Trench Heating Units A good climate and a clear view

Trench Heating Units
A good climate
and a clear view
Katherm HK, Katherm QK, Katherm QK nano, Katherm QE
Genau mein Klima. Exactly my kind of climate.
Intro
Floor trenches are the first choice for
high-end rooms with floor-to-ceiling glazing.
Conventional radiators often obstruct the
view and draw unwanted attention to
them. They clash with the architectural
interior vision. Kampmann floor trenches are
installed in the floor in front of the glazing,
blending into the overall interior design and
providing effective temperature control.
Full space heating and cooling, residual heat
provision, cold air screening and façade
ventilation: Kampmann trench heaters
guarantee a comfortable interior climate
even under difficult conditions.
Inhalt
4
17
22 34 Areas of application
References
Products
In detail
Company
Hotels
Offices and
commercial buildings
Showrooms and
sales floors
Churches and
historical buildings
Image title: Faculty of
Cultural and Social
Science at the University
of Salzburg, Austria
Nursery schools
and schools
Residential
buildings
3
Blends harmoniously into
every room interior.
Faculty of Cultural
and Social Science,
University of Salzburg,
Austria
600 Katherm HK trenches with roll-up
grilles were fitted to the external
façade. EC tangential fans provide
filtered, heated or cooled air on
demand. As such, Katherm HK
provide a good climate from the floor.
Swedbank AB,
Stockholm,
Sweden
Transparency is the most obvious
feature of the full-height windows.
The view remains undisturbed
thanks to 731 Katherms mounted in
the floor as a continous line. The
trench heating units with natural
convection provide effective cold air
screening.
The installed Katherms stand out
with their low thermal mass and are
easy to control. Quick delivery and
fast installation with Eurokonus valve
connections ensured a seamless and
smooth project flow in Sundbyberg.
Heating and cooling
energy-efficiently.
Adapts
to any view.
Kristall-Holzhafen,
Hamburg,
Germany
Katherm HK trench heating units
provide heating or cooling in all
apartments, supplying on-demand
filtered, heated or cooled recirculating
air. The tailor-made trench heating
units respond flexibly to the needs of
the occupants: integrated sockets,
data jacks and even a sound system.
A decentralised indoor climate from
the floor provides a clear view of the
breathtaking panorama of the
Holzhafen timber port, the oldest
preserved docks in Hamburg.
ADAC Headquarters,
Munich,
Germany
In the ADAC headquarters in Munich,
a bespoke version of the Katherm HK
with energy-efficient EC tangential
fans ensures quiet operation and
energy savings. This trench version
channels filtered, heated or cooled
ambient air from the floor in line
with current demand.
In perfect symmetry.
Katherm HK and Katherm HK empty
trenches were individually adapted
to the polygonal external façade.
Manufactured as customised units,
the encased units harmoniously
meet the architectural and design
specification. They also help to heat
the room up faster.
Blending in
unobtrusively.
MobileLifeCampus,
Wolfsburg,
Germany
The Volkswagen AG building features
over 800 networked trench units.
Heating and cooling is largely
provided by 600 Katherm HK units.
There are also an additional 200
Katherm units of other types.
Some 1.2 kilometres of linear Optiline
grilles produce a uniform appearance.
Kampmann Tandem door air curtains
also provide an optimum climate in
the door areas.
Saving energy on
every metre.
SIDI Sport,
Maser (Treviso),
Italy
110 metres of Katherm HK trench
units create perceptible interior
comfort in the new building of the
renowned sporting goods
manufacturer. The trench units
are synonymous with on-demand,
individually adjustable heating
or cooling from the floor. The
Katherm HK configuration with
EC tangential fans guarantees
energy-savings of approximately
60 % over conventional fans.
Empty trenches were connected to
the active units to create a coherent
interior architectural design. Natural
aluminium anodised roll-up grilles
and matching central covers enhance
the sophisticated appearance.
Product | Made-to-measure solutions
Trench heaters
are also available as
customised units
Blowing air gently into
the entire space.
Kampmann is the undisputed market leader
Air conditioning systems are constantly evolving
in trench heating. We have gained this position
at Kampmann, which has enabled us to repeatedly
not least due to our numerous made-to-measure
reduce the dimensions of our Katherm HK. The
solutions, adapted to specific applications.
Katherm HK is now 30 mm shallower and 50 mm
Electric solutions are popular on the international
slimmer than its predecessor without compromising
market. Kampmann meets this demand with its
on output (measured in accordance with EN 16430).
Katherm QE, the trench heater with EC tangential
Thanks to redesigned components, it now delivers
fan-assisted convection and electric heating coil.
optimised air flow for higher outputs. The Katherm HK
No water connection is needed. High heat outputs
is the trench unit that also provides cooling.
with low noise levels are guaranteed.
The Katherm QK nano is even more space-saving than
The Katherm QK is whisper-quiet. It is also available in
the Katherm HK, only 70 mm in height and 165 mm
120 versions. It comes in non-standard lengths, with
in width. The Katherm QK nano is used wherever
curved trench, mitres, cut-outs for columns or angles.
depth is restricted for underfloor solutions and the
Its ultra-long EC fan covers the entire heating range,
room volume needs to be used to the full.
from full space heating to cold air screening.
Schloss Elmau
Retreat, Germany
Katherm QK trench heaters quietly
and quickly warm up the space.
The EC motor-operated fan blows
heated air up the cool window fronts
before it is drawn into the room
and heats it evenly and without
draughts. Katherm HK also provide
additional heating as well as
cooling. The KaControl system links
the trench units to the building
management system.
The air outlets on the Katherm units
stylishly complete their appearance.
Lacquered oak roll-up grilles were
selected for the Retreat, which
wonderfully enhance the rest of the
interior.
17
18 Product | Elbphilharmonie
Product | Elbphilharmonie
Katherm made-to-measure
trenches
for the Elbphilharmonie
in Hamburg
Kampmann is known for finding solutions to
The architectural fittings in the building provided
even the most challenging applications. The
a challenge when implementing the project. Usually
Hamburg Elbphilharmonie, one of Europe’s most
trench heating and cooling units are positioned as
exciting new-build projects, is a case in point.
close as possible to the glazed façade.
Kampmann special Katherm HK trench heating and
cooling units were developed especially for this project.
This was impossible at the Elbphilharmonie, the
The units are used in rooms which musicians use to
Katherm HK had to be installed a metre from
warm up their instruments. Very specific temperatures
the windows.
are subsequently required in these rooms. In addition,
a large volume of air has to be fed into the rooms
As cooling requirements were constantly changing,
to ensure that they are correctly air conditioned. And
between 2009 and 2013 numerous measurements
of course the concentration of the musicians must
of the non-standard trenches were taken in the
not be disturbed by external noise!
Kampmann Research & Development Centre (FEC).
The final measurements were taken in June 2013
According to these key specifications for the project,
for the heating and cooling outputs with particular
the units had to be practically silent. The ultra-
focus on the latter.
silent Katherm HK tipped the balance in favour of
Kampmann when the order was awarded.
The Katherm HK units were finally delivered in two
different versions in a special non-standard design,
Ultimately the plan was to cover the window façades
in a width of 300 mm (the standard trench is 40 mm
of the rooms with heavy fabric curtains. At short
wider) and a single row of tangential fans, and also
notice, the standard Kampmann HK with one row of
in a width of 470 mm with two rows of tangential
tangential fans was transformed into a non-standard
fans, all units in 19 different lengths.
trench with two rows of fans, to ensure that the air
could be distributed noiselessly in front of and behind
the curtains.
19
20 Product | Grilles
Product | Grilles
Individual
Versatile, aesthetic,
resilient
Grille colours
A harmony of material
and design
Cut-outs with a cover plate
Aluminium
Natural anodised E6 / EV1
Aluminium
Brass anodised E6 / EV3
Aluminium
Black anodised E6
Aluminium
Bronze finish E6 / C31
Cut-outs in the grille itself
Aluminium
Painted DB703
Aluminium
Painted white
Brass
Natural CuZn 44
Stainless steel
Natural
Stainless steel
Polished
Oak
Varnished
Merbau
Varnished
Integrated lighting
Integrated sockets
Mitre with profile
Mitred
The diversity of Kampmann design grilles sets
them apart. Many models can be used on both
Alignment of the bar position
Curving of roll-up grille
Curving of linear grille
curved designs
significantly extends the “life” of the grilles. The grilles
integration of structural elements, like columns,
pillars etc.
design options enable even difficult situations to be
corner designs with different angles
covered with ease. Our experts can take site
integration of lighting or sockets
dimensions on your behalf. The following options
polygonal connections to the building facade
are available:
Middle cover in the building grid
anodised aluminium, stainless steel, wood
sides, by simply turning the grilles, a feature, which
can also be shortened and extended. The various
Mitre with cover
various cover plate materials possible: brass,
21
22 In detail | Selection aids
In detail | Selection aids
Which Katherm do I need?
HK, QK, QK nano, QE
Demand
”I would like to
be able to
heat and cool.”
Product
Description
Katherm
The totally redesigned Katherm HK permits
demand-led heating from the floor. It
also features a cooling function. With its new
incremental lengths, the Katherm HK is the
right solution for the most diverse building
requirements. The redesigned EC tangential fan
runs silently and is extremely energy-efficient.
HK
Benefits
cost-effective efficient heating AND
cooling at low noise levels
in line with the Hygiene Directive
VDI 6022
2-pipe or 4-pipe system for
individual comfort in every room
Performance data / Features
Trench height
[mm]
Trench length
[mm]
Trench width
[mm]
Heat output
Cooling output Convection
Heating
Cooling
Ventilation
Control
530 – 14278 W1)
86 – 2665 W2)
116 – 3256 W3)
EC tangential fan
LPHW
CPW
optional (indirect)
KaControl control system or
electromechanical control as standard
optional integration into KaControl
networks or building automation
systems, such as KNX, Modbus or LON
130
915
1200
1700
2000
2500
3000
290
160
950
1200
1700
2000
2500
3000
320
262 – 5982 W1)
-- EC tangential fan
LPHW
----KaControl control system or
electromechanical control as standard
optional integration into KaControl
networks or building automation
systems, such as KNX, Modbus or LON
112
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
3200
182
207
232
Heat output
Cooling output
248 – 3524 W1)
---
70
165
Convection
Heating
Cooling
Ventilation
Control
EC tangential fan
LPHW
----configurations electromechanical control
24 V, electromechanical control 230 V
or KaControl
optional integration into KaControl
networks or building automation
systems, such as KNX, Modbus or LON
900
1400
1800
2100
2600
112
825
1250
1700
207
”I would like
to heat using
low water
temperatures.”
”I have very
little space.”
Katherm
QK
Katherm
QK
nano
”I would like
to heat
electrically.”
Katherm
QE
The Katherm QK is whisper-quiet. It is
also available in 120 versions. It comes
in non-standard lengths, with curved trench,
mitres, cut-outs for columns or angles. Its
ultra-long EC fan covers the entire heating
range, from full space heating to cold air
screening.
made-to-measure trench lengths
high outputs at small trench depths,
even when used with low
temperatures
whisper-quiet EC technology
Heat output
Cooling output
Convection
Heating
Cooling
Ventilation
Control
The Katherm QK nano provides high heat
outputs from minimal dimensions. With
a trench height of only 70 mm and a trench
width of only 165 mm, it can be used wherever
conventional trench solutions are impossible
due to a lack of space. Due to the limited space
in the unit, the interplay of the EC tangential
fan and high-output copper-aluminium
convector has been optimised in the Katherm
QK nano.
extremely low overall height
maximal use of the floor space
usual quietness and
high-performance
The Katherm QE is the ideal solution when
a LPHW convector cannot be used. It stands
out on account of its energy-saving and
ultra-quiet EC tangential fans. The high-output
electric heating element delivers high heat
outputs. coupled with low sound levels.
heating without water
fast warm-up at low sound
emissions
ideal alternative to convectors
with LPHW
Heat output
Cooling output
160 – 2400 W4)
---
Convection
Heating
Cooling
Ventilation
Control
EC tangential fan
electric heating element
----simple, convenient electric control
by via room thermostat or BMS
ready-wired connection and control
box with integral continuously
variable power control
at LPHW 75 / 65 °C, EAT = 20 °C
at CHW 16 / 18 °C, EAT = 27 °C, 48 % rel. humidity
3)
sensible cooling output at CHW 6 / 12 °C, EAT = 24 °C, 50 % rel. humidity
4)
electric heating output at control voltage BMS 2-10 V
1)
2)
23
24 In detail | Katherm HK
In detail | Katherm HK
Product benefits
slimmmer, shallower and more powerful than ever before
EC fan, quiet and energy-efficient
heat and cooling output measured according to EN 16430
Technical details
Unit width
Unit height
Unit length
Sound power
level 4)
B
C
A
2-pipe
4-pipe
2-pipe
[mm]
[mm]
[W]
[W]
[W]
[W]
[dB(A)]
[dB(A)]
915
690 – 2075
530 – 1206
107 – 451
108 – 450
<20 – 39
<28 – 47
1200
1176 – 3602
936 – 2180
191 – 814
192 – 807
<20 – 41
<28 – 49
1700
2135 – 6040
1720 – 3787
354 – 1387
355 – 1357
<20 – 41
<28 – 49
2000
2404 – 7512
1985 – 4755
398 – 1768
398 – 1744
<20 – 44
<28 – 52
2500
3363 – 10026
2773 – 6361
560 – 2339
562 – 2285
<20 – 44
<28 – 52
3000
4324 – 12479
3561 – 7967
724 – 2880
724 – 2839
<20 – 44
<28 – 52
950
780 – 2338
602 – 1357
116 – 543
116 – 525
<20 – 36
<28 – 44
1200
1312 – 3967
1030 – 2340
197 – 917
195 – 888
<20 – 38
<28 – 46
1700
2125 – 6487
1695 – 3888
313 – 1460
311 – 1414
<20 – 40
<28 – 48
2000
2765 – 8457
2214 – 5084
410 – 1912
407 – 1852
<20 – 41
<28 – 49
2500
3579 – 10986
2881 – 6642
524 – 2442
520 – 2365
<20 – 42
<28 – 50
3000
4646 – 14278
3749 – 8645
698 – 3256
693 – 3153
<20 – 43
<28 – 51
130
Katherm
290
160
4-pipe
Dimensions
Room side
115
Cross section
Window side
Trench length
305
50
165 – 210
Front view (example: 2 supply air modules)
80
165
340
ø 80 10 65
C
Window side
B
31 4 130
A
Finned convector length 655
240
Unit length
Max. number of supply
air modules
340
[mm]
420
Trench heating and cooling.
EC tangential fan convection. Quiet and
energy-efficient.
Sound pressure
level 3)
[mm]
320
HK
Sensible
cooling output 2)
Heat output 1)
Room side
915 / 950
1
1200
2
1700
3
2000
4
2500
5
3000
6
Plan view (without cover plate), example HK 320 with supply air modules
Installation example Katherm HK 290
Installed in a raised floor, H = 160 mm, W = 290 mm,
4-pipe, cooling installation
Installed in a raised floor, H = 180 mm, W = 310 mm,
4-pipe, with supply air connections, cooling installation
Exterior window
Exterior window
Air outlet
Air intake
5
3
Installation example Katherm HK 290
with supply air function
4
2
1 Concrete slab
2 Raised floor
3 Floor duct
Air outlet
Air intake
5
3
4
4 High performance
1
convector
5 Filter (optional)
2)
1 Concrete slab
2 Raised floor
3 Floor duct
4 High performance
convector
1
at LPHW 75 / 65 °C, room air temperature 20 °C
at CHW 6 / 12 °C, room air temperature 24 °C, 50 % relative humidity
3)
The sound pressure levels were calculated with an assumed room insulation of 8 dB(A). This corresponds to a distance of 2 m,
a room volume of 100 m3 and a reverberation time of 0.5 s.
4)
Sound pressure level < 20 dB (A) and sound power level < 28 dB (A) outside the usual measuring and audible range.
1)
2
5 Filter (optional)
25
26 In detail | Katherm QK
In detail | Katherm QK
27
Product benefits
project solutions are available for all geometries e.g. mitred corners,
curved designs, column recesses or chamfered trenches
optimised for use with low temperatures
heat outputs in accordance with EN 16430
Technical details
Model
Katherm
At LPHW 35 / 30 °C
Sound power
level
At LPHW 75 / 65 °C
At LPHW 55 / 45 °C
At LPHW 45 / 35 °C
[W]
[W]
[W]
[W]
[dB(A)]
[dB(A)]
Katherm QK 182
455 – 2851
267 – 1676
175 – 1099
108 – 674
28 – 36
36 – 44
Katherm QK 207s 2)
519 – 3250
304 – 1911
200 – 1253
123 – 768
---
---
Katherm QK 207
788 – 4938
473 – 2963
315 – 1975
197 – 1235
28 – 36
36 – 44
Katherm QK 232s 2)
843 – 5284
506 – 3170
337 – 2113
211 – 1321
---
---
Katherm QK 232
954 – 5982
553 – 3463
358 – 2244
217 – 1357
28 – 36
36 – 44
Trench length L
Front view
Room side
max. 146
112
Window side
B
Cross section
Trench length L
Window side
A
Trench
height
Trench
width
[mm]
[mm]
[mm]
112 (+4)
1000 – 3200
Katherm
B
Finned convector length
Trench heating unit with EC tangential
fan convection. All-purpose, individual,
made-to-measure.
Sound pressure
level
Dimensions
4
QK
Heat output 1)
QK 182
182
QK 207s
207
QK 207
207
QK 232s
232
QK 232
232
Room side
Plan view, e.g. QK 207
Installation example QK 182
Installation example QK 232
Installed in screed, H = 112 mm, W = 182 mm
Installed in a raised floor, H = 112 mm, W = 182 mm
Exterior window
Air outlet
Air intake
4
5
1
2)
Air outlet
Air intake
1 Concrete slab
2 Heat and sound
3
3
insulation
3 Screed
4 Floor duct
2
1)
Exterior window
5 High performance
convector
with unit lengths of 1000 mm to 3200 mm, room air temperature 20 °C
provisional performance data
2
4
1
1 Concrete slab
2 Raised floor
3 Floor duct
4 High performance
convector
28 In detail | Katherm QK nano
In detail | Katherm QK nano
Product benefits
savings on floor space at usual high heat outputs
new filigree FineLine grille
heat outputs in accordance with EN 16430
Technical details
Trench height
Katherm
QK
Heat output 1)
Sound pressure
level 2)
Sound power
level
Electromechanical
model
24 V
230 V
electromechanical
model or
KaControl
[mm]
[mm]
[W]
[W]
[W]
[W]
[W]
[dB(A)]
[dB(A)]
900
1100
248 – 772
120 – 461
321 – 928
295 – 874
45 – 229
<20 – 34
<28 – 42
1400
1600
496 – 1545
241 – 922
642 – 1857
590 – 1748
90 – 458
<20 – 37
<28 – 45
1800
2000
744 – 2317
361 – 1384
963 – 2785
885 – 2621
135 – 687
<20 – 39
<28 – 47
At LPHW
75 / 65 °C
At LPHW
55 / 45 °C
At LPHW
90 / 70 °C
At LPHW
82 / 71 °C
At LPHW
40 / 30 °C
2100
2300
935 – 2912
454 – 1739
1211 – 3500
1112 – 3294
170 – 864
<20 – 40
<28 – 48
2600
2700
1132 – 3524
549 – 2105
1465 – 4236
1346 – 3987
206 – 1046
<20 – 41
<28 – 49
Dimensions
24 V electromechanical model
165
nano
4
Window side
70
Trench length A
197
Front view
Cross section (enlarged),
shown with transverse grille
Window side
Trench height
A
Finned convector
length B
[mm]
[mm]
900
435
197
Trench heating unit with EC tangential
fan convection. Top performance from
smallest dimensions.
Finned register length B
165
410
Room side
Plan view (without cover plate)
1400
870
1800
1305
2100
1640
2600
1985
Installation example
Installation example
Installed in screed, H = 70 mm, W = 165 mm
Installed in a raised floor, H = 70 mm, W = 165 mm
Exterior window
Air outlet
Exterior window
Air intake
Air outlet
Air intake
1 Concrete slab
2 Heat and sound
5
4
2
1
1)
2)
3
insulation
3 Screed
4 EC tangential fan
5 High performance
convector
3
2
4
1
at room air temperature 20 °C
The sound pressure levels were calculated with an assumed room insulation of 8 dB(A).
This corresponds to a distance of 2 m, a room volume of 100 m³ and a reverberation time of 0.5 s (in accordance with VDI 2081).
1 Concrete slab
2 Raised floor
3 EC tangential fan
4 High performance
convector
29
30 In detail | Katherm QE
In detail | Katherm QE
Product benefits
2-stage safety switch comprising safety thermostat and temperature control
with air guide panels for optimum air guidance through the heating coil and out of the trench
shallow trench widths and heights to blend discreetly into the interior
Technical details
Trench width
Trench height
Height / Depth of
heating element
Trench height
Finned
coil length
Heat output
max.
Sound pressure
level, max1)
Sound power
level, max.
[mm]
[mm]
[mm]
[mm]
[mm]
[W]
[dB(A)]
[dB(A)]
825
400
800
28
36
1250
835
1600
31
39
1700
1270
2400
33
41
207
112
25 x 50
Katherm
Front view
116 – 155
Window side
207
112
Side view
Trench length 825 / 1250 / 1700
Window side
207
112
Finned register length 400 / 835 / 1270
207
25
351,5
4
50
227
Room side
Plan view (without cover plate)
Tangential fan convection
with electric heating element.
Cross section (enlarged)
Installation example
Installed in a raised floor, H = 112 mm, W = 207 mm
Exterior window
Air outlet
Air inlet
5
4
2
1
1)
3
1 Concrete slab
2 Screed
3 Floor duct
4 Electric heating element
5 EC tangential fan
6 Heat and sound insulation
The sound pressure levels were calculated with an assumed room insulation of 8 dB(A).
This corresponds to a distance of 2 m, a room volume of 100 m³ and a reverberation time of 0.5 s (in accordance with VDI 2081).
116 – 155
QE
Dimensions
31
32 In detail | EN 16430
In detail | EN 16430
28 °C
EN 16430
New EN standard for
trench heating / cooling
Thermal outputs and cooling capacities finally
Comparison of air flow patterns
comparable! Until now there has been no
The diagram shows the major differences of the air
uniform standard for determining the performance
flow of short-cut optimised and non short-cut
of heating / cooling trenches. The EN 16430
optimised heating / cooling trenches in cooling mode.
valid as from December 2014 provides common
With the short-circuit optimised model the air at the
standards which apply with immediate effect.
façade rises significantly higher, blends and penetrates
The EN 16430 defines details for measuring
deeper into the room at a higher temperature.
performance data for heating / cooling trenches under
The result is a more even temperature distribution
real-life conditions and puts an end to uncertainties
and higher comfort in the occupied zone.
28 °C
in the design and in comparing performance data of
different manufacturers.
Heating / cooling trenches with a high short-cut
Thermal outputs and cooling capacities
the room. Performance data based on the entering air
The standard defines details for measuring
temperature are especially misleading as this can be
performance data for heating / cooling trenches based
significantly lower than the reference air temperature
on EN 442.
(room air temperature).
Three parts of EN 16430 specify the measurements.
The development and design of the Katherm HK have
Part 1 Technical specifications and requirements
been optimised to minimise the short-cut as far as
Part 2 Test method and rating for thermal output
technically possible. All performance data refer to the
Part 3 Test method and rating for cooling capacity
750 mm
percentage only provide part of the performance to
reference air temperature measured at a distance of
2 m from the façade, the area in the room occupied by
The EN 16430 part 3 considers the special
people.
requirements for cooling mode. The reference air
temperature is measured in the centre of
the test booth at a distance of 2 m from the façade
at a height of 0.75 m above FFL. The reference air
temperature must not be mixed up with the entering
air temperature into the coil which may deviate
due to the inevitable short-cut between leaving air
17 °C
26 °C
and entering air.
2000 mm
33
34 Company | Technical innovation
Company | Technical innovation
Simulation of a room climate in
the air flow laboratory
Technical innovation
arises in the Research & Development Centre
of Kampmann
Since 2008 the Research & Development Centre is
adjacent to the headquarters of the Kampmann
GmbH. It is one of the most modern facilities of its
type and houses an air flow laboratory, a multipurpose
laboratory and a sound chamber. The equipment is at
the highest technical level and fulfills the customer's
request for transparent product data.
The R & D Centre (FEC) enables the company to
develop new standard products
continually improve its products
undertake applied research
provide detailed analysis of the units to be tested
undertake standard tests.
The in-house Research &
Development Centre (FEC) at the
headquarters in Lingen (Ems)
Sound
chamber
35
36 Company | Kampmann
Company | Kampmann
37
Kampmann.
With over 720 employees at
16 locations around the world,
Kampmann is one of the major
players in the construction
and building services industries.
Kampmann systems for heating,
cooling and ventilation are
at the forefront of different
market segments today.
Consistently there.
Consistently cooperative.
Consistently sophisticated.
Consistently solution-focused.
Kampmann GmbH has continuously evolved since
Wherever our customers and partners
We believe that fairness is the best
We leave nothing to chance. Including
A hotel needs a different climate than
the company was founded in 1972. Exceptionally well
need us: We are there. Around the
foundation for sustainable success.
the future. We check and recheck. We
a retail outlet. And when the southern
trained specialist personnel in Germany and Poland
corner. Around the globe. On the web.
That a handshake can mean more than
enhance and optimize. And we don’t
side of an office block needs to be cooled
produces quality products for customers around
We are there transforming today’s
a 100-page contract. And that mutual
let go until we are thoroughly satisfied.
down, the north may still need warming
the world. Kampmann took its first steps in the United
challenges into tomorrow’s solutions.
respect comes from seeing eye-to-eye.
With a love for detail that is only
up. Our customers’ requirements are
Kingdom in 1983 and has been selling its products
We are there when the standards and
This is the way we are – and this is
rivalled by our passion for thinking in
highly specific. So are our solutions. Which
there as Kampmann UK Ltd. since 2013. Kampmann
norms of the future are defined.
how we interact, with our customers,
systems, we maintain and nurture
means that even the trickiest challenges
Heating, Cooling, Ventilation Ltd., established in 2016,
Down-to-earth, attentive, available at
with our suppliers, with each other: a
our spirit of discovery and invention
have a predictable (and most satisfying)
is responsible for sales in the USA and Canada.
any time. And always ready to go the
cordial and sincere invitation to genuine
that drives us from good ideas to
outcome: We turn complexity into clarity
extra mile.
partnership.
useful products.
– and create the perfect climate.
38 Unternehmen | Kampmann
Further products
A selection of
our product range
International contact
INT Kampmann GmbH
T + 49 591 7108-660 | Kampmann.eu/contact/international
Design Grilles
Decorative air outlets for your
underfloor trench system.
Fan Coils
Environmentally-friendly air conditioning
of buildings for today and tomorrow.
We have the right solution for every
project.
Contact Europe
AT
Kampmann GmbH Representative Office Austria
T + 49 8141 3991-0 | Kampmann.at
HU Kampmann GmbH Representative Office Hungary
T + 36 309 214200 | Kampmann.hu
BE
Kampmann GmbH Representative Office BeNeLux-France
T + 32 11 378467 | Kampmann.be
IT
Kampmann GmbH Representative Office Italy
T + 39 0471 930158 | Kampmann.it
CH Kampmann GmbH Representative Office Switzerland
T + 41 44 2836185 | Kampmann.ch
LU
Kampmann GmbH Representative Office BeNeLux-France
T + 32 11 378467 | Kampmann.lu
DE Kampmann GmbH
T + 49 591 7108-500 | Kampmann.de
NL
Kampmann GmbH Representative Office Netherlands
T + 31 703114174 | Kampmann.nl
DK Ribe Jernindustrie A/S
T + 45 75 4202 55 | Kampmann-dk.dk
PL
Kampmann Polska Sp. z o. o.
T + 48 24 7219185 | Kampmann.pl
FR
RU Kampmann GmbH Representative Office Moscow
T + 7 495 3630244 | Kampmann.ru
Kampmann GmbH Representative Office BeNeLux-France
T + 33 975128216 | Kampmann.fr
GB Kampmann UK Ltd.
T + 44 1932 228592 | Kampmann.co.uk
Unit Heaters
As a wall-or ceiling-mounted unit for
IE
SE
Curant Trading AB
T + 46 19 16 74 90 | Kampmann-se.se
Kampmann UK Ltd.
T + 44 1932 228592 | Kampmann.co.uk
heating, cooling or ventilation in large
spaces, industrial halls, retail outlets
and more, either as recirculating air or
mixed air units.
Door Air Curtains
For controlled screening of
air-conditioned premises with open
doors and industrial doorways.
Creates a comfortable indoor climate
and minimises energy loss.
Find more details and
products here:
Kampmann.eu
Contact North America
Contact China
CA Kampmann Heating, Cooling, Ventilation Ltd.
T + 1 604 362 0180 | Kampmann.ca
CN Shanghai DaTao Science & Trading Co., Ltd.
T + 86 21 6215 1458 | Kampmann.cn
Kampmann.eu
Kampmann GmbH
Friedrich-Ebert-Str. 128 – 130
49811 Lingen (Ems)
Germany
T + 49 591 7108 -660
F + 49 591 7108 -173
E [email protected]
W Kampmann.eu