TopWorx D-Series D2-FF Foundation Fieldbus IOM (for previous model before 2013)

Valvetop™ D-Series with FF Option
FOUNDATION ™Fieldbus
Installation, Operation & Maintenance Manual
Table of Contents
2
2
4
4
5
6
8
10
16
18
20
21
26
27
29
31
35
Introduction
Quick Installation Guide
Installation
Storage
Pneumatic Connection
Electrical Connection
FF Operation
Troubleshooting and Maintenance
Appendix A: FF Technology
Appendix B: Resource Block
Resource Block DD Menu Structure
Appendix C: Transducer Block
Transducer Block DD Menu Structure
Appendix D: Discrete Output (DO) Block
Appendix E: Discrete Input (DI) Block
Appendix F: Dimension & Assembly Drawings
Appendix G: Specifications & Reference Data
™
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Introduction
This manual is intended to provide instruction for Installing, Operating and Maintaining the TopWorx Model
DXP/DXS-FF Discrete Valve Controller with FOUNDATION™ Fieldbus.
Warnings and Precautions that require special instructions or
considerations are noted by this symbol.
DXP Quick Start Installation Guide
Step 1 - Mount DXP/DXS-FF (Fig. 1)
a) Connect bolts firmly between switchbox and bracket
b) Connect bolts loosely between actuator and bracket
c) Cycle actuator to limits in both directions 3 times to center shaft
d) Tighten the bolts between the actuator and bracket
Step 2 - Secure pneumatic connections
a) Refer to Figure 2 for details
b) Use of Locktite 567 is recommended
Step 3 - Make electrical connections
a) Attach fieldbus wiring to FF terminals (Fig. 2)
b) FOUNDATION Fieldbus wiring is polarity insensitive
Step 4 - Calibrate switches
a) Move the valve to the CLOSE position, push and rotate lower
cam to activate the Red LED
b) Move the valve to the OPEN position, push and rotate upper
cam to activate the Green LED
c) Verify calibration by actuating valve open and closed several times
NOTE: Switches can be set using calibration switch without FF connection by
using any 9-32VDC power source.
Step 5 - Commission DXP-FF
a) Connect single DO to Channel 5
• No DI needed - Readback_D provides the actual valve position
b) Set the Mode to AUTO (Automatic) in the Transducer Block
Calibration Switch
Sim
OPEN CLOSE FF
Auxilliary Input
Terminals
(Dry contacts only)
Mounting - Figure 1
Std Operation
Jumper Location
WrtPrt
AUX
SCM-FF
Foundation
Fieldbus Loop
Terminals
2
FF
- V2 +
FLASH RESET
Wiring - Figure 2
- V1 +
Piezo Pilot
Terminals
Single Pilot
Dual Pilot
+ = Orange
- = Black
NOTE: TopWorx has pre-configured
modules and faceplates available for
DeltaV control systems. Contact
TopWorx factory for more
information.
www.topworx.com
TM
Installation on Actuator
Orientations, Normal and Reverse Acting
Normal acting is full CW when the process valve is closed and CCW when the process valve is open. Reverse acting
is full CW when the process valve is open and CCW when the process valve is closed.
90° indicator dome assemblies are design to accommodate any mounting arrangement and can be adjusted up to
9° off axis if needed. 45° indicator dome assemblies can only accommodate normal acting applications that are
mounted parallel ±9°. Consult your local distributor or factory representative for 45° reverse acting or mounted
perpendicular applications.
Illustration #1:
The image to the left shows a Valvetop unit mounted
parallel to the process valve in the closed position.
The green arrow at the top shows the “normal acting”
direction of travel to open the valve. This is the standard
orientation and your unit unless otherwise specified will
be factory set to operate in this fashion.
Illustration #2:
The image to the right shows a Valvetop mounted
perpendicular to the process valve in the closed
position. The green arrow at the top shows the
“normal acting” direction of travel to open the valve.
Notice that the indicator dome has been rotated 90°
compared to the unit above.
3
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Installation on Actuator (continued)
Mounting
TopWorx has numerous mounting bracket kits available to meet your specific application, whether rotary or linear.
Consult your local distributor or factory representative for ordering information. The illustration shows a direct Namur
mount on a quarter turn valve. Refer to your mounting kit documentation for specific mounting instructions.
Storage
Until conduit, conduit plugs, and any applicable spool valve port connections are properly installed, the ValveTop
unit will not support its IP/NEMA rating as the unit ships with temporary covers. Ensure that it is stored in a dry
environment with a relative humidity range between 10%-95% and a temperature ranging from -40ºF (-40ºC) to
160ºF (71ºC). Once properly installed, the temperature range listed on the nameplate will supersede this storage
temperature range.
Illustration #3: Mounting Assembly
Installation Notes
1. Use caution not to allow undue axial (thrust) load on the shaft.
2. Cycle the valve a couple of times prior to final tightening of the
mounting kit hardware. This allows the shaft to self-center in the
pinion slot, or coupler. Refer to the dimensions and materials
section of this document for appropriate tightening torque.
3. Always use sound mechanical practices when torquing down anyhardware or making pneumatic connections. Refer to the Integrated
Pneumatic Control Valves section for detailed information on
pneumatic connections.
4. This product comes shipped with conduit covers in the conduit
entries in an effort to protect the internal components from debris
during shipment and handling. It is the responsibility of the
receiving and/or installing personnel to provide
appropriate permanent sealing devices to prevent
the intrusion of debris, or moisture, when stored
outdoors or when installed.
It is the responsibility of the installer, or end user, to
install this product in accordance with the National
Electrical Code (NFPA 70) or any other national or
regional code defining proper practices.
4
www.topworx.com
TM
Pneumatic Hookup Procedures
Prior to connecting the supply air to the spool valve, flush the system to remove any debris or contaminates. Galvanized pipe can easily flake and contaminate the system and therefore is not recommended. A 40 micron point of use
filter at every device is recommended.
4-Way Spool Valves
The TopWorx spool valve is a 5 port, 4-way valve driven by an internally mounted pilot. The spool valve supply port
and work ports are marked as follows:
Highly Recommended
TopWorx highly recommends Locktite 567 brand thread
sealant. Do not use a hard setting pipe compound. If Teflon
thread seal tape is used, start the wrap on the second
thread from the leading thread of the fitting. This will prevent tape shreds from contaminating the spool valve seals.
Breathers (AL-M31) should be installed in the exhaust
ports to keep debris from falling into the spool valve and
damaging the seals. This must be addressed prior to installation, or storage.
A flow control may be used in Port 3, but should NEVER
BE USED in Port 5. Any blockage or restriction may cause
an internal pressure build-up inside the enclosure and pose
a safety issue.
Spool Valve Specifications
***Never Plug, Block or Restrict Port 5***
Always install vents
or speed controls
Supply
5
3
1
4
2
Always install vents
or speed controls
Supply
5
Dried, filtered air (40 micron)
Max Operating
Pressure
100psi (0.69 MPa) (6.89Bar)
Min. Operating
Pressure
30psi (0.21 MPa) (2.07Bar)
Max Consumption Rate
600 cc/min @ 80psi
Ambient
Temperature Range
Refer to Product Nameplate Marking
Flow Coefficient
1.2Cv or 3.0Cv
Environment Rating
Type 4, 4X, IP67
Port Size
1/2” NPT for 3.0Cv valve
1/4" NPT for 1.2Cv valve
Manual Override
Available in Latching/Non-Latching
Push Type & Palm Actuator Type
Valve Body
Available in Hardcoat Anodized
Aluminum, 304, or 316 Stainless Steel
3
1
4
Medium
2
Valve Seals
Port to Close
Port to Open
DOUBLE ACTING ACTUATORS
Plug
Port to Open /Close
Spool Seals: Buna-N
Valve Body Seals available in
Buna-N, Silicone, EPDM & Viton.
SPRING RETURN ACTUATORS
5
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Electrical / FF Connections
The FOUNDATION Fieldbus Sensor Communications Module (SCM-FF) combines integral switch relays for position
sensing with FOUNDATION Fieldbus communications and pilot valve output drivers.
Pilot Valve Wiring
Single Pilot Valve
·
·
The Orange (or Red) lead is terminated on V1+. (+ = Orange)
The Black lead is terminated on V1-. (- = Black)
Dual Pilot Valve
·
·
The open valve wiring to the V1 terminal (+ = Orange)
The close valve wiring to the V2 terminal (- = Black)
FOUNDATION Fieldbus Wiring
The Fieldbus Segment Wiring is connected to the FF Terminals on the SCM. These terminals are NOT polarity
sensitive.
It is strongly recommended that FF wiring leads are not daisy-chained together and each drop provides
short-circuit protection.
Auxiliary Dry Contact
Attach dry contact wiring to the AUX terminals.
Calibration Switch
Std Operation
Jumper Location
Sim
OPEN CLOSE FF
Auxilliary Input
Terminals
(Dry contacts only)
WrtPrt
AUX
SCM-FF
Foundation
Fieldbus Loop
Terminals
FF
- V2 +
FLASH RESET
- V1 +
Piezo Pilot
Terminals
Single Pilot
Dual Pilot
+ = Orange
- = Black
Illustration #4: Mounting Assembly
Flash Reset Button
When there is an active device alarm, the LEDs will blink. The Flash Reset Button will stop the flashing indications.
For testing of the pneumatics and calibration of the target assembly, a 9 to 32 VDC power supply can be
used with the calibration switch to open and close the valve without a fieldbus loop attached.
6
www.topworx.com
TM
Calibration of Target / Feedback
Calibration of the FOUNDATION Fieldbus SCM-FF
Never perform calibration procedure unless area is known to be safe.
·
·
For Intrinsically Safe models, unit must be wired in accordance with Control Drawing S-K088A, or I.S.
components may be damaged.
For standard explosion-proof models: The OPEN and CLOSED limit switches encapsulated within the
SCM-FF may be calibrated using a DC power supply set between 9-32V, or calibrated once connected
to the Fieldbus network.
Step 1
Connect the power supply, or Fieldbus wires, to the FF terminals. The terminals are not polarity sensitive.
With power applied to the FF terminals, the valve may be manually stroked using the Calibration Switch on
the SCM-FF.
Step 2
Place calibration switch to the CLOSE position. Valve should move to CLOSE position. If it does not, consult
troubleshooting section of page 11.
Step 3
Disengage the bottom Cam from the splined hub and rotate the bottom Cam clockwise until the Red LED
lights. Release the Cam to re-engage the splined hub.
Step 4
Slide the calibration switch to the OPEN position. Valve should move to OPEN position. If it does not,
consult troubleshooting section on page 11.
Step 5
Disengage the top Cam from the splined hub and rotate the top Cam counter-clockwise until the Green
LED lights. Release the Cam to re-engage the splined hub.
Step 6
Cycle the valve CLOSED and OPEN a few times using the calibration switch to verify both limit switches are
maintaining their set points.
Step 7
Place calibration switch in the FF position. If using a power supply to calibrate, disconnect leads to the
supply, and connect the Fieldbus loop when ready to put into service.
Step 8
Manipulate the transducer parameters via the control system as necessary for desired mode of operation.
NOTE: If using a reverse acting actuator, re-calibrate switches using Steps 3-6, but rotate counter-clockwise
for close and clockwise for open. Reverse Action must be set in the Transducer Block (see “Transducer
Block Initialization, Single-Dual Action”).
7
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Section 2: Operation
This section of the manual provides operational information for configuring the SCM-FF device on the
FOUNDATION Fieldbus Host Control System. This section includes both required Control Configuration and
optional Monitoring Configuration information.
Control Configuration (Required)
The TopWorx FOUNDATION Fieldbus products should be configured for operation using a single Discrete
Output (DO) Function Block with Channel Parameter assignment of 5. This module configuration will
provide a multi-value DO Block that will fully control a single or a dual output device. The Readback_D
parameter will provide actual valve position based on the Open / Closed Limit Switches in the device.
Discrete Input (DI) Blocks are neither required nor desired for feedback function.
The values of these parameters are as follows:
DO
DO Channel
Assignment
5
Figure 4
Definition
Readback_D
Valves
Open/Close/Stop 0 - Closed
Outputs
1 - Open
2 - Stopped
3 - Opening
4 - Closing
Control Method
Single Block,
Dual Action
NOTE: TopWorx has pre-configured modules and faceplates available for DeltaV control systems.
Contact the TopWorx factory or www.topworx.com for more information.
The Transducer Block is shipped from the factory in the OOS (Out of Service) Mode to allow field
installation/testing using the SCM calibration switch. Once the installation and the configuration above
are complete, The Transducer Block must be placed in the AUTO (Automatic) Mode for device
operation.
The complete device control algorithm should be as depicted below:
Readback_D
Parameter
8
Discrete
Control
Function
Block
Discrete
Output (DO)
Function
Block
www.topworx.com
TM
Alarm Configuration (Optional)
Discrete Input (DI) Block may be configured for monitoring internal Device Alarms within the Control Strategy
of the Host System.
The Internal Device Alarms can be monitored using a Discrete Input (DI) Block with the Channel Parameter
assignment of 13. All alarms that are activated (checked in the Transducer Block) can be read by this single
DI block in a masked fashion. See Appendix C for Transducer Block parameter settings.
DI Channel
Assignment
Definition
OUT_D Values
13
Device Alarms
0x00 - No Alarm
0x01 - Cycle Count
0x02 - Time to Open
0x04 - Time to Close
0x08 - Time Board Temp Hi
0x10 - Board Temp Lo
Multiple active alarms are depicted by a HEX value representing the sum of all active alarms OUT_D Values. For example, a device with a Cycle Count Alarm and a Time to Close Alarm both active would have an
OUT_D Value of 0x05.
Auxiliary Input Configuration (Optional)
The AUX Input terminal may be monitored using a Discrete Input (DI) Block with the Channel Parameter
assignment of 9.
DI Channel
Assignment
Definition
9
Aux Input
OUT_D Values
0 - Aux Dry Contact Closed
1 - Aux Dry Contact Open
9
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Section 3: Maintenance
This Section provides information on Troubleshooting and Component Replacement for the DXP-FF.
Troubleshooting
Description of Problem
Possible Cause
Possible Solution
Red or green LED does not illuminate when
the valve is either in closed or open position
Target not calibrated properly
Use calibration procedure on page 7
LED's do not operate, regardless of valve
position
Power not connected to FF terminals
Make sure at least 9 VDC connected to FF terminals
LED's not enabled
Transducer block parameter "LED_ENABLE" set to ENABLE
Transducer Block in incorrect mode
Set transducer block actual model to "Out of Service"
Power not connected to FF terminals
Make sure at least 9VDC connected to FF terminals
Piezo and spool valve is not pressurized
Verify proper air pressure. Reference mechanical
troubleshooting chart
LEDs flash from red to green after valve has
shifted
Time to open/close alarm has triggered
Target not calibrated properly. Recalibrate using the
procedure on page 7
LEDs flash from red to green as soon as unit
starts moving during a setpoint change
Operational setpoints do not match limit switch positions
(i.e. the closed switch is made when the unit has an open
setpoint)
Set Transducer Block Action_Element setting according to
chart
Module goes "unattached" from the segment
Power dropped below 9V
Check voltage to ensure that it is consistently above 9V
Check for loose wire connections
Calibration switch will not operate
Verify that the segment has a terminating resistor at each
end
Excessive noise on the segment
Valve will not shift
Using a Fieldbus Monitor, verify that peak and average
noise levels are <11db
See mechanical troubleshooting flowchart on page 12
No response from operator interface
DO Block and/or DO Channel not correctly assigned
Transducer Block Out of Service
Configuration/DO Block NOT downloaded
Follow troubleshooting chart, (pg. 11) then continue with
mechanical troubleshooting chart (pg. 12). If problem
persists contact the factory
Bad Status on FeedBack Signal and/or No
Feedback signal
Transducer Block mode is Out of Service
Place Transducer Block in Auto Mode
10
www.topworx.com
TM
DO
DO
DO
DO
DO
DO
DO
11
D-Series with FF Option
12
Installation, Operation & Maintenance
502.969.8000
www.topworx.com
TM
Component Replacement
Manifold
O-rings,
Buna
Piezoelectric
Pilot Device
Inserts
M4x35
RED Urethane
Tubing (Supply)
10-32 Nylon Plug
Used in Fail Closed
Applications
4-40x.25 (x2)
Bracket
Black
to V -
Orange
to V+
YELLOW
Urethane
Tubing
(Work)
10-32 Nylon
Barb Fitting
Fail Closed Spool Valve Replacement Assemblies
AV-BFCVA20
Std Alum Spool Valve Assy w/Buna seals
AV-BFCVS20
Std 304SS Spool Valve Assy w/Buna seals
AV-BFCV620
Std 316SS Spool Valve Assy w/Buna seals
Flame arrestor O-ring
(x5)
Fail Last Position Spool Valve Replacement Assemblies
M5 x 25mm SHCS (x4)
(4mm hex wrench)
Spool Valve with No Manual Override
AV-BFLPVA20
Std Alum Spool Valve Assy w/Buna seals
AV-BFLPVS20
Std 304SS Spool Valve Assy w/Buna seals
AV-BFLPV620
Std 316SS Spool Valve Assy w/Buna seals
Block-Center Spool Valve Replacement Assemblies
Spool Valve with Single Palm Actuator Override
AV-BBCVA20
Std Alum Spool Valve Assy w/Buna seals
AV-BBCVS20
Std 304SS Spool Valve Assy w/Buna seals
AV-BBCV620
Std 316SS Spool Valve Assy w/Buna seals
Push-button Style Override
Spool Valve with Dual Palm Actuator Override
13
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Indicator Dome,
+ 5O adjustable
Polycarbonate
with keyed mask.
Several rotation and
form options.
Indicator / Dome Replacement
Indicator / Dome Replacement Kits
AV-GB002
90º, Green/Open, Red/Closed, Buna O-Ring
AV-YB002
90º, Yellow/Open, Black/Closed, Buna O-Ring
AV-TB002
90º, Green/Thru, Red/Divert, Buna O-Ring
AV-4B002
90º, Green/Open, Red/Closed, Buna O-Ring
10-32 Captive screws,
Stainless (x4)
O-ring
Available in Buna-N,
Silicone, EPDM, Viton
Color-coded Indicator is
available in several
coordinating rotations and
forms for various valve
types, such as 90deg, 180deg
and Thru-divert applications.
Standard 0.25” DD Shaft,
Stainless
Shaft Replacement
NAMUR Shaft,
Stainless
NAMUR Shaft Replacement Kits
SCM’s with (2) Reed Switches
AV-NSB202
NAMUR Shaft w/Buna-N O-Rings & (2) Cam Assembly
with Installation Hardware
Lubrication
Areas
Standard Shaft Replacement Kits
SCM’s with (2) Reed Switches
AV-SSB202
Standard Shaft w/Buna-N O-Rings & (2) Cam Assembly
with Installation Hardware
2
1
0.375 [9.53mm]
3
0.25 in
0.375 [9.53mm]
4mm
For more shaft dimension
details, see Page 1.
14
www.topworx.com
TM
Sensor Communications Module (SCM-FF) Replacement
Calibration Switch
Std Operation
Jumper Location
Sim
OPEN CLOSE FF
Auxilliary Input
Terminals
(Dry contacts only)
WrtPrt
AUX
SCM-FF
Foundation
Fieldbus Loop
Terminals
FF
- V2 +
FLASH RESET
- V1 +
Piezo Pilot
Terminals
Single Pilot
Dual Pilot
+ = Orange
- = Black
Resetting Factory Defaults in SCM
There are five restart options available for the Resource Block Restart parameter in the TopWorx DXP/DXS-FF. The
fifth parameter is Reset with Factory Defaults and will be implemented by writing 0x05 to the RESTART parameter.
This restart is used to reset the device to factory default initial values.
After Conducting a Reset of Factory Defaults the Device Tag Information will be lost, all DI &
DO Functions Blocks will be assigned to Channel 0 and The Transducer Block will be placed
in Out Of Service.
Do not power down the device for 40 seconds after you execute a “Restart with Factory
Defaults.” Non-Volatile Random Access Memory (NVRAM) is being written and must
complete before device loses power. The device condition is unpredictable if an early
power cycle is executed.
15
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Appendix A: FOUNDATION Fieldbus Technology
Blocks and the User Application
The Fieldbus Foundation has defined a standard for building user applications. The Foundation standard is built
around “Blocks.” Blocks are used to represent different types of functions that the device performs and provide a way
of grouping different parameters and functionality together in an easy to understand framework.
A Fieldbus Foundation device has a Resource Block, Transducer Block, and Function Blocks.
Once the hardware of the TopWorx Sensor-Communication Module (hereafter known as SCM-FF) is set up, fieldbus
communication is used to set the transducer parameters to get the functionality desired. The desired transducer functionality is associated with a function block. The host system is then used to link the function blocks together, and the
application is downloaded to all of the devices in the loop.
Resource Block
The Resource Block describes characteristics of the fieldbus device such as the device name, manufacturer, and serial number. There is only one resource block per device.
Transducer Blocks
Transducer Blocks are the connection of Function Blocks to the real world. Many of the settings unique to a Fieldbus
Device are defined in the transducer block parameters.
The Function Blocks are typically standard between devices, so that they may be linked together to form easily constructed, interoperable applications. The Channels of a transducer block can be attached to a function block for use in
the application.
Function Blocks
Function Blocks provide the control system behavior. The input and output parameters of Function Blocks can be
linked over the fieldbus. The execution of each Function Block is precisely scheduled. There can be many function
blocks in a single user application.
The SCM-FF provides 5 Discrete Input (DI) and 3 Discrete Output (DO) function blocks. Configuration of all these
blocks is NOT required for full device operation.
Process Instrument and its Blocks
Process
Sensors
Resource
Block
Channels
Transducer
Block
Function
Block
Function
Block
Process
Actuators
An application is built by linking together function blocks.
Input
Function
Block
16
Calculation
Or Control
Function
Block
Output
Function
Block
www.topworx.com
TM
FOUNDATION Fieldbus Topology
General Purpose
Power Supply w/ Terminator “ON”
to power (1) Fieldbus segment
T = Fieldbus Terminator
Control
System
T
Terminator “ON”
T
Intrinsically Safe
Power Supply w/ Terminator “ON”
to power (1) Fieldbus segment
Control
System
Repeaters
Terminator “ON”
T
T
T = Fieldbus Terminator
T
T
T
Isolators w/ Terminators “ON”
T
T
T
17
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Appendix B: Resource Block
The resource block contains the hardware specific characteristics associated with a device. It
has no input or output parameters. This block of contained parameters includes such things as
Manufacturer’s ID and revision information. Below is a complete listing of the SCM-FF Resource
Block Parameters.
Complete Resource Block Parameter Listing
ST_REV
TAG_DESC
The revision level of the static data associated with the function block. To support tracking changes
in static parameter attributes, the associated block's static revision parameter will be incremented
each time a static parameter attribute is written but the value is not changed.
The user description of the intended application of the block.
STRATEGY
The strategy field can be used to identify grouping of blocks. This data is not checked or processed
by the block.
ALERT_KEY
The identification number of the plant unit. This information may be used in the host for sorting
alarms, etc.
MODE_BLK
BLOCK_ERR
RESOURCE STATE
TEST READ WRITE
DD_RESOURCE
MANUFAC_ID
DEVICE TYPE
The actual, target, permitted, and normal modes of the block.
This parameter reflects the error status associated with the hardware of software components
associated with a block. It is a bit string, so that multiple errors may be shown.
State of the function block application state machine.
Read/write test parameters - used only for conformance testing.
String identifying the tag of the resource which contains the Device Description for this resource.
Manufacturer identification number - used by an interface device to locate the DD file for the
resource.
Manufacturer's model number associated with the resource - used by interface devices to location
the DD file for the resource.
DD REVISION
Revision of the DD associated with the resource - used by an interface device to locate the DD file
for the resource.
GRANT_DENY
Options for controlling access of host computer and local control panels to operating, tuning and
alarm parameters of the block.
HARD_TYPES
RESTART
FEATURES
FEATURE SELECTION
CYCLE_TYPE
CYCLE SELECTION
MINIMUM CYCLE TIME
FREE_SPACE
FREE_TIME
SHED REMOTE CASCASE
18
The types of hardware available as channel numbers.
Allows a manual restart to be initiated. Several degrees of restart are possible. They are 1: Run, 2:
Restart resource, 3: Restart with defaults, 4: Restart processor; and 5: Restart with factory
defaults.
Used to show supported resource block options.
Used to select resource block options. Enable 0 x 32 bit to allow readbacks from function blocks.
Identifies the block execution methods available for this resource.
Used to select the block execution method for this resource.
Time duration of the shortest cycle interval of which the resource is capable.
Percent of memory available for further configuration. Zero in a preconfigured resource.
Percent of the block processing time that is free to process additional blocks.
Time duration at which to give up on computer writes to function block RCAS locations. Shed from
RCAS shall never happen when SHED REMOTE CASCASE = 0.
www.topworx.com
TM
Complete Resource Block Parameter Listing (cont’d)
SHED REMOTE OUT
FAULT_STATE
SET FAULT STATE
CLEAR FAULT STATE
MAXIMUM NOTIFY
LIMIT NOTIFY
Time duration at which to give up on computer writes to function block Rout locations. Shed from
Rout shall never happen when SHED REMOTE OUT = 0.
Condition set by loss of communication to an output block, fault promoted to an output block or a
physical contact. When Fault State condition is set, then output function blocks will perform their
FSTATE actions.
Allows the Fault State condition to be manually initiated by selecting Set.
Writing a Clear to this parameter will clear the device fault state if the field condition, if any, has
cleared.
Maximum number of unconfirmed alert notify message possible.
Maximum number of unconfirmed alert notify messages allowed.
CONFIRM_TIME
The time the resource will wait for confirmation of receipt of a report before trying again. Retry shall
not happen when CONFIRM_TIME = 0.
WRITE_LOCK
If set, no writes from anywhere are allowed, except to clear WRITE_LOCK. Block inputs will
continue to be updated.
UPDATE_EVT
BLOCK_ALM
ALARM SUMMARY
ACKNOWLEDGE OPTION
WRITE PRIORITY
WR_ALM
ITK_VER
DETAILED BLOCK ERRORS
SUPPORTED_MODES
IKEY
REVISION_ID
REVISION_DATE
This alert is generated by any change to the static data.
The block alarm is used for all configuration, hardware, connection failure or system problems in
the block. The cause of the alert is entered in the subcode field. The first alert to become active will
set the Active status in the Status attribute. As soon as the Unreported status is cleared by the
alert reporting task, another block alert may be reported without clearing the Active status, if the
subcode has changed.
The current alert status, unacknowledged states, unreported states, and disabled states of the
alarms associated with the function block.
Selection of whether alarms associated with the block will be automatically acknowledged.
Priority of the alarm generated by clearing the write lock.
This alert is generated if the write lock parameter is cleared.
Major revision number of the interoperability test case used in certifying this device as
interoperable. The format and range of the version number is defined and controlled by the
Fieldbus Foundation. Note: The value of this parameter will be zero (0) if the device has not been
registered as interoperable by the FF.
Provides list of all active block alarms in the block.
The modes supported by this particular block.
TopWorx revision control.
TopWorx revision control.
TopWorx revision control.
DEVICE REVISION
Manufacturer revision number associated with the resource. Used by an interface device to locate
the DD file for the resource.
CHARACTERISTICS: BLOCK_TAG
Defined to be unique throughout the control system at one plant site. The Tag may be changed
using the FB_TAG service.
MEMORY SIZE
Available configuration memory in the emptry resource. To be checked before attempting
download.
NONVOLATILE CYCLE TIME
Interval between writing copies of NV parameters to non-volatile memory. Zero means never.
19
MODE_RES_BLK_MENU
SETUP_MENU
DISPLAY_RES_MENU
MODE_BLK:TARGET_MODE **
MODE_BLK:ACTUAL_MODE
MODE_BLK: PERMITTED_MODE
MODE:Normal_MODE
RESTART **
**
MAX_NOTIFY **
LIMIT NOTIFY
**CONFIRM TIME
ALARM_SUM_MENU
Acknowledge Option **
Write Priority**
GRANT DENY: GRANT
GRANTDENY:DENY
RESOURCE BLOCK
STRATEGY
ALERT_KEY
RESOURCESTATE
GRANT_DENY_MENU
SHED REMOTECASCADE
SHED REMOTEOUT
FEATURES
FEATURE SELECTION **
FAULT_STATE
SET FAULT STATE **
CLEAR FAULT STATE **
WRITELOCK
CYCLE TYPE
CYCLESELECTION
Alarm
Alarm
Alarm
Alarm
Test
Test
Test
Test
Test
Test
Test
Test
Test
Test
Test
Test
Test
Test
Test
Unacknowledged
Update State
Time Stamp
Static Rev
Relative Index
Unacknowledged
Alarm State
Time Stamp
Subcode
Discrete Value
Read Write: Test Boolean
Read Write: Test Integer8
Read Write: Test Integer16
Read Write: Test Integer32
Read Write: Test Unsigned8
Read Write: Test Unsigned16
Read Write: Test Unsigned32
Read Write: Test Float
Read Write: Test Visible String
Read Write: Test Octet String
Read Write: Test Date
Read Write: Test Time
Read Write: Test Time Difference
Read Write: Test Bit String
Read Write: Test Data Link Layer Time
WR_ALM:
WR_ALM:
WR_ALM:
WR_ALM:
WR_ALM:
EVT:
EVT:
EVT:
EVT:
EVT:
Current
Unacknowledged
Unreported
Disabled
TopWorx SCM-FF
Menu Structure For Handheld Devices and
Host Systems that Support DD Menus
Summary:
Summary:
Summary:
Summary:
ST_REV
HARD TYPES
MINIMUM CYCLE TIME
MEMORY SIZE
NONVOLATILE CYCLE TIME
FREESPACE
FREETIME
DD RESOURCE
REVISION ID
REVISION DATE
UPDATE_EVT_MENU
WRITE_ALM_MENU
SUPPORTED_MODES
Key
BLOCK_ALM: Unacknowledged
BLOCK_ALM: Alarm State
BLOCK_ALM: Time Stamp
BLOCK_ALM: Subcode
BLOCK_ALM: Value
MANUF_ID
DEVICETYPE
DEVICEREVISION
DD REVISION
TAG_DESC **
Characteristics: BLOCK_TAG**
TEST_PARM_MENU
STAT_PARM_MENU
BLOCK_PARM_MENU
Detailed Block Errors
BLOCK_ALM_MENU
BLOCK_ERR
DEV_INFO_MENU
DEV_ID_MENU
BLOCK_OPTION_MENU
BLOCK_EXEC_MENU
ALM_MENU
DEVICE_MENU
BLOCK_MENU
PARAM_MENU
** DenotesWritable Fields
20
502.969.8000
Installation, Operation & Maintenance
D-Series with FF Option
www.topworx.com
Appendix C: Transducer Block
TM
The following is a list of bit selections for Channel 13. Simply select
the appropriate bit to activate the desired functionality.
0x00, No Selection
0x01, Cycle Count
0x02, Time to Open
0x04, Time to Close
0x08, Board Temp Hi
0x10, Board Temp Lo
Transducer Block Initialization
There are several settings in the transducer block that should be set before
commissioning of the SCM-FF.
Through these parameters, a user can configure a wide range of diagnostics
and alarms. These include cycle timers, and counters, as well as temperature
monitoring. The alarm conditions can be configured through a transducer
channel in one DI Block.
Also, the user may configure the SCM-FF for use in Single or Dual pilot valves
for Direct or Reverse Acting applications, all through convenient Transducer
settings.
(a) Diagnostics & Alarming
There will be 5 limit parameters that must be set during calibration. These
parameters will vary with the type of valve the device is operating. The alarm
priorities must also be set, depending on the application.
By simply changing the settings in the transducer, all the diagnostic limits and
functional settings can be set by the end user.
1.
Cycle Times
Set the Cycle Time Open Limit (LIM_CYC_OPEN_TIME) and the
Cycle Time Close Limit (LIM_CYC_CLOSE_TIME) parameters to
the maximum amount of time in seconds the valve is allowed to
complete its stroke before an alarm condition is invoked. If the LEDs
are enabled, they will blink for local notification of the time limit
alarms. If the Cycle Time Open Limit is exceeded, the green LED
will flash. If the Cycle Time Close Limit is exceeded, the red LED will
flash. Pushing the Alarm Reset Pushbutton on the board will stop
the flashing.
The default setting for both the Cycle Time Open and Cycle Time
Closed Time Limit is 10 seconds.
2.
Cycle Count
Set the Cycle Count Limit (LIM_CYC_COUNT) parameter to the
maximum number of valve cycles allowed before a Cycle Count
Alarm condition is activated.
The default setting for the Cycle Count Limit is 50000 cycles.
3.
Temperature
The Temperature High Limit (HI_LIM_BOARD_TEMP) parameter
should be set to alarm when the temperature sensor reads above a
user specified value and the Temperature Low Limit
(LO_LIM_BOARD_TEMP) will be set to alarm when the temperature
sensor reads below a user specified value.
The default setting for the Temperature High Limit is 50°C. The
default setting for the Temperature Low Limit is -10°C.
(c) Calibration Switch Functionality
The SCM-FF is shipped in a mode where the calibration switch is
active. A 9 to 32 VDC power supply can be used to activate and
deactivate the device, to open and close the valve, and set the target.
In order to enable the calibration switch in a safe manner, three
conditions are required to be true simultaneously. These are:
1.
2.
3.
The CAL_SW_STATE parameter transitions to Enabled when all
three conditions have been met simultaneously. This parameter will
transition to the disabled state when the Transducer Block is placed
into service or the CAL_SW_ARM is set to disabled.
NOTE
When the transducer mode changes from OOS mode,
the valve will go to the FF position calculated at the time
regardless of the current position of the valve or the
Calibration switch.
Transducer Special Diagnostic Features
During installation, a special diagnostic parameter called
ACTIVE _BLOCK_ALMS can be used to alert the user of configuration errors specific to the device. This block is used to conveniently
identify some of the issues that may arise with installing the SCM-FF.
The values returned are explained below:
a.
b.
c.
d.
e.
(b) Functional Settings
1.
Single-Dual Action
The ACTION_ELEMENT parameter is used to determine what
direction the actuator goes when energized. The 2 settings of the
ACTION_ELEMENT parameter are Direct and Reverse Acting.
“Reverse Acting” is to be used when the energized state is to close
the valve.
The Default setting for Action Element is DIRECT Action.
2.
Channel 13
Channel 13 is a user configurable input channel. The user can
define the functionality of a DI block associated with Channel 13
by selecting the appropriate bits in the CHAN_13_MASK parameter.
One of several alarms can be used to trigger a DI including cycle
count, over stroke timer, temperature or any combination of these.
The unit is shipped with Channel 13 set up for over/under temperature indication.
CAL_SW_ARM parameter is TRUE/Armed. The
operator may consider this like a calibration switch
lock out parameter when disabled.
The calibration switch on the SCM-FF must be in
the FF position. This allows smooth transition to
the manual control condition.
Transducer block must be in the Out Of Service (OOS)
mode. This sets all of the connected output parameters to
a BAD status, allowing upstream controllers to recognize
the device is not controlled by the control scheme.
f.
g.
h.
i.
None Active - No active block alarms are active.
Invalid Mode - The computed actual mode for the block is
not supported the block’s actual mode will go to out of
service.
Mode Error - The mode calculator detected an error.
Both Contacts Closed - Both contacts are closed.
Conflicting Channels Assigned - Conflicting output
channels have been assigned. (See DO Block Section
for a description of the correct configuration of output
channels).
Open without Close - An ‘Open’ output channel has been
assigned without a ‘Close’ channel.
No Output Channels - No output channels have been
assigned.
Out Of Service - Transducer block is out of service.
Invalid Input - The target position is not valid for the
current device configuration. Check the target setting
to insure that it is in the correct position.
Stroke Valve Method
The method allows the user to simply invoke the method, receive
appropriate warnings of using an operating process and then allow
the user to repeatedly open/close the valve while viewing the actual
feedback from the valve on the screen. This method automatically
makes the necessary transducer block mode changes to enter the
method and automatically reinstate the previous transducer block
mode when the method exits. This prevents the user from unintentionally rendering the device unusable from the host control system.
21
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Transducer Parameters to be set before an application is configured. For a complete list of transducer parameters,
refer to Page 24.
*The timer accuracy for stroke time open and stroke time closed is 60mS minimum.
22
www.topworx.com
TM
Fieldbus Foundation Transducer Channel Architecture
The SCM-FF has one transducer block with 13 channels. The 5 DI and 3 DO function blocks will link to these transducer channels through the standard channel selection capability. (See Function Blocks)
The 13 Transducer Channels are listed below.
Transducer Channels
Notes on Channels
Channels 1 and 5
These are Multi-value DO blocks standard with Fieldbus Foundation. Channel
1 is intended for use with a single control signal, while
Channel 5 is to be used with a dual control signal.
Channels 2, 3 and 4
Channels 2, 3 and 4 use 0 = false and 1 = true for open, close, and stop. This
gives a more comfortable interface for users more familiar with ladder logic. In
the situation where Open and Close are both true (or false) at the same time,
the last input is rejected as invalid.
Readback signals are 0 = false and 1 = true for is-opened, is-closed or isstopped. Channels 2, 3 and 4 cannot be used simultaneously with channels 1
or 5.
Channels 4 and 5
Available with a Dual-Control Pneumatic valve.
Channels 6, 7 and 8
Echoes the Readback information from channels 1, 2 and 3.
Channel 9
Reflects the input from a dry contact type of input wired into the
Auxiliary input screw terminals and uses 0 = closed, 1 = opened
reflecting the contact condition.
Channels 10, 11 and 12
Reflects alarm conditions in the valve. When something needs to happen in
response to these error conditions, a DI should be used to publish the state of the
alarm condition. These channels use 0 = false (no alarm), 1 = true (alarm condition
exists). CTOA, CTCA, and CCA are transducer channels that allow alarms to be
scheduled into the system. These alarms are:
Cycle Time Open Alarm (CTOA – Channel 10)
Cycle Time Closed Alarm (CTCA – Channel 11)
Cycle Count Alarm (CCA – Channel 12)
Above inputs are used in preventative maintenance and indicate when a valve is
operating outside of acceptable times. These channels exist so that some action on
the loop can be scheduled in critical applications. Cycle times may increase with an
increase in valve stiction, and/or a loss of air pressure. The times and counts used
as alarm limits are user settable (see Appendix 2).
Regardless of whether these alarms are linked to function blocks, these FF
standard alarms are always reported to the alarm handling host when one of
these conditions exists and the corresponding priority is set to greater than 1.
Channel 13
Stimulates activity when a set of alarm conditions exist. This channel uses a
user-settable mask to allow any of five alarm conditions to cause the linkable DI
parameter to become true. Channel 13 is a masked OR function. It includes the
previous alarms, as well as a Temperature High (TMPH), and Temperature Low
(TMPL) alerts. For TMPH and TMPL, a sensor is used to sense the temperature of
the circuit board. The user can select which of these alerts on Channel 13 are to be
used by masking out the undesired ones.
23
D-Series with FF Option
Installation, Operation & Maintenance
Complete Transducer Parameter Listing
24
502.969.8000
www.topworx.com
TM
Complete Transducer Parameter Listing (cont.)
25
PRI_BOARD_TEMP **
HI_LIM_BOARD_TEMP **
LO_LIM_BOARD_TEMP **
BOARD_TEMP_ALM_MENU
SUPPORTED_MODES
TAG_DESC **
Characteristics : Block Tag
ALERT KEY
FACTORY_CAL
BLOCK_ERR
ST_REV
UPDATE_EVT_MENU
FINAL_VALUE_D_MENU
SP_D_MENU
FINAL_POS_VAL_D_MENU
DISC_STATE
Unacknowledged
Alarm State
Time Stamp
Subcode
Float Valve
Unacknowledged
Alarm State
Time Stamp
Subcode
Float Valve
TopWorx SCM-FF
Menu Structure For Handheld Devices and
Host Systems that Support
DD Menus
CYC_COUNT_ALM:
CYC_COUNT_ALM:
CYC_COUNT_ALM:
CYC_COUNT_ALM:
CYC_COUNT_ALM:
CYCLE_OPEN_TIME_ALM:
CYCLE_OPEN_TIME_ALM:
CYCLE_OPEN_TIME_ALM:
CYCLE_OPEN_TIME_ALM:
CYCLE_OPEN_TIME_ALM:
Unacknowledged
Alarm State
Time Stamp
Subcode
Float Valve
Unacknowledged
Alarm State
Time Stamp
Subcode
Float Valve
CYCLE_CLOSE_TIME_ALM:
CYCLE_CLOSE_TIME_ALM:
CYCLE_CLOSE_TIME_ALM:
CYCLE_CLOSE_TIME_ALM:
CYCLE_CLOSE_TIME_ALM:
BOARD_TEMP_ALM:
BOARD_TEMP_ALM:
BOARD_TEMP_ALM:
BOARD_TEMP_ALM:
BOARD_TEMP_ALM:
FINAL_POS_VAL_D:DSC_CON_FV
FINAL_POS_VAL_D: Status
SP_D:DSC_CON_SP**
SP_D: Status**
FINAL_VAL_D:DSC_CON_FV
FINAL_VAL_D: Status
UPD_EVT: Unacknowledged
UPD_EVT: Update Set
UPD_EVT: Time Stamp
UPD_EVT: Static Rev
UPD_EVT: Relative Index
PRI_CYC_CLOSE_TIME **
LIM_CYC_CLOSE_TIME **
CYCLE_CLOSE_TIME_ALM_MENU
PRI_CYC_OPEN_TIME **
LIM_CYC_OPEN_TIME **
CYCLE_OPEN_TIME_ALM_MENU
PRI_CYC_COUNT **
LIM_CYC_COUNT **
CYCLE_COUNT_ALM_MENU
TRANSDUCER BLOCK
ACTIVE_BLOCK_AL MS
UNACK_BLOCK_ALMS
ALM_STATE_BLOCK_ALM
TIME_STAMP_BLOCK_ALM
SUBCODE_BLOCK_ALM
VALUE_BLOCK_ALM
DEV_VAR
LAST_OPEN_TIME
LAST_CLOSE_TIME
CYCLECOUNT
ALERT_KEY
BOARD_TEMP
_HI_LO_ALM_
MENU
CYC_CLOSE_
ALM_MENU
CYC_OPEN
_ALM_MENU
CYC_COUNT
_ALM_MENU
ACTION_ELEMENT **
LED_ENABLE **
FAULT_STATE **
CAL_SW_ARM **
CAL_SW_POSITION
CAL_SW_STATE
CLR_CYC_COUNT **
CHAN_13_MASK **
STRATEGY **
ALERT KEY
MODE_BLK:TARGET_MODE**
MODE_BLK: ACTUAL_MODE
MODE_BLK: PERMITTED_MODE**
MODE_BLK:NORMAL_MODE
CONTROL_PARAM_
MENU
MODE_TRANS_BLK_MENU
DEV_SETUP_
MENU
DEV_ALM_MENU
Stroke Valve Method
BLK_ALM_MENU
ALM_VAR_MENU
STATUS_MENU
BLK_PARAM_
MENU
DISPLAY_TRANS_MENU
STROKE_VALVE_
MENU
** DenotesWritable Fields
26
502.969.8000
Installation, Operation & Maintenance
D-Series with FF Option
www.topworx.com
TM
Appendix D: Discrete Output (DO)
Discrete OUTPUT Blocks (DO Block)
There are 3 FOUNDATION Fieldbus standard DO blocks and 5 output channels.
The DO blocks take discrete control data and translate it to actuation in the field.
These blocks are used to open and close the valve. There are 4 different strategies provided to open and close a valve, depending on the system being used,
and whether a single or dual action pilot valve is being used.
Single Block Control Method, Single Action (Default)
Set the Channel Parameter of DO1 to 1(Open/Close Output), and DO2 and DO3
to 0 (No Connection). The valve is now controlled by the wiring going to the V1
terminals. By writing a 0 or a 1 to this DO block will now open and close the
valve.
Single Block Control Method, Dual Action
Set the Channel Parameter of DO1 to 5 (Open/Close/Stop Output), and DO2
and DO3 to 0. The valve is now controlled by the wiring going to the V1 terminals and V2 terminals. By writing a 0 or a 1 to this DO block will now open and
close the valve. Writing a 2 to the DO block will de-energize both the V1 and V2
terminals, stopping a valve using a block center type of pneumatic valve.
To use the READBACK_D values for the BACK CALCULATION OUTPUT
DISCRETE parameter of the DO block, the following two options must be selected:
1. In the Resource Block the “Output Readback” option should be selected.
2. In the DO Block under IO_OPTS, select the “Use PV for BKCAL_OUT” option.
Configuration Error Handling
In order to minimize configuration errors, several write checking features have
been added to the SCM-FF. Write checks to the CHANNEL parameter of the DO
blocks should prevent illegal configurations. These illegal configurations are:
1.
2.
3.
Dual Block Control Method, Single Action
Set the Channel Parameter of DO1 to 2 (Open), DO2 to 3 (Close), and DO3 to
0. Now by writing a 1 to DO1, the valve will Open. Changing this value back to
0, and writing a 1 to DO2 will cause the valve to close.
4.
Three Block Control Method, Dual Action
Set the Channel Parameter of DO1 to 2 (Open) , DO2 to 3 (Close), and DO3 to
4 (Stop). Now by writing a 1 to DO1, the valve will Open. Changing this value
back to 0, and writing a 1 to DO2 will cause the valve to close. Changing this
value back to 0, and writing a 1 to DO3 will cause the outputs to terminals V1
and V2 to turn off, stopping an actuator using a block center pneumatic valve.
5.
Note on Energize to Close
To energize to close (also called Reverse Acting), the ACTION_ELEMENT
parameter must be reset to Reverse Acting. See the Transducer section for
more details.
If the two-state Channel 1 Open-Close has been assigned, an attempt to
assign Channel 2 Open, Channel 3 Close or the Channel 5 Open/Close/
Stop channels will be rejected with a write check.
If the three-state Channel 5 Open-Close-Stop has been assigned, an
attempt to assign the Channel 2 Open, the Channel 3 Close or the Channel 1 Open/Close channels will be rejected with a write check.
If the channel you are trying to assign has already been assigned to another Function Block, the write will be rejected with a write check.
If the Open channel has been assigned and the Close channel has not,
an ‘Open without Close’ block alarm is generated by the block. NO OTHER LOCK-OUTS ARE IMPLEMENTED (no write-check). This
becomes an open only valve. Without the close signal, the last position
will be maintained.
If the Close channel has been assigned and the Open channel has not,
a ‘Conflicting Channels Assigned’ block alarm is generated by the block.
NO OTHER LOCK-OUTS ARE IMPLEMENTED (no write-check).
This becomes a close only valve.
Error handling for the configuration of channels has been modified as well. The
Transducer Block has a special BLOCK_ALARMS_ACTIVE parameter which may
be used to diagnose a configuration problem. The configuration errors are listed in
Table 2.
Table 2. Transducer Block’s
BLOCK_ALARMS_ACTIVE Parameter
Table 1. Discrete Output Channel Assignments
27
D-Series with FF Option
Installation, Operation & Maintenance
Complete Discrete Output Block Parameter Listing
28
502.969.8000
www.topworx.com
TM
Appendix E: Discrete Input (DI) Block
Discrete INPUT Blocks (DI Block)
There are 5 Discrete Input Blocks available on the
SCM-FF. The DI block takes the manufacturer’s discrete
input data, selected by channel number, and makes it
available to other function blocks at its output. These DI
blocks become available to the user when linked to one
of the Transducer Channels available for inputs.
Table 1:
DI Channel Parameter Settings List
A host may retrieve internal information at any time and
alarms are reported as they occur. To make a light come
on or another valve close requires a DI to publish the
information on the bus.
Channels
The 5 DI Function Blocks in the device are associated to
the real world by setting the CHANNEL parameter to the
desired Transducer Channel. Illustration 11 shows the
relationship between Transducer channels and the DI
assigned channels. The output of the DI block (viewed in
the OUT_D parameter) is defined by the DI block’s
CHANNEL assignment. The valid settings for the CHANNEL parameters are listed in Table 7.
By resetting a DI CHANNEL parameter to a different
transducer channel number (0, 6-13, see Table 1) an
end user may customize the functionality of the SCM-FF
to fit a particular application requiring DI’s on temperature
limits and cycle counts instead of the defaults.
Illustration 11.
Channel Assignment for DI Function Blocks
Transducer
DI Function Block
Channels
Valve is Opened/ Valve is Closed
Valve is Opened
Valve is Closed
Auxillary Limit Switch.input
Cycle Time Open Alarm (CTOA )
Cycle Time Closed Alarm (CTCA)
Cycle Count Alarm (CCA )
CTOA | CTCA | CCA| TMPH|TMPL
6
7
8
9
10
11
12
13
Channel = 6
PV_D
Is
Is
Is
Is
Is
Closed
Opened
Stopped
Opening
Closing
1
2
3
4
5
OUT_D
29
D-Series with FF Option
Installation, Operation & Maintenance
Complete Discrete Input Block Parameter Listing
30
502.969.8000
www.topworx.com
TM
Appendix F: Dimension and Assembly Drawings
Valvetop DXP
MATERIALS OF CONSTRUCTION
Illustration #4
MINIMUM 2.5" REQUIRED CLEARANCE
IN ORDER TO DISINGAGE THE SHAFT FROM THE ID BUSHING
AND REMOVE LID WHERE OPTIMUM CONDITIONS APPLY
6.21
Enclosure
Cast A360 aluminum with dichromate conversion coating inside &
out, epoxy coated exterior rated for
250 hrs salt spray per ASTM B117
Fasteners
304 Stainless Steel standard
316 Stainless Steel optional
Shaft
304 Stainless Steel standard
316 Stainless Steel optional
Shaft
Bushing
Oilite Bronze
Indicator
Dome
Polycarbonate, UV F1 rated
Seals
O-ring seals available in: Buna,
Silicone, EPDM & Viton
4.52
Maximum Fastener Torque Specifications
.85 2.10
Enclosure Housing Bolts
8 ft-lbs [10.8 N·m]
Indicator Dome Screws
20 in-oz [141 mN·m]
Bottom Mounting Holes
10 ft-lbs [13.6 N·m]
MOUNTING SURFACE
SHAFT TYPE OPTIONAL
SEE SHAFT DETAIL
SECTION
2.13
OPTIONAL CONDUIT ENTRIES
USED ONLY WHEN 4 ENTRIES
ARE SPECIFIED
OPTIONAL CONDUIT ENTRIES
6.65
3.85
2.19
6.76
2.25
2.25
5/16-18 UNC - 2B
.44 DEEP
VALVE TYPE OPTIONAL
SEE INTEGRATED PNEUMATIC
CONTROL VALVES SECTION
31
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Valvetop DXP - IIC
Illustration #5
MATERIALS OF CONSTRUCTION
Enclosure
Cast A360 aluminum with dichromate conversion coating inside &
out, epoxy coated exterior rated for
250 hrs salt spray per ASTM B117
Fasteners
304 Stainless Steel standard
316 Stainless Steel optional
Shaft
304 Stainless Steel standard
316 Stainless Steel optional
Shaft Bushing
Oilite Bronze
Indicator Dome
Polycarbonate, UV F1 rated
Seals
O-ring seals available in: Buna,
Silicone, EPDM & Viton
Maximum Fastener Torque Specifications
32
Enclosure Housing Bolts
8 ft-lbs [10.8 N·m]
Indicator Dome Screws
20 in-oz [141 mN·m]
Bottom Mounting Holes
10 ft-lbs [13.6 N·m]
www.topworx.com
TM
Valvetop DXS
Illustration #6
MATERIALS OF CONSTRUCTION
MINIMUM 2.5" REQUIRED CLEARANCE
IN ORDER TO DISINGAGE THE SHAFT FROM THE ID BUSHING
AND REMOVE LID WHERE OPTIMUM CONDITIONS APPLY
6.21
4.52
.85 2.10
Enclosure
Cast 316 Stainless Steel
Fasteners
304 Stainless Steel standard
316 Stainless Steel optional
Shaft
304 Stainless Steel standard
316 Stainless Steel optional
Shaft Bushing
N/A
Indicator Dome
Polycarbonate, UV F1 rated
Seals
O-ring seals available in: Buna,
Silicone, EPDM & Viton
Maximum Fastener Torque Specifications
Enclosure Housing Bolts
8 ft-lbs [10.8 N·m]
Indicator Dome Screws
20 in-oz [141 mN·m]
Bottom Mounting Holes
10 ft-lbs [13.6 N·m]
MOUNTING SURFACE
SHAFT TYPE OPTIONAL
SEE SHAFT DETAIL
SECTION
2.13
OPTIONAL CONDUIT ENTRIES
USED ONLY WHEN 4 ENTRIES
ARE SPECIFIED
OPTIONAL CONDUIT ENTRIES
6.65
3.85
2.19
6.76
2.25
2.25
5/16-18 UNC - 2B
.44 DEEP
VALVE TYPE OPTIONAL
SEE INTEGRATED PNEUMATIC
CONTROL VALVES SECTION
33
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Valvetop DXR
Illustration #7
MATERIALS OF CONSTRUCTION
MINIMUM 2.5" REQUIRED CLEARANCE
IN ORDER TO DISINGAGE THE SHAFT FROM THE ID BUSHING
AND REMOVE LID WHERE OPTIMUM CONDITIONS APPLY
Enclosure
Valox® 364
Fasteners
304 Stainless Steel standard
316 Stainless Steel optional
Shaft
304 Stainless Steel standard
316 Stainless Steel optional
Shaft Bushing
Delrin® 500P white
Indicator Dome
Polycarbonate, UV F1 rated
Seals
O-ring seals available in: Buna,
Silicone, EPDM & Viton
6.21
4.51
2.10
1.10
Maximum Fastener Torque Specifications
Enclosure Housing Bolts
10 in-lbs [903 mN·m]
Indicator Dome Screws
20 in-oz [141 mN·m]
Bottom Mounting Holes
8 ft-lbs [13.6 N·m]
MOUNTING SURFACE
SHAFT TYPE OPTIONAL
SEE SHAFT DETAIL
SECTION
2.00
OPTIONAL CONDUIT ENTRIES
USED ONLY WHEN 4 ENTRIES
ARE SPECIFIED
OPTIONAL CONDUIT ENTRIES
5.03
3.66
2.14
6.10
2.25
2.25
34
5/16-18 UNC - 2B
.44DP
VALVE TYPE OPTIONAL
SEE INTEGRATED PNEUMATIC
CONTROL VALVES SECTION
www.topworx.com
TM
Appendix G: Specifications and Reference Data
Table 1. Intrinsically Safe Entity Parameters
Table 3. Fieldbus Specifications
Table 2. Electrical Specifications
Safe Use
Special Conditions of Safe Use (All installations)
Clean only with a damp cloth to prevent possibility of electrostatic discharge.
For Explosion Proof installations, the internal ground connection shall be used and the external ground connection, if
supplied in addition, is supplemental bonding allowed where local authorities permit, or is required.
When installing with a third party listed nipple-mount solenoid, it is the responsibility of the installer to provide fittings,
and apparatus, suitable for the area classification in accordance with the National Electrical Code.
All cable entry devices or conduit stopping boxes shall be certified in type of explosion protection ‘d’, suitable for the
conditions of use and correctly installed.
The IIC enclosures are excluded from use in carbon disulphide atmospheres.
The air pressure to the valve block, when fitted, shall not exceed 7bar.
Preventative Maintenance
The TopWorx Valvetop is designed to operate for one million cycles without servicing. Call TopWorx when you are
approaching this milestone for a preventative maintenance kit and instructions.
35
D-Series with FF Option
Installation, Operation & Maintenance
502.969.8000
Certifications & Approvals
AREA
0
Ex ia IIC T4 –40°C ≤ Tamb ≤ 80°C, IP67
DEMKO 02ATEX0223499X
Ui:24Vdc, Ii:250mA, Pi:1,2W, Ci:2.5nF, Li:129µH
Class I Div 1&2 Groups A,B,C,D; T4; Type 4, 4X
Intrinsically Safe / Securite Intrinsique
Electrical Rating: 9-32Vdc, 20mA
1
Class I Div 1 Groups C,D; Class 1 Div 2
Groups A,B,C,D Type 4, 4X
Ex d IIB+H2 T6 –40°C ≤ Tamb ≤ 60°C, IP67
SIRA 07ATEX1273X IECEx SIR 07.0093X
Electrical Rating: 9-32Vdc, 20mA
2
Class I Div 2 Groups A,B,C,D; Type 4, 4X
Ex nC IIC T6 –40°C ≤ Tamb ≤ 60°C, IP67
Electrical Rating: 9-32Vdc, 20mA
C
Ex d IIC T6 –40°C ≤ Tamb ≤ 60°C, IP67
SIRA 07ATEX1273X
IECEx SIR 06.0093X
Max Current 500mA @ Max Voltage 25V
W
NEMA 4, 4X
0
Ex ia IIC T4 –40°C ≤ Tamb ≤ 80°C, IP67
DEMKO 02ATEX0223499X
Ui:24Vdc, Ii:250mA, Pi:1,2W, Ci:2.5nF, Li:129µH
Class I Div 1&2 Groups A,B,C,D; T4; Type 4, 4X
Intrinsically Safe / Securite Intrinsique
Electrical Rating: 9-32Vdc, 20mA
1
Class I Div 1 Groups C,D; Class 1 Div 2
Groups A,B,C,D Type 4, 4X
Ex d IIB+H2 T6 –40°C ≤ Tamb ≤ 60°C, IP67
SIRA 07ATEX1273X IECEx SIR 07.0093X
Max Current 500mA @ Max Voltage 25V
2
Class I Div 2 Groups A,B,C,D; Type 4, 4X
Ex nC IIC T6 –40°C ≤ Tamb ≤ 60°C, IP67
Electrical Rating: 9-32Vdc, 20mA
W
NEMA 4, 4X
G
Type 4, 4X
Electrical Rating: 9-32Vdc, 20mA
W
Type 4, 4X
Electrical Rating: 9-32Vdc, 20mA
DXP
DXS
DXR
36
CERTIFICATION
0518
www.topworx.com
TM
Warranty
37
D-Series with FF Option
NOTES:
38
Installation, Operation & Maintenance
502.969.8000
www.topworx.com
TM
NOTES:
39
GLOBAL SUPPORT OFFICES
North America
3300 Fern Valley Road
Louisville, Kentucky 40213 USA
+1 502 969 8000
[email protected]
Asia-Pacific
1 Pandan Crescent
Singapore 128461
+65 6891 7550
[email protected]
Middle East
P.O. Box 17033
Jebel Ali Free Zone —South 2
Dubai 17033
United Arab Emirates
+9714 8118283
[email protected]
Africa
24 Angus Crescent
Longmeadow Business Estate East
Modderfontein
Gauteng
South Africa
+27 011 451 3700
[email protected]
Europe
Horsfield Way
Bredbury Industrial Estate
Stockport
SK6 2SU UK
+44 0161 406 5155
[email protected]
Visit www.topworx.com for comprehensive information on our company,
capabilities, and products — including model numbers, data sheets,
specifications, dimensions, and certifications.
[email protected]
www.topworx.com
The Emerson logo is a trademark and a service mark of Emerson Electric Co. ©2014 Emerson
Electric Co. ©2014 TopWorx™, All rights reserved.TopWorx, Valvetop, and GO Switch are
trademarks of TopWorx™. All other marks used in this document are the property of their
respective owners. Information contained herein - including product specifications is subject
to change without notice.
™
™
S-K131 R13