Application Manual MMI-20030076, Rev AA October 2015 Micro Motion® Advanced Phase Measurement Application Manual Safety messages Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step. Emerson Flow customer service Email: • Worldwide: [email protected] • Asia-Pacific: [email protected] Telephone: North and South America Europe and Middle East Asia Pacific United States 800-522-6277 U.K. 0870 240 1978 Australia 800 158 727 Canada +1 303-527-5200 The Netherlands +31 (0) 704 136 666 New Zealand 099 128 804 Mexico +41 (0) 41 7686 111 France 0800 917 901 India 800 440 1468 Argentina +54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682 Brazil +55 15 3413 8000 Italy 8008 77334 China +86 21 2892 9000 Venezuela +58 26 1731 3446 Central & Eastern +41 (0) 41 7686 111 Japan +81 3 5769 6803 Russia/CIS +7 495 981 9811 South Korea +82 2 3438 4600 Egypt 0800 000 0015 Singapore +65 6 777 8211 Oman 800 70101 Thailand 001 800 441 6426 Qatar 431 0044 Malaysia 800 814 008 Kuwait 663 299 01 South Africa 800 991 390 Saudi Arabia 800 844 9564 UAE 800 0444 0684 Contents Contents Chapter 1 Before you begin ............................................................................................................ 1 1.1 1.2 1.3 1.4 1.5 Chapter 2 APM measurement ........................................................................................................ 5 2.1 2.2 2.3 2.4 Chapter 3 Configure APM to measure liquid with gas, using ProLink III .......................................................25 Configure APM to measure net oil with gas, using ProLink III ......................................................26 Configure APM to measure gas with entrained liquid (mist), using ProLink III .............................34 Additional configuration for APM ................................................................................. 37 5.1 5.2 5.3 Chapter 6 Configure APM to measure liquid with gas, using the display ..................................................... 15 Configure APM to measure net oil with gas, using the display .................................................... 16 Configure APM to measure gas with entrained liquid (mist), using the display ........................... 22 Configure APM using ProLink III ....................................................................................25 4.1 4.2 4.3 Chapter 5 APM installations ......................................................................................................................... 5 APM measurement option: Liquid with gas .................................................................................. 7 APM measurement option: Net oil with gas ................................................................................. 9 APM measurement option: Gas with liquid ................................................................................ 12 Configure APM using the display .................................................................................. 15 3.1 3.2 3.3 Chapter 4 About this application manual ..................................................................................................... 1 About the Advanced Phase Measurement (APM) application ....................................................... 1 APM requirements ....................................................................................................................... 2 Terms and definitions .................................................................................................................. 3 Additional documentation from Micro Motion .............................................................................4 Configure viewing and reporting for APM process variables ....................................................... 37 Configure the totalizer history log to include APM contract totals ..............................................39 Configure events ....................................................................................................................... 39 Transmitter operation ..................................................................................................41 6.1 6.2 Read APM process variables ....................................................................................................... 41 Read APM contract totals ...........................................................................................................41 Appendices and reference Appendix A Application parameters and data ................................................................................. 43 A.1 A.2 Modbus interface to APM configuration parameters ..................................................................43 Modbus interface to APM process data ...................................................................................... 44 Application Manual i Contents ii Micro Motion® Advanced Phase Measurement Before you begin 1 Before you begin Topics covered in this chapter: 1.1 • • • • About this application manual About the Advanced Phase Measurement (APM) application APM requirements Terms and definitions • Additional documentation from Micro Motion About this application manual This application manual explains how to configure and use the Advanced Phase Measurement application. This application manual does not provide information on installation of the Model 5700 transmitter, or installation of any sensors. It does not provide general configuration and operation information. This information can be found in the applicable installation manual or the transmitter configuration manual. Related information Additional documentation from Micro Motion 1.2 About the Advanced Phase Measurement (APM) application Advanced Phase Measurement (APM) provides accurate measurement of fluid streams during periods of two-phase flow: either gas in a liquid stream or liquid in a gas stream. APM also supports measurement of net oil. There are three license options for APM. The options are described in the following table. Table 1-1: APM license options Application Manual APM license option Process fluid Desired measurement Liquid with gas Liquid with entrained gas Liquid flow rate and totals, gas void fraction (GVF) NOC with gas Mixture of oil, gas, and water from a wellhead Net oil(1) and net water flow rates and totals, GVF 1 Before you begin Table 1-1: APM license options (continued) APM license option Process fluid Desired measurement Gas with liquid Gas with entrained liquid (mist) Gas flow rate and totals (1) Dry oil at reference conditions For purchasing information, see the product data sheet for the Model 5700 transmitter. 1.3 APM requirements Ensure that your installation meets these requirements. Transmitter requirements APM is available only on the Model 5700 transmitter. Sensor requirements APM does not require a specific sensor. You can use any sensor that is supported by the Model 5700 transmitter and that meets your application requirements. Core processor requirements APM requires the enhanced core processor. The standard core processor does not support APM. Installation and wiring requirements There are no specific installation requirements. On the transmitter, Channel E must be enabled and must be wired to a Modbus host. If you plan to use the NOC measurement option with an external water cut monitor, Channel D on the transmitter must be enabled, and must be configured as an mA input, wired to the water cut monitor, and configured appropriately. I/O requirements To configure APM, you can use either of the following: • Transmitter display • ProLink III v3.2 or later For operation, APM process data is available over a Modbus connection. The following are required: 2 • A Modbus/RS-485 connection from your Modbus host to the transmitter • A Modbus program that reads APM process data on the appropriate schedule Micro Motion® Advanced Phase Measurement Before you begin 1.4 Terms and definitions The terms used to describe oil and gas vary widely. The APM application and this manual use the terms defined here. Terms used in APM Correction The process of calculating the value of a process variable at reference temperature, starting from the value of the process variable at line temperature (the measured value) Uncorrected density The density of the process fluid at line temperature Corrected density The density of the process fluid at reference temperature that is equivalent to its density at line temperature Uncorrected volume The volume of the process fluid at line temperature Corrected volume The volume of the process fluid at reference temperature that is equivalent to its volume at line temperature Mixture The process fluid before separation, e.g., a combination of oil and water, or gas, oil, and water Water cut (Net oil with gas only) The amount of water in the oil, in % External water cut (Net A water cut value measured by an external device and oil with gas only) supplied to APM via the mA input Density-based water cut (Net oil with gas only) A water cut value calculated by APM based on current process density, the density of produced oil (user-supplied value), and the density of produced water (user-supplied value) Density determination (Net oil with gas only) The procedure used to obtain two required values: The density of dry oil at reference temperature, and the density of water and reference temperature Net A measurement of a single component of the process fluid, e.g., oil only, water only Entrained, entrainment The presence of small amounts of gas in a liquid stream, or liquid in a gas stream Application Manual Remediation An adjustment applied to a process variable during periods of entrained gas or mist when a substitute density value has been used for volume calculation (liquid flows) or the flow rate has been increased or decreased to compensate for unmeasured flow (gas flows). Contract total Up to four user-specified inventories that are used to measure production Contract period The 24-hour period over which contract totals are incremented. Contract totals are reset at the beginning of each contract period. 3 Before you begin 1.5 Additional documentation from Micro Motion Table 1-2: Additional documentation for APM installations 4 Document Use Sensor installation manual for your sensor Installation and wiring for the sensor Transmitter installation manual for the Model 5700 transmitter Installation and wiring for the Model 5700 transmitter Configuration manual for the Model 5700 transmitter Configuration, operation, maintenance, and troubleshooting for features that are not related to APM ProLink III user manual Installation and use of ProLink III Modbus Interface Tool Programming the Modbus host Micro Motion® Advanced Phase Measurement APM measurement 2 APM measurement Topics covered in this chapter: • • • • 2.1 APM installations APM measurement option: Liquid with gas APM measurement option: Net oil with gas APM measurement option: Gas with liquid APM installations The APM device can be installed directly at the wellhead, on the oil leg and/or gas leg of a three-phase separator, or on the oil/water and/or gas leg of a two-phase separator. If the APM device is installed at the wellhead, the need for a test separator may be eliminated. APM at the wellhead Figure 2-1: APM at the wellhead A. B. C. D. Application Manual Wellhead Coriolis sensor Transmitter with APM (NOC with gas) Modbus host (flow computer) 5 APM measurement APM with a three-phase separator Figure 2-2: APM with a three-phase separator A. B. C. D. E. F. G. H. I. 6 From wellhead Separator Water leg Oil leg Gas leg Coriolis sensor and transmitter with APM (Liquid with gas, variable flow) Coriolis sensor and transmitter with APM (Liquid with gas, variable flow) (optional, used in applications where oil measurement is needed in the water leg to detect a malfunctioning separator) Coriolis sensor and transmitter with APM (Gas with liquid) Modbus host (flow computer) Micro Motion® Advanced Phase Measurement APM measurement APM with a two-phase separator Figure 2-3: APM with a two-phase separator A. B. C. D. E. F. G. From wellhead Separator Gas leg Oil/water leg Coriolis sensor and transmitter with APM (NOC with gas) Coriolis sensor and transmitter with APM (Gas with liquid) Modbus host (flow computer) 2.2 APM measurement option: Liquid with gas This measurement option reports liquid data from a process fluid that is liquid with intermittent entrained gas. APM Liquid with gas: Measurement process Entrained gas, or bubbles in the process fluid, has a negative effect on liquid volume measurement accuracy. The Coriolis sensor calculates volume based on direct density and mass measurements. When a bubble is present, mixture density is reduced, causing the reported volume to be higher than the actual liquid volume. The presence of bubbles is reflected in the drive gain. The following figure shows how the change in drive gain affects density measurement. Because volume is calculated from mass and density, all volume measurements are also affected. Application Manual 7 APM measurement Drive gain (%) Figure 2-4: Effect of entrained gas on drive gain and density measurement A B A. B. Density Drive gain (actual) The drive gain threshold is calculated automatically upon startup. After startup, APM updates the drive gain threshold every 60 seconds. This eliminates the need for the user to guess at the value of drive gain that indicates two-phase flow. APM volume calculation during entrained gas events If the drive gain threshold is exceeded, the volume calculation for the period of high drive gain can be handled in either of two ways. Option Description Hold Last Value Use an average density value from an earlier point in the process to calculate volume. If this option is chosen, the water cut from the point just before the entrained gas event is effectively held constant throughout the event. Use Input Density of Convert the density of dry oil at reference temperature (a userDry Oil Converted to configured value) to density at line temperature, and calculate Line Conditions volume. This option assumes that all volume during the entrained gas event is dry oil. Hold Last Value in operation The following figure illustrates Hold Last Value in operation 8 Micro Motion® Advanced Phase Measurement APM measurement Figure 2-5: Hold Last Value in operation Drive gain (%) E A B C D A. B. C. D. E. 2.3 D Density Drive gain threshold Drive gain (actual) Earlier point in process Averaged density values APM measurement option: Net oil with gas This measurement option reports net oil data from a process fluid that is a mixture of oil and water with intermittent entrained gas. This measurement option has two components: 2.3.1 • Net oil measurement (NOC) • Entrained gas remediation APM Net oil measurement The Net Oil Computer (NOC) algorithm calculates the water fraction of the liquid stream so that net oil and net water can be determined. Net oil is the volume of oil, corrected to a reference temperature, that is contained within the gross volume of produced fluid. This algorithm requires four types of data: Application Manual • Current flow rate • Density of dry oil from this well at reference conditions • Density of water from this well at reference conditions 9 APM measurement • Current water cut The current flow rate is always available from the device. The user is responsible for determining the density of dry oil and the density of water, correcting to reference conditions, and supplying the values during configuration. The current water cut can be measured by a water cut monitor and supplied to APM via the mA input, or it can be calculated by APM from current density data via the density-based net oil calculation. If density-based water cut is chosen, APM uses the following equation to calculate the water cut. Equation 2-1: Calculation of density-based water cut ρL-ρO WaterCut= ρ 2.3.2 W-ρO ρL Density of the liquid (oil/gas mixture) as measured by the sensor ρO Density of produced oil (calculated from user-supplied value) ρW Density of produced water (calculated from user-supplied value) Entrained gas remediation Entrained gas remediation uses the meter's extended drive gain to indicate if there is entrained gas in the liquid stream, and adjust the measurement accordingly. The following figure shows how the change in drive gain affects density measurement. Because volume is calculated from mass and density, all volume measurements are also affected. Drive gain (%) Figure 2-6: Effect of entrained gas on drive gain and density measurement A B A. B. 10 Density Drive gain (actual) Micro Motion® Advanced Phase Measurement APM measurement The drive gain threshold is calculated automatically upon startup. After startup, APM updates the drive gain threshold every 60 seconds. This eliminates the need for the user to guess at the value of drive gain that indicates two-phase flow. APM volume calculation during entrained gas If the drive gain threshold is exceeded, the volume calculation for the period of high drive gain can be handled in either of two ways. Option Description Hold Last Value Use an average density value from an earlier point in the process to calculate volume. If this option is chosen, the water cut from the point just before the entrained gas event is effectively held constant throughout the event. Use Input Density of Convert the density of dry oil at reference temperature (a userDry Oil Converted to configured value) to density at line temperature, and calculate Line Conditions volume. This option assumes that all volume during the entrained gas event is dry oil. The following figure illustrates Hold Last Value in operation Figure 2-7: Hold Last Value in operation Drive gain (%) E A B C D A. B. C. D. E. Application Manual D Density Drive gain threshold Drive gain (actual) Earlier point in process Averaged density values 11 APM measurement 2.4 APM measurement option: Gas with liquid This measurement option reports gas data from a process fluid that is gas with intermittent entrained liquid (mist). APM Gas with liquid: Measurement process Mist in the process fluid has a negative effect on measurement accuracy, because liquid has a significantly higher density than gas. Therefore, small amounts of liquid can significantly impact the mass totals. The following figure shows how the change in drive gain affects density measurement. Drive gain (%) Figure 2-8: Effect of transient mist on drive gain and density measurement A B A transient mist condition is defined in terms of the sensor's extended drive gain: If the drive gain exceeds the drive gain threshold, the transmitter automatically performs transient mist remediation. The transient mist interval persists until drive gain is below the threshold. The drive gain threshold is calculated automatically upon startup. After startup, APM updates the drive gain threshold every 60 seconds. This eliminates the need for the user to guess at the value of drive gain that indicates two-phase flow. APM: Gas with liquid remediation The following figure illustrates APM processing when mist is detected in the gas stream. 12 Micro Motion® Advanced Phase Measurement APM measurement Figure 2-9: APM: Gas with liquid remediation G G E H E H A B C D A. B. C. D. E. F. G. H. F D F Flow rate Drive gain threshold Extended drive gain Pre-mist averaging period and source of M1 Averaged flow rate values Post-mist adjustment delay and source of M2 Adjustment period Adjusted flow rate values When mist is detected, the transmitter substitutes an average flow rate value, M1, for the measured flow rate, for the entire transient mist interval. The substitute flow rate is calculated from the actual flow rate data for the previous n seconds, where n is determined by the setting of Pre-Mist Averaging Period. When the transient mist interval is over, the transmitter waits for the number of seconds specified by Post-Mist Adjustment Delay. During that period, the transmitter calculates a second average flow rate, M2. M1 and M2 are then averaged, producing an approximate value for the actual flow rate during the transient mist interval. The measured flow rate is then increased by a maximum of 10% until the flow total has been compensated for all of the unmeasured flow. Application Manual 13 APM measurement 14 Micro Motion® Advanced Phase Measurement Configure APM using the display 3 Configure APM using the display Topics covered in this chapter: • • • 3.1 Configure APM to measure liquid with gas, using the display Configure APM to measure net oil with gas, using the display Configure APM to measure gas with entrained liquid (mist), using the display Configure APM to measure liquid with gas, using the display This measurement option is appropriate for liquids with intermittent entrained gas. Prerequisites Ensure that Mass Flow Cutoff is set to a non-zero value. This ensures that totalizing stops when remediation is active. In most installations, the default value is satisfactory. See the transmitter configuration manual for instructions on setting or verifying Mass Flow Cutoff. Ensure that the two-phase flow limits are set to the default values: Two-Phase Flow Low Limit = 0 g/cm³, Two-Phase Flow High Limit = 5 g/cm³. In a typical application, these limits will never be reached, so the transmitter will never initiate standard two-phase flow processing. APM processing will be implemented instead. Procedure 1. Choose Menu > Configuration > Process Measurement > Adv Phase Measurement > Application Setup. 2. Select Single Liq. 3. Set Production Type to the option that best describes the majority of flow in your system. Option Description Continuous Flow Relatively constant flow rate, e.g., natural production, ESP Variable Flow 4. Flow that stops and starts, or fluctuates frequently between high and low flow rates, e.g., pump jack, test separator Enter the density of the entrained gas. • If line pressure is less than 250 psi absolute, set Gas @ Line to Standard. • If line pressure is greater than 250 psi absolute, set Gas @ Line to the density of the entrained gas at typical line conditions. 5. Application Manual Choose Menu > Configuration > Process Measurement > Adv Phase Measurement > Reporting Interval and enter the time period, in minutes, over which process variables will be averaged. 15 Configure APM using the display The averages are written to the Modbus registers, and are available for retrieval by a Modbus host. 6. Configure the contract period. a. Choose Menu > Configuration > Process Measurement > Adv Phase Measurement > Contract Period. b. Set Time Zone to the time zone that you are using for the contract period. If necessary, set Special Time Zone to the number of hours to add or subtract from UTC. Note The time zone displayed here is the time zone setting for the transmitter. If you change the time zone here, you are changing the setting of the transmitter clock. c. Set Contract Start Hour to the time of day at which the contract starts. Enter the time in a 24-hour HH:MM format, where 00:00 = midnight. Example: 18:30 Restriction You cannot configure contract totals using the display. If you want to configure contract totals, you must use ProLink III. See Chapter 4. 3.2 Configure APM to measure net oil with gas, using the display This measurement option is used to measure the oil content of an oil/liquid mixture with intermittent entrained gas. 1. 2. 3. 3.2.1 Determine the density of dry oil and water (Section 3.2.1) Configure APM to measure net oil with gas, using the display (Section 3.2) Configure APM to measure gas with entrained liquid (mist), using the display (Section 3.3) Determine the density of dry oil and water Before configuring the application, you must know the density of water from the well, corrected to reference temperature, and the density of dry oil from the well, corrected to reference temperature. Important Micro Motion recommends working with a laboratory to obtain the most accurate values. The accuracy of the net oil data depends upon the accuracy of these two density values. 16 Micro Motion® Advanced Phase Measurement Configure APM using the display • • Density determination using a petroleum laboratory Density determination using the display and a three-phase separator Density determination using a petroleum laboratory To configure APM for net oil measurement, you must know the density of dry oil at reference temperature, and the density of produced water at reference temperature. You can obtain these values from a petroleum laboratory. Note Even after separation, oil typically contains some amount of interstitial water. The water cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil. Important If you are using a three-phase separator, you can collect the oil sample and the water sample separately, after separation, or you can collect one sample before separation and have the laboratory perform the separation. If you are using a two-phase separator, you should collect one sample before separation and have the laboratory perform the separation. Prerequisites Sample collection must meet these requirements: • You must be able to collect a sample that is representative of your process. • The sample must be collected by a qualified person, using industry-accepted safety standards. • You must know the minimum required sample size. This varies depending on the water cut and the volume of the sample cylinder. Consult the petroleum laboratory for specific values. • If the sample contains oil, you must be able to collect and maintain the sample at line pressure, so that the oil will not lose pressure and outgas. • If you collect the water sample separately, you must be able to protect it from contamination and evaporation. You must know the reference temperature that you plan to use. The petroleum laboratory must be able to meet these requirements: Application Manual • The laboratory density meter must be able to keep the oil sample pressurized at line pressure during the density measurement. • The sample cylinder must be a constant-pressure type, and must be properly rated for the oil–water composition and for sample pressure. • The oil density measurement units should be in g/cm³ at reference temperature and/or °API at reference temperature. The water density measurement should be in g/cm³ at reference temperature. • The laboratory report must include the oil density, water density, and the reference temperature. 17 Configure APM using the display Procedure 1. Communicate the handling and measurement requirements and the reference temperature to the petroleum laboratory. 2. If you are collecting one sample that contains both oil and water, identify the point in the line where the sample will be taken. Recommendations: • Collect the sample at a point where the fluid is well mixed. • The line pressure at the sample point should be close to the line pressure at the sensor. • The line temperature at the sample point should be close to the line temperature at the sensor. 3. If you are using a three-phase separator and collecting the oil and water samples separately: a. Identify the points where the samples will be taken. Recommendations: • The sample point for oil must be on the oil leg, as close to the sensor as possible. See Figure 2-2. • The line pressure at the oil sample point should be similar to the line pressure at the sensor. • The sample point for water must be on the water leg, as close to the sensor as possible. See Figure 2-2. • The line temperature at the water sample point should be similar to the line temperature at the sensor. b. Wait until separation has occurred. 4. Collect the sample or samples, meeting all requirements for pressure and protection from contamination or evaporation. 5. Mark and tag the sample or samples with the well name or number, time and date, sample type, line pressure, and line temeprature. 6. Transport the samples to the laboratory safely, as soon as is practical. Postrequisites If the laboratory measurements were not corrected to your reference temperature, use the Oil & Water Density Calculator to calculate density at reference temperature. This is a spreadsheet tool developed by Micro Motion. You can obtain a copy from your Micro Motion representative. Density determination using the display and a three-phase separator To configure APM for net oil measurement, you must know the density of dry oil at reference temperature, and the density of produced water at reference temperature. If you have a three-phase separator, you can use density data and the Oil & Water Density Calculator to obtain these values. 18 Micro Motion® Advanced Phase Measurement Configure APM using the display Note Even after separation, oil typically contains some amount of interstitial water. The water cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil. Prerequisites You must have a three-phase separator in the process. You can use a mobile three-phase test separator. You must have a sensor and transmitter installed on the oil leg, and a sensor and transmitter installed on the water leg. See Figure 2-2. You must know the reference temperature that you plan to use. You must have the Oil & Water Density Calculator. This is a spreadsheet tool developed by Micro Motion. You can obtain a copy from your Micro Motion representative. Procedure 1. Wait until separation has occurred. 2. At the transmitter on the oil leg, read and record the density value and the temperature value. Tip If density and temperature are not configured as display variables, you can read them from this location: Menu > Operations > Process Variable Values. Important The accuracy of net oil data depends on the accuracy of the density data. Never use an unstable density value, or any density value that has an elevated drive gain. 3. At the transmitter on the water leg, read and record the density value and the temperature value. Tip If density and temperature are not configured as display variables, you can read them from this location: Menu > Operations > Process Variable Values. Important The accuracy of net oil data depends on the accuracy of the density data. Never use an unstable density value, or any density value that has an elevated drive gain. 4. Application Manual Use the Oil & Water Density Calculator to calculate the density of dry oil at reference temperature and the density of produced water at reference temperature. 19 Configure APM using the display Tip Unless the oil is light hot condensate, the oil will almost always contain some interstitial water. This is generally acceptable for allocation measurements. However, if further accuracy is desired, you can determine the water cut and use it in the calculation. To determine or estimate the water cut, take a shakeout sample from one of the following: • The current flow/dump cycle, at the time of minimum density • Similar oils produced from the same reservoir • The tank or tanks that the separator flows into Enter this water cut into the Oil & Water Density Calculator to calculate the density of dry oil at reference temperature. 3.2.2 Configure NOC parameters using the display You must configure the transmitter with site-specific values for net oil measurement. Prerequisites Ensure that Mass Flow Cutoff is set to a non-zero value. This ensures that totalizing stops when remediation is active. In most installations, the default value is satisfactory. See the transmitter configuration manual for instructions on setting or verifying Mass Flow Cutoff. Ensure that the two-phase flow limits are set to the default values: Two-Phase Flow Low Limit = 0 g/cm³, Two-Phase Flow High Limit = 5 g/cm³. In a typical application, these limits will never be reached, so the transmitter will never initiate standard two-phase flow processing. APM processing will be implemented instead. If you plan to use a water cut monitor: • Channel D must be available to use as a mA input. • The water cut monitor must be installed and wired to Channel D. Procedure 1. Choose Menu > Configuration > Process Measurement > Adv Phase Measurement > Application Setup. 2. Select Net Oil (NOC). 3. Enter the values obtained from density determination. a. Set Oil Density @ Ref to the density of dry oil, corrected to reference temperature. b. Set Water Density @ Ref to the density of water, corrected to reference temperature. 4. Set Production Type to the option that best describes the majority of flow in your system. Option Description Continuous Flow Relatively constant flow rate, e.g., natural production, ESP Variable Flow 20 Flow that stops and starts, or fluctuates frequently between high and low flow rates, e.g., pump jack, test separator Micro Motion® Advanced Phase Measurement Configure APM using the display 5. Enter the density of the entrained gas. • If line pressure is less than 250 psi absolute, set Gas @ Line to Standard. • If line pressure is greater than 250 psi absolute, set Gas @ Line to the density of the entrained gas at typical line conditions. 6. Set Reference Temp to the temperature to which net oil and net water measurements will be corrected. 7. Set View Production Meas to the type of net oil data that will be shown on the display. Option Description Corrected to Standard The display will show Watercut @ Ref, Net Oil Flow @ Ref, etc. Uncorrected The display will show Watercut @ Line, Net Oil Flow @ Line, etc. This parameter is applicable only if a net oil process variable is configured as a display variable. 8. Choose Menu > Configuration > Process Measurement > Adv Phase Measurement > Reporting Interval and enter the time period, in minutes, over which process variables will be averaged. The averages are written to the Modbus registers, and are available for retrieval by a Modbus host. 9. Configure the contract period. a. Choose Menu > Configuration > Process Measurement > Adv Phase Measurement > Contract Period. b. Set Time Zone to the time zone that you are using for the contract period. If necessary, set Special Time Zone to the number of hours to add or subtract from UTC. Note The time zone displayed here is the time zone setting for the transmitter. If you change the time zone here, you are changing the setting of the transmitter clock. c. Set Contract Start Hour to the time of day at which the contract starts. Enter the time in a 24-hour HH:MM format, where 00:00 = midnight. Example: 18:30 Restriction You cannot configure contract totals using the display. If you want to configure contract totals, you must use ProLink III. See Chapter 4. 10. Application Manual If you want to use a water cut monitor, set up the mA input to receive the water cut data. 21 Configure APM using the display a. Choose Menu > Configuration > Inputs/Outputs > Channels and configure Channel D to operate as an mA input. b. Choose Device Tools > Configuration > I/O > Inputs > mA Input. c. Verify that Assignment is set to Watercut @ Line. This is the default assignment. Do not change it; if you do, you will have to use ProLink III to change it back. d. Verify the settings of Lower Range Value and Upper Range Value. Default values: • Lower Range Value = 0% • Upper Range Value = 100% In most cases, these values are not changed. e. Set mA Input Damping as desired. Postrequisites If you set Production Type to Variable Flow, there is an additional parameter that controls the action to be taken when gas is detected. This parameter is called Density Corrective Action, and can be set to either Hold Last Value or Density Oil @ Line. This parameter is not available from the display. The default setting is Hold Last Value. If you want to change it, you must use ProLink III. 3.3 Configure APM to measure gas with entrained liquid (mist), using the display This measurement option is appropriate for gas process fluids with intermittent entrained liquid (mist). Prerequisites Ensure that Mass Flow Cutoff is set to a non-zero value. This ensures that totalizing stops when remediation is active. In most installations, the default value is satisfactory. See the transmitter configuration manual for instructions on setting or verifying Mass Flow Cutoff. Ensure that the two-phase flow limits are set to the default values: Two-Phase Flow Low Limit = 0 g/cm³, Two-Phase Flow High Limit = 5 g/cm³. In a typical application, these limits will never be reached, so the transmitter will never initiate standard two-phase flow processing. APM processing will be implemented instead. Procedure 22 1. Choose Menu > Configuration > Process Measurement > Adv Phase Measurement > Application Setup. 2. Select Gas with Liquid. 3. Set Pre-Mist Ave Period to the number of seconds over which density data will be averaged, to produce the substitute density value. Micro Motion® Advanced Phase Measurement Configure APM using the display 4. Set Post-Mist Adj Delay to the number of seconds that the system will wait before beginning measurement remediation. 5. Choose Menu > Configuration > Process Measurement > Adv Phase Measurement > Reporting Interval and enter the time period, in minutes, over which process variables will be averaged. The averages are written to the Modbus registers, and are available for retrieval by a Modbus host. 6. Configure the contract period. a. Choose Menu > Configuration > Process Measurement > Adv Phase Measurement > Contract Period. b. Set Time Zone to the time zone that you are using for the contract period. If necessary, set Special Time Zone to the number of hours to add or subtract from UTC. Note The time zone displayed here is the time zone setting for the transmitter. If you change the time zone here, you are changing the setting of the transmitter clock. c. Set Contract Start Hour to the time of day at which the contract starts. Enter the time in a 24-hour HH:MM format, where 00:00 = midnight. Example: 18:30 Restriction You cannot configure contract totals using the display. If you want to configure contract totals, you must use ProLink III. See Chapter 4. Application Manual 23 Configure APM using the display 24 Micro Motion® Advanced Phase Measurement Configure APM using ProLink III 4 Configure APM using ProLink III Topics covered in this chapter: • • • 4.1 Configure APM to measure liquid with gas, using ProLink III Configure APM to measure net oil with gas, using ProLink III Configure APM to measure gas with entrained liquid (mist), using ProLink III Configure APM to measure liquid with gas, using ProLink III This measurement option is appropriate for liquids with intermittent entrained gas. Prerequisites Ensure that Mass Flow Cutoff is set to a non-zero value. This ensures that totalizing stops when remediation is active. In most installations, the default value is satisfactory. See the transmitter configuration manual for instructions on setting or verifying Mass Flow Cutoff. Ensure that the two-phase flow limits are set to the default values: Two-Phase Flow Low Limit = 0 g/cm³, Two-Phase Flow High Limit = 5 g/cm³. In a typical application, these limits will never be reached, so the transmitter will never initiate standard two-phase flow processing. APM processing will be implemented instead. Procedure 1. Choose Device Tools > Configuration > Process Measurement > Advanced Phase Measurement. 2. If necessary, set Fluid Type to Liquid with Gas and click Apply. 3. Set Production Type to the option that best describes the majority of flow in your system and click Apply. Option Description Continuous Flow Relatively constant flow rate, e.g., natural production, ESP Variable Flow 4. Flow that stops and starts, or fluctuates frequently between high and low flow rates, e.g., pump jack, test separator If line pressure is greater than 250 psi absolute, enter the density of the entrained gas at typical line conditions. Tip If you need help determining this value, use the Gas Wizard provided in the ProLink III window. 5. Application Manual Set Average Reporting Interval to the time period, in minutes, over which process variables will be averaged. 25 Configure APM using ProLink III The averages are written to the Modbus registers, and are available for retrieval by a Modbus host. 6. Set Contract Start Time to the time of day at which the contract starts. The contract time is based on the transmitter clock. You can change the setting of the transmitter clock if necessary. See the transmitter configuration manual for more information. Enter the time in a 24-hour HH:MM format, where 00:00 = midnight. Example: 18:30 7. Select up to four inventory values to use as contract totals, to be tracked for each contract period. Each contract total is set to 0 every 24 hours, at the configured Contract Start Time. Tip You can configure custom inventories and use them for contract totals. See the transmitter configuration manual for more information. 4.2 Configure APM to measure net oil with gas, using ProLink III This measurement option is used to measure the oil content of an oil/liquid mixture with intermittent entrained gas. 1. 2. 4.2.1 Determine the density of dry oil and water (Section 4.2.1) Configure NOC parameters using ProLink III (Section 4.2.2) Determine the density of dry oil and water Before configuring the application, you must know the density of water from the well, corrected to reference temperature, and the density of dry oil from the well, corrected to reference temperature. Important Micro Motion recommends working with a laboratory to obtain the most accurate values. The accuracy of the net oil data depends upon the accuracy of these two density values. • • • 26 Density determination using a petroleum laboratory Density determination using ProLink III and a two-phase separator Density determination using ProLink III and a three-phase separator Micro Motion® Advanced Phase Measurement Configure APM using ProLink III Density determination using a petroleum laboratory To configure APM for net oil measurement, you must know the density of dry oil at reference temperature, and the density of produced water at reference temperature. You can obtain these values from a petroleum laboratory. Note Even after separation, oil typically contains some amount of interstitial water. The water cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil. Important If you are using a three-phase separator, you can collect the oil sample and the water sample separately, after separation, or you can collect one sample before separation and have the laboratory perform the separation. If you are using a two-phase separator, you should collect one sample before separation and have the laboratory perform the separation. Prerequisites Sample collection must meet these requirements: • You must be able to collect a sample that is representative of your process. • The sample must be collected by a qualified person, using industry-accepted safety standards. • You must know the minimum required sample size. This varies depending on the water cut and the volume of the sample cylinder. Consult the petroleum laboratory for specific values. • If the sample contains oil, you must be able to collect and maintain the sample at line pressure, so that the oil will not lose pressure and outgas. • If you collect the water sample separately, you must be able to protect it from contamination and evaporation. You must know the reference temperature that you plan to use. The petroleum laboratory must be able to meet these requirements: Application Manual • The laboratory density meter must be able to keep the oil sample pressurized at line pressure during the density measurement. • The sample cylinder must be a constant-pressure type, and must be properly rated for the oil–water composition and for sample pressure. • The oil density measurement units should be in g/cm³ at reference temperature and/or °API at reference temperature. The water density measurement should be in g/cm³ at reference temperature. • The laboratory report must include the oil density, water density, and the reference temperature. 27 Configure APM using ProLink III Procedure 1. Communicate the handling and measurement requirements and the reference temperature to the petroleum laboratory. 2. If you are collecting one sample that contains both oil and water, identify the point in the line where the sample will be taken. Recommendations: • Collect the sample at a point where the fluid is well mixed. • The line pressure at the sample point should be close to the line pressure at the sensor. • The line temperature at the sample point should be close to the line temperature at the sensor. 3. If you are using a three-phase separator and collecting the oil and water samples separately: a. Identify the points where the samples will be taken. Recommendations: • The sample point for oil must be on the oil leg, as close to the sensor as possible. See Figure 2-2. • The line pressure at the oil sample point should be similar to the line pressure at the sensor. • The sample point for water must be on the water leg, as close to the sensor as possible. See Figure 2-2. • The line temperature at the water sample point should be similar to the line temperature at the sensor. b. Wait until separation has occurred. 4. Collect the sample or samples, meeting all requirements for pressure and protection from contamination or evaporation. 5. Mark and tag the sample or samples with the well name or number, time and date, sample type, line pressure, and line temeprature. 6. Transport the samples to the laboratory safely, as soon as is practical. Postrequisites If the laboratory measurements were not corrected to your reference temperature, use the Oil & Water Density Calculator to calculate density at reference temperature. This is a spreadsheet tool developed by Micro Motion. You can obtain a copy from your Micro Motion representative. Density determination using ProLink III and a two-phase separator To configure APM for net oil measurement, you must know the density of dry oil at reference temperature, and the density of produced water at reference temperature. You can use log data from ProLink III, with the Oil & Water Density Calculator, to obtain these values. 28 Micro Motion® Advanced Phase Measurement Configure APM using ProLink III Note Even after separation, oil typically contains some amount of interstitial water. The water cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil. This procedure assumes the following: • The highest density value in the logged data represents produced water. • The lowest density value in the logged data represents dry oil. Prerequisites You must have a two-phase separator in the process. You can use a mobile two-phase test separator. You must know the reference temperature that you plan to use. You must have a sensor and transmitter installed on the oil/water leg. See Figure 2-3 You must be able to connect to the transmitter with ProLink III. You must know how to use the data logging feature in ProLink III. You must be able to run data logging for the necessary time period, which may be a few minutes or a few hours, depending on your separator. You must have the Oil & Water Density Calculator. This is a spreadsheet tool developed by Micro Motion. You can obtain a copy from your Micro Motion representative. Procedure 1. Connect to the transmitter with ProLink III. 2. Set up data logging to record the following process variables, with a logging interval of 1 second: • Mass flow rate • Volume flow rate • Density • Temperature • Drive gain 3. Collect data. a. Open the level control valve on the separator, and allow the separator to drop to the lowest safe level, or until gas is first drawn into the liquid leg. b. Close the level control valve and allow the level to rise to the maximum safe level. This will increase the residence time for the liquid in the separator, and may allow the water to settle to the bottom and the oil to rise to the top. c. Open the level control valve partially, so that the level drops slowly. d. Start data logging. Application Manual 29 Configure APM using ProLink III e. Allow the separator to drop to the lowest safe level, or until gas is first drawn into the liquid leg. f. Stop data logging. g. Return the separator to automatic level control. 4. Obtain maximum and minimum density data from the log. Shortly after the control valve is opened or the dump phase begins, you should see the temperature stabilizing and the density rising to a maximum value and stabilizing. This may represent produced water. Just before the lowest safe level, or before the point where gas is drawn into the liquid leg, you should see the density falling to a minimum value and stabilizing. This may represent dry oil. a. Record the maximum density and the corresponding temperature. b. Record the minimum density and the corresponding temperature. Important Never use an unstable density value, or any density value that has an elevated drive gain. 5. Use the Oil & Water Density Calculator to calculate the density of dry oil at reference temperature and the density of produced water at reference temperature. Tip Unless the oil is light hot condensate, the oil will almost always contain some interstitial water. This is generally acceptable for allocation measurements. However, if further accuracy is desired, you can determine the water cut and use it in the calculation. To determine or estimate the water cut, take a shakeout sample from one of the following: • The current flow/dump cycle, at the time of minimum density • Similar oils produced from the same reservoir • The tank or tanks that the separator flows into Enter this water cut into the Oil & Water Density Calculator to calculate the density of dry oil at reference temperature. Density determination using ProLink III and a three-phase separator To configure APM for net oil measurement, you must know the density of dry oil at reference temperature, and the density of produced water at reference temperature. If you have a three-phase separator, you can use density data and the Oil & Water Density Calculator to obtain these values. Note Even after separation, oil typically contains some amount of interstitial water. The water cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil. 30 Micro Motion® Advanced Phase Measurement Configure APM using ProLink III Prerequisites You must have a three-phase separator in the process. You can use a mobile three-phase test separator. You must have a sensor and transmitter installed on the oil leg, and a sensor and transmitter installed on the water leg. See Figure 2-2. You must be able to connect to both transmitters from ProLink III. You must know the reference temperature that you plan to use. You must have the Oil & Water Density Calculator. This is a spreadsheet tool developed by Micro Motion. You can obtain a copy from your Micro Motion representative. Procedure 1. Wait until separation has occurred. 2. Collect data from the oil leg. a. Make a connection to the transmitter on the oil leg. b. Read and record the density value. Important The accuracy of net oil data depends on the accuracy of the density data. Never use an unstable density value, or any density value that has an elevated drive gain. c. Read and record the temperature value. 3. Collect data from the water leg. a. Make a connection to the transmitter on the water leg. b. Read and record the density value. Important The accuracy of net oil data depends on the accuracy of the density data. Never use an unstable density value, or any density value that has an elevated drive gain. c. Read and record the temperature value. 4. Use the Oil & Water Density Calculator to calculate the density of dry oil at reference temperature and the density of produced water at reference temperature. Tip Unless the oil is light hot condensate, the oil will almost always contain some interstitial water. This is generally acceptable for allocation measurements. However, if further accuracy is desired, you can determine the water cut and use it in the calculation. To determine or estimate the water cut, take a shakeout sample from one of the following: • The current flow/dump cycle, at the time of minimum density • Similar oils produced from the same reservoir Application Manual 31 Configure APM using ProLink III • The tank or tanks that the separator flows into Enter this water cut into the Oil & Water Density Calculator to calculate the density of dry oil at reference temperature. 4.2.2 Configure NOC parameters using ProLink III You must configure the transmitter with site-specific values for net oil measurement. Prerequisites Ensure that Mass Flow Cutoff is set to a non-zero value. This ensures that totalizing stops when remediation is active. In most installations, the default value is satisfactory. See the transmitter configuration manual for instructions on setting or verifying Mass Flow Cutoff. Ensure that the two-phase flow limits are set to the default values: Two-Phase Flow Low Limit = 0 g/cm³, Two-Phase Flow High Limit = 5 g/cm³. In a typical application, these limits will never be reached, so the transmitter will never initiate standard two-phase flow processing. APM processing will be implemented instead. If you plan to use a water cut monitor: • Channel D must be available to use as a mA input. • The water cut monitor must be installed and wired to Channel D. Procedure 1. Choose Device Tools > Configuration > Process Measurement > Advanced Phase Measurement. 2. If necessary, set Fluid Type to Net Oil (NOC) and click Apply. 3. Set Production Type to the option that best describes the majority of flow in your system and click Apply. Option Description Continuous Flow Relatively constant flow rate, e.g., natural production, ESP Variable Flow 4. Flow that stops and starts, or fluctuates frequently between high and low flow rates, e.g., pump jack, test separator If you set Production Type to Variable Flow, set Density Corrective Action to the action to be taken when gas is detected. Option Description Hold Last Value Volume is calculated using an average density value from an earlier point in the process. Density Oil @ Line Volume is calculated using the density of dry oil at line conditions. 5. 32 If line pressure is greater than 250 psi absolute, enter the density of the entrained gas at typical line conditions. Micro Motion® Advanced Phase Measurement Configure APM using ProLink III Tip If you need help determining this value, use the Gas Wizard provided in the ProLink III window. 6. Enter the values obtained from density determination. a. Set Dry Oil Density at Reference to the density of dry oil, corrected to reference temperature. b. Set Water Density at Reference to the density of water, corrected to reference temperature. 7. Set Reference Temperature to the temperature to which net oil and net water measurements will be corrected. 8. If you want to use a water cut monitor, set up the mA input to receive the water cut data. a. Choose Device Tools > Configuration > I/O > Channels and configure Channel D to operate as an mA input. b. Choose Device Tools > Configuration > I/O > Inputs > mA Input. c. Set Assignment to Watercut @ Line. d. Verify the settings of Lower Range Value and Upper Range Value. Default values: • Lower Range Value = 0% • Upper Range Value = 100% In most cases, these values are not changed. e. Set mA Input Damping as desired. 9. Set Average Reporting Interval to the time period, in minutes, over which process variables will be averaged. The averages are written to the Modbus registers, and are available for retrieval by a Modbus host. 10. Set Contract Start Time to the time of day at which the contract starts. The contract time is based on the transmitter clock. You can change the setting of the transmitter clock if necessary. See the transmitter configuration manual for more information. Enter the time in a 24-hour HH:MM format, where 00:00 = midnight. Example: 18:30 11. Select up to four inventory values to use as contract totals, to be tracked for each contract period. Each contract total is set to 0 every 24 hours, at the configured Contract Start Time. Application Manual 33 Configure APM using ProLink III Tip You can configure custom inventories and use them for contract totals. See the transmitter configuration manual for more information. 4.3 Configure APM to measure gas with entrained liquid (mist), using ProLink III This measurement option is appropriate for gas process fluids with intermittent entrained liquid (mist). Prerequisites Ensure that Mass Flow Cutoff is set to a non-zero value. This ensures that totalizing stops when remediation is active. In most installations, the default value is satisfactory. See the transmitter configuration manual for instructions on setting or verifying Mass Flow Cutoff. Ensure that the two-phase flow limits are set to the default values: Two-Phase Flow Low Limit = 0 g/cm³, Two-Phase Flow High Limit = 5 g/cm³. In a typical application, these limits will never be reached, so the transmitter will never initiate standard two-phase flow processing. APM processing will be implemented instead. Procedure 1. Choose Device Tools > Configuration > Process Measurement > Advanced Phase Measurement. 2. If necessary, set Fluid Type to Gas with Liquid and click Apply. 3. Set Pre-Mist Averaging Period to the number of seconds over which density data will be averaged, to produce the substitute density value. 4. Set Post-Mist Adjustment Delay to the number of seconds that the system will wait before beginning measurement remediation. 5. Set Average Reporting Interval to the time period, in minutes, over which process variables will be averaged. The averages are written to the Modbus registers, and are available for retrieval by a Modbus host. 6. Set Contract Start Time to the time of day at which the contract starts. The contract time is based on the transmitter clock. You can change the setting of the transmitter clock if necessary. See the transmitter configuration manual for more information. Enter the time in a 24-hour HH:MM format, where 00:00 = midnight. Example: 18:30 7. 34 Select up to four inventory values to use as contract totals, to be tracked for each contract period. Micro Motion® Advanced Phase Measurement Configure APM using ProLink III Each contract total is set to 0 every 24 hours, at the configured Contract Start Time. Tip You can configure custom inventories and use them for contract totals. See the transmitter configuration manual for more information. Application Manual 35 Configure APM using ProLink III 36 Micro Motion® Advanced Phase Measurement Additional configuration for APM 5 Additional configuration for APM Topics covered in this chapter: • • • 5.1 Configure viewing and reporting for APM process variables Configure the totalizer history log to include APM contract totals Configure events Configure viewing and reporting for APM process variables When APM is enabled, additional process variables are available. 5.1.1 • To configure a process variable as a display variable, see the manual entitled . • To report a process variable over an output, see the manual entitled . • To query a process variable using Modbus, follow standard Modbus programming techniques. APM-specific process variables The process variables listed here are available only when APM is enabled. The following table lists the APM-specific process variables by measurement option, and provides information on reporting. Table 5-1: APM-specific process variables APM measurement option Viewing and reporting MAO1, MAO2, MAO3 Process variable Liquid with gas Net Oil with gas Gas with liquid Display Modbus Extended Drive Gain ✓ ✓ ✓ ✓ ✓ Gas Void Fraction ✓ ✓ ✓ ✓ DensityOil@Line ✓ ✓ ✓ DensityOil@Ref ✓ ✓ ✓ NetFlowOil@Line ✓ ✓ ✓ ✓ ✓ NetFlowOil@Ref ✓ ✓ ✓ ✓ ✓ NetTotalOil@Line ✓ ✓ ✓ NetTotalOil@Ref ✓ ✓ ✓ NetFlowWater@Line ✓ ✓ ✓ ✓ ✓ NetFlowWater@Ref ✓ ✓ ✓ ✓ ✓ Application Manual FO1, FO2 ✓ 37 Additional configuration for APM Table 5-1: APM-specific process variables (continued) APM measurement option Liquid with gas Process variable Net Oil with gas Gas with liquid Viewing and reporting Display Modbus MAO1, MAO2, MAO3 NetTotalWater@Line ✓ ✓ ✓ NetTotalWater@Ref ✓ ✓ ✓ Watercut@Line ✓ ✓ ✓ ✓ Watercut@Ref ✓ ✓ ✓ ✓ FO1, FO2 APM contract period Today's total ✓ ✓ ✓ ✓ Yesterday's total ✓ ✓ ✓ ✓ 5.1.2 Default display variables The following table lists the default display variables for APM. In all cases, the two-line display option is enabled. All APM process variables can be configured as display variables. Table 5-2: Default display variables APM measurement option Display variable 38 Liquid with gas NOC with gas Gas with liquid Two-line display, Varia- Volume Flow Rate ble 1 Volume Flow Rate Mass Flow Rate Two-line display, Varia- Volume Total ble 2 Water Cut@Line Mass Total Display Variable 1 Density Net Oil Flow Rate@Line Temperature Display Variable 2 Temperature Net Oil Total@Line Density Display Variable 3 GVF Net Water Total@Line Empty Display Variable 4 Empty Temperature Empty Display Variable 5 Empty GVF Empty Display Variable 6–15 Empty Empty Empty Micro Motion® Advanced Phase Measurement Additional configuration for APM 5.2 Configure the totalizer history log to include APM contract totals The transmitter can store APM contract totals to the totalizer history log. This allows you to access totals from earlier contract periods. Otherwise, the transmitter maintains data for only the current contract period (today) and the immediately preceding contract period (yesterday). 1. Ensure that you have configured the APM contract totals as desired. 2. Choose Device Tools > Configuration > Totalizer History Log. 3. Do not change the settings of Start Logging Date, Start Logging Time, or Log Interval. These parameters are set automatically by the APM application. 4. Set Log Total 1, Log Total 2, Log Total 3, and/or Log Total 4 to the desired APM contract total. You can configure the totalizer history log to include both APM and non-APM totals. 5.3 Configure events When APM is enabled, additional process variables are available to use in event configuration. See the transmitter configuration manual for instructions on configuring events. Application Manual 39 Additional configuration for APM 40 Micro Motion® Advanced Phase Measurement Transmitter operation 6 Transmitter operation Topics covered in this chapter: • • 6.1 Read APM process variables Read APM contract totals Read APM process variables You can use any standard method to read APM process variables. APM process variables can be configured as display variables or assigned to outputs. See the transmitter configuration manual for information on using the display to read process variables. You can write a Modbus program to read APM process variables. 6.2 Read APM contract totals APM operates on a 24-hour contract period. You can read APM contract totals for the current contract period and for the previous contract period. Depending on the configuration of the totalizer history log, you may be able to read contract totals for earlier periods. The APM contract totals are derived from existing inventories. However, the APM contract totals are reset automatically at the beginning of each contract period. Therefore, the values shown for APM contract totals will probably not match the values shown for the inventories. Important You can reset inventories manually, and you can stop and start inventories manually. However, if you do this, data for the current contract period will not reflect the entire 24-hour period. Data for earlier contract periods is not affected. Procedure • • Application Manual To read APM contract totals for the current contract period: - Using the display: Menu > Operations > Totalizers > See APM Totals > Current Totals - Using ProLink III: Device Tools > Totalizer Control > APM Contract Totals To read APM contract totals for the previous contract period: - Using the display: Menu > Operations > Totalizers > See APM Totals > Yesterday's Totals - Using ProLink III: Device Tools > Totalizer Control > APM Contract Totals 41 Transmitter operation • To read APM contract totals from earlier contract periods, you must read the totalizer history log. See the transmitter configuration manual for more information. Related information Configure the totalizer history log to include APM contract totals 42 Micro Motion® Advanced Phase Measurement Application parameters and data Appendix A Application parameters and data Topics covered in this appendix: • • A.1 Modbus interface to APM configuration parameters Modbus interface to APM process data Modbus interface to APM configuration parameters You can use a Modbus tool to configure APM or to modify the existing configuration. This section provides information on the Modbus registers that are used in APM configuration. Tip Typically, APM configuration is performed using either ProLink III or the display. This information is provided for completeness. Restriction This section includes only Modbus registers that are specific to APM configuration, or that have been redefined for APM configuration. To use Modbus to configure other parameters, see the Modbus Interface Tool. Table A-1: APM-specific configuration parameters APM measurement option Modbus Parameter Liquid with gas Net Oil with gas Gas with liquid Address Data type Integer codes / Unit (Range) Output Type ✓ ✓ ✓ 3940 U16 • 0 = No remediation • 1 = Liquid with gas, consistent flow • 2 = NOC with gas, consistent flow • 3 = Liquid with gas, variable flow • 4 = NOC with gas, variable flow • 5 = Gas with liquid Gas Density(1) ✓ ✓ ✓ 3935 Float Configured unit Density Corrective Action ✓ 4450 U16 • 0 = Hold Last Value • 1 = Density Oil @ Line Reference Temperature ✓ 319 Float Configured unit Application Manual 43 Application parameters and data Table A-1: APM-specific configuration parameters (continued) APM measurement option Liquid with gas Parameter Net Oil with gas Gas with liquid Modbus Address Data type Integer codes / Unit (Range) Dry Oil Density @ Ref ✓ 1959 Float g/cm³ (0.2–1.5) Water Density @ Ref ✓ 1831 Float g/cm³ (0.5–1.5) Pre-Mist Averaging Period ✓ 619 U16 seconds (2–128) Post-Mist Averaging Period ✓ 620 U16 seconds (2–128) Average Reporting Inter- ✓ val ✓ ✓ 3900 U16 minutes (1–1440) Contract Start Time ✓ ✓ ✓ 3966 U16 hours (0–23) Contract Total 1 ✓ ✓ ✓ 3967 U16 Contract Total 2 ✓ ✓ ✓ 3968 U16 Contract Total 3 ✓ ✓ ✓ 3969 U16 Contract Total 4 ✓ ✓ ✓ 3970 U16 • • • • • • • 4 = Inventory 1 7 = Inventory 2 18 = Inventory 3 64 = Inventory 4 25 = Inventory 5 28 = Inventory 6 31 = Inventory 7 (1) At line conditions A.2 Modbus interface to APM process data In typical operation, a Modbus interface is used to read process data. This section provides information on the Modbus registers that contain APM process data. Restriction This section includes only process data that is specific to APM. To use Modbus to read other process data, see the Modbus Interface Tool. Table A-2: APM-specific process variables APM measurement option Process variable Liquid with gas Net Oil with gas Gas Void Fraction ✓ Gas with liquid Modbus Address Data type Unit ✓ 3907 Float % Density Oil @ Line ✓ 345 Float SGU Density Oil @ Line ✓ 347 Float °API Net Oil Flow @ Line ✓ 1553 Float Configured unit Net Oil Flow @ Ref ✓ 1547 Float Configured unit 44 Micro Motion® Advanced Phase Measurement Application parameters and data Table A-2: APM-specific process variables (continued) APM measurement option Liquid with gas Net Oil with gas Gas with liquid Modbus Address Data type Unit ✓ 1665 Float Automatically derived from configured unit Net Oil Total @ Line(2) ✓ 4240 Double Automatically derived from configured unit Net Oil Total @ Ref(1) ✓ 1661 Float Automatically derived from configured unit Net Oil Total @ Ref(3) ✓ 4236 Double Automatically derived from configured unit Net Water Flow @ Line ✓ 1561 Float Configured unit Net Water Flow @ Ref ✓ 1549 Float Configured unit Net Water Total @ Line (1) ✓ 1667 Float Automatically derived from configured unit Net Water Total @ Line(4) ✓ 4248 Double Automatically derived from configured unit Net Water Total @ Ref(1) ✓ 1663 Float Automatically derived from configured unit Net Water Total @ Ref(5) ✓ 4244 Double Automatically derived from configured unit Watercut @ Line ✓ 1555 Float % Watercut @ Ref ✓ 1557 Float % 989 U32 Seconds 433, Bit #12 U16 • 0 = Inactive • 1 = Active Process variable Net Oil Total @ Line(1) ✓ Total Mist Time(6) TMR remediation status Current period data (Period Averaged Outputs) PAO Mass Flow ✓ ✓ ✓ 3949 Float Configured unit PAO Density ✓ ✓ ✓ 3951 Float Configured unit PAO Volume Flow ✓ ✓ ✓ 3953 Float Configured unit PAO Net Oil Flow @ Line ✓ 3955 Float Configured unit PAO Net Oil Flow @ Ref ✓ 3957 Float Configured unit PAO Watercut @ Line ✓ 3959 Float Configured unit 3961 Float Configured unit PAO Gas Void Fraction ✓ ✓ PAO Temperature ✓ ✓ ✓ 3963 Float Configured unit ✓ ✓ ✓ 3972 Float Automatically derived from configured unit APM contract period Today's total 1 Application Manual 45 Application parameters and data Table A-2: APM-specific process variables (continued) APM measurement option Modbus Process variable Liquid with gas Net Oil with gas Gas with liquid Address Data type Unit Today's total 2 ✓ ✓ ✓ 3974 Float Automatically derived from configured unit Today's total 3 ✓ ✓ ✓ 3976 Float Automatically derived from configured unit Today's total 4 ✓ ✓ ✓ 3978 Float Automatically derived from configured unit Yesterday's total 1 ✓ ✓ ✓ 3980 Float Automatically derived from configured unit Yesterday's total 2 ✓ ✓ ✓ 3982 Float Automatically derived from configured unit Yesterday's total 3 ✓ ✓ ✓ 3984 Float Automatically derived from configured unit Yesterday's total 4 ✓ ✓ ✓ 3986 Float Automatically derived from configured unit (1) (2) (3) (4) (5) (6) 46 Legacy NOC register Inventory 4 (only if you are using the default configuration) Inventory 3 (only if you are using the default configuration) Inventory 6 (only if you are using the default configuration) Inventory 5 (only if you are using the default configuration) Automatically set to 0 on a power cycle Micro Motion® Advanced Phase Measurement Application parameters and data Application Manual 47 *MMI-20030076* MMI-20030076 Rev AA 2015 Micro Motion Inc. USA Worldwide Headquarters 7070 Winchester Circle Boulder, Colorado 80301 T +1 303-527-5200 T +1 800-522-6277 F +1 303-530-8459 www.micromotion.com Micro Motion Europe Emerson Process Management Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 70 413 6666 F +31 (0) 318 495 556 www.micromotion.nl Micro Motion Asia Emerson Process Management 1 Pandan Crescent Singapore 128461 Republic of Singapore T +65 6777-8211 F +65 6770-8003 Micro Motion United Kingdom Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U.K. T +44 0870 240 1978 F +44 0800 966 181 Micro Motion Japan Emerson Process Management 1-2-5, Higashi Shinagawa Shinagawa-ku Tokyo 140-0002 Japan T +81 3 5769-6803 F +81 3 5769-6844 ©2015 Micro Motion, Inc. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Process Management family of companies. All other marks are property of their respective owners.
© Copyright 2026 Paperzz