Monitoring the Interface Cards in the Cisco cBR Chassis
Monitoring the Interface Card in the Cisco cBR Chassis 2
Monitoring the Interface Cards in the Cisco cBR Chassis using LEDs 2
Monitoring the Downstream PHY Module 2
Revised: January 31, 2017,
Monitoring the Interface Card in the Cisco cBR Chassis
Monitoring the Interface Cards in the Cisco cBR Chassis using LEDs
The LEDs on the interface cards (that is, interface line cards, the RF Through PIC and the RF Protect PIC) are the same.
Table 1: Verifying the LEDs on the Interface Cards
LED
Status
Description
STATUS
Off
The line card has not initialized correctly.
Yellow
The line card has initialized, but HA fault is detected.
Possible hardware fault.
PROTECT
REPLACE
Green
The line card is operational.
Off
The Interface line card is not a Protect card.
Blue
The Interface line card is configured as a Protect card.
Green
The Protect card is operational and traffic is flowing.
Off
The Interface line card is operational and does not
require replacement.
White
The Interface line card requires replacement.
Monitoring the Downstream PHY Module
To display the OBFL for downstream PHY module events, use the show logging onboard slot message command.
Router# show logging onboard slot 1 message | include DS-PHY
01/11/14 23:06:32
DS-PHY
0
G2P1E000039 Gemini 0 Set
1.0V_FPGA Max15301 Major Low
To display the system logs for downstream PHY module events, use the show logging | in DS-PHY command.
Router# show logging | include DS-PHY
2
Verifying the Downstream PHY Module Upgrade
To verify the downstream PHY module is upgraded from Downstream D3.0 to Downstream D3.1, use the show inventory command.
This extract of the output of the show inventory command:
Router#show inventory
NAME: "Cable PHY Module", DESCR:
PID: CBR-D31-DS-MOD , VID: V01 ,
NAME: "Cable PHY Module", DESCR:
PID: CBR-D31-DS-MOD , VID: V01 ,
"CLC Downstream PHY Module 2/0"
SN: CAT1829E06B
"CLC Downstream PHY Module 2/0"
SN: CAT1829E08B
The downstream D3.0 module is indicated by the PID, CBR-D30-DS-MOD. The downstream D3.1 module is indicated by the PID,
CBR-D31-DS-MOD.
To verify the downstream PHY module is powered up, use the show cable card ds-phy display | include PowerGood command.
Router#show cable card 3/0 ds-phy display | include PowerGood
Serial Number: G2P1E000009 HW VERSION 9. ds_phy_ctrl_status: 55f PowerGood: 400
Serial Number: HW VERSION 0. ds_phy_ctrl_status: 55f PowerGood: 0
Router#
The following indicate the downstream PHY module version and power-up status:
• The serial number shows the version of the downstream PHY module. G2 in the Serial Number indicates downstream D3.1
module.
• The PowerGood value indicates if the downstream PHY module is powered up after the reload. This values should be non-zero
to indicate that the downstream PHY module is properly powered up. See Troubleshooting the Interface Cards in Cisco cBR
Chassis for details on PowerGood indications.
3
© 2017
Cisco Systems, Inc. All rights reserved.
Americas Headquarters
Cisco Systems, Inc.
San Jose, CA 95134-1706
USA
Asia Pacific Headquarters
Cisco Systems (USA) Pte. Ltd.
Singapore
Europe Headquarters
Cisco Systems International BV
Amsterdam, The Netherlands
Cisco has more than 200 offices worldwide. Addresses, phone numbers, and fax numbers are listed on the
Cisco Website at www.cisco.com/go/offices.