Rosemount Tank Gauging Accessories
for tank gauging systems
Accessories for the Rosemount Tank Gauging system, including:

Rosemount Segment Coupler

Fieldbus Terminator

Rosemount 2180 Field Bus Modem

Rosemount 3180 Enraf Bus Mode

Rosemount TankMaster I/O Terminals
Rosemount Tank Gauging Accessories
March 2014
Rosemount Segment Coupler
Segment
Coupler
2410
Tank
Hub
Rx
Tx
USB
RS-232
Ext. pwr
Rosemount TankRadar
Lo - GAIN - Hi
On - TERM - Off
FBM 2180
Segment
Coupler
The 6-channel Tankbus Segment Coupler is designed for
FOUNDATION™ fieldbus systems and is Entity and FISCO
compliant. It includes adjustable spur short circuit protection
and an integrated switchable bus termination. It is typically used
as a junction box to distribute the Tankbus to multiple tanks
and/or transmitters.
The spur circuit protection maximum current limitation is
selected for all channels via a rotary switch. Different current
values, 30, 35, 45 and 60 mA, can be selected, which allows all
Rosemount tank gauging devices to be connected and
protected.
Segment
Coupler
Segment
Coupler
Fieldbus Terminator
2410
Tank
Hub
A Fieldbus terminator is required at the end of the Tankbus. The
external Fieldbus terminator eliminates signal reflections at the
end of the cable and converts the fieldbus signal transmitted as
a current into a voltage, which is detectable by all devices.
There is no need for a separate bus terminator if a 2230, 2240S,
or 5900S is the last device on the bus.
Fieldbus
Terminator
Contents
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2
www.rosemount-tg.com
March 2014
Rosemount Tank Gauging Accessories
Rosemount 2180 Field Bus Modem
The Rosemount 2180 Field Bus Modem is used for connecting a
TankMaster PC to the TRL2 fieldbus. The modem is connected to
the PC using either the RS232 or the USB interface.
DCS / Host
It has LEDs indicating power on and communication.
There are front panel switches to set gain and termination, if
required.
Rx
Tx
Rosemount TankRadar
USB
TRL2
Modbus
2180
Modem
RS-232
The field bus modem is delivered with cables for RS232 and USB
connection. The USB cable also supplies power to the modem.
A separately power supply cable (included in delivery) is only
necessary for the RS232 option.
2160 Field
Communication
Unit
Ext. pwr
The modem is fitted on a standard DIN rail with the mounting kit
included in all deliveries.
Lo - GAIN - Hi
On - TERM - Off
FBM 2180
TankMaster
PC
Network
Rosemount 3180 Enraf Bus Modem
When an Enraf gauge is replaced with a Rosemount Radar Gauge
using emulation, it is necessary to configure the Rosemount
gauge for emulation. Configuration is made with the WinSetup
software and requires a 3180 Enraf Bus Modem. How the
procedure is done depends on the system type.
USB or
RS232
Modbus
Entis /
TankMaster
PLC
The 3180 Enraf Bus Modem can also be used to connect Enraf
gauges directly to the TankMaster Inventory Software.
3180 Enraf
Bus Modem
CIU
Laptop with WinSetup
www.rosemount-tg.com
3
Rosemount Tank Gauging Accessories
March 2014
Rosemount TankMaster I/O Terminals
The I/O Terminals can be used for communication between the
TankMaster Inventory Software and field equipment, for a more
versatile system. The four versions are:
TankMaster
IOT
5110
IOT
5130
IOT
5120
IOT
5140

IOT 5110 for Analog Inputs

IOT 5120 for Analog Outputs

IOT 5130 for Digital Inputs

IOT 5140 for Digital Outputs
The analog inputs open up TankMaster for all 4-20 mA devices,
such as pressure and temperature sensors.
The analog outputs enable mapping of values to analog
indicators.
The digital inputs can for example be used to display alarms
from external equipment in TankMaster.
The digital outputs can be used for alarm panels, horns, signal
lamps etc.
The I/O terminals are complements to the TankMaster system,
and are not designed to be used as stand-alone devices for
critical operations.
4
www.rosemount-tg.com
March 2014
Rosemount Tank Gauging Accessories
Ordering information
Rosemount Tankbus Segment Coupler

Entity and FISCO compliant

Adjustable spur short-circuit protection

Robust die-cast aluminum housing

Protection degree IP 67

Integrated bus termination
Additional information
Specifications: page 8
Dimensional drawings: page 13
Table 1. Rosemount Tankbus Segment Coupler ordering information
Part Number
Product Description
6853511-493
Tankbus segment coupler with integrated user-selectable on/off termination and spur short-circuit protection
(max 60 mA/spur). Connections; trunk input, trunk output, 6 spurs M20x1,5. Wall-mounted, IP 67. Delivered with
junction box. Entity and FISCO compliant.
Fieldbus Terminator

Prevents reflections/distortions

Protection degree IP 67
Additional information
Specifications: page 10
Dimensional drawings: page 13
Table 2. Fieldbus Terminator ordering information
Part Number
Product Description
6853511-494
Tankbus termination, external, ½ NPT male thread. Termination for external installation, mounted on a junction
box or a transmitter field housing, IP 67. Entity and FISCO compliant.
www.rosemount-tg.com
5
Rosemount Tank Gauging Accessories
March 2014
Rosemount 2180 Field Bus Modem

Increases the maximum possible distance between a Rosemount 2160 Field
Communication Unit and a TankMaster PC

Features diagnostic LEDs on front cover

Enables multidrop - one TankMaster can communicate with several 2160 units

Provides multiple mounting options
Additional information
Specifications: page 11
Dimensional drawings: page 14
Table 3. Rosemount 2180 Field Bus Modem ordering information
Item No
Product Description
FBM 2180
TRL2 Fieldbus Modem
Rosemount 3180 Enraf Bus Modem

Enables configuration of a Rosemount Radar gauge for Enraf emulation

Can connect Enraf gauges directly to the TankMaster Inventory software

Each 3180 can be connected to up to 10 Enraf gauges
Additional information
Specifications: page 11
Dimensional drawings: page 14
Table 4. Rosemount 3180 Enraf Bus Modem ordering information
Item No
Product Description
EBM 3180
Enraf Bus Modem
6
www.rosemount-tg.com
March 2014
Rosemount Tank Gauging Accessories
Rosemount TankMaster I/O terminals

Modules for communication between TankMaster and field equipment

Free mix of module types

Up to 64 modules per loop

8 or 16 channels per module

RS485 multi-drop bus connection

12-bit A/D- and D/A converter

Flexible mounting – DIN or a choice with enclosure for ESP protection
Additional information
Specifications: page 12
Table 5. Rosemount TankMaster I/O ordering information
Item No
Product Description
IOT 5110 AI(1)
I/O Module Analog In, 16 channels
IOT 5120 AO(1)
I/O Module Analog Out, 16 channels
IOT 5130 DI(1)
I/O Module Digital In, 16 channels
IOT 5140 DO(1) I/O Module Digital Out, 8 channels
(1) Power supply (24 VDC) required, not included. TankMaster customized views option recommended for best functionality. Modules not designed for fail-safe
usage.
www.rosemount-tg.com
7
Rosemount Tank Gauging Accessories
March 2014
Specifications
Rosemount Tankbus Segment Coupler
Table 6. Rosemount Tankbus Segment Coupler specifications
General
Electrical connection cable glands
TRUNK IN 1 x M20 x 1.5 (Ø 6 to 13 mm), nickel-plated brass
TRUNK OUT 1 x M20 x 1.5 (Ø 6 to 13 mm), nickel-plated brass
Spur 6 x M20 x 1.5 (Ø 6 to 13 mm), nickel-plated brass
Terminal cross-section 2.5 mm²
Earthing bolt M5 x 1
Fieldbus standard
IEC 61158-2
Operating voltage range
12 to 32 VDC
Current self-consumption 7 mA
Voltage drop 0.3 V
Short-circuit protection
30, 35, 45, 60 mA
Ex approval according to
conformity certificate PTB 03 ATEX
2236
Entity Parameter
Max. output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po 2560 mW
Max. input voltage Ui 24 V
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter acc. to IEC TS 60079-27
Max. output voltage Uo 17.5 V
Max. output current Io 380 mA
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance / capacitance Li /Ci trunk (in/out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.47 nF
 field current circuits:
negligible / 5.00 nF
Device designation:
II 2 G Ex ib IIC/IIB T4
II 2(1) G Ex ia IIC/IIB T4
II 2 G (2D) [Ex ibD] Ex ib IIB T4
II 2 (1) G (1D)[Ex iaD] Ex ia IIB T4
FISCO / Entity field device
IP 67
MTTF 117 years acc. to SN 29500 (Ed. 99) 40 °C
Ambient temperature -25 to +70 °C (-13 to +158 °F)
Protection class
Housing material
Powder-coated die-cast aluminum
Housing color
Black / blue RAL 5015
Connection mode
Wall mounting with nickel plated brass cable glands
8
www.rosemount-tg.com
March 2014
Rosemount Tank Gauging Accessories
Figure 1. Segment Coupler, connections
5400 Level
Transmitter
Trunk OUT
S0
Trunk IN
P1
Spur
S1
Spur
S2
Spur
S3
Spur
S4
Spur
S5
Spur
S6
644 Temperature
Transmitter
5400 Level
Transmitter
2410 Tank Hub
Tankbus (trunk)
Case ground
(Spur <60m)
(Spur <60m)
Segment
coupler
2230 Display
Tankbus (trunk)
2240S
Temperature
Transmitter
5900S Radar
Level Gauge
www.rosemount-tg.com
9
Rosemount Tank Gauging Accessories
March 2014
Fieldbus Terminator
Table 7. Fieldbus Terminator specifications
Fieldbus Interface
Connection
2-wire cable, red+, black-
Rated voltage
32 V DC
Ambient conditions
Ambient temperature
-50 to + 85 °C (-58 to +185 °F)
Storage temperature
-50 to + 85 °C (-58 to +185 °F)
Mechanical specifications
Core cross-section
0.75 mm²
Protection degree
IP 67
Weight
100 g (0.2 lb)
Mounting
½ NPT thread
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC
EN 61326-1:2006
Standard conformity
Electromagnetic compatibility
NE 21:2006
Protection degree
IEC/EN 60529
Fieldbus standard
IEC 61158-2
Hazardous Location Certifications
EC-Type Examination Certificate
Group, category, type of
protection, temperature class
DMT 01 ATEX 104 X
II 1 G EEx ia IIC T6
Directive conformity
Directive 94/9/EC
EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007, IEC 60079-27:2008
International approvals
IECEx approval
IECEx BVS 10.0022X
Approved for
Ex ia IIC T6 Ga
Hazardous Location Data
Temperature class
T6 for ambient temperatures: 60 °C
T5 for ambient temperatures: 75 °C
T4 for ambient temperatures: 85 °C
Voltage Ui
 30 V
Rated voltage
 30 V
10
www.rosemount-tg.com
March 2014
Rosemount Tank Gauging Accessories
Rosemount 2180 Field Bus Modem
Table 8. Rosemount 2180 Field Bus Modem specifications
General
Protocol
Modbus
Baudrate
4800
Explosion protection
None
Power supply (only used for
RS232)
AC/DC converter supplied (7-12 V, 50 mA)
Cable to PC
RS232: 3 m (10 ft)
USB: 3 m (10 ft)
Included in delivery
Fieldbus over-voltage protection
Galvanic insulation, and transient suppressors
Ambient temperature
0 to + 55 °C (0 to +130 °F)
Rosemount 3180 Field Bus Modem (Enraf)
Table 9. Rosemount 3180 Field Bus Modem (Enraf) specifications
General
Protocol
Modbus/Enraf GPU
Baudrate
2400/1200
Compatible with
Enraf devices with GPU protocol
Explosion protection
None
Power supply
9 VDC (AC/DC converter included)
Cable to PC
RS232
Signal gain control via internal
jumpers
Ambient temperature
www.rosemount-tg.com
•10% (default)
•35%
•100%
0 to + 55 °C (0 to +130 °F)
11
Rosemount Tank Gauging Accessories
March 2014
Rosemount TankMaster I/O Terminals
Table 10. Rosemount TankMaster I/O Terminals specifications
Technical data for TankMaster IOT 5110-5140
Communication type
RS485
Communication speed
115 kbit/s
Isolation
Opto-coupled (in I/O box)
Dimensions
160x100x80 mm (6.3x3.9x3.2 in.)
Mounting method
DIN rail 35 mm (1.4 in.) clip
Supply voltage
24 VDC
Ambient temperature
0 to + 55 °C (0 to +130 °F)
IOT 5110 Analog In; 4-20 mA, 0-10 V
Channels
16 single ended
Input load
50  (current), 10 k (voltage)
Accuracy (current and voltage)
Max ±0.5% of full range
Temperature drift
(current and voltage)
Accuracy valid for 0 to +55 °C (0 to +130 °F)
IOT 5120 Analog Out; 4-20 mA, 0-10 V
Channels
16 single ended
Load impedance
50  / max 500 
Load current
< 5 mA for 0-10 VDC
Accuracy (current)
Max ±0.5% of full range
Accuracy (voltage)
Max ±0.2% of full range
Temperature drift
(current and voltage)
Accuracy valid for 0 to +55 °C (0 to +130 °F)
IOT 5130 Digital In
Channels
16 negative common
Voltage range input
0 to +35 VDC
Source type
Potential free contact
Input current
Max 0.6 mA
IOT 5140 Digital Out
Channels
8 pot free SPDT
Capacity
Max 250 VAC, 2 A
12
www.rosemount-tg.com
March 2014
Rosemount Tank Gauging Accessories
Dimensional drawings
Rosemount Segment Coupler
Figure 2. Rosemount Segment Coupler dimensions
122 (4.8)
64 (2.5)
36 (1.4)
207 (8.1)
173,5 (6.8)
185,5 (7.3)
45 (1.8)
Note
Dimensions are in millimeters (inches).
Fieldbus Terminator
Figure 3. Fieldbus Terminator dimensions
1
22
(0.9)
2
55 (2.2)
22
(0.9)
1. Cable cross sectional area
1.0 mm (0.04 in.)
Cable length
min. 290 mm (11.4 in.)
2. FN: ½” NPT thread
Note
Dimensions are in millimeters (inches).
www.rosemount-tg.com
13
Rosemount Tank Gauging Accessories
March 2014
Rosemount 2180 Field Bus Modem
Figure 4. Rosemount 2180 Field Bus Modem dimensions
Connection to fieldbus
(via Rosemount 2160/2165/2175
or Rosemount 2410)
Rx
Tx
DC IN
USB
RS-232
Ext. pwr
Connection to PC
Lo - GAIN - Hi
On - TERM - Off
RS-232
USB
Shield|Bus|Bus|Gnd
FIELD BUS
±7-12V
50mA ROSEMOUNT 2180
Only for Field Bus Modem
RS-232
Made in
Operation
Part No. 9240002-635 X
Sweden
Rosemount 2180 Field Bus Modem
114 (4.5)
Note
Dimensions are in millimeters (inches).
109 (4.3)
Rosemount 3180 Enraf Bus Modem
Figure 5. Rosemount 3180 Enraf Bus Modem dimensions
Field Bus
Field Bus: Pin 4,6
EBM 3180
PC-modem
Shield: Pin5
Tank Gauging
114(4.5)
Rosemount Tank Radar AB
Gothenburg, Sweden
External DC
Power Supply
8-12V, 60mA
Modbus
(4800 baud)
Normal (GPU)
Pos+
Note
Dimensions are in millimeters (inches).
14
MADE IN SWEDEN
2400 baud
1200 baud
Computer
RS 232
Neg-
109(4.3)
www.rosemount-tg.com
March 2014
www.rosemount-tg.com
Rosemount Tank Gauging Accessories
15
Rosemount Tank Gauging Accessories
00813-0100-5101, Rev AA
Product Data Sheet
March 2014
Emerson Process Management
Rosemount Tank Gauging
Emerson Process Management
Rosemount Tank Gauging North America Inc.
Emerson Process Management
Latin America
Box 130 45
SE-402 51 Göteborg
SWEDEN
Tel: +46 31 337 00 00
Fax: +46 31 25 30 22
E-mail: [email protected]
www.rosemount-tg.com
6005 Rogerdale Road
Mail Stop NC 136
77072 TX Houston
United States
Primary Phone: +1 281 988 4000
Secondary Phone: +1 800 722 2865
E-mail: [email protected]
1300 Concord Terrace, Suite 400
Sunrise Florida 33323
United States
Tel: +1 954 846 5030
Emerson Process Management
Rosemount Tank Gauging Middle East & Africa.
Emerson Process Management
Asia Pacific Pte Ltd
P. O Box 20048
Manama
Bahrain
Tel: +973 1722 6610
Fax: +973 1722 7771
E-mail: [email protected]
1 Pandan Crescent
SINGAPORE 128461
Tel: +65 6777 8211
Fax: +65 6777 0947
Email: [email protected]
The Emerson logo is a trade mark and service mark of Emerson Electric Co.
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
PlantWeb is a registered trademark of one of the Emerson Process Management group of companies.
HART and WirelessHART are registered trademarks of the HART Communication Foundation
All other marks are the property of their respective owners.