EUBA-20/53, EUBB-60/84 – General instruc

EU Air Handling Unit
INSTALLATION
EUBA-20/53, EUBB-60/84 – General instructions, outdoor version
Delivery
Lifting and transport
The EUB(A,B) unit is delivered as a single unit, i.e.
factory-assembled unit with roof and mounted on a
base frame. The unit can also be delivered as individual blocks with roof and mounted on a base frame for
assembly at the building site.
The EUAZ-02 jointing pieces must be fitted at the
lower edge of the unit as shown in Fig. 2, if the block
has a roof. Use a lifting spreader so that the roof eaves
will not be damaged.
The weight of each multi-function block is specified on
the rating plate. Use EUAZ-06 lifting tubes and
EUAZ-07 lifting spreader set to lift the unit/blocks
onto the previously prepared foundation.
Max. 6000 kg
Fig. 1
Lifting spreader
On site-built roof
covering to protect
projecting part of
the unit
EUAZ-06
Lifting tube
EUAZ-04 Base frame
Fig. 3
Piece of wood min. 50 x 50
L=1m
EUAZ-02
lifting device
The upper unit section must be secured
by EUAZ-16 jointing pieces. Max. distance between jointing pieces: 1.5 m
(see SE FLE/GB 4065, page 5).
Weather-proof
jointing compound all
around the
joint.
Fig. 2
Fläkt Woods
4067 GB 05.08
1
Specifications are subject to alteration without notice
EU Air Handling Unit
INSTALLATION
EUBA-20/53, EUBB-60/84 – General instructions, outdoor version
Mounting on the foundation, Sizes 20–53
Mounting on the foundation, Sizes 60–84
The foundation, on which the unit is placed, must be
level to ensure problem-free operation.
Check the foundation carefully to avoid distortion of
the unit and thus ensure that the doors will open and
close easily.
Secure the air handling unit base frame to the foundation by means of bolts. It is important to make sure
that the unit is level.
For connection of the duct to the underside of the unit,
accessability must be provided from underneath. If the
unit is mounted on plinths, the spacing of the plinths in
the longitudinal direction of the unit must not exceed
1.5 m.
Beams
Separate, tightly sealed
roof duct for connecting
ducts max. 1.5 m
150 EUAZ-04 (d=1)
300 EUAZ-04 (d=2)
max. 1,5 m
EUAZ-04
Base frame
Fig. 4 a
Size
A
Plinths
max. 1,5 m
Fig. 5 a
20 21, 30 22, 31, 40 32, 41, 50 42, 51
774 1074
1374
1674
52
53
1974 2274 2574
Size
60
62, 71, 80
64, 73, 82
84
A
2050
2650
3250
4000
150
15
58
58
30
15
120
120
30
A
A
Fig. 5 b
Fig. 4 b
Fläkt Woods
4067 GB 05.08
2
Specifications are subject to alteration without notice
EU Air Handling Unit
INSTALLATION
EUBA-20/53, EUBB-60/84 – General instructions, outdoor version
Anchoring of EUBB-60-80 outdoors
To remove individual panels
~ 1500
~1500
Screw
Bushing
Screw
Fig. 9
L 50 x 50 x 5
8 x 100 x 100
Bushing
M6S-TT 8 x 20 (Taptite)
Connecting multi-function blocks
Sealing strip is supplied loose and must thus be fitted
before the blocks are connected together. See Fig. 6 and 7.
Fig. 7
15 x 5
Fig. 8
Fläkt Woods
4067 GB 05.08
3
Specifications are subject to alteration without notice
EU Air Handling Unit
INSTALLATION
EUBA-20/53, EUBB-60/84 – General instructions, outdoor version
Connection to Regoterm (EURA) and
Jointing frame (EUVH c = 3, 4)
Jointing of blocks, sizes 20–53
Internal bolted joints at the bolt lugs fitted along the
frame are used for jointing the blocks to one another.
Access to the inside of the casing can be gained either
by opening an inspection door or by removing a wall
panel. If nesessary, withdraw any unit sections that
are in the way.
1. Fit the sealing strips supplied to the frame of one of
the blocks.
2. Push the blocks towards one another, making sure
that they are well lined up with one another.
3. Fit the joint bolts into the corner brackets on the
inside of the frame and make sure that they are
firmly in position.
4. Use a 14 mm spanner for the joint bolts to pull the
blocks together.
5. Tighten all four bolts alternately, compressing the
seal to 1–2 mm.
The connector is attached to the strut with self-tappping screws and is tightened with a size 14 spanner.
~35
Fig. 10 b
Connection to Angle section
(EUTA b = 1–4)
The connector is attached to the top/bottom with selftapping screws and is tightened with a size 14 spanner.
N.B! Make sure that the joint bolt is located in the
bottom of the screw pocket throughout the
tightening process. The cone of the joint bolt
will then fit into the cone of the screw pocket
(see Fig. 10).
~35
Connection to next EU block
Fit the self-tapping screws in the existing holes in the
frame profiles, and tighten the connector with a size
14 spanner.
Fig. 10 c
~ 2 mm
Fig. 10 a
Fig. 10 d
Distribute the thread length equally
Left-hand screw where indicated.
Fläkt Woods
4067 GB 05.08
4
Specifications are subject to alteration without notice
EU Air Handling Unit
INSTALLATION
EUBA-20/53, EUBB-60/84 – General instructions, outdoor version
Jointing of blocks, sizes 60–84
Internal bolted joints at the bolt lugs fitted along the
frame are used for jointing the blocks to one another.
Access to the inside of the casing can be gained either
by opening an inspection door or by removing a wall
panel. Some of the unit sections, such as the filter
section, may be dismantled for better access.
1. Fit the sealing strips supplied to the frame of one of
the blocks.
2. Push the blocks towards one another, making sure
that they are well lined up with one another.
3. Fit the joint bolts into the corner brackets on the
inside of the frame and make sure that they are
firmly in position.
4. Tighten all four bolts alternately, compressing the
seal to 1–2 mm, see the figures below.
Supplied
M 10 x 160
M10
l
ea
ss
s
re m
mp m
Co 1–2
to
Fig. 12
Fig. 11
15 x 5 mm
sealing strip,
supplied
Fläkt Woods
4067 GB 05.08
5
Specifications are subject to alteration without notice
EU Air Handling Unit
INSTALLATION
EUBA-20/53, EUBB-60/84 – General instructions, outdoor version
On size 60–84 units, place the cover trim on the joint
where the folded edges of the roof sections meet and
secure it by applying light hammer blows to ”snap”
it on.
To fit the roof joint
The EUBZ-01 roof is fitted to each individual unit at the
factory as shown in Fig. 13.
PG slip clamp, to be fitted
over the joints between
the units (supplied)
End plate
PG slip clamp,
factory-mounted
Roof panel
Secured roof joint
Fig. 13
Roof joint to be fitted on site when multi-function
blocks are delivered.
PG slip clamp, sizes
20–53, or cover trim,
sizes 60–84, to be fitted
over the joints between the
units (supplied)
Secure the end pieces using self-threading
screws.
Center the PG slip clamp so
that its right-hand end
extends equally as much as
its left-hand end from the
edge of the roof. Then bend
the clip clamp ends over the
edge of the roof.
Delivery
unit
Fig. 14
Fläkt Woods
Delivery
unit
4067 GB 05.08
6