actuator
77
Actuator Type
78
El. Actuator Arm
79
El. Actuator
Gear Ratio
AO-20064-A
Pn-Saa
EL.Act
text
ELACT
ELACT
1-320.00
mm
140.00
140.00
0-1000
ratio
89
89
9
Parameterlist
See page 11!!!
Regulator - OpCode 2
Signal
chan
1*
Ext. Stop, SHD form SSU
Stop 2 (Br. Contr.) (or QPT )
QPT active (if QPT function = true)
Not Go 2 (Br. Ctrl.)
2*
3*
4
5
6*
7*
8*
9
10
10
11
(Actuator; Servo Brake Off)
(Actuator; Position Speed Cmd)
(Actuator; Reset Servo Amplifier)
(Actuator; Servo ampl.Fail)
(Actuator; Manual)
12
13
14
15
16
(Actuator; Torque Enable)*
Analog Channels
Error Low
Error High
Count Zero
Count Low
Count High
tec. Low
tec. High
Limit Low
Limit High
Filter const.
0-4095
0 or CL-CH
1 - CH
CL - 4095
+/+/+/+
300.00
300.00
300.00
300.00
0-60.0 sec.
EL
EH
CO
CL
CH
tL
tH
LL
LH
tF
(I/O adjustments) BASIC Parameters
Type
Inverted
Pass
d-out
Pass
Pass
d-in
d-out
A-out
d-out
d-in
d-in
see special backwiring
see special backwiring
see special backwiring
see special backwiring
see special backwiring
see special backwiring
Non-Adjustable; Only ELACT
see special backwiring
Or =
d=
Or =
d=
Or =
d=
Or =
d=
pass
pass
pass
pass
pass
Non-Adjustable; act D-Out
Non-Adjustable; act A-Out
Non-Adjustable; act D-Out
Non-Adjustable; act D-In
Non-Adjustable; act D-In
d-in
d-in
On delay
17
18
Rpm Cmd
Rpm Cmd
19
Pitch
C. Room
Bridge
feedback
200
1750
0
611
1656
25
131
23
133
1.5
2350
4000
0
2430
3927
25
131
23
133
1.5
Off delay
nn 801.3
d2 =
d2 =
d2 =
d2 =
nn 801.3
nn 803.4
nn 801.3
nn 801.1
nn 801.1
20
Scav.
Air Pres.
0 0-4095
2350
4095
4000
2000
0
1000
2430
3000
3910
-1.00
0.0
1.00
4.0
1.00
0.0
1.00
4.0
0.0
5.0
21
not used
0
4095
0
50
2000
2.0
103
0
0
0
Signal
Stop 1 (Ctrl. Room)
Not Go 1 (Ctrl. Room)
Passive
Cmd Select (Bridge)
BridgeControl, Power Fail
Fixed Speed
Slow Down
Cancel Lim. (Bridge,+)
Rpm Pickup A
Rpm Pickup B
chan
Type
Inverted
On delay
Off delay
22
d-in
Or =
d=
D2 =
23
d-in
Or =
d=
D2 =
24*
d-in
Or =
d=
D2 =
25
d-in
Or = true
d=
D2 =
26
d-in
Or =
d=
D2 =
27
d-in
Or =
d=
d2 =
28
d-in
Or =
d=
d2 =
29
d-in
Or =
d=
d2 =
Lop Fail Input (d-in)
30
F-in
Or =
Lop Fail Input (d-in)
31
F-in
Or =
32*
d-in
Or =
d=
d2 =
Note 1. For channel type d-in => "Or"=false, d and d2 = 0.0, unless otherwise specified.
Note 2. * => Special backwiring is required, for this channel! See special backwiring.
End of Basic Parameters.
AO-20064-A
10
Parameterlist
ty
d1
In
Or
d
d2
Si
Su
5
d-in
open
open
false
0
0
false
open
9
d-in
open
close
true
0
0
false
close
10
d-in
close
close
false
0
0
false
close
11
d-in
close
close
false
0
0
false
close
22
d-in
close
close
false
0
0
false
close
23
d-in
close
close
false
0
0
false
close
24
d-in
open
close
true
0
0
false
close
25
d-in
open
close
true
0
0
false
close
26
d-in
close
close
false
0
0
false
close
27
d-in
open
close
true
0
0
false
close
28
d-in
open
close
true
0
0
false
close
29
d-in
open
close
true
0
0
false
close
30
31
32
F-in F-in d-in
close close open
close close close
false false true
0
0
false false false
close close close
Analog channel
ty
AC
A1
LF
EL
EH
CO
CL
CH
tL
tH
LL
LH
tF
AO-20064-A
17
A-in
236
23
normal
200
1750
0
611
1656
25
131
23
133
1.5
18
A-in
2713
45.00
normal
2350
4000
0
2430
2927
25
131
23
133
1.5
19
A-in
0
1.00
normal
0
4095
2000
1000
3000
-1.00
1.00
1.00
1.00
0.0
20
A-in
2430
0.00
normal
2350
4000
0
2430
3910
0.00
4.00
0.00
4.00
5.0
21
A-in
0
0.00
normal
0
4095
0
50
2000
2.00
103.00
0.00
0.00
0.0
11
Parameterlist
Regulator: EXPERT Parameters;
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Auto-R
(40%)
RPM Command Limiters
18
Slow down level
19
Fixed speed
0 - 280
RPM
40.0
64
20 - 280
RPM
75.0
75.0
RPM Command Acceleration Filter, Diagram & Parameters.
Rpm
B
C
Change level
A
20
Change level.
21
D
Seconds.
0 - 280
RPM
75
95
A) Pos. low lev. rate
0.5 - 1000
200.0
200.0
22
B) Pos. hi. lev. rate
0.5 - 1000
2.0
2.0
23
C) Neg. hi. lev. rate
0.5 - 1000
2.0
2.0
24
D) Neg. low lev. rate
0.5 -1000
RPM
/sec.
RPM
/sec.
RPM
/sec.
RPM
/sec.
1.0
2.0
Auto-R
(75%)
Critical RPM Areas (barred speed range)
25
26
27
28
29
Critical RPM.
Low RPM level 1
Critical RPM.
High RPM level 1
Critical RPM.
Low RPM level 2
Critical RPM.
High RPM level 2
0 - 280
RPM
40
50
0 - 280
RPM
40
61
0 - 280
RPM
70
70
0 - 280
RPM
70
70
Max. speed
at cancel limiters
0 - 280
RPM
110
133
AO-20064-A
Auto-R
(105.0 %)
12
Parameterlist
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Measured RPM
30
31
32
33
Rpm Detector
Warning Delay
Max Rpm Variation
Filter
Low Pass Filter
Measured RPM
low pass filter
0 - 2.50
Sec.
0.50
0.9
0 - 280
RPM
/20ms
e
4
4
0.70
0.70
0.50-0.80
Display Filter (for parameter 3 only)
e
0 - 0.99
0.99
0.99
Notch Filter
34
35
Notch Function
36
Filter Connect
Hysterese
Filter Disconnect
Hysterese
37
Filter max. RPM
(0-1)
0 - 280
text
RPM
no Flt
50
no Flt
50
0 - 50
RPM
2
2
0 - 50
RPM
6
6
Start detection speed (Sulzer only)
38
39
Start detection speed
for Remote
Start detection speed
Backup and Local
AO-20064-A
(0-20)
rpm
0
0
(0-20)
rpm
6
6
13
Parameterlist
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
D-Gain
40
41
42
43
D-Gain Function
enabled
D-Gain Function
in “normal sea” also
Filter of RPM used
in D- gain function.
D-Gain factor
True/False
text
False
False
True/False
text
False
False
1-7
samp.
20 ms
3
3
0 - 10.00
K
0.10
0.10
Moving avg.
Filter
Regulator Control
44
Cmd forward gain
45
Reduction gain
0 - 10.00
X
1.00
1.00
1 - 20
1/K
5
5
In deadband
P/I-Gain
46
Rough sea P-Gain
0.1 - 10
X
0.90
0.9
47
Rough sea I Gain
0.1 - 10
Time
const.
3.00
3.00
48
Normal P-Gain
0.1 - 10
X
1.00
1.00
49
Normal I-Gain
0.1 - 10
Time
const.
1.00
1.00
LDG Function (Load Dependent Gain)
50
LDG Function
True/False
text
False
False
51
Idle Offset load
0-80
%
20
20
52
LDG - Gain
0-10.00
rel.
1.00
1.00
0.00 equals
Function OFF
CPP Settings (Controllable Pitch Propeller)
53
CPP VERSION
54
Min. Pitch used for
Pitch forward gain.
Min. Pitch used for
Igain and Fuel Lim.
Zero Pitch Fuel
Limiter Level.
55
56
AO-20064-A
CPP /
F-Reg
text
F-Reg
0 - 1.00
rel
0.30
0 - 1.00
rel
0.50
0 - 150
Pump
index
30
Cpp Version
Only
Cpp Version
Only
Cpp Version
Only
14
Parameterlist
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Fuel Setpoint Adjustments (Regulator bypass)
58
Fuel Setpoint
Function enabled.
Handle zero fuel.
59
Handle 100% fuel.
57
RPM Cmd when 0% fuel
RPM Cmd when 100% fuel
true/false
text
False
False
CCO function
must be passive
0 - 280
RPM
20
32
0 - 280
RPM
90
120
Auto-R
(25%)
Auto-R
(95%)
Fuel Limiters
60
61
62
Raise Fuel Limiter
internally
Set Fuel-Limiters
from Engine Data
Raise Fuel Limiter at
cancel limiters
0-30
%
0.0
automatic
setting
Text
0-110
%
FUELIM
0.0
Ref. CPP
Loadcontroler
Auto set the Scav. air, Torque
and Manual fuel limiters !!
10
10
at Cancel lim.
Signal
Torque Fuel Limit (MAN B&W)
63
Torque RPM 2
0 - 281
RPM
70.0
53
Auto-F
64
Torque RPM 3
0 - 282
RPM
96.0
117
Auto-F
65
Torque RPM 4
0 - 283
RPM
105.0
127
Auto-F
66
Torque RPM 5
0 - 284
RPM
107.0
130.8
Auto-F
67
Torque range 1,2
0 - 100
%
100.0
60.2
Auto-F
68
Torque range 3,4
0 - 100
%
100.0
100.0
Auto-F
69
Torque range 5,6
0 - 100
%
100.0
100.0
Auto-F
(Overspeed start)
(Overspeed Zero Fuel)
(Overspeed- ZERO FUEL)
%
Fuel
Torque Limiter
100%
1
0.0
AO-20064-A
3
4
5
6
2
MC R
speed (rpm)
15
Parameterlist
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Scavenge Air Fuel Limit (MAN B&W)
70
Scav.air press 2
0 - 4.01
Bar
0.00
0.00
Auto-F
71
Scav.air press 3
0 - 4.02
Bar
1.00
0.5
Auto-F
72
Scav.air press 4
0 - 4.03
Bar
1.40
2.30
Auto-F
73
Scav.air range 1,2
0 - 100
%
100.0
60.2
Auto-F
74
Scav. air range 3
0 - 100
%
100.0
68.4
Auto-F
75
Scav. air range 4,5
0 - 100
%
100.0
don't care
Fixed
@ 100 %
Scavenge Air Limiter
%
Fuel
100%
4
5
3
1
0.0
2
Pscav (Bar)
The fuel limiters set in the governor is transferred to “cpp load controller”
and the governor is using 10% higher limites (adjustable in parameter 1.60).
AO-20064-A
16
Parameterlist
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
Setting:
Commission
setting:
Remarks/
reference:
Pump Index
See page 37
Actuator Type
76
77
Actuator Display
Show value select
Actuator Type
(0-4)
Text
Load %
Pn-Saa
EL-Act
Text
EL-Act
Electric Actuator
78
El. Actuator Arm
1-320.00
mm
140.00
140
79
0-1000
ratio
89
89
80
El. Actuator
Gear Ratio
Enable new Scale,
text
Sc Dis
Sc Dis
81
Make new scale (Sc.)
text
Scale
Scale
82
(Fuelrack / Actuator)
Disable /
Enable
Scale,
Set Scale
No save.
Auto reset.
No save.
Auto reset
Blank
LCDL Function (Load Change Dependent Lubrication )
83
84
85
86
LCD controlled by
telegraph lever
Load change filter
(Tr)
Extra lubrication
action level (Ir
Extra lubrication off
delay (ts)
AO-20064-A
else by
fuel command
true/false
Text
True
True
2 - 120
Sec.
10.0
10.0
0.05- 0.25
Rel.
0.10
0.10
Relative
fuel
15 - 60
Min.
30.0
30.0
Minutes
17
Parameterlist
Regulator - OpCode 1
Par.
no.:
Expert Parameters
Parameter name /
Limits
Unit Default Commission
description:
Min/Max: type: setting:
setting:
VIT Function (Variable Injection Timing)
87
V.I.T. Function On
true/false
Text
false
False
88
Pmax,
100 - 250
Bar
140
140
89
Pmax, allowed pressure
0 - 50
Bar
35
35
25.0-50.0
Bar
35.0*
35.0
0.5 - 0.95
0.85*
0.85
0.20
0.20
10-50
rel.
load
rel.
load
Bar
35*
35
0 - 25
Bar
15*
15
+ - 50
Bar
15*
15
Max. press. in cylinder
Remarks/
reference:
rise from Pcomp to Pmax
90
kc, Ratio of
91
Pk, Power at breakpoint
92
Pmin, Min. Power,
93
 Pk,
Pcomp relative to Psc
(rel. meas. unit)
curve III. (rel. meas. unit)
0 - 0.60
Press. raise at breakpoint
94
 Pmcr,
Press. rise at MCR
95
 Pmin,
=  Pmcr
Min. value of press. rise
96
ki, Output conv. factor
0 - 2.000
mA/
Bar
0.350
0.350
97
 Pmax, control,
0 - 20
Bar
10
10
+ - 50
Bar
0
0
0.2 - 120
sec.
30.0
30.0
0.2 - 120
sec.
1.0
1.0
from p to 4-20mA
Max.allowed control range
98
99-A0
Poffset, Adjustment for
Pmax. level
Blank
A1
Increase, max rate
A2
Decrease, max rate
From 4 to 20 mA
From 20 to 4 mA.
Pmax. Lim. (if
press sensor
fail)
Adjustment for
fuel quality
* Calculated engine dependent data. (May have to be adjusted for actual testbed data).
Readable values for V.I.T. - Note: OpCode 0 !!!
0-84
0-85
0-86
Readable
Readable
Readable
0-87
0-88
0- 89
0-90
0-91
0-92
0-93
0-94
0-95
0-96
Readable
Readable
Readable
Readable
Readable
Readable
Readable
Readable
Readable
Readable
0-97
0-98
Adjustable
Adjustable
AO-20064-A
V.I.T. (Variable Injection Timing) Internal signals
rel engine speed. (0 - 1.0)
rel fuel pump index. (0 - 1.0)
Scav. air pressure (abs Bar)
V.I.T. (Variable Injection Timing) Calculations
Range 1
 p, I
Range 2
 p, II
Range 3
 p, III
Range 4
 p, IV
Range 5
 p, V
Range
Selected Range (1-5)
selected pressure rise
p
Pcomp
= kc * Psc, Compression pressure in cylinder.
I
4-20 mA output signal
ALARM
Operation in Range "V"
V.I.T. (Variable Injection Timing) Test output signal
Output select
"norMAL"= Normal VIT signal. "VitSim"= Simulate output signal.
Test signal
4.0 - 20.0 mA simulation signal.
nr
Ir
Psc
18
Parameterlist
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Constant Fuel Mode
true/false
text
false
true
0-320
sec.
5
5
0-280
Rpm
3
3
Relative to
Rpm Cmd
0-280
Rpm
3
3
Relative to
Rpm Cmd
0-280
Rpm
8
5
Relative to
Rpm Cmd
0-280
Rpm
8
5
Relative to
Rpm Cmd
AA
Constant Fuel
Function
Timer for
engage const. fuel
Engage Band
Lower Limit
Engage Band
Upper Limit
Disengage Band
Lower Limit
Disengage Band
Upper Limit
RPM Lower Limit
0-280
Rpm
30
85
Absolute RPM
AB
RPM Upper Limit
0-280
Rpm
110
121
Absolute RPM
A4
A5
A6
A7
A8
A9
Miscellaneous
AC
AD
AE
NotGo/Stop,
only one signal
Cancel limiters,
only one signal
Fuel limiter
Prewarning
Fixed speed location.
AF
Ch. 27 Fixed speed to be
active with location:
true/false
text
False
fals
true/false
text
False
False
0 - 150
%
0
0
none,
Bridge,
Ctrl. Room,
both
text
none
none
Cancel limiter
K4 Alarm Relay
B0
B1
B2
B3
b4-bf
Alarm input filter,
Time delay
Alarm active,
Time delay
Alarm passive,
Time delay
Invert alarm relay,
"Or" function
0-10.0
Sec.
1.0
1.0
0-10.0
Sec.
5.0
5.0
0-10.0
Sec.
5.0
5.0
True/False
text
False
False
Blank
AO-20064-A
19
Parameterlist
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Non-Linear Compensation, due to Fuel Pump Position
True/
False
text
false
C1
Non Linear Position,
Function On
x1
0-100.0
%
20.0
20.0
C2
x2
0-100.0
%
25.0
25.0
C3
x3
0-100.0
%
30.0
30.0
C4
x4
0-100.0
%
40.0
40.0
C5
y1
0-100.0
%
20.0
20.0
C6
y2
0-100.0
%
25.0
25.0
C7
y3
0-100.0
%
30.0
30.0
C8
y4
0-100.0
%
40.0
40.0
C0
C9
Blank
SG Function (Shaft Generator)
CA
Shaft generator,
Function on/off
CB
Shaft generator,
Basic RPM
Shaft generator,
Basic timer
Shaft gen. available,
RPM Band
Shaft gen. available,
Stabilizing delay
CC
CD
CE
CF
Off /
Sh-GEn
0 - 280
text
Off
Off
RPM
99
99
0 - 250
Sec.
60
60
0 - 280
RPM
5.0
5.0
0 - 250
Sec.
10
10
Relative to
fixed speed
Delay for
output signal
Blank
AO-20064-A
20
Parameterlist
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Non-Linear Compensation, due to Low RPM
False/
True
text
False
False
D1
Non Linear by Low
Rpm, Function On
x1 Speed
0-280.0
rpm
20.0
20.0
D2
x2 Speed
0-280.0
rpm
30.0
30.0
D3
x3 Speed
0-280.0
rpm
40.0
40.0
D4
x4 Speed
0-280.0
rpm
50.0
50.0
D5
y1 factor
1.00-2.00
rel.
1.50
1.50
D6
y2 factor
1.00-2.00
rel.
1.20
1.20
D7
y3 factor
1.00-2.00
rel.
1.10
1.10
D8
y4 factor
1.00
rel.
1.00
1.00
D0
Not adjustable
Non linear peak ability.
D9
Non linear functions
able to override
fuel limiters
da-df
Blank
AO-20064-A
true / false
text
False
False
21
Parameterlist
Regulator - OpCode 1
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
QPT Function (Quick Pass Through barred speed for CPP systems)
QPT - Shut Down
(Quick Pass Through barred speed)
E0
QPT - SHD On
true / false
text
False
False
E1
Barred speed high
0- 280
rpm
50.0
50.0
E2
Barred speed low
0- 280
rpm
40.0
40.0
E3
Barred speed time
0- 60.0
sec.
5.0
5.0
E4
SHD output signal
(Output “OR”)
true / false
text
False
False
SHD signal
output to
Safety Systen
if engine is
running too
long in barred
speed.
QPT - Start, Stop & Slow Down (Quick Pass Through barred speed)
E5
QPT Function On
true / false
text
False
False
E6
Barred speed band
0- 280
rpm
4.0
4.0
E7
Idle speed, Level
0- 280
rpm
95.0
95.0
E8
Idle speed, Time
0- 60.0
sec.
5.0
5.0
E9
Zero pitch low index
0- 150
25
25
EA
Zero pitch high index
35
35
EB
Zero Pitch Level
Pump
Index
Pump
Index
rel
Pitch
0.20
0.20
EC
Zero pitch request
signal (Output “OR”)
False
False
ed-ef
Blank
Margin to barred speed
Speed cmd, starting engine
Extra time for zero pitch
Fuel level after slow down.
Set fuel level after start.
Accepted pitch for passing
0- 150
0- 1.00
true / false
text
Manual Fuel Limiter Unit ( Load (100%) or Pump Index (mm) )
text
true
true
F0 Scale select
(0-1)
f1-fd
Blank
Display decimal point position.
FE
FF
Dcimal point
for rpm par. 2 and 3
rPm-d0
rPm-d1
rPm-d2
Blank
Not used
AO-20064-A
text
rPm-d0
rPm-d0
change key in
“lock” position
22
Parameterlist
Regulator - OpCode 3
Expert Parameters
Special backwiring table (special channel connection )
Ch.
P1-M
ch.01
ch.02
ch.03
ch.04
ch.05
ch.06
ch.07
ch.08
ch.21
ch.24
ch.32
P1M-35
P1M-36
P1M-33
P1M-34
P1M-31
P1M-32
P1M-29
P1M-30
P1M-15
P1M-14
P1M-06
Wired to:
Normally used as:
Actually used as:
connection
P1R-08 - LCD Lubrication output
PIR-10
actuator : Fuel position output
actuator: Torque enable output
P1R-05 Vit output signal
P1R-15 Cancel limiter @ECR input
Fixed Output, for PPI Port 2PB (information only)
P1R-01
P1R-02
P1R-04
QPT, zero pitch req,
Reserved
QPT, Critical speed
Selectable Output Source, for PPI Port 2PC
Par.
no.:
05
06
07
08
09
10
11
Parameter name /
description:
P1R-05 select
P1R-06 select
P1R-07 select
P1R-08 select
P1R-09 select
P1R-10 select
P1R-12 select
Limits
Min/Max:
0 - 31
0 - 31
0 - 31
0 - 31
0 - 31
0 - 31
0 - 31
Unit
type:
Default
setting:
Commission
setting:
nr
nr
nr
nr
nr
nr
nr
16
7
4
5
2
3
1
16
7
4
5
2
24
1
Remarks/
reference:
Output Source, Selection Table (nr.0-31) for PPI Port 2PC
nr
DIGITAL SIGNAL
source [NN-801.3]
Remarks
nr
0
16
1 Fuel prewarning
17
2 Fuel limiter active
18
3 Start Diesel Generator
19
4 Sh. Gen. Available
20
5 LCD Lubrication
21
6 75% Load
22
7 VIT_Alarm
23
8 CCO group 1
24
9 CCO group 2
25
10-13
26-29
14
30
15 oscilator 3 Hz
31
Note 1. See also analog scaling selection parameter. of signal type.
AO-20064-A
ANALOG SIGNAL source
[varius adaptorcards]
Vit out [NN-803.2] 4-20 mA
Rpm Cmd ECR (from input ch.17)
Rpm Cmd WH (from input ch.18)
Rpm Cmd diffrence (wh-Ecr)
Rpm Cmd in control (as param.2)
Meassured Rpm
Max. Available fuel (the fuel limitation)
Fuel Margine (limiter-fuelrack diffrence)
Actuator position, Fuel output
Remarks
note 1
note 1
testsignal (range 4-20 mA)
testsignal (range +/ -10 Volt)
23
Parameterlist
Regulator - OpCode 3
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
False
QPT,
zero pitch req,
Digital output "OR" function
12
13
14
15
16
17
18
19
20
21
Signal 'P1R-01'
"Or" function
Signal 'P1R-02'
"Or" function
Signal 'P1R-04'
"Or" function
Signal 'P1R-05'
"Or" function
Signal 'P1R-06'
"Or" function
Signal 'P1R-07'
"Or" function
Signal 'P1R-08'
"Or" function
Signal 'P1R-09'
"Or" function
Signal 'P1R-10'
"Or" function
Signal 'P1R-12'
"Or" function
AO-20064-A
Digital output from 2PB
text False
True/False
True/False
text
False
False
reserved
True/False
text
False
False
Critical speed
Digital output from 2PC
True/False
text False
False
selectable
True/False
text
False
False
selectable
True/False
text
False
False
selectable
True/False
text
False
False
selectable
True/False
text
False
False
selectable
True/False
text
False
False
selectable
True/False
text
False
False
selectable
24
Parameterlist
Regulator - OpCode 3
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Analog output parameters
Analog output select 16 scaling. - not used
( Vit output have fixed scale - reserved parameters only )
22
Blank
Not used
23
Simulation
true/false
text
false
False
24
Simulate counts
0 - 4095
count
0
0
25
Count Low
0 - 4095
count
2048
2048
26
Count High
0 - 4095
count
3800
3800
27
Tec. Low
0 - 300
rpm
0.0
0.0
28
Tec. High
0 - 300
rpm
120.0
120.0
Analog output select 17 scaling. - Rpm Cmd (Ctrl.Room), setpoint from i/o ch 17
29
Blank
Not used
30
Simulation
true/false
text
false
False
31
Simulate counts
0 - 4095
count
0
0
32
Count Low
0 - 4095
count
2450
2450
33
Count High
0 - 4095
count
3800
3800
34
Tec. Low
0 - 300
rpm
0.0
0.0
35
Tec. High
0 - 300
rpm
120.0
120.0
Analog output select 18 scaling. - Rpm Cmd (Bridge.), setpoint from i/o ch 18
36
Blank
Not used
37
Simulation
true/false
text
false
False
38
Simulate counts
0 - 4095
count
0
0
39
Count Low
0 - 4095
count
2450
2450
40
Count High
0 - 4095
count
3800
3800
41
Tec. Low
0 - 300
rpm
0.0
0.0
42
Tec. High
0 - 300
rpm
120.0
120.0
AO-20064-A
25
Parameterlist
Regulator - OpCode 3
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Analog output select 19 scaling. - Command diffrence signal.
43
Blank
Not used
44
Simulation
true/false
text
false
False
45
Simulate counts
0 - 4095
count
0
0
46
Count Low
0 - 4095
count
0
0
47
Count High
0 - 4095
count
4095
4095
48
Tec. Low
/ 300
rpm
-119.9
-119.9
49
Tec. High
/ 300
rpm
120.0
120.0
Analog output select 20 scaling. - Rpm Command.
50
Blank
Not used
51
Simulation
true/false
text
false
False
52
Simulate counts
0 - 4095
count
0
0
53
Count Low
0 - 4095
count
2450
2450
54
Count High
0 - 4095
count
3800
3800
55
Tec. Low
0 - 300
rpm
0.0
0.0
56
Tec. High
0 - 300
rpm
120.0
120.0
Analog output select 21 scaling. - Meassured Rpm.
False
true/false text
57 Displayfiltered
False
58
signal
Simulation
59
true/false
text
false
False
Simulate counts
0 - 4095
count
0
0
60
Count Low
0 - 4095
count
2048
2048
61
Count High
0 - 4095
count
4095
4095
62
Tec. Low
0 - 300
rpm
0.0
0.0
63
Tec. High
0 - 300
rpm
120.0
120.0
AO-20064-A
26
Parameterlist
Regulator - OpCode 3
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Analog output select 22 scaling. - Max Available Fuel 0-110 to “Load Controller”.
64
Blank
Not used
65
Simulation
true/false
text
false
False
66
Simulate counts
0 - 4095
count
0
0
67
Count Low
0 - 4095
count
2450
2450
68
Count High
0 - 4095
count
3800
3800
69
Tec. Low
0 - 150
0.0
0.0
70
Tec. High
0 - 150
%
fuel
%
fuel
110.0
110.0
Analog output select 23 scaling. - Fuel Margine 110% to “Load Controller”.
Ref. CPP
False
true/false text
False
Loadcontroller
71 Fuel margine signal
72
restricted to par 1.60
Simulation
73
true/false
text
false
False
Simulate counts
0 - 4095
count
0
0
74
Count Low
0 - 4095
count
0
0
75
Count High
0 - 4095
count
4095
4095
76
Tec. Low
+/- 150
-109.9
-109.9
77
Tec. High
+/- 150
%
fuel
%
fuel
110.0
110.0
Analog output select 24 scaling. - Actuator position 0-100%.
78
Blank
Not used
79
Simulation
true/false
text
false
False
80
Simulate counts
0 - 4095
count
0
2445
81
Count Low
0 - 4095
count
2430
2443
82
Count High
0 - 4095
count
4095
4095
83
Tec. Low
0 - 150
0.0
0.0
84
Tec. High
0 - 150
%
fuel
%
fuel
100.0
100
AO-20064-A
If change this figure Par.80
change to 2445 also
27
Parameterlist
Regulator - OpCode 4
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Expert Parameters
Unit
type:
Default
setting:
Commission
setting:
Remarks/
reference:
true / false
text
False
False
true / false
text
False
False
true / false
text
True
True
0- 100
0- 50
0- 50
0- 120
0- 120
0- 120
0- 60
0- 1.00
0- 10
0- 10
rpm
rpm
rpm
38.0
5.0
5.0
38.0
5.0
5.0
X1
sec.
sec.
sec.
min.
sec.
10
10
30
10
0.25
10
10
30
10
0.25
t1
rpm
rpm
3.0
5.0
3.0
5.0
H1
CCO - Cylinder Cut Out function
01
CCO
Function enabeld
NOTE: If this function is
enabled then Fuel setpoint
function will be disabled.
02
03
04
05
06
07
08
09
10
11
12
13
button protected
by Change Lock Key
External Remote
Control Signal
Cut out enable level
CCO
Cmd above actual rpm
Engine stop detection
Delay Cut out enable
Delay Disable by change cmd
Delay Cut out during start
Delay Cut out seqense
Delay Cut out overlap
Hyst. cut out level
Hyst. cmd override
X2
X3
t2
t3
t4
t5
H2
Readable parameters
0.02
0.03
Rpm Cmd
Engine speed
rpm
rpm
14
15
16
CCO automatic mode. (function param + panel button)
* Remot control ( io ch.32)
* Engine Low speed
enable CCO
enable CCO
enable CCO
true/false
true/false
true/false
17
18
19
20
*
*
*
*
disable CCO
disable CCO
disable CCO
disable CCO
true/false
true/false
true/false
true/false
21
22
23
24
* CCO avtive (enabled)
LCD Lubricaton blocked by CCO
Actuator blocked
t4 timer (remaining time, countdown )
Cmd high above engine speed
Engine stopped (cmd lever or meassured)
Cmd high
Limiters cancelled ( io ch.29)
stops t4 timer
CCO Group 1 active
25
CCO Group 2 active
26
* NOTE: Parameter 14 -20 is only opdated in CCO automatic mode (ref. par.4.13)
AO-20064-A
true/false
true/false
true/false
min.sec 10.00
true/false
true/false
28
Parameterlist
Regulator - OpCode 5
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Special test parameters
DAC Select (Digital to Analog Converters)
nr.
9
9
0- 50
01
Dac 1 select
02
Dac 2 select
0- 50
nr.
12
12
03
Dac 3 select
0- 50
nr.
29
29
04
Dac 4 select
0- 50
nr.
31
31
05
06
Calibrate Timer
Simulation Step
sec.
6.0
0- 60.0
count
200
0- 5000
6.0
07
Calibrate Step
Rpm Cmd
Calibrate Step
Rpm Measured
0- 5000
count
200
Connector
PC-3
200
200
Direct fuel setpoint and oscillator simulation.
09
Function select
0
1
2
3
10
Direct output par.
0-100.00
11
Direct output (ch. 21)
12
Direct output (ch. 21)
13
Oscillator,
Curve function
0
1
2
3
14
Oscillator,
Frequency
Oscillator,
Amplitude
Oscillator,
Center reference
15
16
(or output from ch. 21)
Counts Low
Counts High
AO-20064-A
NORMAL Reg.
Direct /f. ch. 21
Direct /f. par.
Direct /f. oscilla.
nr.
Normal
Normal
not savable
%
2
2
Only adj. if set
to
direct from par.
0-4095
count
25
25
0-4095
count
4000
4000
text
C-LinE
C-Line
0.1 - 5.0
Hz
1.0
1.0
2 - 100
%
80
80
1 - 60
%
40
40
Center line,
Sinus wave,
Triangle wave,
Square wave,
29
Parameterlist
Regulator - OpCode 6
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Expert Parameters
Default
setting:
Commission
setting:
Remarks/
reference:
Параметры неменять. Сбиваются предыдущие настройки!!!
Sulzer Engine Data
1
P charge air
0.0 - 4
Bar
1.00
0.1 - 4
Bar
2.00
0 - 10.00
Linkage
Index
2.00
0 - 10.00
Linkage
Index
4.00
0 - 10.00
Linkage
Index
8.00
0 -10.00
Linkage
Index
10.00
at 50% power
2
3
4
5
6
P charge air
at 100% power
Fuel Rack position
at 25% power
Fuel Rack position
at 50% power
Fuel Rack position
at 100% power
Linkage Index. max
AO-20064-A
30
Parameterlist
Pneumatic Actuator type B: List of parameters
Actuator type B, List of parameters
SAA (Switch Air Actuator)
01
02
03
04
05
06
07
08
09
10
Information:
Information:
Readable:
Readable:
Information:
Information:
Information:
Information:
Readable:
Readable:
Sw 20114
(5,8 MHz)
Mode select (0-6), not to be adjusted.
Actuator fuel command value from regulator (0 - 100.0 mm)
Actuator measured position from feedback (0-100.0 mm)
Servo error value (± 100.0)
Servo dead band (± 100.0), standard set to 0.4, do not adjust.
Regulator Show. Value selected in regulator is displayed.
Feedback fail. status (reset by up-button) (Hex), std. set to 00.
In-data error status (reset by up-button) (Hex), std. set to 00.
Other status (no message in this program)
Other alarm
Actuator type B, List of parameters
Par.
no.:
SAA (Switch Air Actuator) Sw 20114
Parameter name /
Limits
Unit Default
description:
Min/Max: type: setting:
(5,8 MHz)
Commission
setting:
Remarks/
reference:
System
11
12
Systemdate
CPU Speed
Process. card type
SW system date (dd.mm.y), CAUTION, DO NOT RESET!
0 = 5 MHz
1 = 8 MHz
no
0-1
1
Adjustment
13
14
15
16
17
18
Number of fine-tuning
pulses in auto cal.
Fine adj. (-) of pulse
width, negative move.
Fine adj. (-) of pulse
width, positive move.
Fine adj. (+) of pulse
width, negative move.
Fine adj. (+) of pulse
width, positive move.
Coarse adj. of pulse
width, negative move
19
Coarse adj. of pulse
width positive move
20
Pulse period
21
High speed gain,
negative move.
22
High speed gain,
positive move.
23
Low speed gain,
negative move.
24
High speed gain,
positive move.
AO-20064-A
1-10
No
2
0
0
0
0
mSec
4 (auto)
5
mSec
5
mSec
0.25
mm
0.25
mm
0.1
mm
0.1
mm
4 (auto)
Autocalibration
Autocalibration
6
50
50
50
50
Autocalibration
Autocalibration
Autocalibration
Autocalibration
31
Parameterlist
Actuator type B, List of parameters
Par.
no.:
SAA (Switch Air Actuator) Sw 20114
Parameter name /
Limits
Unit Default
description:
Min/Max: type: setting:
25
Sub. mode select
(Manual calibration)
26
Information:
27
Local cal., high speed
min. acceptable value
28
Readable:
29
Calibration center
position
30
31
Information:
Information:
32
Timing of calibration
half period
33
Readable:
34
1B register activity
level setting
35
Readable:
36
2C register activity
level setting
Exclusive alarming
37
38
Delay time of
alarming/prewarning
39
Allowed dead-band bef.
feedback fail warning
40
Readable:
41
"Too slo" (to slow)
alarm function
42
Allowed dead time bef.
pulse width adaptation
43
Readable:
44
Display filter constant
of parameter 3
Dip-switch setting
on panel card
45
(5,8 MHz)
Commission
setting:
0
Mode select (0-6) not be adjusted. (Same as parameter no. 1).
mm/
200
Sec
Local calibration status low (0) or high (1) (Default = 1)
mm
50
Upper limit of high speed position control (mm) (Default=98)
Lower limit of high speed position control (mm) (Default=2)
5
300
mSec
1B register status (HEX)
Hex
21
2C register status (HEX)
Hex
0 or 1
on/
off
5
mSec
Sec
4F
0
0 = Off
1 = On
50
1.00
Delay timer display for parameter 39 (Sec.)
on/
0
0 or 1
off
Sec
1.00
0 = On
1 = Off
Delay timer display for parameter 41 (Sec.)
4
Readable
only
Actuator position, counts value (raw data) (12-1012) Do not adjust.
Counts
12
HEX
FF
46
Information:
47
Zero offset value
(Autozero setting)
48
49
Not used
Information:
Actuator position unfiltered (0-100 mm)
50
Service code
Set to 27 for adjustments, otherwise set to 0.
AO-20064-A
Remarks/
reference:
32
Parameterlist
Electric Actuator: USER Parameters;
Electric Actuator,
01
02
03
04
05
06
Information:
07
08
09
10
Resetable:
11
12
Readable:
13
Blank
99
Service code
BASIC Parameters
Information:
Mode select (0-6), not to be adjusted.
Actuator fuel command value from regulator
Actuator measured position from feedback
Servo error value
Servo dead band
Information:
General Information. Value selected in regulator is displayed.
Information:
Readable:
Readable:
1
0.0
0.0
0.0
0.0
Information:
0.0
Feedback fail. status (reset by up-button).
In-data error status (reset by up-button).
Other Status
Information.
Alarm (ref. Instruction Manual, Chapter. 3, Trouble Shooting)
Resetable:
0.0
0.0
normal
Alarm Information
Readable:
Alarm Nr.
Alarm Text.
normal
normal
Set to 0.
Electric Actuator: BASIC Parameters;
Par.
no.:
Parameter name /
description:
Limits
Min/Max:
Unit
type:
Default
setting:
Commission
setting:
System
Sw 20xxx-xx
14
Software Version
15
Actuator type
ELA 01-03
nr
ELA-01
16
Engine Maker
Sulzer or
ManB&W
no
ManB&W
fact.
120
124-A8
ELA-01
ManB&W
Actuator Gain
17
Actuator P - Gain
Gain for actuator response
0-1000
120
Speed output signal
18
19
Ch
13
AO-20064-A
Offset tuning
Speed cmd, output offset
Compensation for hardware
0 oFFSEt,
1 tuning
 200
text
offset
offset
(auto-tuning of
offset (par
19))
count
0
3
33
Parameterlist
Electric Actuator: EXPERT Parameters;
Electric Actuator,
Par.
no.:
Parameter name /
description:
Expert parameters
Limits
Min/Max:
Unit
type:
Default
setting:
Commission
setting:
5000
5000
Servo position feedback signal
20
Encoder Offset
Pos. feedback offset counts.
0-10000
count
Servo position feedbackfail testing
Position limit Timeout
21.
Actuator out of range
Wrong Way Timeout
22
Rotation opposite to cmd
Wrong Way cmd level
Feedb.
alarm 1
0 - 3.000
sec.
0.200
0.200
Feedb.
alarm 2
0 - 3.000
sec.
0.500
0.500
20-20000
count
/ 5ms
300
300
0.001-3.000
sec.
0.300
0.300
0.001-3.000
sec.
0.500
0.500
1 - 100%
%
25
25
0 - 20.0
sec.
5.0
10.0
23.
Actuator rotation opposite
to cmd
24
Too Slow Timeout
at fast speedcmd
25
Too Slow Timeout
at slow speedcmd
26
Too Slow, slow speed
(% of max speedcmd)
Feedb.
alarm 2
Other
Status
Other
Status
Other
Status
27
Too Slow Block, Timeout
Blocks only if time is
adjusted above 0.0 sec.
Feedb.
alarm 8
Feedbackfail,
alarm
nr.
01
02
Data out of range
Wrong way
08
10
Too slow (or not moving)
Loopfail
Continuously tested
These alarms are only tested
in running mode.
Continuously tested
Idle Mode
28
Plus Key, actuator speed.
29
Minus Key, actuator speed.
30
Range Limitations On.
31
blank
32
Setting of actuator behavior in
Idle Mode. (In Stop)
33
34-36
(Double speed if rate is on)
(Double speed if rate is on)
Limited range: 0 - max Pump Index
Actuator force in Idle Mode
(Max speed cmd) if activ in idle
blank
AO-20064-A
0-1000
count
100
200
0-1000
count
100
200
text
Lim-On
Not saveable
Maker
passive
Lim-On or
LimOFF
Maker,
Active,
Passive,
Passive-Block
text
0 - 2047
count
(MAN B&W
= passive)
300
300
34
Parameterlist
Electric Actuator,
Par.
no.:
Parameter name /
description:
Expert parameters
Limits
Min/Max:
Unit
type:
Default
setting:
Commission
setting:
Major Alarm
37
38
K2
Relay
39
Alarm input filter
0 - 25
sec
1.0
1.0
Holding on delay
0 - 20
sec
5.0
5.0
Holding off delay
0 - 20
sec
5.0
5.0
Digital input signals
Ch. 09 Ext. Stop ( f / Safety)
“Or” mask
Ch. 15 Servo Ampl. Fail. (DSU)
“Or” mask
Ch. 16 Manual Mode. (DSU)
“Or” mask
True / False
text
True
True
True / False
text
False
False
True / False
text
True
True
43
Block when Low Voltage
True/False
text
True
True
44
Actoator Rotation Direction
CW / CCW
text
from
dip sw.!
CCW
40
41
42
Clock Wise or Counter Clock Wise.
ch 4, Fuel output signal. Actuator position.
45
46
47
48
Counts low
(dac1 = 8bit)
Counts high
(dac1 = 8bit)
Technical low
(100% = max actuator stroke)
Technical high
(100% = max actuator stroke)
0 - 255
count
50
(4mA)
0 - 255
count
254
(20mA)
50
254
0 - 100.0
%
25
25
0 - 100.0
%
100.0
100.0
On/Off
text
Off
Off
disable or
enable
text
disable
Disable
Output signal test
49
Test switch
50
Test switch
51
Idle mode only
Idle mode only
Brake On
(ch 12)
Torque
enable (ch 7)
blank
AO-20064-A
35
Parameterlist
Electric Actuator,
Par.
no.:
Parameter name /
description:
Expert parameters
Limits
Min/Max:
Unit
type:
Default
setting:
Commission
setting:
Analog readable signals,
52
53
54
55
0
14
-14
3
Actuator, Command Position (counts ) same as param. 02, but in counts.
Actuator, Actual Position (counts) same as param. 03, but in counts.
Actuator, Cmd/Actual Difference (counts) same as param. 04, but in counts.
Servo speed Cmd, from servo speed regulator ( Ch.13 output  2047 counts)
Digital readable signals,
56
57
58
59
60
61
62
True
Handle in stop position.
Ch.09, External Stop (Safety System SHD).
Ch. 15, Servo Amplifier Fail active.
Ch. 16, Manual Mode active.
Ch. 12, Dig. output - Brake deactivated. Run signal
Ch. 07, Dig. output - Torque enable signal
Block Condition
False
False
False
False
False
0000
0001 Low Voltage
0002 Feedback Fail
0004 Indata error
0010 Reg. Watch Dog (Hardware)
0020 Reg. Fatal Error (Double Pickup Fail)
0100 Servo Amp. Fail (Power 440V, DSU int.24V, Thermic Switch in motor, Servo amp.)
0200 Buffer com. error (NA-1105)
63
blank
64
Signals from Dac2, Dac3 & Dac4.
true/false
65
System Date, If adjusted and saved,
all adjustments will be reset
dd-mm-y
Special parameters,
text
False
7017
( at power up ).
66
67
68
99
Eprom checksum (readable)
Processor Speed
Process. card type
Desimal point for
Fuel parameters 2,3 & 4
Service code
AO-20064-A
false
ISCF
5 or 8
MHz
8 MHz
dp0 - dp2
text
Fu-dP0
Set to
8 MHz
Fu-dp0
47.
36
Parameterlist
Gereral Information, Regulator.
REGULATOR
OpCode 0,
Param. 14
selected nr.
0
1
2
3
4
5
6
7
8
REGULATOR
OpCode 0,
"Reg. General Information"
param. 4
Displayed value
Propeller pitch
1.0
RPM command difference (Control room - bridge) (RPM)
-22.0
RPM command alternative (The one not in use) (RPM)
45.0
RPM command from control room (RPM)
23.0
RPM command from bridge (RPM)
45.0
Fuel command to actuator (% fuel)
0.0
Lowest fuel limiter (% fuel)
45.0
Margin to lowest fuel limiter (% fuel)
45.0
Identity of lowest active fuel limiter:
0.0
identity value
0.0 = No Fuel Limiter
4.0 = Zero Pitch Fuel Limiter,Cpp only
1.0 = Torque Fuel Limiter
5.0 = Start Fuel Setpoint
2.0 = Scav. air Fuel Limiter
3.0 = Manual Fuel Limiter
99.0 = Maximum Fuel Output
Gereral Information, Actuator.
REGULATOR
OpCode 1,
Param. 76
selected text
0
Cmd Rpm
1
Eng. Rpm
2
torque
3
Power
4
Load
5
PuMP I
6
ACt. MM
7
AnGLE
8
Count
ACTUATOR,
param. 6
"Act. General Information"
Value displayed
Speed setpoint ( 0-300 Rpm )
Actual engine speed ( 0-300 Rpm)
Fuel pump position cmd. ( 0 - 100 %) without nonlinear compensation
Engine Power ( 0 - 100 %) = (Fuel cmd * Engine speed)
Fuel pump position cmd. ( 0 - 100 %) with nonlinear compensation
Pump Index ( 0 - 150 Pump mm)
Actuator stroke (0 - 100 mm)
Angle (0 - 42 Deg.,) Only relevant for El. Actuator
Actuator Command (Counts)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
System in test, Regulator.
OpCode 0,
Param. 19
Readable
Info.
"System in test"
00 = Normal
01 = Special Mode; - Test, Calibrate or Self-Test
02 = Special Mode; - Fuel Setpoint (Regulator Bypass)
04 = Special Mode; - RPM Measured, Step Signal Added.
08 = not used
10 = Simulation; - Analog Input
20 = Simulation; - Digital Input
40 = Special Mode; - Fixed Fuel (indicator diagram mode)
80 = Simulation; - Multi-freq. sinus noise (for Notch Filter)
AO-20064-A
change with;
OpCode 0, Param. 1
Panel, Push Button
Panel, Push Button
Panel, Push Buttons
OpCode 2, dig.Chan.
OpCode 0, Param. 20
OpCode 1, Param. B8
37
Parameterlist
Alarm codes, Regulator.
ALARMS
ERROR
POSSIBLE CORRECTIVE MEASURE
OpCode 0
par. 11 par. 12
normal
normal
No errors
ALr 1
30Loop
ALr 2
31Loop
ALr 3
30Sign
Adaptor Ch.30
Loop Fail
Adaptor Ch.31
Loop Fail
Adaptor Ch.30
Signal Fail
ALr 4
31Sign
Adaptor Ch.31
Signal Fail
ALr 5
bUFF H
Data Buffer NA-1105,
Hardware not responding
ALr 6
bUFF C
Data Buffer NA-1105,
Communication error.
Checksum error.
ALr 7
SiMuLA
System in test
ALr 8
FAtALr
Adaptor Ch.30 & 31
Dual Rpm Detector Fail.
ALr 9
17-Err
ALr10
18-Err
ALr11
19-Err
ALr12
20-Err
ALr13
21-Err
Adaptor Ch.17
Rpm Cmd (Ctrl.Room)
Adaptor Ch.18
Rpm Cmd (Bridge)
Adaptor Ch.19
Pitch fedback.
Adaptor Ch.20
Scav Air Pressure
Adaptor Ch.21
normally not used !
ALr 15
LoVolt
AO-20064-A
Power Monitoring Card,
NN-825
Rpm detector fail
Check inside DGU at adaptor-card
ch 30 / 31 and find which led is on.
a) Upper diode indicate open circuit
b) Lower diode indicate short circuit.
a) Check pickup distance
b) Check pickup for dirt
c) Change pickup
d) Check the supply voltage in the pickup,
box, terminal 1-3 and 5-7.
e) Change Counter IC-18a on NN-791
f) Change the NN-791 processor card
Outdata error
Check inside DGU and locate NA-1105.
See if the card or the flat cable has loosend or is
damaged.
Change the Data Buffer or the processor cards.
System in test
Reset test function.
Rpm detector fail
a) Check all the above possibillities .
Indata error
a) Check cables for short/open circuit.
b) Replace or adjust adaptor-card.
c) Check transducer.
d) Check for the “AC” parameter and see if
Actual Counts is changed when changing
the input signal.
e) Check adjustments in OpCode 2.
signal error limits (EL, EH) and
scale (CO, CL, CH, tL, tH).
Low Voltage
Check inside DGU and locate NN-825.
See which led diode is lighting
38
Parameterlist
Alarm codes, Actuator.
ALARMS
ERROR
POSSIBLE CORRECTIVE MEASURE
OpCode 0
par. 11 par. 12
normal
normal
No errors
ALr 1
rAnGE
ALr 2
Wr Way
ALr 3
StEP
ALr 4
too SLo
Feedback fail,
Signal out of range.
Feedback fail,
actuator wrong way
rotation.
Feedback fail,
Abrupt change.
Feedback fail,
Too Slow response.
ALr 5
Loop F
Feedback fail,
Loop Fail.
ALr 9
reg-dG
Regulator Watch Dog
passive.
ALr 12
bUFF H
ALr 13
bUFF C
Data Buffer NA-1105,
Hardware not responding
Data Buffer NA-1105,
Communication error.
Checksum error.
ALr 14
SErVo
Servo Amplifier fail
AO-20064-A
Feedback fail
Check actuator function in test mode.
Adjust the range if nesseserry.
Adjust the Wrong Way Timer if nesseserry (see
actuator parameter adjustments).
Replace the Parvex ABS or SBS.
Check feedback cable or plug. Replace the NN1105 data buffer or absolut encoder.
Check mechanical limits or restrictions. Check
fuelrack for friction. Increase the adjustment of the
Too Slow Timer or Cmd.
Increase the actuator gain.
Check feedback cable and plug. Replace the NN1105 data buffer or absolut encoder.
Indata error
a) Check the power plugs to the proc. card.
b) Replace the processor card.
c) Check the flatcables to P1 plugs.
d) Replace the PPI on actuator processor card.
Check inside DGU and locate NA-1105.
See if the card or the flat cable is loose or damaged.
Change the Data Buffer or the processor cards.
Servo amplifier fail
a) Servo power supply(220/440V, 3phase),
b) Servo drive enable signal in DSU,
c) El.motor thermic shut down,
d) 24 Volt in DSU not operative.
39