FORM 098.202 REV 1405 DDC INTEROPERABLE PRESSURE INDEPENDENCE MODULE E-PIM DAMPER POSITION INDICATOR OPTION -DPI Option for E-PIM SERVICE PIN NETWORK CONTENTS NETWORK INSTALLATION AND CONFIGURATION ........................... 1 POSITION INDICATOR CALIBRATION .............................. 1 CONFIGURATION VARIABLES ............................................ 2 INPUT NETWORK VARIABLES ............................................ 2 OUTPUT NETWORK VARIABLES ........................................ 2 DAMPER POSITION OUTPUT ............................................. 2 TROUBLESHOOTING ............................................................ 2 NETWORK 2 6 CW W CCW 10 CCW W CW Damper Position Indicator option for E-PIM DDC Interoperable Pressure Independence Module. 9 45 60 Connect 24 VAC Power to 9 and 10 100 Models: 8 These instructions are for the Damper Position Indicator option only and are supplemental to the E-PIM Installation, Operation and Maintenance manual. See Acutherm Form 35.2 for the complete E-PIM instructions. 9 & 10 24 VAC Supply 7 9 6 10 5 11 4 12 3 13 2 14 1 INSTALLATION AND CONFIGURATION Follow the instructions as detailed in the E-PIM Installation, Operation and Maintenance manual. _Fig. 1 – E-PIM-DPI_ POSITION INDICATOR CALIBRATION The position indicator requires calibration for proper operation. Calibration requires that the E-PIM be installed on the damper and network communication is established. 1. Identify if the damper is a clockwise to open or counter clockwise to open. 2. Enter the damper opening direction into the configuration variable nciValveRotCW. A value of ‘1’ indicates the damper is clockwise to open and a value of ‘0’ indicates the damper is counterclockwise to open. 3. Using the input network variable nviManOverride close the damper. (nviManOverride = HVO_MINIMUM,0,0) Note: the actuator has a magnetic clutch that will release when the damper bumps up against a stop. 4. Take note of the value returned in the output network variable nvoValveCalib. 5. Enter the nvoValveCalib value when the damper is closed into the configuration variable nciValveMin. 6. Using the input network variable nviManOverride open the damper. (nviManOverride = HVO_MAXIMUM,0,0) Note the value returned in the output network variable nvoValveCalib. 7. Enter the nvoValveCalib value when the damper is open into the configuration variable nciValveMax. 8. . Page 1 of 2 FORM 098.202 REV 1101 E-PIM DAMPER POSITION INDICATOR OPTION 9. (Supersedes Nothing) Return the unit from override using the input network variable nviManOverride. (nviManOverride = HVO_OFF,0,0)) 10. The damper position is now available on variable nvoValvePosition as 0-100 percentage where 0 is closed and 100 is open. CONFIGURATION VARIABLES These configuration variables are in addition to the E-PIM configuration variables. Function Damper Maximum Damper Minimum Damper Rotation Description Sets the maximum damper position for the damper position indicator Sets the minimum damper position for the damper position indicator Sets the damper rotation to either clockwise or counterclockwise Symbol On Screen (SCPTs, SNVTs) Default value Range Available nciValveMax 0 0 – 255 nciValveMin 0 0 – 255 nciValveRotCW 1 1 = clockwise 0 = counterclockwise OUTPUT NETWORK VARIABLES These output network variables are in addition to the E-PIM output network variables. Function Description Damper Calibration Damper Position Used to set nciValveMax and nciValveMin Displays the damper position as percent open Symbol On Screen (SCPTs, SNVTs) Default value Range Available nvoValveCalib <varies> 0 – 255 nvoValvePosition 0.00 0 - 100 See Acutherm Form 35.2 for the complete list of variables. DAMPER POSITION OUTPUT Once calibrated the damper position will be available on output network variable nvoValvePosition as a percentage of full open. TROUBLESHOOTING In addition to the Troubleshooting section of Acutherm Form 35.2 E-PIM Installation, Operations and Maintenance manual: 1. Confirm the wiring from the pc board to the position sensor is secure (see CCW, W and CW on Fig. 1). 2. Confirm the position sensor is securely fastened to the actuator hub (see Fig. 1). 3. Confirm the voltage between CCW and CW (see Fig. 1) is 2.5VDC. 4. Confirm the voltage between CCW and W is progressing (or regressing) between 0VDC and 2.5VDC smoothly as the damper turns. ACUTHERM HEADQUARTERS 1766 Sabre Street Hayward, CA 94545 USA Tel +1 510 785 0510 Fax +1 510 785 2517 www.acutherm.com
© Copyright 2026 Paperzz