Waveform-Relaxation Based Iterative Real-Time Playback Schemes for Testing of Wide Area Power System Controllers A M Kulkarni, K Salunkhe and M C Chandorkar S P Panda and N Sankaranarayanan Department of Electrical Engineering Indian Institute of Technology Mumbai, India, 400076 Email: [email protected] Electrical Design Group Nuclear Power Corporation of India Ltd Mumbai, India, 400094 Email:[email protected] Abstract—An alternative to real-time simulation for hardwarein-the-loop testing is proposed. This involves system simulation, not necessarily done in real time, and real-time playback of the simulated output to the controller under test. The time-stamped controller output is stored and subsequently fed as an input to the simulation. This whole process is done iteratively as in the Waveform Relaxation method, till the waveforms converge. This method can be used for testing multiple and dispersed controller hardware and the associated communication equipment, e.g., wide-area measurement based control and system protection schemes. It also has the potential to be an alternative to realtime simulators which are expensive when large systems have to be simulated. The basic scheme and potential applications are discussed in this paper. Index Terms—Real-Time Simulation, Hardware in the Loop Simulation, Waveform Relaxation Method, Wide Area Measurements Systems, Wide Area Control and Protection I. I NTRODUCTION Testing of protection and control equipment under various simulated transient conditions is a necessary step before their actual deployment in the field, i.e., their interface to high power apparatus. This testing relies on digital simulators to simulate power system transients in real-time with “Hardware In the Loop” (HIL) [1] - see Fig.1. Real-Time Simulators are available commercially and are widely used. However the cost of a simulator is dependent on the maximum size of the system that can be simulated on it. Moreover, if more than one controller, relay or measurement system, placed at geographically distant locations, are to be tested in situ with the associated communication system, then HIL simulation is infeasible. This situation may arise with centralized decision and control schemes which use Wide Area Measurement Systems (WAMS) [3], [4], wherein the performance of the complete system is to be tested. A WAMS scheme consists of Phasor Measurement Units (PMUs) at various locations which are time sycnhronized with each other using Global Positioning System (GPS) signals. The PMUs convey time stamped measurements to a control centre which may use the measurements for monitoring, control or system protection schemes. WAMS are now be- 978-1-4244-6551-4/10/$26.00 ©2010 IEEE ing deployed in various power systems. However WAMS applications for system protection and control, e.g., Wide Area Power System Stabilizers (WA-PSS) [5] and Controlled System Separation schemes, require adequate testing so that power system operators have the confidence to use them. The infeasibility of HIL testing for wide area controllers is the main motivation for this paper. Non-Real-Time Power System Simulator Real time Power System Simulator Real Time Player Controller or System under Relay Decision Test Relay Equipment and operating Time Fig. 1. HIL Simulation Fig. 2. Real-Time Playback For testing equipment action which involves only one discrete event (e.g. relay tripping), it is adequate to test the equipment with real-time playback of transients which have been simulated in non-real-time [2] - see Fig. 2. If a protection system which uses remote measurements is to be tested with its associated communication system, or the operation of a relay in conjunction with other relays is to be verified, then the relevant transient waveforms at different locations can be played-back in a time-sychronized fashion, to the geographically dispersed components of the protection system [6] - see Fig. 3. Time synchronization can be achieved using GPS signals. This feature is available in some commercial relay test equipment. If more than one discrete action of an equipment are involved (e.g., tripping followed by auto-reclosure), then the evolution of the system behaviour after any action has to be k−1 (t) c1 Non-Real Time Power System Simulator Non−Real Time Power System Simulator y Time Real Time Player Time Synchronized Communication Equipment Relay Real Time Player Real Time Player System Relay Controller under Synchronized Communication Equipment Real Time Player System Controller Test Decision and operating Time Fig. 3. Time Synchronized Real-Time Playback Testing re-simulated, and the entire transient has to be replayed to the equipment - see Fig. 4. This becomes infeasible if the number of discrete actions is large. Also, if the equipment to be tested delivers continuous feedback (as in a Wide-Area Power System Stabilizer) to the system, such “open loop” playback schemes are not meaningful. Decision and operating Time (s) Real Time Player Relay Fig. 4. Decision and operating Time (s) Discrete Multi-event Real-Time Playback To overcome the infeasibility of HIL real-time simulation and open loop real-time playback for testing of Wide-Area control and system protection schemes, we propose the use of Waveform-Relaxation (WR) [7] based iterative and timesynchronized real-time playback of simulated responses to geographically dispersed components of the system. The basic scheme is shown in Fig. 5 wherein the system under test has two geographically dispersed controllers. The scheme can be generalized to a larger number of such controllers. The output of the controllers under test in the (k − 1) th iteration, yck−1 (t), are fed as inputs to the non-real time power system simulator. The simulation is performed using these inputs and the simulated waveforms are played back in real time to the controller to obtain the response for the new iteration, y ck (t). under Test k c1 Decision and operating Time Non-Real-Time Power System Simulator k−1 (t) c2 y Fig. 5. k c2 y (t) y (t) Output Waveform Output Waveform Waveform Relaxation based Iterative Real-Time Playback This is repeated till convergence is obtained. Note that if ycl−1 (t) = ycl (t) for some l, then it is equivalent to “closing the loop” in Fig. 5. Therefore if the WR iteration converges as above, then the converged response of the tested equipment is the same as the HIL response. In practice, the convergence of the waveforms is only up to the specified tolerance, therefore the equality given above is not strictly true. However, a small enough convergence tolerance can be chosen by a user to get the desired accuracy. While this WR based scheme is uniquely suited for testing Wide Area controllers, it may also be used as a cheap alternative to HIL real-time simulation in a more conventional setting (no communication or geographical dispersion of equipment). However, it is slower, requires repeated triggering of the control equipment and may face convergence problems. It should be noted that WR method was proposed as a method of parallelizing the numerical integration of very large systems (e.g., VLSI) [8], [9]. It was also attempted for parallelizing transient stability simulations of large power systems [10] in order to get overall speed-up. However, the aim here is to use it for controller testing. The overall scheme requires hardware interfaces and real-time playback. Therefore the application proposed in this paper is distinct from the earlier work on WR, and consequently the issues are unique to this application. In this paper we first give a brief description of WR method. We also present examples to illustrate the use of the scheme as an alternative to HIL simulation, as well its unique application for testing Wide-Area controllers. II. WAVEFORM R ELAXATION M ETHOD The essence of the WR method [7], or rather the family of WR algorithms, can be illustrated using a simple example. Consider the first-order two-dimensional differential equations: ẋ1 = f1 (x1 , x2 ) ẋ2 = f2 (x1 , x2 ) (1) (2) The basic idea of a WR algorithm is to fix the waveform x 2 in the time window [0, T ] and solve (1) as a one dimensional differential equation. The solution thus obtained for x 1 , can be substituted into (2) which will then reduce to another firstorder differential equation. Equation (1) is then re-solved using the new solution for x 2 . This is done till x1 and x2 converge. The algorithm can been seen as the analogue of the GaussSeidel technique for solving non-linear algebraic equations. A Gauss-Jacobi variant of the algorithm can also be constructed. However, unlike the problem of solving nonlinear algebraic equations, the unknowns are waveforms rather than real variables. In this sense, the algorithms are techniques for timedomain de-coupling of differential equations. In general, for large order systems, the system can be partitioned into two or more sub-systems in many ways. In practice and for most systems, the solution for the differential equations is obtained numerically by discretization. The rate of convergence is greatly affected by the choice of the sub-systems as well as the numerical method used for discretization [7]. A. WR method for Hardware Testing The application of the WR method for hardware testing can be understood by considering an example. Suppose we desire to test the controller of a generator excitation system, automatic voltage regulation of the generator bus being one of its functions. The generator and exciter (excluding the excitation controller which is to be tested), and the rest of the power system are modeled in a power system simulator as follows ẋp = fp (xp , up , t) yp = gp (xp ) xp denotes the states of the generator, exciter and the rest of the power system, u p denotes the firing pulses for the thyristors of the exciter, which are obtained from the Excitation System Controller (ESC) and y p (t) denotes the variables which are inputs to the ESC e.g., the three phase voltages at the generator bus and field current. The ESC is implemented on external electronic hardware. The output of the ESC, y c (t) are the thyristor firing pulses. If HIL testing is to be done, then y p (t) are obtained from a real-time power system simulator and are fed to the ESC via appropriate interface hardware. The firing pulses obtained at the output of the ESC are fed back as inputs into the simulator. However there is no delay in this process (the simulator and controller are in a closed loop.) On the other hand the WR method of hardware testing involves the following steps: 1: Simulate the generator, exciter and the rest of the power system (not necessarily in real-time) for an interval [0 T ]. In the first iteration, the firing pulse trains to the thyristors of the exciter u 1p (t) = yc0 (t) are guessed. 2: The simulator gives the waveforms of the generator voltages and other variables. The waveforms of variables which are used as inputs to the ESC, y pk (t), are played back in real-time to the ESC. The ESC produces pulse trains for the thyristors of the exciter, y ck (t), which are time stamped and stored. 3: The time stamped pulse trains for the thyristors are made available to the power system simulator (Step 1) as inputs, for evaluating its response for the next iteration,i.e., (t) = yck (t). uk+1 p The procedure is repeated till convergence is obtained. The converged waveforms will be practically identical to those obtained from HIL testing, as discussed in Section I. The issues in the usage of WR based iterative real-time playback for controller testing are somewhat different from those encountered in typical applications of WR. We discuss these issues below. 1) Partitioning of the dynamical system: In typical applications of WR method, like circuit simulation and transient stability simulations [8]–[10], convergence of the algorithm is determined by how the system differential equations are partitioned. In this application, the controller under test is embodied in the external electronic hardware. It accepts physical feedback signals from the simulation (played back to it in real time) and subsequently provides control inputs to the simulator. 2) Numerical Integration Algorithms: It is possible to directly use a readily available non-real-time Power System Simulator. Normally, the simulation algorithm, i.e., the numerical integration method and the time step for such a simulator will be geared towards achieving a numerical stable and fast solution of the differential equations. However, the simulation algorithm may need to be changed or modified to optimize the overall WR convergence time. On the other hand, there is no flexibility to alter the digital algorithms of the equipment under test merely to improve WR convergence; the controller under test would have to be treated as a black box. Therefore, no general statement or analysis relating to the convergence properties can be presented without appropriate system identification of the controller. Nonetheless, an idea of the viability of the scheme can be obtained from the numerical experiments carried out in the next section. 3) Selection of Time Interval: The time interval T could be sub-divided to improve overall WR convergence. If convergence is very slow for a given interval, then the time interval can be reduced. Once the waveforms are close to convergence in this smaller interval, the interval can be increased. Depending on the extent of convergence, the entire previous interval need not be simulated again for further iterations. Even so, it defeats the purpose of WR method if we sub-divide the time Generator x xTCSC Infinite bus Xmax s Tw Generator Slip XTCSC K 1 + s Tw Xmin Fig. 6. SMIB system with a TCSC damping controller 2 1.5 1 Rotor Angle (rad) interval into very small intervals. 4) Acceleration techniques like Sequential Over-Relaxation [11] have been proposed. However, their efficacy for power system applications need to be investigated further. 5) Automation of the Process: The controller which is to be tested should allow for automated and repeated testing and resetting. Direct manual set-point changes in a controller during the testing are precluded because it is difficult to ensure consistent timing of the manual action for each iteration. This is not a major issue in system protection schemes and stabilizing controllers, but can be an issue, say if the controller being tested is a regulator with manual set point adjustment and startup. 6) Synchronization: Synchronization of Real Time Playback is necessary for testing of geographically dispersed multiple controllers. A method for implementing time synchronization is the GPS system. The communication channel between a centralized simulator and the real time player in the field can be used to download the playback waveforms at each iteration. This process can be automated too. 0.5 0 III. E XAMPLES To illustrate the method and bring out the relevant issues, we present three examples in this section. The first example is an illustration of how the method works. The second example illustrates testing of a wide-area controller for which WR method is uniquely suited. Subsequently, we ‘try out’ the method for a conventional HVDC controller testing application as well. We first present examples in which the controller, measurement/communication delay and playback itself is simulated, i.e., the actual controller and playback hardware is not used. However, in the last sub-section we also present the laboratory implementation of the scheme wherein we interface the non-real-time simulation with a real-time implementation of a controller and playback. 0.5 initial waveform(no controller) iteration 5 iteration 10 iteration 15 1 0 1 2 3 4 time(s) 5 6 7 8 Fig. 7. WR iterations for the SMIB system with a TCSC Damping Controller number of iterations for convergence increases with an increase in the controller gain (the limiter also comes into the picture). B. Wide Area Applications: WA-PSS A. Single Machine System Consider the Single-Machine Infinite Bus (SMIB) system shown in Fig. 6. The transmission line connecting the machine to the infinite bus is compensated using a Thyristor Controlled Series Compensator (TCSC) [12]. A damping controller for the same is to be tested as given in the figure. The system excluding the damping controller is simulated using the Trapeziodal method (time step: 1ms), with the controller also being discretized with the same algorithm. The controller uses a remote signal (generator speed). Although controller testing normally requires a detailed “EMTP” model of a power system, a simplified low frequency model is used here for the purpose of illustration. The rotor angle waveforms at various WR iterations are shown in Fig. 7. The disturbance is a three phase self-clearing fault at the generator terminals. Convergence of the initial part of the waveform (0 - 3 s) takes place quickly, however, the tail of the waveform takes more time to converge. The A WA-PSS is an application in which signals with favourable properties for damping inter-area power swings, are synthesized from wide area measurements. The measurement units are synchronized using GPS signals and the measurements are communicated to the WA-PSS. One possible objective of a WA-PSS is to selectively damp of critical interarea modes. To synthesize a signal which practically contains only the modal speed of interest, we can utilize the following expression: ωm = q T ω where ωm is the modal speed, ω are the measured speeds of the generators and q denotes a vector containing the left eigenvector components corresponding to the speed of generators for this mode 1 . The complete wide area control 1 The eigenvector is obtained from the linearized model of the power system for a given operating point. For major changes in the operating point or system topology, the eigenvector would need to be re-calculated Hardware to be tested Real Time Player Phasor Measurement Unit Communication Synchronized and Phasor Measurement Unit Processing Power Real Time Player Synchronized Equipment Central Synchronized System Synchronized Simulator Real Time Player Phasor Measurement Unit To Generator Synthesized Inter − area Slip k−1 (t) c y Excitation Input k c Wide area PSS y (t) Fig. 8. Wide Area PSS testing system, excluding the power apparatus, can be tested using the WR based iterative scheme as shown in Fig. 8. Note that if the same system (e.g. GPS) is used for synchronizing both the real-time playback as well as the measurement units, a test of the synchronization itself cannot be done. We carry 1 0 Modal Speed Deviation (rad/s) 1 2 3 4 C. HVDC Link 5 6 7 converged waveform initial waveform (PSS disabled) iteration 5 iteration 10 8 9 modulate the voltage reference of the exciters of the largest power station in the region (which significantly participates in this mode). Since the aim here is not to optimize the WAPSS design but to show the performance of the WR scheme, we consider the simple controller structure in Fig. 6. A pure transport delay of 50 ms is assumed to account for the WAMS communication and processing delays. Fig. 9 shows the modal speed signal as the iterations progress. The initial waveform is the waveform obtained without the WA-PSS - the disturbance being a fault in one transmission line which is cleared in 60 ms. The iterations practically converge in 10 iterations. Incidentally, the improved damping with a WA-PSS is clearly seen. 0 2 4 6 Fig. 9. 8 10 time 12 14 16 18 20 Modal Speed Deviations out the simulation of a large system - adapted from the Central power grid of India ( 300 generators). This system has a poorly damped swing mode of around 0.65 Hz between the machines of the eastern and western parts of the grid. To damp this mode, a WA-PSS is used which uses a modal speed signal synthesized as shown previously. This signal is used to We now evaluate the performance of the scheme for a HVDC controller application.This is distinct and more complicated than the previous examples because the final output of the controller are the thyristor firing pulses (which have discrete levels). In general, a controller includes blocks like synchronization blocks, limiters, a start up and shutdown sequence, in addition to the current regulators and power system stabilizers. This system is highly non-linear and it is interesting to see how the proposed scheme behaves. The system and controller is adapted from the demonstration file (psbhvdc.mdl) of the SimPowerSystems Toolbox of MATLAB/SIMULINK [13] - see Fig. 10. A complete description is available in the simulation file, but is summarized here for convenience: A 500 MW (250 kV, 2 kA) DC interconnection is used to transmit power from a 315 kV, 5000 MVA, 60 Hz, Fig. 10. Block diagram of HVDC system [13] AC network. The control system uses two main blocks: a synchronized six-pulse generator and a PI Curent Regulator. Voltages sent to the synchronization system are filtered by 2nd order band pass filters. The sequence of disturbances and the corresponding converged transient waveforms have the following features: 1) A step change in regulator set point is given at 0.3 s, which is tracked quite well by the controller. 2) Subsequently, a DC side fault is given at 0.5 s. The fault current increases to 5 kA and the Id current increases to to 2 pu (4 kA) in 10 ms. 3) The fast regulator action lowers the current back to its reference value of 1 pu. 4) At 0.55 s, the delay angle is forced by the protection system (not simulated) to reach 165 degrees. The rectifier thus passes in inverter mode and sends the energy stored in the line back to the 345 kV network. As a result, the arc current producing the fault rapidly decreases. The fault is cleared at 0.555 s when the fault current zero crossing is reached. 5) At 0.57 s, the regulator is released and it starts to regulate the DC current again. The steady-state 1 pu current is reached at t = 0.75 s. The waveforms as the WR iterations progress are shown in Fig. 11. Note that: 1) At the first iteration, the thyristors of the rectifier are blocked. 2) Set point changes in the controller are programmed to occur in the given manner in each iteration. Inspite of the inherent complexity of the problem (nonlinearities, switchings, faulted conditions), convergence is obtained,which comes as a bit of a surprise. However the number of iterations is quite large. Although a HIL real-time simulation scheme is well suited for this application, the WR iterative scheme may be explored as an alternative (inspite of slow convergence), as it can give a substantial saving on the cost of a simulator. A similar exercise was carried out with both rectifier and inverter modeled as twelve pulse converters (using the MATLAB demonstration file (psbhvdc12pulse.mdl). The controllers for the converters are more realistic with appropriate startup and fault recovery features. The output of both rectifier and inverter controllers were decoupled simultaneously and the WR iterations were performed. The number of iterations were large, as in the previous HVDC simulation; nonetheless the iterations did converge. Note that the rectifier and inverter controllers are at different geographical locations. Therefore in situ testing of HVDC controllers along with their associated communication system (before connection to the high power apparatus), using the iterative approach, appears to be worth exploring. Note: In the previous examples all the controllers are well tuned. However, we also checked the performance of the method when the controllers were faulty. For example, 1) Pulses to a thyristor valve in the HVDC Controller missing 2) TCSC damping controller with the incorrect sign of the gain. It was verified that the WR method converged to the response corresponding to the faulty controllers. D. Laboratory Implementation of controller and playback In the previous examples, the effect of playback and controller behaviour was simulated in non-real-time. Studies were 5 becomes comparable to the noise. This is an issue which needs further investigation. 4 IV. OTHER A PPLICATIONS Current (pu) 3 Rest of the i = 84 2 converged waveform Idref i = 42 1 Power System i = 105 i = 63 i = 21 0 Boundary nodes fault 1 0 0.1 0.2 0.4 time (s) 0.3 0.5 0.6 0.7 0.8 Sub−network Controller Fig. 11. Simulated Current waveforms using the iterative scheme for the HVDC system Fig. 13. also carried out using of real-time implementation of the controller and playback along with automation of the entire process of WR. The MATLAB simulation of the power apparatus - running in non-real-time on Linux platform - and the real-time playback and controller implementation using RTAI (Real-Time Application Interface) on Linux, are run sequentially using two computers interfaced with Peripheral Component Interconnect (PCI) cards. The schematic is shown in Fig. 12 Partitioning of System at boundary nodes Non−Real−Time Simulator Entire power system } excluding sub−network ( Low frequency model ) Current phasors at boundary nodes U Y Instantaneous to dynamic phasor conversion Voltage phasor at boundary nodes Convert Phasor to Instantaneous y k−1 (t) s u=y Non-Real-time data transfer(digital signals) via LAN Real Time Player k s y (t) Real-time playback PCI Card Non-Real-time simulator with Real-time player (Analog signals) PCI Card Real − time Simulator Real-time implementation of Controller ( EMTP − detailed model ) HIL Fig. 12. Laboratory Implementation for Controller Testing RTAI [14] is based on the Linux kernel, providing the ability to make it fully pre-emptable. It is a real-time extension for the Linux kernel - which allows us to write applications with strict timing constraints (hard real-time) for Linux. RTAI offers the same services of the Linux kernel core (device drivers, networking etc), adding the features of an industrial real-time operating system. The performance of the WR algorithm using this system was verified for the TCSC example. Some differences in performance and the response (as compared to the MATLABsimulated controller implementation) were found due to numerical precision issues in A/D conversion and the superimposed noise in the transferred analog signal (which varies at every iteration). This affects WR convergence for a TCSC damping controller because the signal level of the playback when the system comes near its equilibrium, is low and } Simulator Sub−network Control Equipment Fig. 14. Hybrid, Multi-Time Scale Real-Time and WR simulation While the main motivation of using WR based iterative real-time playback is the possibility of carrying out testing of geographically dispersed controllers which use wide area measurements, this approach shows promise of application even in the conventional domain. Consider the problem of testing a TCSC controller. The controller includes not only the lower level reactance and firing angle controllers, but damping and transient stability controllers as well. If the TCSC is being utilised for stability improvement of inter-area angle stability, it would be desirable to model the entire power system. However, a typical real-time simulator would not be able to handle the large number of elements involved. This would necessitate creation of system equivalents at the chosen “boundary nodes” - see Fig.13. The development of this equivalent (and its validation) would in itself be a challenging task. Therefore one can use a multi-time scale hybrid approach. Detailed real-time simulations of a small sub-network (“EMTP model”), can be carried out with the controller hardware in the loop. These simulations are used iteratively as inputs to the remaining larger system (simulated in non-real-time using low frequency models) whose outputs are the voltages at the boundary nodes. This approach is shown in Fig. 14. The inputs to the rest of the system simulation need to be converted to (dynamic) phasors and down-sampled because the time-steps are larger for this simulation. The main issue in this scheme is the choice of the boundary nodes which will result in the quickest convergence of the iterations. V. C ONCLUSIONS The use of a Waveform Relaxation based iterative real-time playback scheme for controller and protection system testing has been explored in this paper. This scheme is uniquely suited for Wide Area control and protection schemes. The results are encouraging and convergence could be attained for the cases considered. The method is also tested for a conventional application like HVDC controller testing. Inspite of the inherent complexities like power electronic switching, line faults, controller startup, synchronization etc., the method does converge, but requires a large number of iterations. Given the relatively low cost and the promise of easy implementation, this method can be explored as an alternative to real-time HIL simulations, even in conventional applications. Large scale system testing using a hybrid and multi-time scale approach also is conceivable using a combination of realtime simulation and the proposed iterative approach. Further research should be focussed on acceleration techniques to improve convergence. R EFERENCES [1] M. Kezunovic and M. McKenna, “Real-Time Digital Simulator for Protective Relay Testing”, IEEE Computer Applications in Power, July 1994, pp: 30-35 [2] M. Kezunovic, T. Popovic, D. Sevcik, and H. DoCarmo, “ Transient Testing of Protection Relays: Results, Methodology and Tools”, International Conference on Power Systems Transients IPST, 2003, Hong Kong. [3] A.G. Phadke, “Synchronized Phasor Measurements in Power Systems”, IEEE Computer Applications in Power, Vol. 6, No.2, April 1993, pp:1015. [4] M.G.Adamiak, A.P. Apostolov, M.M. Begovic, C.F. Henville, K.E. Martin, G.L. Michel, A.G. Phadke, J.S.Thorp, IEEE Transactions on Power Delivery, Vol. 21, No.2, April 2006, pp:601-609. [5] I. Kamwa, R. Grodin, Y. Herbert, “Wide Area Measurement based Stabilizing Control of a Large Power System”, IEEE Transactions on Power Systems, Vol 16, No. 1, Feb 2001, pp:136-153. [6] M. E. Agudo, W. Young, B. Kasperek, S. I. Thornpson, “End to End Relay Tests use Secondary Injection”, IEEE Computer Applications in Power, July 2000 ,pp:32-37 [7] J. White, A. Sangiovanni-Vincentelli, F. Odeh, and A. Ruehli, “Waveform relaxation; Theory and practice”, Transactions of the Society for Computer Simulation, vol. 2, 1985, pp:95 133. [8] E. Lelarasmee, A. Ruelhi, A. Sangiovanni-Vintecelli, “ The Waveform Relaxation Method for Time Domain analysis of Large Scale Integrated Circuits”, IEEE Transactions on Computer Aided Design of Integrated Circuits and Systems, IEEE Transactions, Vol. 1, No. 3, July 1982, pp: 131- 145 [9] J. White, A, A. Sangiovanni-Vintecelli, Relaxation Techniques for the simulation of VLSI Circuits, Kluwer Academic Publishers, Boston, 1987 [10] M. Illic Spong, M.L.Crow, M.A.Pai, “Transient Stability Simulation by Waveform Relaxation Methods”, IEEE Transactions on Power Systems, Vol. 2, No. 4, Nov. 1987, pp: 943-949 [11] M.W. Reichelt, Techniques for Parallel Transient Simulation of Semiconductor Devices, PhD Thesis, Massachusetts Institute of Technology, Boston, 1993 [12] K.R.Padiyar, FACTS Controllers In Power Transmission and Distribution, New Age International, New Delhi, 2007 [13] G. Sybille, SimPowerSystems User’s Guide, Version 4: HydroQubec/The MathWorks, Inc.,Oct. 2004,[Online].Available: http://www.mathworks.com. [14] RTAI Programming Guide 1.0,Sept. 2000,[Online].Available: http://www.rtai.org.
© Copyright 2026 Paperzz