1 Analysis of Faulted Power Systems in Three Phase Coordinates–A Generic Approach Rajeev Kumar Gajbhiye, Student Member, IEEE, Pushpa Kulkarni, Student Member, IEEE, S. A. Soman Abstract— Analysis of faulted power systems in 3-phase coordinates is desirable when dealing with unbalanced networks and complex faults. Thevenin’s model in 3-phase domain is wellknown for shunt faults. However, lack of generic circuit model for series and simultaneous faults is an impediment, as it sacrifices both simplicity and computational efficiency. In this paper, we extend this approach to arbitrarily complex faults. Case studies with complex faults on two example systems demonstrate the claims made in the paper. 3−φ Thevenin’s Voltage 3−φ Coupled Thevenin’s Impedence 3−φ Fault Model l Zf a Vtha Vthb Vthc ab Z th aa Z th bc Z th bb Z th l Zf b ca Z th cc Z th Fig. 1. l Zf g l Zf c Thevenin’s equivalent circuit for shunt fault Index Terms— Fault Circuit Analysis, Phase Coordinates, Thevenin’s approach where, −1 I. I NTRODUCTION NALYSIS of standard shunt faults in sequence domain is based upon construction of Thevenin’s equivalent circuit in sequence domain. However, analysis of shunt, series and simultaneous faults in sequence domain is cumbersome [1]. Further, sequence domain analysis requires a balanced network assumption. More precisely, network elements should have circulant symmetry. Unfortunately, distribution systems as well as transmission systems with untransposed lines are unbalanced. This motivates analysis in 3-phase co-ordinates which does not require balanced network assumption [2], [3]. Even in the 3-phase domain, Thevenin’s equivalent circuit representation is available for standard shunt faults [4]–[6]. We now briefly describe 3-phase Thevenin’s model for the analysis of shunt faults Let Yfsh represent a 3 × 3 shunt fault admittance matrix for a fault at the ith bus of a network and 3-phase pre-fault admittance matrix model be given by the following equation A old old old = Ybus V Iinj (1) Then, under the assumption that inverse of the matrix (I3 + old (i, i)Yfsh ) exists, where I3 is an identity matrix of size Zbus 3 × 3, Thevenin’s equivalent circuit in 3-phase coordinates is given by the following equation: sh sh If + Vfsh Viold = Zth (2) Ifsh = Yfsh Vfsh (3) This research work has been funded by CPRI project titled ”Coordination of Overcurrent and Distance Relays Considering Power Swings in Object Oriented Paradigm”. R. K. Gajbhiye, P. Kulkarni and S. A. Soman are with the Indian Institute of Technology, Bombay 400076, India (e-mail: [email protected]; [email protected]; [email protected]). sh Zth old old Zbus = Ybus aa ab zii zii old ba bb = Zbus (i, i) = zii zii ca cb zii zii T a b sh If = if if icf Viold = [ viaold vibold Vfsh = Vinew = [ vianew ac zii bc zii cc zii vicold ]T vibnew vicnew ]T Superscript old and new refer to pre and post fault network quantities respectively. This result can be proved by application of compensation theorem [5]. An alternative proof using Woodbury’s generalization of Sherman- Morrison formula has been presented in [6]. Fig 1 provides the visualization of this model. The representation is simple and straightforward. This simplifies the analysis of standard shunt faults. However, series faults do not have such simpler version of analysis. Typically, analysis of complex faults involves specifying additional constraint equations like Ia = 0 for phase a open circuit, Va = 0 for bolted short circuit on phase a etc. Elimination of such constraints leads to a reduced system of equations [7]. An alternative approach is to approximate bolted shunt and series faults by approximate small and large impedances and modify the admittance matrix [8]. Either way, we obtain a modified network admittance matrix formulation. Solution of the resulting system of equations provides the post fault system voltages. Such an approach is computationally inefficient, as a new matrix refactorization is required for a fault. Yet another strategy is to use hybrid approach [9], [10] where in mixed phase and sequence coordinate representation is used. This leads to computational efficiency. However, in our opinion, such an approach is also complex. In [11], Tinney has presented a compensation approach, wherein opening of a branch is modeled by the addition of a parallel current source of appropriate value. For the case of mutually coupled branches, with one branch being opened, compensating current Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 2, 2008 at 02:01 from IEEE Xplore. Restrictions apply. 2 Bus i Bus i Network ∆Yf Network sh ∆Yf sr Bus j (a) Shunt fault (Type 1) (b) Series fault (Type 2) Bus i Network ∆Yf sh ∆I (c) Type 3 fault Fig. 2. Schematic for various fault models source has to be attached in parallel to both the branches. The advantage of this approach is that original Ybus need not to be modified and hence no need of refactorization. In [12], the idea of compensated Thevenin’s impedance is developed to accommodate line outage in fault analysis. The key idea is to express network changes as low-order matrix product of the form BRC T . Fault analysis of simultaneous shunt faults using Thevenin’s model is also discussed in [13]. To conclude, a considerable amount of literature exists on fault analysis, both in sequence and 3-phase domain. However, its study reveals lack of an integrated yet simplified treatment. One of the goals of this paper is to provide such an unified treatment that includes generalization of Thevenin’s model to accommodate series and simultaneous fault. To the best of our knowledge, no such consolidation of existing literature into an integrated yet simple approach is available. This paper is organized as follows: 1) Section II presents the fault models in three phase coordinates. 2) Section III generalizes Thevenin’s model for series and simultaneous faults. 3) Section IV presents case studies for varies types of faults. 4) Section V concludes the paper. The nomenclature followed in this paper is as follows: 1) The variables in capital letters are blockmatrices or “vector of vectors”. 2) The variables in capital letters which are indexed, either in bracket like Z(i, i) or by subscripts e.g. Vi , represent either a matrix of size 3 × 3 or a vector of size 3. 3) Small letters are reserved for scalars. Thevenin’s equivalent circuit in sections III and III-B. A fault can alter the network admittance as well as current / voltage injections. Therefore, we classify faults in to following types: 1) A fault which alters a 3 × 3 block diagonal entry in the 3-phase Ybus . Let ∆Yfsh be the alteration in ith block diagonal element of Ybus . Such faults will be referred as shunt faults. All standard faults, like bolted 3-phase fault, line to line (LL), single line to ground (SLG), etc. belong to this class. For standard shunt faults, ∆Yfsh = Yfsh , which is the fault admittance matrix itself. Schematically, such a fault can be represented by fig 2(a). 2) A fault which alters both 3 × 3 block diagonal entries and off diagonal entries in the 3-phase Ybus . Such faults will be referred as series faults, e.g. open circuit fault due to opening of any phase conductor of a transmission line belongs to this class. Schematically, such a fault can be represented by fig 2(b). For phase open circuit on a line, ∆Yfsr is the alteration in the line admittance. 3) A fault which also alters the injection of current / voltage in the system. Open circuit of a generator phase belongs to this class. It results in alteration in current injection and shunt admittances. Schematically, such a fault can be represented by fig 2(c). A fault which involves multiple instances of either the same or different fault types (1–3) will be referred as simultaneous fault. In what follows, we show that faults of type 1 and 2 can be effectively handled through Thevenin’s equivalent circuit in 3-phase coordinates. Faults of type 3 in addition, require application of superposition theorem. III. T HEVENIN ’ S E QUIVALENT IN P HASE C OORDINATES A. Analysis of Series Faults Series fault refers to fault between busses, like opening of phase a conductor. Such faults are common in distribution systems. Let a series fault be created in a branch connected between nodes i and j. Correspondingly, let the 3×3 primitive admittance of branch change from Ylold to Ylnew . The resulting change will modify the four block entries namely (i, i), (i, j), old . Let, (j, i) and (j, j) in Ybus ∆Yfsr = Ylnew − Ylold (4) The modification of block diagonal entries will involve addition of ∆Yfsr where as the modification of block non-diagonal entries will involve subtraction of ∆Yfsr . So the modified block entries in new admittance matrix will be given by, new old (i, i) = Ybus (i, i) + ∆Yfsr Ybus new old Ybus (i, j) = Ybus (i, j) − ∆Yfsr new old Ybus (j, i) = Ybus (j, i) − ∆Yfsr II. FAULT M ODEL IN 3- PHASE C OORDINATES new old Ybus (j, j) = Ybus (j, j) + ∆Yfsr A fundamental principle that we have used in fault modeling is that the fault model should depict the change perceived by the network. This notion is fundamental to development of This modification can be represented as the rank-6 update, T new old Ybus = Ybus + Ei Ej Ŷfsr Ei Ej (5) Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 2, 2008 at 02:01 from IEEE Xplore. Restrictions apply. 3 I f1 Thevenin’s Voltage Thevenin’s Impedence Fault Side Z ii old i V I f2 sr Z & ij Z ji If Z jj old j Vth1 sr Vth2 ∆Y f Z th Yf sr V If Vthm I fm I f =Yf Vf Vth =Zth If Fig. 3. Block diagram representation of Thevenin’s equivalent circuit for series fault where, Ŷfsr = ∆Yfsr −∆Yfsr −∆Yfsr ∆Yfsr (6) Ei is a block vector such that, Ei (j) = O3 i = j = I3 i=j with O3 being zero matrix of size 3 × 3 and I3 is identity matrix of the same size. The key result of this work is stated by the following theorem. Theorem 1 (Series Fault). For a series fault created in a branch between bus i and j, post-fault voltages and fault currents at the faulted buses are given by the following relationships, new −1 V old Vi sr sr i Ŷ + Z = I (7) 6 th f Vjnew Vjold (8) Ifl = Ylnew Vinew − Vjnew where, Ŷfsr is given by (6) and old old Zbus (i, i) Zbus (i, j) sr Zth = old old Zbus (j, i) Zbus (j, j) Fig. 4. Block representation of Thevenin’s model for multiple faults S. Let the fault admittance Yfsh k represent a shunt admittance to be connected on bus k and Yfsr k,l represents series fault admittance required between bus k and l to capture the postnew old can be obtained from Ybus fault changes in the network. Ybus by the following sequence of steps: 1) Set ∆Y to n × n zero block matrix. 2) Identify subset Ssh of busses in set S on which shunt fault occurs. Similarly, identify subset Ssr of busses from set S involved in series fault. Note that S = Ssh ∪ Ssr and Ssh ∩ Ssr need not be empty. sh 3) For all the shunt faults Yfsh is , is ∈ Ssh , add Yf is to ∆Y (is , is ). 4) For all the series faults Yfsr is ,it , is , it ∈ Ssr , add the said admittance to the diagonal entries ∆Y (is , is ) and ∆Y (it , it ). Also subtract the same admittance from ∆Y (is , it ) and ∆Y (it , is ). Finally, new old = Ybus + ∆Y (10) Ybus In matrix ∆Y , all the entries except those belonging to faulted nodes, are zero (or more precisely O3 ). Eqn 10 can old , also be expressed as rank-3m update of Ybus new old Ybus = Ybus + [Ei1 :im ] Yfsim [Ei1 :im ] (9) Proof. The result is derived by the application of Woodbury’s formula to eqn (5). It is detailed in appendix I. Equation 7 describes the Thevenin’s equivalent circuit for the sr given by equation (9). Fig 3 visualizes series fault with Zth this equation. The Thevenin’s equivalent circuit consists of old old (i, i) and Zbus (j, j) mutually two 3-phase impedances Zbus old old (j, i). Current coupled with each other by Zbus (i, j) and Zbus in the faulted line (Ifl ) is given by eqn 8. The current Ifsr is a fictitious current associated with the sub-network depicting the change due to the fault. B. Simultaneous Faults We now consider the case of simultaneous fault where one or more busses may be involved in more than one fault. The simultaneous fault is composed of shunt and series faults. Let the set of busses involved in the fault be S = {i1 , i2 , . . . , im }. Let us assume that msh number of shunt faults and msr number of series faults occur on busses that belong to the set T (11) where, [Ei1 :im ] = [Ei1 Ei2 · · · Eim ]. An entry (k, l) in Yfsim is given by Yfsim (k, l) = ∆Y (ik , il ) k, l ∈ {1, 2, · · · , m} i.e., Yfsim is a compressed representation of ∆Y , in which all zero rows and columns of ∆Y have been eliminated. Proceeding in a similar fashion to the case of series fault, one can verify that post fault bus voltages at faulted busses can be calculated using following equation T Vf = V new (i1 )T V new (i2 )T · · · V new (im )T sim sim −1 sim = (I3m + Zth Yf ) Vth (12) where, resultant Thevenin’s voltage source vector and impedance matrix are given by the following relationships: T sim = V old (i1 )T V old (i2 )T · · · V old (im )T (13) Vth sim old = Zbus (i1 : im , i1 : im ) Zth old old Zbus (i1 , i1 ) Zbus (i1 , i2 ) old old Zbus (i , i ) Z (i2 , i2 ) 2 1 bus = .. .. . . old (im , i1 ) Zbus ··· ··· .. . old Zbus (im , i2 ) · · · Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 2, 2008 at 02:01 from IEEE Xplore. Restrictions apply. old Zbus (i1 , im ) old Zbus (i2 , im ) .. . old Zbus (im , im ) (14) 4 e1 Z ( i1 , i1 ) i1 Iffict i2 Iffict Remark 1. Knowing the postfault voltages, postfault current can be easily computed for each component in the system from their primitive 3-phase admittance matrix. 1 Viold 1 sr e2 V Z ( i2 , i2 ) ∆ Yf 1 2 old IV. T EST C ASES i2 sh Yf sr ∆ Yf e3 V 1 2 i3 Iffict old In this section, we consider faults whose analysis in sequence component is cumbersome and complex. Further, we show how their analysis in 3-phase coordinates is simplified. 3 i3 Z ( i3 , i3 ) e4 A. Analysis of Open Conductor Falling on Ground 3 i4 Iffict Viold 4 The single line diagram of the system [1] along with sequence data for base values of 30M V A, 34.5KV is shown in figure 6. The positive and negative sequence impedances of load are 1.0∠25.84◦ p.u, 0.60∠29◦ p.u. respectively. Load voltage is kept at 1.0 p.u. 4 Z ( i4 , i4 ) 4 sh Yf 2 Thevenin’s Voltage Fault Network Thevenin’s Impedance Fig. 5. Figure shows the Thevenin’s equivalent circuit for simultaneous fault analysis. Faults are at busses i1 , i2 , i3 and i4 . The faults consists of two shunt faults on bus i2 and i4 , and two series faults, one between bus i1 and i3 , another between i1 and i4 . The expressions for mutual couplings in Thevenin’s impedance are not shown for clarity. G 50MVA X1s = X2s= 15% V =V + old Zbus [Ei1 Ei2 · · · 67 m (17) Eim ][−Iff ict ] (18) 30MVA 34.5: 13.8KV XTH = 8% Single line diagram of system Consider the case of a simultaneous fault. Conductor in phase a of transmission line between bus G and bus H breaks and it gets grounded on the load side. Now we apply the Thevenin’s equivalent method, for simultaneous fault (section III-B). Block diagram of Thevenin’s equivalent circuit sim is represented in figure 7. Here, Thevenin’s impedance Zth Thevenin’s Voltage Thevenin’s Impedence Fault Side V old Z GG Z Z Z Now, post fault voltages can now be calculated by applying superposition theorem. old 0.64 & can be calculated as follows: new V (i1 ) V new (i2 ) Iff ict = Yfsim ··· new (im ) V new = G is as shown in fig 3. 3) Simultaneous Fault: Let the fictitious current vector associated with sub-network depicting the change be represented as T T T T Iff ict = Iffiict Iffiict · · · Iffiict 2 Z 0GH 30MVA LOAD 90 %P.F Per Unit at 30 MVA, 34.5 KV Base V Ifsr 1 71 XTG= 7% where, i and j are the faulty busses, and sr new If sr Vi = Ŷf Vjnew −Ifsr Iff ict 0.21 50MVA 115 : 34.5 KV Fig. 6. 2) Series Fault: Fictitious current in fig 3 represents the compensation current required to model the post fault system. Hence, by the application of superposition theorem sr If old Ei E j − V new = V old + Zbus (16) −Ifsr = Fault Fig 4 illustrates the scheme to analyze simultaneous fault using Thevenin’s equivalent circuit. Figure 5 illustrates Thevenin’s equivalent circuit for simultaneous fault at four busses in a system. C. Calculation of Post Fault Voltages It can be shown by the application of superposition theorem that, post fault voltages are given by the following equations. 1) Shunt Fault: sh old Ei −If (15) V new = V old + Zbus H Z 1GH old sr ∆Y f GH HG HH If H sh Yf Fig. 7. Block diagram representation of Thevenin’s equivalent circuit for simultaneous fault on system shown in figure 6. and fault admittance Yfsim are block matrices of size 2 × 2. Entries of Yfsim are given as follows: ∆Yfsr −∆Yfsr sim Yf = −∆Yfsr ∆Yfsr + Yfsh where, ∆Yfsr is the series admittance (see equation 4) representing the change due to opening of phase a of transmission Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 2, 2008 at 02:01 from IEEE Xplore. Restrictions apply. 5 line between busses G and H. Yfsh is shunt fault admittance representing single line to ground (SLG) fault on phase a of bus H. Though Yfsh can not be represented for bolted fault, it is constructed by assuming very small value of ground impedance (10−6 p.u.). Thus, fault bus voltages is calculated using eqn 12. This leads to the following results: old new VG VG sim sim −1 + Z Y ) = (I (19) 6 th sh VHnew VHold 1.26199, ∠−58.809◦ (20) If = 1.01855, ∠5.175◦ 1.68279, ∠−91.727◦ Thevenin’s Impedence Thevenin’s Voltage V (1) Ifict f Z 22 old Z 2 & V Fault Side Z sh Yf 24 42 Z 44 old SLG fault (2) I fict f ∆I 4 sh ∆Y f Generator Fault The result is consistent with sequence component analysis [1]. Fig. 9. Thevenin’s equivalent circuit for system in fig 8 B. Simultaneous fault on system with mutually coupled lines TABLE I P OST- FAULT VOLTAGES ( IN KV) 1 Bus 1 2 3 4 2 4 E=345 kV X1=17.5 Ω X0=12.0 Ω E=345 kV X1=17.5 Ω X0=12.0 Ω 3 • Fig. 8. System with Mutually Coupled Lines In this example, taken from [8], we analyze 345 kV double circuit transmission line for simultaneous fault on it. T-type equivalent of the 100 mi double circuit 345 kV transmission line with equivalent impedances of the receiving and the sending end systems is reproduced here in fig 8. In [14], a old in sequence domain considering procedure to calculate Ybus the mutual couplings has been presented. Similar steps are followed in 3-phase domain to obtain 3-phase Ybus . The simultaneous fault considered for this system is a SLG fault on phase a of bus 2 and open phase fault on phase b of generator on bus 4. Open circuit fault on a generator bus is a shunt fault. It has a peculiar nature that it not only modifies the Ybus but it also alters the current injection. Hence, this fault is combination of type 1 and type 3 faults. The effect of change in current injection on post fault system is analyzed by using superposition theorem. Fault analysis is done as follows: sim old • Zth is formed by picking proper entries from Zbus corresponding to buses involved in fault. Figure 9 shows Thevenin’s equivalent circuit for simultaneous fault. Shunt admittance Yfsh is connected at bus two and open circuit of generator is shown by a current injection ∆I with shunt admittance ∆Yfsh . • ∆I is calculated as ∆I new old − Igen = Igen 2 2 new old = Ygen Egen2 − Ygen Egen2 2 2 = ∆Yfsh Egen2 Define for the faulted busses, ∆Iinj O3 = ∆I • Phase A 157.9 0.0 92.1 156.8 Phase B 201.4 248.9 239.9 209.1 Phase C 200.4 255.0 248.9 199.7 Using eqn (12), post fault voltages at faulted busses are calculated as follows: new V2 sim sim −1 Yf ) = (I6 + Zth V4new old V2 sim × + Zth ∆Iinj (21) V4old sim ∆Iinj in above equation is The additional term Zth a consequence of superposition effect of ∆I current injection. Fictitious current vector (see fig 9) is calculated by using the following equation Yfsh V2new Iff ict = ∆Yfsh V4new − ∆I The post fault voltages are calculated by eqn (18). These are tabulated in table I. They are consistent with results in [8], which validates the proposed approach. V. C ONCLUSIONS Three phase analysis is suitable for fault analysis of unbalanced systems and complex faults. In this paper, we have proposed generic Thevenin’s circuit representation for shunt, series and simultaneous faults. It’s advantage is conceptual simplicity and computational efficiency as repeated matrix factorization is not required. Two test systems with complex faults were analyzed to validate the approach. ACKNOWLEDGMENT The authors acknowledge the valuable suggestions and feedback by Prof. M. A. Pai, University of Illinois at Urbana Champaign, Prof. D. Thukaram, Indian Institute of Science, Bangalore and Profs S. A. Khaparde and A. M. Kulkarni of Indian Institute of Technology, Bombay. Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 2, 2008 at 02:01 from IEEE Xplore. Restrictions apply. 6 R EFERENCES [1] J. L. Blackburn, Symmetrical Components for Power Systems Engineering. New York: Marcel Dekker,Inc, 1993. [2] M. A. Laughton, “Analysis of unbalanced polyphase networks by the method of phase coordinates, part 1: System representation in phase frame of reference,” Proc.IEE, vol. 115, No. 8, pp. 1163–1172, 1968. [3] M. A. Laughton, “Analysis of unbalanced polyphase networks by the method of phase coordinates, part 2: Fault analysis,” Proc.IEE, vol. 116, No. 6, pp. 857–865, 1969. [4] M. A. Pai, Computer Techniques in Power System Analysis. Delhi: Tata McGraw Hill Inc, 1979. [5] L. P. Singh, Advanced Power System Analysis and Dynamics, 2nd ed. Wiley Eastern Limited, 1986. [6] P. Kulkarni, R. K. Gajbhiye, and S. A. Soman, “Generic fault analysis in phase coordinates,” vol. I. Nepal: International Conference on Power Systems, Nov.3-5 2005, pp. 593–598. [7] W. X. He and C. Y. Teo, “Unbalanced short circuit calculation by phase co-ordinates,” in Proceedings of EMPD’95, 1995 International Conference on , Volume: 2, Nov. 1995, pp. 21–23. [8] A. Berman and W. Xu, “Analysis of faulted power systems by phase coordinates,” IEEE Transactions on Power Delivery, vol. 13, No. 2, pp. 587–595, Apr. 1998. [9] G. Gross and H. Hong, “A two step compensation method for solving short circuit problems,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-101, No. 6, pp. 1322–1331, June 1982. [10] V. Brandwajin and W. F. Tinney, “Generalized method of fault analysis,” IEEE Transactions on Power Systems, vol. PAS-104, No. 6, pp. 1301– 1306, June 1985. [11] W. F. Tinney, “Compensation methods for network solutions by optimally ordered triangular factorization,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-91, No. 1, pp. 123–127, Jan. 1972. [12] F. L. Alvarado, S. K. Mong, and M. K. Enns, “A fault program with macros, monitors and direct compensation in mutual groups,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-104, No. 5, pp. 1109–1120, May 1985. [13] T. H. Chen, M. S. Chen, W. J. Lee, P. Kotas, and P. V. Olinda, “Distribution system short circuit analysis – a rigid approach,” IEEE Transactions on Power Systems, vol. 7, No. 1, pp. 444–450, Feb. 1992. [14] S. A. Soman, S. A. Khaparde, and S. Pandit, Computational Methods For Large Sparse Power Systems Analysis: An Object oriented Approach. London: Kluwer Academic Publishers, 2001. [15] M. Woodbury, Inverting Modified Matrices. Princeton, New Jersey: Memorandum 42, Statistics Research Group, 1950. A PPENDIX I P ROOF OF T HEOREM 1 The Woodbury’s formula [15] for calculating inverse of a rank-k updated matrix A is given by, −1 −1 T −1 A + UV T = A−1 − A−1 U Ik + V T A−1 U V A (22) where, A is n × n matrix, U and V are n × k matrices and Ik is k × k identity matrix. It is assumed that necessary inverse in eqn (22) exists. For the case of series fault, from equation (5), we set T −1 new old = Ybus + Ei Ej Ŷfsr Ei Ej Zbus where, Ŷfsr is defined in the eqn (6) old formula (eqn 22) with A = Ybus , U = Applying Woodbury’s sr Ei Ej Ŷf and V = Ei Ej T old new old old Ei Ej Ŷfsr I6 + Ei Ej Zbus ⇒ Zbus = Zbus − Zbus −1 T old Ei Ej Ŷfsr Ei Ej Zbus old old old (:, i) Zbus (:, j) Ŷfsr = Zbus − Zbus old −1 old old Z (i, i) Zbus (i, j) Zbus (i, :) sr Ŷ I6 + bus old old old Zbus Zbus (j, i) Zbus (j, j) f (j, :) (23) old and sampling ith and j th row and Post-multiplying by Iinj old old old old substituting Zbus (i, :)Iinj = Viold and Zbus (j, :)Iinj = Vjold , new old old old Vi Vi (i, j) Zbus (i, i) Zbus Ŷ sr = − old old Vjnew Vjold Zbus (j, i) Zbus (j, j) f old −1 old old Vi Zbus (i, i) Zbus (i, j) sr Ŷ I6 + old old Vjold Zbus (j, i) Zbus (j, j) f (24) Let, T T T = Vth T Vinew T Vjnew T = Vf old old Zbus (i, i) Zbus (i, j) sr = Zth old old Zbus (j, i) Zbus (j, j) Viold Vjold (25) (26) (27) Then we have −1 sr sr sr sr Ŷf I6 + Zth Ŷf Vf =Vth − Zth Vth −1 sr sr sr sr sr sr I6 + Zth Ŷf − Zth Ŷf Ŷf = I6 + Zth Vth −1 sr sr Ŷf ⇒ Vf = I6 + Zth Vth (28) Rajeev Kumar Gajbhiye is currently working towards Ph.D. degree in Department of Electrical Engineering at Indian Institute of Technology, Bombay, India. His research interests include power system analysis and object oriented analysis. Pushpa Kulkarni is currently pursuing M.Tech degree in Indian Institute of Technology, Bombay, India. S. A. Soman is Associate Professor in the Department of Electrical Engineering at Indian Institute of Technology Bombay, India. Along with Prof. S. A. Khaparde, he has authored a book on Computational Methods for Large Sparse Power System Analysis: An Object Oriented Approach, published by Kluwer Academic Publishers in 2001. Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 2, 2008 at 02:01 from IEEE Xplore. Restrictions apply.
© Copyright 2025 Paperzz