CSA Electrical Safety FieldQ Control Modules, Class 2252 05 2252 85

B
---Ill>
CSA INTERNATIONAL
Certificate of Compliance
Certificate:
1796497
Master Contract:
Project:
2220552
Date Issued: October 7, 2009
Issued to:
Emerson Process Management Valve Automation
Div. EL-0-Matic B.V.
Asveldweg 11
7556 AE Hengelo
THE NETHERLANDS
174756
The products listed below are eligible to bear the CSA Mark shown with
adjacent indicators 'C' and 'US' for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.
~®
c
us
Issued by:
Hans Werner Zeller
Authorized by: M.H.J. Hoendervangers
Area Director Europe
/l
1JJ/~v~~
PRODUCTS
CLASS 2252 05 - PROCESS CONTROL EQUIPMENT
CLASS 2252 85- PROCESS CONTROL EQUIPMENT-Certified to US Standards
PART A
Valve Actuator Controller FieldQ, Model QC01, QC02, QC03, QC04, QC30, QC31 and QC34, permanently
connected, rated: QC02: 85-254 V, 50/60Hz, 2,85 W, QC01: 24 Vdc, 0,1 A, 2,5 W, QC03, QC04: 30 Vdc, 300
rnA, 1,2 W, QC30: 24-31,6 V, 3 W,QC31: 11 -25 Vdc, 120mA-75mA, QC34: 9-30 Vdc, 22 rnA
NOTE: The above model QC02 is Equipment Class I, Pollution Degree 3.
PARTB:
Valve Switchbox Field Q, Model QC14, QC11, QC12, QC13, QC21, QC22 and QC23, permanently connected,
rated: QC14: 24 Vdc, 0,9 W, QC11: 24 Vdc, 1,3 W, QC12: 115 Vac, 50/60Hz, 1,3 W, QC13: 230 Vac, 50/60Hz,
1,9 W, QC21: 24 Vdc, 3 W, QC22: 115 Vac, 50/60Hz, 5 W, QC23: 230 Vac, 50/60Hz, 5 W
Outputs: Potential free contact rating: Switches: 30 Vdc/5 A, 125 Vac/5 A, 125 Vdc/0,5 A, 250 Vac/5 A, 250
Vdc/0,25 A. Proximity switches: 16 Vdc/0,034W. or 140 V/0,2 A
D 507 Rev. 2004-06-30
P eI
Certificate:
Project:
I796497
2220552
APPLICABLE REQUIREMENTS
0
------<II>
CSA INTERNATIONAL
Master Contract: I74756
Date Issued: October 7, 2009
CAN/CSA-C22.2 No. 610IO.I-04
Safety Requirements for Electrical Equipment for Measurement,
Control, and Laboratory Use, Part I: General Requirements
UL Std. No. 6I 0 I 0-I (2"d Edition)
Safety Requirements for Electrical Equipment for Measurement,
Control, and Laboratory Use- Part I: General Requirements
CONDITIONS OF ACCEPTABILITY
PART A:
The units are evaluated for an ambient temperature of 80 oc
For model QC02 the membrane key-board is only accessible by means of a tool. Only trained personal may control
the unit.
For model QC02 the unit may only be used in combination with a pneumatic module mounted on an actuator to
prevent against electric shock.
Models QCOI, QC03, QC04, QC30, QC3I and QC34 shall be powered by a DC voltage< 60 Vdc which is
separated from hazardous live by double or reinforced insulation at the source of the supply with a power limitation
of I 50 VA. Also all input and output connections shall be separated from hazardous live by double or reinforced
insulation with a voltage < 60 V de
PARTB:
The input/output specifications and following instructions for building-in are given by the manufacturer.
The units are evaluated for an ambient temperature of: 50 oc (QCI4), 80 oc (QCII, QCI2, QC13),
60 °C (QC2I, QC22, QC23)
Models QC I4, QC II and QC21 shall be powered by a DC voltage < 60 V de which is separated from hazardous live
by double or reinforced insulation at the source of the supply with a power limitation of 150 VA.
MARKINGS
The following markings appear on the product and may be described in further detail in the Certification Report
Supplement, Section C:
I.
2.
3.
4.
5.
Submittor's identification (company name and/or file number and/or registered tradename );
Model designation;
Electrical rating; (only for PART A)
Date of manufacture (or traceable serial number);
The CSA Monogram with C/US subscript;
D 507 Rev. 2004-06-30
Pa e2
0
-------e
CSA INTERNATIONAL
Supplement to Certificate of Compliance
Certificate:
1796497
Master Contract:
174756
The products listed, including the latest revision described below,
are eligible to be marked in accordance with the referenced Certificate.
Product Certification History
Project
Date
Description
2220552
October 7,
2009
June 3, 2009
Update to report 1796497. Additional changes of edition 4
2186761
Update to report 1796497. Addition of low voltage model QC31. Small lay-out
changes on QC31 model PWB' s. Minor changes in critical components.
2064112
September 18, Update to report 1796497. Addition of low voltage model QC31. Small
2008
lay-out changes on QC31 model PWB' s. Minor changes in critical
components.
2017277
April 16, 2008 Update to report 1796497. Addition of low voltage models QC01, QC03, QC04,
QC30 and QC34. Small lay-out changes on QC02 model PWB's. Minor changes
in critical components
1796497
D D 507 Rev. 2004-06-30
May 29, 2006 Original cCSAusCertification.ofFieldQ model QC02
P eI