Laser Link III Mainframe and Laser Link Mini-Mainframe (LLMM) Installation and Operation Guide

Laser Link III Mainframe and
Laser Link Mini-Mainframe
Installation and Operation Guide
For Your Safety
Explanation of Warning and Caution Icons
Avoid personal injury and product damage! Do not proceed beyond any symbol
until you fully understand the indicated conditions.
The following warning and caution icons alert you to important information about
the safe operation of this product:
You may find this symbol in the document that accompanies this product.
This symbol indicates important operating or maintenance instructions.
You may find this symbol affixed to the product. This symbol indicates a
live terminal where a dangerous voltage may be present; the tip of the
flash points to the terminal device.
You may find this symbol affixed to the product. This symbol indicates a
protective ground terminal.
You may find this symbol affixed to the product. This symbol indicates a
chassis terminal (normally used for equipotential bonding).
You may find this symbol affixed to the product. This symbol warns of a
potentially hot surface.
You may find this symbol affixed to the product and in this document.
This symbol indicates an infrared laser that transmits intensitymodulated light and emits invisible laser radiation or an LED that
transmits intensity-modulated light.
Important
Please read this entire guide. If this guide provides installation or operation
instructions, give particular attention to all safety statements included in this guide.
Notices
Trademark Acknowledgments
Cisco and the Cisco logo are trademarks or registered trademarks of Cisco and/or its
affiliates in the U.S. and other countries. To view a list of cisco trademarks, go to this
URL: www.cisco.com/go/trademarks.
Third party trademarks mentioned are the property of their respective owners.
The use of the word partner does not imply a partnership relationship between Cisco
and any other company. (1110R)
Publication Disclaimer
Cisco Systems, Inc. assumes no responsibility for errors or omissions that may appear in
this publication. We reserve the right to change this publication at any time without
notice. This document is not to be construed as conferring by implication, estoppel, or
otherwise any license or right under any copyright or patent, whether or not the use of
any information in this document employs an invention claimed in any existing or later
issued patent.
Copyright
© 2008, 2012 Cisco and/or its affiliates. All rights reserved. Printed in the United States of
America.
Information in this publication is subject to change without notice. No part of this
publication may be reproduced or transmitted in any form, by photocopy, microfilm,
xerography, or any other means, or incorporated into any information retrieval system,
electronic or mechanical, for any purpose, without the express permission of Cisco
Systems, Inc.
Contents
Important Safety Instructions............................................................................................................................... iv
Laser Safety ............................................................................................................................................................. xii
Chapter 1
Chapter 2
Chapter 3
General Information
Overview....................................................................................................................... 1-1
Laser Link System Equipment Description ............................................................. 1-2
Laser Link III Mainframe Description ...................................................................... 1-3
Laser Link Mini-Mainframe Description ................................................................. 1-7
List of Abbreviations ................................................................................................... 1-9
Installation
Overview....................................................................................................................... 2-1
Laser Link III Mainframe Installation ....................................................................... 2-2
Laser Link III Mainframe Electrical Connections.................................................... 2-5
Laser Link Mini-Mainframe Installation .................................................................. 2-9
Laser Link Mini-Mainframe Electrical Connections ............................................. 2-10
Setup and Operation
Overview....................................................................................................................... 3-1
Section A Initial Checkout
Laser Link III Mainframe Initial Checkout .............................................................. 3-3
Laser Link Mini-Mainframe Initial Checkout .......................................................... 3-5
Section B Controls and Indicators
Laser Link III Mainframe Controls and Indicators ................................................. 3-8
Laser Link Mini-Mainframe Controls and Indicators .......................................... 3-11
Section C Alarms
Alarm Tables .............................................................................................................. 3-14
Telemetry Connectors ............................................................................................... 3-25
Chapter 4
Customer Information .................................................................................................. 6-1
78-4004177-01 Rev D
iii
Important Safety Instructions
Read and Retain Instructions
Carefully read all safety and operating instructions before operating this equipment, and
retain them for future reference.
Follow Instructions and Heed Warnings
Follow all operating and use instructions. Pay attention to all warnings and cautions in the
operating instructions, as well as those that are affixed to this equipment.
Terminology
The terms defined below are used in this document. The definitions given are based on those
found in safety standards.
Service Personnel - The term service personnel applies to trained and qualified individuals
who are allowed to install, replace, or service electrical equipment. The service personnel are
expected to use their experience and technical skills to avoid possible injury to themselves
and others due to hazards that exist in service and restricted access areas.
User and Operator - The terms user and operator apply to persons other than service
personnel.
Ground(ing) and Earth(ing) - The terms ground(ing) and earth(ing) are synonymous. This
document uses ground(ing) for clarity, but it can be interpreted as having the same meaning
as earth(ing).
Electric Shock Hazard
This equipment meets applicable safety standards.
WARNING!
To reduce risk of electric shock, perform only the instructions that are included in the
operating instructions. Refer all servicing to qualified service personnel only.
Electric shock can cause personal injury or even death. Avoid direct contact with dangerous
voltages at all times. The protective ground connection, where provided, is essential to safe
operation and must be verified before connecting the power supply.
Know the following safety warnings and guidelines:
• Dangerous Voltages
− Only qualified service personnel are allowed to perform equipment installation or
replacement.
− Only qualified service personnel are allowed to remove chassis covers and access any of
the components inside the chassis.
• Grounding
− Do not violate the protective grounding by using an extension cable, power cable, or
autotransformer without a protective ground conductor.
− Take care to maintain the protective grounding of this equipment during service or
repair and to re-establish the protective grounding before putting this equipment back
into operation.
iv
78-4004177-01 Rev D
Important Safety Instructions, Continued
Installation Site
When selecting the installation site, comply with the following:
• Protective Ground - The protective ground lead of the building’s electrical installation
should comply with national and local requirements.
• Environmental Condition – The installation site should be dry, clean, and ventilated. Do
not use this equipment where it could be at risk of contact with water. Ensure that this
equipment is operated in an environment that meets the requirements as stated in this
equipment’s technical specifications, which may be found on this equipment’s data sheet.
Installation Requirements
WARNING:
Allow only qualified service personnel to install this equipment. The installation must
conform to all local codes and regulations.
Equipment Placement
WARNING:
Avoid personal injury and damage to this equipment. An unstable mounting surface
may cause this equipment to fall.
To protect against equipment damage or injury to personnel, comply with the following:
• Install this equipment in a restricted access location.
• Do not install near any heat sources such as radiators, heat registers, stoves, or other
equipment (including amplifiers) that produce heat.
• Place this equipment close enough to a mains AC outlet to accommodate the length of this
equipment’s power cord.
• Route all power cords so that people cannot walk on, place objects on, or lean objects
against them. This may pinch or damage the power cords. Pay particular attention to
power cords at plugs, outlets, and the points where the power cords exit this equipment.
• Use only with a cart, stand, tripod, bracket, or table specified by the manufacturer, or sold
with this equipment.
• Make sure the mounting surface or rack is stable and can support the size and weight of
this equipment.
• The mounting surface or rack should be appropriately anchored according to
manufacturer’s specifications. Ensure this equipment is securely fastened to the mounting
surface or rack where necessary to protect against damage due to any disturbance and
subsequent fall.
Ventilation
This equipment has openings for ventilation to protect it from overheating. To ensure
equipment reliability and safe operation, do not block or cover any of the ventilation
openings. Install the equipment in accordance with the manufacturer’s instructions.
78-4004177-01 Rev D
v
Important Safety Instructions, Continued
Rack Mounting Safety Precautions
Mechanical Loading
Make sure that the rack is placed on a stable surface. If the rack has stabilizing devices, install
these stabilizing devices before mounting any equipment in the rack.
WARNING:
Avoid personal injury and damage to this equipment. Mounting this equipment in the
rack should be such that a hazardous condition is not caused due to uneven mechanical
loading.
Reduced Airflow
When mounting this equipment in the rack, do not obstruct the cooling airflow through the
rack. Be sure to mount the blanking plates to cover unused rack space. Additional
components such as combiners and net strips should be mounted at the back of the rack, so
that the free airflow is not restricted.
CAUTION:
Installation of this equipment in a rack should be such that the amount of airflow
required for safe operation of this equipment is not compromised.
Elevated Operating Ambient Temperature
Only install this equipment in a humidity- and temperature-controlled environment that
meets the requirements given in this equipment’s technical specifications.
CAUTION:
If installed in a closed or multi-unit rack assembly, the operating ambient temperature
of the rack environment may be greater than room ambient temperature. Therefore,
install this equipment in an environment compatible with the manufacturer’s maximum
rated ambient temperature.
Handling Precautions
When moving a cart that contains this equipment, check for any of the following possible
hazards:
WARNING:
Avoid personal injury and damage to this equipment! Move any
equipment and cart combination with care. Quick stops, excessive
force, and uneven surfaces may cause this equipment and cart to
overturn.
• Use caution when moving this equipment/cart combination to avoid injury from tip-over.
vi
78-4004177-01 Rev D
Important Safety Instructions, Continued
• If the cart does not move easily, this condition may indicate obstructions or cables that may
need to be disconnected before moving this equipment to another location.
• Avoid quick stops and starts when moving the cart.
• Check for uneven floor surfaces such as cracks or cables and cords.
Grounding
This section provides instructions for verifying that the equipment is properly grounded.
Safety Plugs (USA Only)
This equipment is equipped with either a 3-terminal (grounding-type) safety plug or a 2terminal (polarized) safety plug. The wide blade or the third terminal is provided for safety.
Do not defeat the safety purpose of the grounding-type or polarized safety plug.
To properly ground this equipment, follow these safety guidelines:
• Grounding-Type Plug - For a 3-terminal plug (one terminal on this plug is a protective
grounding pin), insert the plug into a grounded mains, 3-terminal outlet.
Note: This plug fits only one way. If this plug cannot be fully inserted into the outlet,
contact an electrician to replace the obsolete 3-terminal outlet.
• Polarized Plug - For a 2-terminal plug (a polarized plug with one wide blade and one
narrow blade), insert the plug into a polarized mains, 2-terminal outlet in which one socket
is wider than the other.
Note: If this plug cannot be fully inserted into the outlet, try reversing the plug. If the plug
still fails to fit, contact an electrician to replace the obsolete 2-terminal outlet.
Grounding Terminal
If this equipment is equipped with an external grounding terminal, attach one end of an 18gauge wire (or larger) to the grounding terminal; then, attach the other end of the wire to a
ground, such as a grounded equipment rack.
Safety Plugs (European Union)
• Class I Mains Powered Equipment – Provided with a 3-terminal AC inlet and requires
connection to a 3-terminal mains supply outlet via a 3-terminal power cord for proper
connection to the protective ground.
Note: The equipotential bonding terminal provided on some equipment is not designed to
function as a protective ground connection.
• Class II Mains Powered Equipment – Provided with a 2-terminal AC inlet that may be
connected by a 2-terminal power cord to the mains supply outlet. No connection to the
protective ground is required as this class of equipment is provided with double or
reinforced and/or supplementary insulation in addition to the basic insulation provided in
Class I equipment.
Note: Class II equipment, which is subject to EN 50083-1, is provided with a chassis
mounted equipotential bonding terminal. See the section titled Equipotential Bonding for
connection instructions.
78-4004177-01 Rev D
vii
Important Safety Instructions, Continued
Equipotential Bonding
If this equipment is equipped with an external chassis terminal marked with the IEC 604175020 chassis icon ( ), the installer should refer to CENELEC standard EN 50083-1 or IEC
standard IEC 60728-11 for correct equipotential bonding connection instructions.
AC Power
Important: If this equipment is a Class I equipment, it must be grounded.
• If this equipment plugs into an outlet, the outlet must be near this equipment, and must be
easily accessible.
• Connect this equipment only to the power sources that are identified on the equipmentrating label normally located close to the power inlet connector(s).
• This equipment may have two power sources. Be sure to disconnect all power sources
before working on this equipment.
• If this equipment does not have a main power switch, the power cord connector serves as
the disconnect device.
• Always pull on the plug or the connector to disconnect a cable. Never pull on the cable
itself.
• Unplug this equipment when unused for long periods of time.
Connection to –48 V DC/–60 V DC Power Sources
If this equipment is DC-powered, refer to the specific installation instructions in this manual
or in companion manuals in this series for information on connecting this equipment to
nominal -48 V DC/-60 V DC power sources.
Circuit Overload
Know the effects of circuit overloading before connecting this equipment to the power
supply.
CAUTION:
Consider the connection of this equipment to the supply circuit and the effect that
overloading of circuits might have on overcurrent protection and supply wiring. Refer
to the information on the equipment-rating label when addressing this concern.
General Servicing Precautions
WARNING:
Avoid electric shock! Opening or removing this equipment’s cover may expose you to
dangerous voltages.
Be aware of the following general precautions and guidelines:
• Servicing - Refer all servicing to qualified service personnel. Servicing is required when
this equipment has been damaged in any way, such as power supply cord or plug is
damaged, liquid has been spilled or objects have fallen into this equipment, this equipment
has been exposed to rain or moisture, does not operate normally, or has been dropped.
viii
78-4004177-01 Rev D
Important Safety Instructions, Continued
• Wristwatch and Jewelry - For personal safety and to avoid damage of this equipment
during service and repair, do not wear electrically conducting objects such as a wristwatch
or jewelry.
• Lightning - Do not work on this equipment, or connect or disconnect cables, during
periods of lightning.
• Labels - Do not remove any warning labels. Replace damaged or illegible warning labels
with new ones.
• Covers - Do not open the cover of this equipment and attempt service unless instructed to
do so in the instructions. Refer all servicing to qualified service personnel only.
• Moisture - Do not allow moisture to enter this equipment.
• Cleaning - Use a damp cloth for cleaning.
• Safety Checks - After service, assemble this equipment and perform safety checks to
ensure it is safe to use before putting it back into operation.
Electrostatic Discharge
Electrostatic discharge (ESD) results from the static electricity buildup on the human body
and other objects. This static discharge can degrade components and cause failures.
Take the following precautions against electrostatic discharge:
• Use an anti-static bench mat and a wrist strap or ankle strap designed to safely ground
ESD potentials through a resistive element.
• Keep components in their anti-static packaging until installed.
• Avoid touching electronic components when installing a module.
Fuse Replacement
To replace a fuse, comply with the following:
• Disconnect the power before changing fuses.
• Identify and clear the condition that caused the original fuse failure.
• Always use a fuse of the correct type and rating. The correct type and rating are indicated
on this equipment.
Lithium Battery
For equipment with a lithium battery, observe the following rules:
• Do not dispose of used batteries through the regular garbage collection system, but follow
the local regulations. The batteries may contain substances that could be harmful to the
environment.
• Replace batteries with the same or equivalent type recommended by Cisco.
• Insert batteries correctly. There may be a risk of explosion if the batteries are incorrectly
inserted.
• When disposing of this equipment, remove the batteries and dispose of them separately in
accordance with local regulations.
• Do not recharge the batteries or expose them to temperatures above 100°C (212°F).
78-4004177-01 Rev D
ix
Important Safety Instructions, Continued
Electromagnetic Compatibility Regulatory Requirements
This equipment meets applicable electromagnetic compatibility (EMC) regulatory
requirements. EMC performance is dependent upon the use of correctly shielded cables of
good quality for all external connections, except the power source, when installing this
equipment.
• Ensure compliance with cable/connector specifications and associated installation
instructions where given elsewhere in this manual.
Otherwise, comply with the following good practices:
• Multi-conductor cables should be of single-braided, shielded type and have conductive
connector bodies and backshells with cable clamps that are conductively bonded to the
backshell and capable of making 360° connection to the cable shielding. Exceptions from
this general rule will be clearly stated in the connector description for the excepted
connector in question.
• Ethernet cables should be of single-shielded or double-shielded type.
• Coaxial cables should be of the double-braided shielded type.
EMC
Where this equipment is subject to USA FCC and/or Industry Canada rules, the following
statements apply:
FCC Statement for Class A Equipment
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when this equipment is operated in a
commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case users will be required to correct the interference at their own
expense.
Industry Canada – Industrie Canadienne Statement
This apparatus complies with Canadian ICES-003.
Cet appareil est confome à la norme NMB-003 du Canada.
CENELEC/CISPR Statement with Respect to Class A Information Technology Equipment
This is a Class A equipment. In a domestic environment this equipment may cause radio
interference in which case the user may be required to take adequate measures.
x
78-4004177-01 Rev D
Important Safety Instructions, Continued
Modifications
This equipment has been designed and tested to comply with applicable safety, laser safety,
and EMC regulations, codes, and standards to ensure safe operation in its intended
environment.
Do not make modifications to this equipment. Any changes or modifications could void the
user’s authority to operate this equipment.
Modifications have the potential to degrade the level of protection built into this equipment,
putting people and property at risk of injury or damage. Those persons making any
modifications expose themselves to the penalties arising from proven non-compliance with
regulatory requirements and to civil litigation for compensation in respect of consequential
damages or injury.
Accessories
Use only attachments or accessories specified by the manufacturer.
78-4004177-01 Rev D
xi
Laser Safety
Introduction
These are general laser safety precautions, not related to any specific procedure, that all
personnel should understand and apply.
Warning: Radiation
WARNINGS:
• Avoid personal injury! Use of controls, adjustments, or performance of procedures
other than those specified herein may result in hazardous radiation exposure.
• Avoid personal injury! The laser light source on this equipment emits invisible laser
radiation. Avoid direct exposure to the laser light source.
• Do not apply power to this equipment if the fiber is unmated or unterminated.
• Do not stare into an unmated fiber or at any mirror-like surface that could reflect light that
is emitted from an unterminated fiber.
• Do not view an activated fiber with optical instruments (e.g., eye loupes, magnifiers,
microscopes).
• Use safety-approved optical fiber cable to maintain compliance with applicable laser safety
requirements.
Warning: Fiber Optic Cables
WARNING:
Avoid personal injury! Qualified service personnel may only perform the procedures in
this manual. Wear safety glasses and use extreme caution when handling fiber optic
cables, particularly during splicing or terminating operations. The thin glass fiber core
at the center of the cable is fragile when exposed by the removal of cladding and buffer
material. It easily fragments into glass splinters. Using tweezers, place splinters
immediately in a sealed waste container and dispose of them safely in accordance with
local regulations.
xii
78-4004177-01 Rev D
Laser Safety, Continued
Safe Operation For Software Controlling Optical Transmission Equipment
If this manual discusses software, the software described is used to monitor and/or control
Cisco and other vendors’ electrical and optical equipment designed to transmit video, voice,
or data signals. Certain safety precautions should be observed when operating equipment of
this nature.
For equipment specific safety requirements, refer to the appropriate section of the equipment
documentation.
For safe operation of this software, refer to the following warnings.
WARNINGS:
• Ensure that all optical connections are complete or terminated before using this
equipment to remotely control a laser device. An optical or laser device can pose a
hazard to remotely located personnel when operated without their knowledge.
• Allow only personnel trained in laser safety to operate this software. Otherwise,
injuries to personnel may occur.
• Restrict access of this software to authorized personnel only.
• Install this software in equipment that is located in a restricted access area.
78-4004177-01 Rev D
xiii
Chapter 1
General Information
Overview
Introduction
This manual describes the installation and operation of the following mainframes:
• Laser Link III™ Mainframe
• Laser Link® Mini-Mainframe
In This Chapter
This chapter contains the following topics.
Topic
See Page
Laser Link System Equipment Description
1-2
Laser Link III Mainframe Description
1-3
Laser Link Mini-Mainframe Description
1-7
List of Abbreviations
1-9
78-4004177-01 Rev D
General Information
1-1
Laser Link System Equipment Description
Overview
The Laser Link system is used to transport broadband telecommunications signals
on fiber optic cable. The Laser Link system consists of a mainframe (standard or
mini), power supplies, and a family of modules including transmitters (upstream
and downstream), optical/RF amplifiers, receivers (upstream and downstream),
block up/down converters, and RF/optical switches.
Mainframe Functional Description
The Laser Link III Mainframe and the Laser Link Mini-Mainframe perform four
essential functions in the overall system application:
• Housing the Laser Link modules
• Powering the modules
• Routing control and status signals to and from the modules
• Cooling
Instructions pertaining to the installation of specific modules are provided in the
Installation and Operation Guide accompanying each module. Functional
descriptions of power distribution and status monitoring of modules are contained
in this section.
Laser Link Equipment
The Laser Link modules accommodated by the Laser Link III Mainframe and the
Laser Link Mini-Mainframe include the following:
• Transmitter 1310 nm/45–870 MHz, LLT III (half-width)
• Transmitter 1550 nm/45–870 MHz, LEMT (full-width)
• Narrowcast Transmitter 1550 nm/45–870 MHz, LLNT (full-width)
• Narrowcast Return Transmitter 1550 nm/5–200 MHz, LLNTR (full-width)
• Optical Amplifier C-Band, LLOA (full-width)
• Return Receiver – 5–210 MHz, ELLRR-S (half-width)
• Receiver 50–870 MHz, LLFR (full-width)
• Return Transmitter 1310 nm/5–210 MHz, LLRT (full-width)
• Dual Amplifier, 870 MHz, LLDA (full-width)
• RF Switch 5 MHz–1 GHz, LLRS (half-width)
• Block Converter, LLUC/LLDC (half-width)
1-2
General Information
78-4004177-01 Rev D
Laser Link III Mainframe Description
Overview
This section contains physical and functional descriptions of the Laser Link III
Mainframe.
Physical Description
The Laser Link III Mainframe has seven full-width module bays that may be
configured to support optical/RF amplifiers, upstream/downstream transmitters or
downstream receivers. Plug-in modules may be arranged in various combinations
within the mainframe to meet particular application needs.
Two half-width modules may be supported in a full-width bay to allow housing up
to 14 such units in a 5 RU space.
The Laser Link III Mainframe fits into a standard 5 RU (8.75 inches/22 cm) high by
19- or 23-inch (48 or 58 cm) wide area that is approximately 20 inches (51 cm) deep.
It should be mounted in a cabinet that conforms to ANSI/EIA-310-C standards.
Adjustable mounting ears are provided with each unit. Four positions allow
selecting the depth to which the frame is installed. The mainframe may be mounted
flush to the bay or protruding up to 5 inches (13 cm). See Chapter 2, Installation, for
information regarding maximum torque requirements when moving the ears.
Note: Ears for mounting the mainframe in a 23-inch bay are not included and must
be ordered separately (P/N 704095). Also, rack screws are not included with the
mainframe. See Chapter 2, Installation, for information regarding maximum torque
requirements when replacing the ears.
78-4004177-01 Rev D
General Information
1-3
Laser Link III Mainframe Description, Continued
Fiber may be routed from the chassis through the bubble front of the door, through
ear holes on the side, or through the channel on the right side and out the rear of the
unit. Nineteen-inch rear support brackets are included and their use is
recommended.
Power Distribution
Main power can be universal AC,-48 V DC, or +24 V DC input. With universal AC
or -48 V DC, the Laser Link III chassis requires a power supply (converter). This unit
accepts the AC or the -48 V DC and performs the required conversion to output +24
V DC to the power distribution board (under which the power supply resides).
Should the +24 V DC be available, the mainframe can be operated without a power
supply by applying the voltage directly to the power distribution board.
Voltage applied to the power distribution board (+24 V DC) is routed to the various
modules installed in the mainframe. Each module requires this voltage for normal
operation. The power distribution board accepts +24 V DC as the primary input
power (supply A) through the connector labeled J10. The potential is then applied to
the modules through the interface cable provided with each module. This cable
connects the 26-pin interface on the mainframe to the rear panel power/status D
connector on the module. Fuse F2 protects the primary power (supply A). Fuse F5
is not applicable.
Redundant power (supply B) is provided in the form of +24 V DC to the terminal
block of the power distribution board. The connecting point is labeled J11 and
accepts +24 V DC through a spade lug type of interface. The redundant input is also
load protected (fuse F1).
1-4
General Information
78-4004177-01 Rev D
Laser Link III Mainframe Description, Continued
Important: Wire gauge specifications for 24 V DC/15 A input are as follows:
10’ cable: 12 AWG minimum
5’ cable: 15 AWG minimum
Terminal Block
Normally open (NO) and normally closed (NC) contact points are available on the
terminal block (J11) of the power distribution board. These interface points allow
you to trigger an external alarm should the general operation alarm of the
mainframe toggle to an alarm state. The number five position of the terminal block
may be utilized in conjunction with the common position, number six, in a normally
closed alarm relay. The number seven pin may be used in conjunction with the
common position in a normally open alarm relay configuration. Under normal
operation (no alarm), number six and number five are closed.
Status Monitoring
Status of housed modules is supplied to users via front panel LEDs, or the ROSA™
Element Management System, or TNCS Element Management System (if used). The
available monitored parameters are provided in the respective module manuals.
Status monitoring signals are routed from the rear of the module to the power
distribution board. This is accomplished by connecting the module’s DB15, DB26, or
DB9 connector to the respective DB26 connector on the power distribution board
using the interface cable provided with each module. From the board, signals are
available to the user panel (J12), the element management system interface point (J8),
and the telemetry interface point (J9A and J9B).
78-4004177-01 Rev D
General Information
1-5
Laser Link III Mainframe Description, Continued
Fan Assembly
The fan assembly in the Laser Link III Mainframe is controlled by the processor.
Power and signals are routed from jumper cable J6 on the fan assembly to J19 on the
power distribution board. The fan assembly is accessible through a removable panel
on top of the assembly. However, a minimum of 1 RU is needed for this access. See
Chapter 2, Installation, for guidance on selecting a location to install the mainframe.
As shown in the following diagram, as a module is plugged into a particular slot in
the mainframe, a corresponding fan will turn on.
Individual fans are monitored for rotation. If rotation is not detected, a fan alarm is
generated causing the ALARM LED to flash red.
1-6
General Information
78-4004177-01 Rev D
Laser Link Mini-Mainframe Description
Overview
This section contains physical and functional descriptions of the Laser Link MiniMainframe.
Physical Description
The Laser Link Mini-Mainframe fits into a standard 2 RU (3.5 inch/8.89 cm) high by
19- or 23-inch (48 or 58 cm) wide area that is approximately 20 inches (51 cm) deep.
It should be mounted in a cabinet that conforms to ANSI/EIA-310-C standards. The
2 RU space accommodates four half-width modules or two full-width modules.
Mounting brackets (19”) are provided with each unit.
Self-adhesive fiber routing clips are provided to secure fiber routed from modules.
Power Distribution
Main power may be universal AC, -48 V DC, or +24 V DC input. With universal AC
or -48 V DC, the mainframe chassis requires a power supply or converter,
respectively. The power supply is located behind the fan assembly. This unit
accepts the AC or the -48 V DC and performs the required conversion to output +24
V DC to the power distribution board. Should the +24 V DC be available, the
mainframe may be operated without a power supply by applying the voltage
directly to the power distribution board.
Voltage applied to the power distribution board (+24 V DC, 2.5 A maximum) is
routed to the various modules installed in the mainframe. Each module requires this
voltage for normal operation. The power distribution board accepts +24 V DC as the
primary input power (supply A) through the connector labeled J3. The potential is
then applied to the modules through the interface cable provided with each module.
This cable connects the 26-pin interface on the Mini-Mainframe (JXA1) to the rear
panel power/status D connector on the module. The fuse labeled F3 protects the
primary power (supply A).
78-4004177-01 Rev D
General Information
1-7
Laser Link Mini-Mainframe Description, Continued
Redundant power (supply B) is provided in the form of +24 V DC to the terminal
block of the power distribution board. The connecting point, located on the bottom
rear of the assembly, is labeled J1 and accepts +24 V DC through a 4-pin connector.
The redundant load is also load protected (fuse F1).
Alarm Relay
Normally open and normally closed contact points are available on the alarm relay
(J4) of the power distribution board. These interface points allow you to trigger an
external alarm should the general operation alarm of the mainframe toggle to an
alarm state. The pinout is shown in the following table.
Relay Contact
Condition
Pin
NC
Normal
1
NO
Normal
2
NO
Alarm
1
NC
Alarm
2
Common
3
Status Monitoring
Status of housed modules is supplied to users via front panel LEDs.
Status monitoring signals are routed from the rear of the module to the power
distribution board. This is accomplished through connection of the power
distribution board’s (HD DB26F) connectors to the individual modules using the
appropriate interface cables.
Integrated Dual Fan Assembly
A dual fan assembly provides cooling for the Mini-Mainframe.
Note: The dual fan assembly is removable from the front of the mainframe.
1-8
General Information
78-4004177-01 Rev D
List of Abbreviations
Abbreviations
This table lists abbreviations used in this publication.
Abbreviation
Definition
°C
degrees Celsius
°F
degrees Fahrenheit
A
ampere
AC
alternating current
ADDR
address
AMP
amplifier
ANSI
American National Standards Institute
cm
centimeter
COM
common
dB
decibel
dBm
decibel referenced to one milliwatt
dBmV
decibel relative to one millivolt
DC
direct current
DFB
distributed feedback
DWDM
dense wave division multiplexing
EIA
Electronic Industry Association
EMIC
Element Management Interface Card
GHz
gigahertz
GND
ground
kg
kilogram
lb
pound (weight)
LED
light emitting diode
ma
milliampere
78-4004177-01 Rev D
General Information
1-9
List of Abbreviations, Continued
Abbreviation
1-10
Definition
MHz
megahertz
mm
millimeter
mW
milliwatt
nm
nanometer
NC
normally closed
NO
normally open
RCVR
receiver
RF
radio frequency
RPAN
redundant power alarm
RU
rack unit
V
volt
V AC
volts alternating current
V DC
volts direct current
W
watt
XMTR
transmitter
General Information
78-4004177-01 Rev D
Chapter 2
Installation
Overview
Introduction
This chapter describes the installation of the following mainframes:
• Laser Link III Mainframe
• Laser Link Mini-Mainframe
This chapter covers installing the mainframe hardware and making electrical
connections. For information on installing modules in the mainframe, refer to the
installation and operation guides for the specific modules.
In This Chapter
This chapter contains the following sections.
Section
See Page
Laser Link III Mainframe Installation
2-2
Laser Link III Mainframe Electrical Connections
2-5
Laser Link Mini-Mainframe Installation
2-9
Laser Link Mini-Mainframe Electrical Connections
2-10
78-4004177-01 Rev D
Installation
2-1
Laser Link III Mainframe Installation
Overview
This section provides step-by-step instructions for installing the Laser Link III
Mainframe and describes how to make electrical connections. For information on
installing modules in the mainframes, refer to the specific module manual.
For ease of installation and safety, keep the following in mind throughout this
procedure.
CAUTION:
Any time the mounting ears attached to the mainframe are moved (in order to
adjust the depth to which the mainframe is installed) or replaced (in order to
mount the mainframe in a 23-inch bay) the maximum allowable torque for
tightening the screws is 7 to 9 in-lbs. Failure to adhere to this caution may result
in equipment damage.
Elevated Operating Ambient
If the mainframe is installed in a closed or multi-unit rack assembly, the operating
temperature inside the rack may become elevated. Use care to ensure that this
elevated temperature does not exceed the rated temperature for the unit.
Reduced Air Flow
When selecting a location to install the mainframe, follow these guidelines.
• A 1 RU (1.75-inch/4.4 cm) clearance above the uppermost mainframe in the rack is
required for ventilation.
• A 1 RU (1.75-inch/4.4 cm) clearance is necessary if the product mounted above the
mainframe has a solid, flat bottom that would restrict airflow when placed directly
on top of the mainframe.
• Additional mainframes may be directly racked on top of one another, as
ventilation space is integral to the mainframe. However, this particular
configuration does not allow access to, or removal of, the fan assembly.
• An enclosed rack with side panels and rear doors installed will allow for “chimney
effect” airflow to occur. This type of airflow maximizes the convection cooling
characteristics of the mainframe.
Mechanical Loading
When mounting the mainframe in the rack, be aware that uneven loading could
skew the center of gravity, resulting in a hazardous condition.
2-2
Installation
78-4004177-01 Rev D
Laser Link III Mainframe Installation, Continued
Circuit Overloading
When connecting the equipment to the supply circuit be aware of the effect that
overloading of circuits could have on overcurrent protection and supply wiring.
Consideration of equipment nameplate ratings should be used when addressing this
concern.
Reliable Grounding
Reliable grounding of rack-mounted equipment should be maintained. Particular
attention should be given to supply connections other than direct connections to the
branch (e.g. use of power strips).
Tools and Equipment
The following tools and equipment are required for installation.
• #2 Phillips-head screwdriver
Procedure
Follow this procedure to install the Laser Link III Mainframe.
1.
Position the mainframe in the desired location, using two people to support it
until it can be secured with hardware.
Note: The Laser Link III Mainframe is intended for installation and operation
in a restricted access area.
2.
Secure the mainframe into position from the front using four standard rack
screws.
78-4004177-01 Rev D
Installation
2-3
Laser Link III Mainframe Installation, Continued
3.
Install the two support brackets to the mainframe, using screws (A) as shown
below. Do not tighten screws at this time.
Note: The screws (A) are inserted from inside the mainframe, passing
through the bracket and then into the mainframe side panel. These screws
should be put in first.
2-4
4.
Push the support bracket forward until it contacts the rear upright of the
cabinet.
5.
Tighten the support bracket to the cabinet upright, using screws (B).
6.
Tighten the screws (A) holding the support mounting brackets to the side
plates.
7.
Prepare incoming fiber cable through utilization of a fiber management
system or direct connection. In the case of direct connection, provide strain
relief with a cable clamp.
Installation
78-4004177-01 Rev D
Laser Link III Mainframe Electrical Connections
Overview
The Laser Link III Mainframe requires the following electrical connections:
• Power supply
• Power distribution board
Power Supply Connections
Connect the power supplies as described below.
IF the primary input
is…
THEN…
an AC power source
connect the power cord to the mainframe and power
source.
a -48 V DC power
source
apply -48 V DC potential on the rear of the power supply,
using the supplied connectors (and noting polarity). See
Rear Panel Drawing.
Rear Panel Drawing
The following illustration shows the rear panel.
Important: Connect the -48 V potential to the negative terminal. Connect the
ground potential (DC return) to the positive terminal. Wire gauge specifications for
the -48 V DC/13 A input are as follows:
10’ cable: 17 AWG minimum
5’ cable: 20 AWG minimum
78-4004177-01 Rev D
Installation
2-5
Laser Link III Mainframe Electrical Connections, Continued
Power Distribution Board
The power distribution board routes status and powering signals to and from the
housed modules. The illustration below is a general location view of the power
distribution board.
2-6
Installation
78-4004177-01 Rev D
Laser Link III Mainframe Electrical Connections, Continued
Power Distribution Board Connectors
Interfaces J1 through J7 (A and B) provide the connection points for housed modules
to the mainframe. Individual module manuals describe the pins utilized for each
module. Status monitoring (J12), EMIC (J8), primary power (J10) and telemetry
connection points (J9A and J9B) are labeled on the board. The terminal block (J11)
provides connection for the +24 V DC redundant input and for the alarm relay
contacts. Alarm relays may be used to trigger external alarming systems.
Important: Wire gauge specifications for 24 V DC/15 A input are as follows:
10’ cable: 12 AWG minimum
5’ cable: 15 AWG minimum
78-4004177-01 Rev D
Installation
2-7
Laser Link III Mainframe Electrical Connections, Continued
Procedure
Follow these steps to install power supply B.
2-8
1.
Physically secure the alternate (redundant) power supply in a suitable
location near the mainframe.
2.
Connect the provided power interface cable to the redundant supply (female
to male molex connection).
3.
Connect the four wires on the opposite end of the power interface cable to the
terminal block of the power distribution board (J11) as follows:
•
+24 V DC to terminal 1
•
+24 V DC to terminal 2
•
Ground leads to terminals 3 and 4
4.
Ensure the Redundant Power/“B” Alarm switch is to the forward position on
the EMIC module or the ON position on the Status Monitoring module.
5.
Continue to Chapter 3, Setup and Operation.
Installation
78-4004177-01 Rev D
Laser Link Mini-Mainframe Installation
Procedure
Follow these steps to install the Laser Link Mini-Mainframe.
1.
Position the Mini-Mainframe in the desired location, using two people to
support it until it can be secured with hardware.
Note: The Laser Link Mini-Mainframe is intended for installation and
operation in a restricted access area.
2.
Secure the Mini-Mainframe into position from the front using the rack clips
and mounting screws provided. Tighten screws using a #2 Phillips-head
screwdriver.
Note: The Mini-Mainframe is equipped with 19-inch mounting brackets.
3.
Place self-adhesive fiber routing clips in the appropriate position on the MiniMainframe (in front of the module’s right/left side fiber connector, ½ inch in)
to secure the module’s routed fiber.
78-4004177-01 Rev D
Installation
2-9
Laser Link Mini-Mainframe Electrical Connections
Overview
The Laser Link Mini-Mainframe requires electrical connections to the power supply
and the power distribution board.
Power Supply Connections
CAUTION:
Use extreme caution and maintain proper polarity when connecting the supply
voltage to the mainframe. Improper polarity will cause an internal fuse failure.
Failure to adhere to this caution will result in equipment damage.
Connect the power supplies as described below.
IF the primary input…
THEN…
is an AC power source
connect the power cord to the mainframe and power
source.
is a -48 V DC power
source
apply -48 V DC potential using the supplied connector
pins (noting polarity). Use the PEM stud to ground the
Mini-Mainframe to the equipment rack. See Rear Panel
Drawing below for a connection example.
Rear Panel Drawing
The following illustration shows the correct connections for -48 V DC power.
Important: Facing the back of the unit (as shown), the connector pin on the left is
positive, as marked. The connector pin on the right is negative, as marked.
2-10
Installation
78-4004177-01 Rev D
Laser Link Mini-Mainframe Electrical Connections, Continued
Clamp-on Ferrite Bead
The clamp-on ferrite bead provided with the unit is required for EMI shielding.
Refer to the illustrations below and observe the following:
• AC Unit: Place the ferrite bead on the AC power cord in the location shown and
snap it shut.
• DC Unit: Position the ferrite bead in the location shown and place the two -48 V
DC wires in the ferrite bead barrel. Loop the wires around the ferrite bead once
and snap it shut.
78-4004177-01 Rev D
Installation
2-11
Laser Link Mini-Mainframe Electrical Connections, Continued
Power Distribution Board
The power distribution board routes status and powering signals to and from the
housed modules. It is located on the rear of the product.
Procedure
Follow these steps to install power supply B.
1.
Physically secure the alternate (redundant) power supply in a suitable
location near the Mini-Mainframe.
2.
Connect the power supply B interface cable to J1 on the power distribution
board.
3.
Connect the four wires on the opposite end of the power interface cable to
power supply B as follows:
4.
2-12
•
+24 V DC to J1-1 and J1-2
•
Ground leads to J1-3 and J1-4
Continue to Chapter 3, Setup and Operation.
Installation
78-4004177-01 Rev D
Chapter 3
Setup and Operation
Overview
Introduction
This chapter describes how to set up and operate the Laser Link III Mainframe and
the Laser Link Mini-Mainframe. These procedures assume the mainframe is
installed according to the procedures in Chapter 2 of this manual.
In This Chapter
This chapter contains the following sections.
Section
See Page
Section A
Initial Checkout
3-2
Section B
Controls and Indicators
3-7
Section C
Alarms
3-13
78-4004177-01 Rev D
Setup and Operation
3-1
Section A
Initial Checkout
Overview
Introduction
Initial checkout provides a means of proving the operational readiness of the Laser
Link III Mainframe or Laser Link Mini-Mainframe.
In This Section
This section contains the following topics.
Topic
3-2
See Page
Laser Link III Mainframe Initial Checkout
3-3
Laser Link Mini-Mainframe Initial Checkout
3-5
Setup and Operation
78-4004177-01 Rev D
Laser Link III Mainframe Initial Checkout
Introduction
Initial checkout provides a means of proving the operational readiness of the Laser
Link III Mainframe.
Important: Perform this procedure immediately following the installation of the
mainframe and prior to the installation of additional Laser Link components.
Procedure
The following procedure contains individual step-by-step instructions to perform
the initial checkout. Additional operational information is provided following the
step-by-step instructions that may be useful as the unit remains in service over time.
This procedure is valid for mainframes containing either the User Panel or the
Element Management Interface Card (EMIC).
Follow these steps to perform the initial checkout procedure.
1.
IF the mainframe…
THEN…
is equipped with a redundant power supply
perform steps 2 and 3.
is NOT equipped with a redundant power
supply
go to step 4.
2.
If a redundant power supply is connected to the mainframe, place the
Redundant Power/“B” Alarm switch on the Status Monitoring module in the
ON position or place the Redundant Power/“B” Alarm switch on the EMIC
module in the forward position.
3.
Apply power to the mainframe. On the Status Monitoring/EMIC module:
•
PWR A LED is lit green
•
PWR B LED is lit green
•
ALARM LED is extinguished
78-4004177-01 Rev D
Setup and Operation
3-3
Laser Link III Mainframe Initial Checkout, Continued
4.
If the Laser Link III Mainframe is not equipped with a redundant power
supply, perform the following steps; otherwise, the initial checkout for a
mainframe with a redundant power supply is already complete.
a. Place the Redundant Power/“B” Alarm switch on the Status Monitoring
module to the OFF position. If the Laser Link III Mainframe is equipped
with an EMIC, position the Redundant Power/“B” Alarm switch to the
back position.
b. Apply power to the Laser Link III Mainframe.
On the Status Monitoring/EMIC module:
3-4
•
PWR A LED is lit green
•
PWR B LED is extinguished
•
ALARM LED is extinguished
Setup and Operation
78-4004177-01 Rev D
Laser Link Mini-Mainframe Initial Checkout
Introduction
Initial checkout provides a means of proving the operational readiness of the Laser
Link Mini-Mainframe.
Important: Perform this procedure immediately following the installation of the
mainframe and prior to the installation of additional Laser Link components.
Procedure
The following procedure contains individual step-by-step instructions to perform
the initial checkout.
IF the mainframe…
1.
THEN…
is equipped with a redundant power perform steps 2 and 3.
supply
is NOT equipped with a redundant
power supply
2.
go to step 4.
Clear the power supply B alarm, if present.
Note: If power supply B is disconnected with power supply A present, the
Mini-Mainframe will automatically indicate a power supply B alarm. Clear
the alarm by turning off power supply A.
3.
Apply power to the mainframe. On the Status Display Panel:
•
PWR A LED is lit green
•
PWR B LED is extinguished
•
ALARM LED is extinguished
78-4004177-01 Rev D
Setup and Operation
3-5
Laser Link Mini-Mainframe Initial Checkout, Continued
4.
If the Laser Link Mini-Mainframe is not equipped with a redundant power
supply, perform the following step; otherwise, the initial checkout for a MiniMainframe with a redundant power supply is already complete.
Apply power to the Laser Link Mini-Mainframe.
On the Status Display Panel:
3-6
•
PWR A LED is lit green
•
PWR B LED is extinguished
•
ALARM LED is extinguished
Setup and Operation
78-4004177-01 Rev D
Section B
Controls and Indicators
Overview
Introduction
This section describes the controls and indicators of the Laser Link III Mainframe
and Laser Link Mini-Mainframe.
In This Section
This section contains the following topics.
Topic
See Page
Laser Link III Mainframe Controls and Indicators
3-8
Laser Link Mini-Mainframe Controls and Indicators
3-11
78-4004177-01 Rev D
Setup and Operation
3-7
Laser Link III Mainframe Controls and Indicators
Overview
This illustrations show the Laser Link III Mainframe Status Monitoring module and
EMIC module indicators and test points.
3-8
Setup and Operation
78-4004177-01 Rev D
Laser Link III Mainframe Controls and Indicators, Continued
Status Monitoring Module
The following table describes the indicators and test points on the Status Monitoring
module.
Indicator/Test Point
PWR A LED
Description
Indicates operational status of power supply A:
•
Green indicates proper operation
•
Red indicates a power supply A malfunction (voltage
too high or too low)
Note: Function is controlled by position of the Redundant
Power/“B” Alarm switch.
PWR B LED
Indicates operation of a redundant power supply:
•
Green indicates proper operation
•
Red indicates a malfunction (voltage too high or too
low)
Note: If a redundant power supply is not present, the
LED will be extinguished. Function is controlled by
position of the Redundant Power/“B” Alarm switch.
ALARM LED
Indicates alarm condition:
•
Normally extinguished
•
Red indicates the presence of a general alarm condition
with the power supplies or a housed module
•
Flashing red indicates fan failure
+24 V A Test Point
Test point for the output of power supply A.
GND Test Point
Ground point.
+24 V B Test Point
Test point for the output of power supply B.
Ground Symbol
Plug-in for electrostatic wrist strap. Use of an electrostatic
wrist strap is recommended whenever plug-in modules
are going to be removed.
78-4004177-01 Rev D
Setup and Operation
3-9
Laser Link III Mainframe Controls and Indicators, Continued
EMIC Module
The following table describes the indicators and test points on the EMIC module.
Indicator/Test Point
PWR A LED
Description
Indicates operational status of power supply A:
•
Green indicates proper operation
•
Red indicates a power supply A malfunction (voltage
too high or too low)
Note: Function is controlled by position of the Redundant
Power/“B” Alarm switch.
PWR B LED
Indicates operation of a redundant power supply:
•
Green indicates proper operation
•
Red indicates a malfunction (voltage too high/too low)
Note: If a redundant power supply is not present, the
LED will be extinguished. Function is controlled by
position of the Redundant Power/“B” Alarm switch.
ALARM LED
3-10
Indicates alarm condition:
•
Normally extinguished
•
Red indicates the presence of a general alarm condition
with the power supplies or a housed module
•
Flashing red indicates fan failure
ADDR. LED
Illuminates green as element management system
software polls the EMIC. Expect intermittent illumination.
STATUS LED
Indicates operational status of the EMIC:
•
Normally extinguished
•
Red indicates a malfunction
+24 V A Test Point
Test point for the output of power supply A.
GND Test Point
Ground point.
+24 V B Test Point
Test point for the output of power supply B.
Ground Symbol
Plug-in for electrostatic wrist strap. Use of an electrostatic
wrist strap is recommended whenever plug-in modules
are going to be removed.
Setup and Operation
78-4004177-01 Rev D
Laser Link Mini-Mainframe Controls and Indicators
Overview
This section describes operational information pertaining to the Status Display Panel
that will be useful during the course of normal operation.
The following illustration shows the Status Display Panel indicators and test points.
78-4004177-01 Rev D
Setup and Operation
3-11
Laser Link Mini-Mainframe Controls and Indicators, Continued
Status Display Panel
The following table describes the indicators and test points on the Status Display
Panel for all Mini-Mainframes.
Indicator/Test Point
POWER A LED
POWER B LED
Description
Indicates operational status of power supply A:
•
Green indicates proper operation
•
Red indicates a power supply A malfunction (voltage
too high or too low)
Indicates operation of a redundant power supply:
•
Green indicates proper operation
•
Red indicates a power supply B malfunction (voltage
too high or too low)
Note: If a redundant power supply is not present, the
LED will be extinguished.
ALARM LED
3-12
Indicates alarm condition:
•
Normally extinguished
•
Red indicates the presence of a general alarm condition
with the power supplies or a housed module
•
Flashing red indicates fan failure
GND Test Point
Ground point.
+24 V A Test Point
Test point for the output of power supply A.
+24 V B Test Point
Test point for the output of power supply B.
Ground Symbol
Plug-in for electrostatic wrist strap. Use of an electrostatic
wrist strap is recommended whenever plug-in modules
are going to be removed.
Setup and Operation
78-4004177-01 Rev D
Section C
Alarms
Overview
Introduction
The Laser Link III Mainframe and Laser Link Mini-Mainframe have module and
mainframe level alarms (also known as vital signs) that are available on the power
distribution board’s telemetry connector(s) for interface with element management
systems. The Laser Link modules are capable of producing alarms that are reported
at the telemetry connector(s) by logic signals.
This section contains a summary of vital sign logic signals grouped by module type.
In This Section
This section contains the following topics.
Topic
See Page
Alarm Tables
3-14
Telemetry Connectors
3-25
78-4004177-01 Rev D
Setup and Operation
3-13
Alarm Tables
1310 nm Forward Transmitters Alarm Table
Models
(front panel
label)
LLII
LLII+
LLII
LLII SP
LLII+
LLII+LP
LLII+SP
LLII+HP
3-14
Description
Laser Link II
identified by 2.4 mm
pigtail
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2
No connection on this
module
No connection
#3/#12
Laser Temp./Laser Bias –
alarm when laser
temperature or laser bias
current is out of range
0 V = normal
5 V = alarm
#4/#4
Global Alarm – any above
condition and +5 or -5 V
DC fails
24 V = normal
0 V = alarm
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
No connection on this
module
No connection
#3/#12
Laser Temp./Laser Bias –
alarm when laser
temperature or laser bias
current is out of range
0 V = normal
5 V = alarm
#4/#4
Global Alarm – any above
condition and +5 or -5 V
DC fails
24 V = normal
0 V = alarm
#1/#5
Laser Link II
transmitters with 900
mm pigtail or rear
panel optical
connector
#2
Setup and Operation
78-4004177-01 Rev D
Alarm Tables, Continued
Models
(front panel
label)
LLII
LLII+SP
LLII+HP
Description
Vital Sign Description
Logic
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Output Power
1 V/mW
#3/#12
Laser Temp./Laser Bias –
alarm when laser
temperature or laser bias
current is out of range
0 V = normal
5 V = alarm
#4/#4
Global Alarm – any above
condition
24 V = normal
0 V = alarm
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Output Power
1 V/mW
#3/#12
Laser Bias Current
1 V/50 mA
#4/#4
Global Alarm – optical
power – 25%, “A” supply
fails
24 V = normal
0 V = alarm
Laser Link LLTxxxxD dual RF input
LLT MP F7D- 750 and 870 MHz
(two RF inputs) rear
H7D
LLT HP I7D- panel optical
connector and fan,
J7D
front panel slope
LLT LP A8Dand attenuator
E8D
adjust controls,
LLT MP F8D- power and laser
H8D
status LEDs
LLT HP I8DJ8D
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Output Power
1 V/mW
#3/#12
Laser Bias Current
1 V/50 mA
#4/#4
Global Alarm – +5 V DC
24 V = normal
fails, laser temp ±5%, laser 0 V = alarm
bias current ±10%, optical
power – 25%, “A” supply
fails
78-4004177-01 Rev D
Setup and Operation
LLT LP A7E7
LLT MP F7H7
LLT HP I7-J7
Laser Link II
transmitters
identified with a
serial number
starting with 45 and
rear panel optical
connector with fan,
front panel gain
adjust
Vital Sign
VS#/Pin#
Laser Link LLT
transmitters, single
RF input 750 MHz,
rear panel optical
connector with fan,
front panel slope
and attenuator
adjust controls,
power and laser
status LEDs
LLT LP A7DE7D
3-15
Alarm Tables, Continued
Models
(front panel
label)
Description
LLT LP A7DE7D
Laser Link LLTxxxxD, front panel
optical connector,
LLT MP F7Ddual RF input 750
H7D
and 870 MHz (two
LLT HP I7D- RF inputs) rear panel
fan, front panel
J7D
slope and attenuator
LLT LP A8D- adjust controls, six
E8D
LEDs
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Output Power
1 V/mW
#3/#12
Laser Bias Current
1 V/50 mA
#4/#4
Global Alarm – +5 V DC
24 V = normal
fails, laser temp ±5%, laser 0 V = alarm
bias current ±20%, optical
power – 25%, “A” supply
fails
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Output Power
1 V/mW
#3/#12
Laser Bias Current
1 V/50 mA
#4/#4
24 V = normal
Global Alarm – +5 V DC
fails, laser temp ±5%, laser 0 V = alarm
bias current ±20%, optical
power – 25%, “A” supply
fails, fan failure
LLT MP F8DH8D
LLT HP I8DJ8D
XMTR
LLTIII-3-15
3-16
Laser Link halfwidth 45-870 MHz
Setup and Operation
78-4004177-01 Rev D
Alarm Tables, Continued
Models
(front panel
label)
ELLT-3-14
Description
Laser Link fullwidth 45-870 MHz,
front panel optical
connector, front
panel slope and
attenuator adjust
controls
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Output Power
1 V/mW
#3/#12
Laser Bias Current
1 V/50 mA
#4/#4
Global Alarm – +5 V DC
24 V = normal
fails, laser temp ±5%, laser 0 V = alarm
bias current ±20%, optical
power – 25%, “A” supply
fails
1550 nm Forward Transmitters Alarm Table
Models
(front panel
label)
XMTR
LEMT-P-10
LEMT-S-10
LEMT-I-10
Description
Laser Link singlewidth transmitter,
dual outputs
78-4004177-01 Rev D
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
#1/#15
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#5
Optical Output Power
1 V/mW
#3/#6
Laser Bias Current
1 V/50 mA
#4/#7
Global Alarm – +5 V DC
24 V = normal
fails, laser temp ±5%, laser 0 V = alarm
bias current ±20%, optical
power – 25%, “A” supply
fails, fan failure
Setup and Operation
3-17
Alarm Tables, Continued
1310 nm Reverse Transmitters Alarm Table
Models
(front panel
label)
XMTR
5-200 MHz
LLRT
5-210 MHz
3-18
Description
Laser Link II return
transmitter, rear
panel optical
connector
Laser Link LLRT 5210 MHz return
transmitter, front
panel optical
connector, rear panel
fan
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2
No connection on this
module
No connection
#3/#12
Laser Temp./Laser Bias –
alarm when laser
temperature or laser bias
current is out of range
0 V = normal
5 V = alarm
#4/#4
Global Alarm – any above
condition and +5 or -5 V
DC fails
24 V = normal
0 V = alarm
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Output Power
1 V/mW
#3/#12
Laser Bias Current
1 V/50 mA
#4/#4
Global Alarm – +5 V DC
24 V = normal
fails, laser temp ±5%, laser 0 V = alarm
bias current ±20%, optical
power – 25%, “A” supply
fails
Setup and Operation
78-4004177-01 Rev D
Alarm Tables, Continued
Return Receivers Alarm Table
Models
(front panel
label)
RCVR
5-200 MHz
LLRR
5-210 MHz
LLDR
5-210 MHz
Description
Laser Link II fullwidth receiver
module, 5-200 MHz,
rear panel optical
connector
Laser Link halfwidth 5-210 MHz
return receiver, front
panel optical
connector
Laser Link halfwidth 5-210 MHz
receiver, front panel
optical connector
78-4004177-01 Rev D
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Receive Power
Alarm (< -17 dBm)
0 V = normal
5 V = alarm
#3
No connection
No connection
#4/#4
Global Alarm – any above
condition
24 V = normal
0 V = alarm
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Receive Power
1 V/mW
#3/#12
Loss of RF Alarm (< +18
dBmV total power)
5 V = normal
0 V = alarm
#4/#4
Global Alarm – optical
receive power < -17 dBm,
“A” supply fails
24 V = normal
0 V = alarm
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Receive Power
1 V/mW
#3
No connection
No connection
#4/#4
Global Alarm – optical
receive power < -17 dBm,
“A” supply fails
24 V = normal
0 V = alarm
Setup and Operation
3-19
Alarm Tables, Continued
Models
(front panel
label)
ELLRR
5-210 MHz
Description
Laser Link halfwidth 5-210 MHz
receiver, front panel
optical connector
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Receive Power
1 V/mW
#3
No connection
No connection
#4/#4
Global Alarm – optical
receive power < -17 dBm,
“A” supply fails
24 V = normal
0 V = alarm
Vital Sign Description
Logic
Amplifier Modules Alarm Table
Models
(front panel
label)
Description
Vital Sign
VS#/Pin#
AMP/4
Laser Link quad (4
outputs)
50-600 MHz and
50-750 MHz
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
AMP/FF
Feedforward (single
output) 50-550 MHz
amplifier
#2
No connection
No connection
#3
No connection
No connection
#4/#4
Global Alarm – “A”
supply fails
24 V = normal
0 V = alarm
AMP Dual
3-20
Laser Link dual amp
(2 outputs),
50-750 MHz and
50-870 MHz
Setup and Operation
78-4004177-01 Rev D
Alarm Tables, Continued
Models
(front panel
label)
EDFA
Description
Laser Link
Vital Sign
VS#/Pin#
LLOA-C20BM
Logic
#1/#15
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#5
Optical Receive Power
0 V = -20 dBm
2.5 V = -5 dBm
5.0 V = +10dBm
#3/#6
Optical Power Out
0 V = 6 dBm
2.4 V = 30 dBm
2.6 V = 6 dBm
5.0 V = 30 dBm
#4/#7
Global Alarm – RPAN
high, optical power alarm
out of tolerance, laser bias
alarm high, laser temp
high, fan failure
24 V = normal
0 V = alarm
Vital Sign Description
Logic
LLOA-C14BM
LLOA-C17BM
Vital Sign Description
LLOA-C22BM
Forward Receivers Alarm Table
Models
(front panel
label)
RCVR
50-550 MHz
RCVR
EAW32
50-750 MHz
Description
Vital Sign
VS#/Pin#
Laser Link II fullwidth receiver
module, 50-550
MHz, rear panel
optical connector
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Receive Power
Alarm (< -17 dBm)
0 V = normal
5 V = alarm
Laser Link II fullwidth receiver
module, 50-750
MHz, rear panel
optical connector
#3
No connection
No connection
#4/#4
Global Alarm – any above
condition
24 V = normal
0 V = alarm
78-4004177-01 Rev D
Setup and Operation
3-21
Alarm Tables, Continued
Models
(front panel
label)
LLFR
Description
Laser Link fullwidth 50-750 MHz
and 45-870 MHz
forward receiver,
front panel optical
connector
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Receive Power
1 V/mW
#3/#12
Loss of RF Alarm (< +31
dBmV total power)
5 V = normal
0 V = alarm
#4/#4
Global Alarm – optical
receive power < -10 dBm,
“A” supply fails
24 V = normal
0 V = alarm
Vital Sign Description
Logic
1550 nm DFB Forward Transmitters Alarm Table
Models
(front panel
label)
LLNT
3-22
Description
Laser Link LLNT 750
MHz and 870 MHz
1550 nm transmitter
for DWDM
applications
Vital Sign
VS#/Pin#
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Output Power
1 V/mW
#3/#12
Laser Bias Current
1 V/50 mA
#4/#4
Global Alarm – +5 V DC
24 V = normal
fails, laser temp ±5%, laser 0 V = alarm
bias current ±10%, optical
power – 25%, “A” supply
fails
Setup and Operation
78-4004177-01 Rev D
Alarm Tables, Continued
1550 nm DFB Reverse Transmitters Alarm Table
Models
(front panel
label)
LLNTR
Description
Laser Link LLNTR 5210 MHz 1550 nm
reverse transmitter
for DWDM
applications
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Optical Output Power
1 V/mW
#3/#12
Laser Bias Current
1 V/50 mA
#4/#4
Global Alarm – +5 V DC
24 V = normal
fails, laser temp ±5%, laser 0 V = alarm
bias current ±10%, optical
power – 25%, “A” supply
fails
Switch Module Alarm Table
Models
(front panel
label)
LLRS
Description
Laser Link LLRS RF
switch, half-width
module
78-4004177-01 Rev D
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
#2/#11
Switch Mode
0 V = auto mode
5 V = local mode
#3/#12
Switch position “x” port
connected to common
port
0V=A
5V=B
#4/#4
Global Alarm – “A”
supply fails switch
position B, switch failure
24 V = normal
0 V = alarm
Setup and Operation
3-23
Alarm Tables, Continued
Block Converters Alarm Table
Models
(front panel
label)
Description
Vital Sign
VS#/Pin#
Vital Sign Description
Logic
LLUC-65
LLDC-65
Laser Link block
upconverter and
downconverter,
5-65 MHz
#1/#5
Redundant Power Alarm
– active when module
detects loss of +24 V DC
“A” supply
0 V = normal
+5 V = alarm
LLUC-40
LLDC-40
Laser Link block
upconverter and
downconverter,
5-42 MHz
#4/#4
Global Alarm – loss of
phase lock for any PLL,
fan failure, “A” supply
fails
24 V = normal
0 V = alarm
3-24
Setup and Operation
78-4004177-01 Rev D
Telemetry Connectors
J9A and J9B Connector Pinout
The following table shows the pinout data for J9A and J9B, the telemetry connectors,
on the Laser Link III Mainframe.
J9A Pin#
Connection
J9B Pin #
Connection
1
GND
1
GND
2
Analog 1 Slot 7A
2
Analog 1 Slot 7B
3
Analog 2 Slot 7A
3
Analog 2 Slot 7B
4
RPAN Slot 7A
4
RPAN Slot 7B
5
Analog 1 Slot 6A
5
Analog 1 Slot 6B
6
Analog 2 Slot 6A
6
Analog 2 Slot 6B
7
RPAN Slot 6A
7
RPAN Slot 6B
8
Analog 1 Slot 5A
8
Analog 1 Slot 5B
9
Analog 2 Slot 5A
9
Analog 2 Slot 5B
10
RPAN Slot 5A
10
RPAN Slot 5B
11
No Connect
11
No Connect
12
RPAN Slot 4A
12
RPAN Slot 4B
13
+24 V A Supply
13
+24 V A Supply
14
Analog 1 Slot 1A
14
Analog 1 Slot 1B
15
Analog 2 Slot 1A
15
Analog 2 Slot 1B
16
RPAN Slot 1A
16
RPAN Slot 1B
17
Analog 1 Slot 2A
17
Analog 1 Slot 2B
18
Analog 2 Slot 2A
18
Analog 2 Slot 2B
19
RPAN Slot 2A
19
RPAN Slot 2B
20
Analog 1 Slot 3A
20
Analog 1 Slot 3B
21
Analog 2 Slot 3A
21
Analog 2 Slot 3B
22
RPAN Slot 3A
22
RPAN Slot 3B
23
Analog 1 Slot 4A
23
Analog 1 Slot 4B
24
Analog 2 Slot 4A
24
Analog 2 Slot 4B
25
+24 V B Supply
25
+24 V B Supply
78-4004177-01 Rev D
Setup and Operation
3-25
Chapter 4
Customer Information
Overview
Introduction
If you have technical questions, call Cisco Services for assistance. Follow the menu
options to speak with a service engineer.
Access your company's extranet site to view or order additional technical publications.
For accessing instructions, contact the representative who handles your account. Check
your extranet site often as the information is updated frequently.
78-4004177-01 Rev D
Customer Information
4-1
Cisco Systems, Inc.
5030 Sugarloaf Parkway, Box 465447
Lawrenceville, GA 30042
678 277-1120
800 722-2009
www.cisco.com
This document includes various trademarks of Cisco Systems, Inc. Please see the Notices
section of this document for a list of the Cisco Systems, Inc. trademarks used in this
document.