LABORATORY EVALUATIONS OF CORROSION PREVENTION COMPOUNDS FOR AIRCRAFT Feng Gui1, Keith Furrow2, Jackie Williams2, Kevin Cooper2, Robert G. Kelly1 1 Department of Materials Science and Engineering University of Virginia P. O. Box 400475 Charlottesville, VA 22904 2 Luna Innovations 701 Charlton Ave. Charlottesville, VA 22903 Submitted to: Garth Cooke Program Manager NCI Information Systems Fairborn, OH Index 1 2 3 4 5 Introduction ......................................................................................................................................... 4 1.1 Fundamentals of Corrosion Prevention Compounds .................................................................. 4 1.2 Objectives of the Current Work..................................................................................................... 5 1.3 CPC Tested..................................................................................................................................... 5 Design of Test Protocols ...................................................................................................................... 6 2.1 Test Selection ................................................................................................................................. 6 2.1.1 Solution Composition and Exposure Modes ......................................................................... 6 2.1.2 Protective Film Formation..................................................................................................... 7 2.1.3 Inhibitor Leaching and Electrolyte Modification ................................................................. 7 2.1.4 Surface Chemistry .................................................................................................................. 7 2.1.5 CPC Wicking Ability .............................................................................................................. 8 Sample Preparation and Test Methods ............................................................................................. 9 3.1 Sample Preparation ....................................................................................................................... 9 3.1.1 Aluminum Alloy Sample Preparation ................................................................................... 9 3.1.2 CPC Application Method ....................................................................................................... 9 3.2 Test Methods................................................................................................................................ 10 3.2.1 Exposure Methods................................................................................................................ 10 3.2.2 Electrochemical Impedance Spectroscopy .......................................................................... 10 3.2.3 Cyclic Potentiodynamic Polarization................................................................................... 10 3.2.4 FTIR ..................................................................................................................................... 10 3.3 Surface Property Measurements................................................................................................. 10 3.4 Wicking Tests............................................................................................................................... 12 3.4.1 Assembly Of Wicking Specimens......................................................................................... 12 3.4.2 Wicking Into Wet And Dry Simulated Lap Joints............................................................... 13 3.4.3 Fiber Optic Sensor Instrumentation and Data Reduction.................................................. 14 3.4.4 Wicking Into CPC-Treated Lap Joints ................................................................................ 16 Results................................................................................................................................................. 17 4.1 Constant Immersion .................................................................................................................... 17 4.1.1 AA7075-T6............................................................................................................................ 17 4.1.2 Clad AA2024-T3................................................................................................................... 18 4.1.3 Precorroded AA7075-T6 ...................................................................................................... 19 4.1.4 Precorroded Clad AA2024-T3 ............................................................................................. 20 4.2 Alternate immersion .................................................................................................................... 20 4.2.1 AA7075-T6............................................................................................................................ 20 4.2.2 Clad AA2024-T3................................................................................................................... 21 4.2.3 Precorroded AA7075-T6 ...................................................................................................... 22 4.2.4 Precorroded Clad AA2024-T3 ............................................................................................. 22 4.3 Proof of Remnant CPC After Apparent Loss of Film ................................................................ 23 4.3.1 FTIR ..................................................................................................................................... 23 4.3.2 Cyclic Polarization Scan ...................................................................................................... 24 4.4 Leaching ...................................................................................................................................... 25 4.5 Surface Properties of CPC, AA2024-T3 and Al2O3 .................................................................... 26 4.6 Water Displacement..................................................................................................................... 27 4.7 Water Emulsification................................................................................................................... 29 4.8 Wicking into Dry Lap Joints ....................................................................................................... 31 4.9 Wicking into Wet Lap Joints ....................................................................................................... 35 4.10 Wicking into CPC-Treated Lap Joints........................................................................................ 42 Discussion ........................................................................................................................................... 44 5.1 Testing Protocol Development For Boldly Exposed Surface..................................................... 44 5.1.1 Assessment Vs. Prediction of CPC Performance by Test Protocol .................................... 44 2 6 7 8 9 5.1.2 Relative Corrosivity of Exposure Protocols......................................................................... 47 5.1.3 Ranked Performance of CPC............................................................................................... 48 5.1.4 Failure Mode ........................................................................................................................ 48 5.2 Precorrosion Effects .................................................................................................................... 49 5.2.1 Effect of Prior Corrosion on Effectiveness of CPC for Boldly Exposed Aluminum ......... 49 5.3 Wicking ........................................................................................................................................ 50 5.3.1 CPC Surface Chemistry ....................................................................................................... 50 5.3.2 Wicking Into Dry and Wet Lap Joints................................................................................. 54 5.3.3 Wicking Into a Pretreated Lap Joint ................................................................................... 56 Conclusions......................................................................................................................................... 57 6.1 Development of Quantitative Testing Protocol........................................................................... 58 6.2 Relative Effectiveness of Several Commercial CPC................................................................... 59 6.3 Surface Thermodynamic Properties and Wicking into Occluded Regions ............................... 59 Future Work ...................................................................................................................................... 60 Acknowledgements ............................................................................................................................ 60 Appendix—Kruss Report ................................................................................................................. 61 3 1 1.1 Introduction Fundamentals of Corrosion Prevention Compounds Corrosion management of aircraft is beginning to replace “find-it-fix-it” philosophies in both the commercial and defense sectors. Successful implementation of corrosion management requires a range of technologies. Corrosion prevention compounds (CPC) are materials that can both prevent new corrosion sites from forming and, more importantly, suppress any corrosion that has initiated. It is important to recognize that CPC are applied as a post-production treatment to provide cost-effective, temporary corrosion protection and to control existing corrosion. CPC have been used on aircraft for many years as a relatively inexpensive method of combating corrosion. [1] One of the main advantages of using CPC is that little or no preparation of the affected site is required before application. Consequently, these CPC can be used at the field maintenance level instead of requiring application at the depot. Thus, corrosion can be suppressed early on, before substantial structural damage can occur. CPC are not meant to replace high-performance coating systems, but they can be effective for on-site repair of coated regions that may have been damaged or degraded, for extending the service life of a coating, and for protecting regions of aircraft that did not receive corrosion prevention treatments during original manufacture. CPC can, in principle, serve a key function as a component of a corrosion management strategy. Effective CPC function via one or more of four mechanisms: (a) blocking film formation, (b) kinetic inhibition of surface reactions, (c) water displacement, or (d) local electrolyte modification. Film formers produce a covering on the surface to be protected that prevents the formation of an aqueous phase at the metal surface. Without such a phase, the electrochemical reactions required for corrosion cannot occur. Inhibitors that directly impede the electrochemical kinetics can be added to CPC. Some CPC seek to actively remove moisture from a metal surface, with this water displacement serving to stop any corrosion that could occur. Finally, CPC can function by altering the chemical conditions of any aqueous phase that does form at a surface by, for example, buffering the pH to a less aggressive range or reacting with aggressive species that my be present. 4 In general, CPC development and deployment has been ad hoc. Most commercially available CPC were in fact developed for other uses, such as lubrication. Due to the cost involved, corrosion inhibitors have been only sporadically used in CPC, although they are more widely applied to primers. Unfortunately, many effective corrosion inhibitors are environmentally damaging and/or have health risks for worker exposure. In addition, recent work [2] has shown that the currently available CPC are not effective at inhibiting corrosion inside occluded regions on aircraft (e.g., lap joints). These types of sites are very often the location of some of the more severe corrosion on aircraft, affecting repair costs and time, fleet readiness, and potentially safety of flight. To be effective in occluded regions, the CPC requires the ability to wick into the occluded region and perform some corrosion inhibition. 1.2 Objectives of the Current Work The current work has two primary objectives: (a) to develop a quantitative testing protocol that allows both discrimination of CPC performance and guidance on selection of the most effective CPC for a particular component, and (b) to test the effectiveness of several commercial CPC on both boldly exposed and occluded regions on aircraft. 1.3 CPC Tested There are several different types of CPC. These CPC were selected not only to cover the range of CPC types, but also to allow comparison with exposure work being performed by S&K Technologies in Dayton, OH. The classification of CPC given in the following table is based upon the manufacturer self-reporting. 5 Table 1 CPC selected for testing in Year 1. *Water Displacing Hard Film (WDHF), **Water Displacing Soft Film (WDSF), ***Non-Water Displacing Soft Film (NWDSF) CPC Specifications Color of Liquid Description Film Type General purpose, heavy Amlguard Mil-C-85054 duty, durable, hard film Dark Blue/Green forming CPC Dinitrol ® AV30 Dinitrol® AV8 None Light Brown BMS 3-23 Light Brown Penetration, inhibiting High penetration, corrosion inhibiting BMS 3-23 LPS3 Self-healing, Dark Yellow dry film) WDSF**(waxy) WDSF (non tacky) anti-sling NWDSF***(self lubricant, high VOC BMS 3-29 2 corrosion WDHF*(hard, healing waxy film) Design of Test Protocols 2.1 2.1.1 Test Selection Solution Composition and Exposure Modes As mentioned above, one of the project objectives is to develop an effective test for corrosion prevention and abatement compounds used for both boldly exposed and occluded regions on aircraft. In the past several years, work at the University of Virginia on the chemical conditions inside occluded regions has led to the development of the Lap Joint Simulation Solution (LJSS)[3]. This solution has been shown to mimic the occluded solution inside lap joints. The corrosion morphology observed after exposure corresponded to the attack observed in the field. Therefore, in this project, LJSS was used as the sample exposure environment. 6 The two most widely used aerospace alloys, AA7075-T6 and clad AA2024-T3, were the materials investigated. Both constant immersion (CI) and alternate immersion (AI) were used to study the degradation of the CPC protection. Although AI is generally found to be more aggressive, CI is a more straightforward exposure method. 2.1.2 Protective Film Formation As a non-destructive inspection method, electrochemical impedance spectroscopy (EIS) has been widely used to study organic coatings on metals to get complementary information to that obtained by traditional techniques for characterizing the behavior of organic coatings in corrosive environments [4]. In this work, EIS was used to investigate the ability of CPC to form and maintain a protective film on aluminum alloys in LJSS. The interfacial impedance was used to characterize the protective film performance. 2.1.3 Inhibitor Leaching and Electrolyte Modification One means by which CPC may function is via the release of corrosion inhibitors. Any inhibitors that may be present in CPC film could leach into the LJSS solution to enhance the protection of metal from corrosion. To study the ability of the CPC tested to leach inhibitors, each CPC was applied onto Pt- coated Nb mesh and then exposed to a small volume of LJSS. The mesh was exposed to the LJSS, and the effects of the leachate solution on the interfacial impedance of clad AA2024-T3 were investigated by EIS. As with inhibitor leaching, electrolyte modification from CPC could be another factor to influence the protection of metal in corrosion environment. The release of species that could change the pH or the buffering capacity could act to make the local solution more benign. Thus, for each of leaching solutions, the pH values were monitored periodically. 2.1.4 Surface Chemistry The purpose of this portion of the project was to develop test methods that will quantify the ability of CPC to penetrate lap joints and displace water. The testing evaluated the surface properties of the CPC and their ability to form water-in-oil emulsions. Accompanying the surface property testing, the ability of the CPC to penetrate simulated lap joints was measured using embedded fiber optic sensors. The penetration tests were conducted on pristine specimens, with and without previously entrained water. 7 The surface free energy and contact angle are thermodynamic properties describing, in part, the ability of a fluid to wet a surface. Metals and metal oxides have high-energy surfaces, whereas oil presents a low energy surface. Therefore the oil-based CPC would be expected to easily wet the dry lap joint surfaces based on thermodynamic considerations. The presence of entrained water in the lap joint complicates the wetting process, but thermodynamics can again be used to assess the feasibility of water displacement. Thermodynamic surface properties do not indicate the rate of penetration or the rate of water displacement, only whether or not these processes will occur spontaneously. The rates need to be measured in a wicking test. The challenge is to relate macroscopic wicking effects to the interfacial properties of the materials involved and to learn how to manipulate the latter to achieve the desired effects. [5] The surface thermodynamic property testing was contracted to Kruss—a manufacturer of surface chemistry instrumentation. The data and discussion are condensed from the Kruss report, which is included in the appendix. The testing specifically evaluated: 1. The surface properties of the CPC, and the surfaces to which they are applied. 2. The ability of various CPC to displace water from surfaces to which they are applied (both in an equilibrium sense, and in a dynamic sense). 3. The propensity of various CPC to form emulsions with water (which might be found to be an advantage, in that it gives the displaced water somewhere to reside, away from the protected surface). 2.1.5 CPC Wicking Ability The CPC ability to penetrate simulated lap joints was measured using embedded fiber optic sensors that could detect the presence of water or CPC. The penetration tests were conducted on pristine joints, with and without entrained water. Two types of simulated joints were used. The first consisted of an aluminum face sheet and a Plexiglas face sheet that allowed visual observation of the wicking process. The second simulated lap joint consisted of two AA2024-T3 face sheets. CPC was dropped at the edge of the faying surfaces and allowed to wick into the joint. The response of the fiber optic sensor was monitored as a function of time. When the Plexiglas face sheet was used, the sensor response was verified with visual observations. The last set of wicking tests involved treating the joint with CPC and then soaking the joint in water. Embedded sensors monitored the ingress of any water into the joint. 8 3 Sample Preparation and Test Methods 3.1 Sample Preparation 3.1.1 Aluminum Alloy Sample Preparation The materials used in this project are shown in the table below. Materials Sample Thickness Size Clad AA 2024-T3 0.072” 3”×3” AA 7075-T6 0.090” 3” ×3” All panel samples were degreased in an ultrasonic bath with acetone for 5 minutes, methanol for 5 minutes, rinsed in high purity water, and then dried in the air. All lap joint coupons were treated as panels before they are assembled into lap joints. 3.1.2 CPC Application Method All CPC were applied on the samples by spraying. Figure 1 is the schematic drawing for spraying: Release spraying button here Figure 1. Schematic drawing for CPC applied on samples After CPC applied, all samples were allowed to dry for overnight before expose to the solution. 9 3.2 3.2.1 Test Methods Exposure Methods Constant immersion samples were immersed in the LJSS by hanging the fully exposed samples via a nylon line. Alternate immersion cycles involved immersion in the LJSS solution for 12 hours followed by drying in air for 12 hours. Both pristine and precorroded samples were used. The precorroded samples were exposed in either NaCl or LJSS for one week before CPC application, while the pristine samples were not exposed immediately after the washing process. 3.2.2 Electrochemical Impedance Spectroscopy Electrochemical Impedance Spectroscopy (EIS) was used to measure CPC performance with the increase of exposure time. Every 5 days, the samples were taken EIS test after one-hour open circuit potential (OCP) monitoring. The frequency range is 100KHz~10mHz and voltage amplitude is 7mV rms. EIS was performed on the AI samples at the end of the wet portion of the cycle. 3.2.3 Cyclic Potentiodynamic Polarization Cyclic polarization scans were generated in 0.5M borate solution (0.42M H3BO3/0.08M Na2B4O7) + 10-5 M NaCl at pH=8 at a scan rate of 5mv/s. 3.2.4 FTIR FTIR spectra were generated on areas of exposed AA7075-T6 that had appeared to have lost its CPC film during exposure and compared to a surface of pristine AA7075 coated with CPC. A FTS 6000 Spectrometer was used for FTIR and the wavenumber range used was from 4500 to 700. 3.3 Surface Property Measurements Dinotrol AV8, Dinotrol AV30, LPS-3, and Amlguard (So Sure) were characterized for overall surface tension (energy) by the pendant drop technique. The overall surface tension was then divided into polar and dispersive components according to the Fowkes approach.[6] In the pendant drop technique, a drop of liquid is suspended on the end of a downward-pointing capillary tip. The drop is typically formed to about 90% of its detachment volume. The drop is then digitally imaged. The drop’s image is mathematically fit to determine the drop’s mean curvature over its surface. The curvature of a drop at any given point on its surface is dependent 10 on two opposing forces—gravity and surface tension. Gravity works to elongate the drop while surface tension works to keep the drop spherical. Pendant drop surface tension evaluation involves observing the balance between these two forces, in the form of the drop’s mean curvature at various points along its surface. Lower surface tension leads to a more “drip-like” shape, whereas higher surface tension leads to a more spherical drop shape. The surface energy components of Al2O3 powder were characterized using ethylene glycol and water as the probe liquids and applying Fowkes theory to the resultant contact angle data. However, a different contact angle determination method is applied to powders. The necessary contact angle values were obtained (in duplicate) by the Washburn adsorption method using a Kruss Processor Tensiometer K12, with an FL12 powder cell accessory. Hexane was used as the material constant determination liquid. Interfacial tensions at the CPC/water interface were also measured by the pendant drop method. The measurement procedure for this work was equivalent to that used for the pendant drop surface tension experiments described above except that instead of a drop of CPC being formed in air, it is formed on the end of an upward facing capillary tip submerged in water A key purpose of this project was to consider water displacement in lap joints. To measure, in part, the ability of a CPC to penetrate a lap joint, the contact angle of CPC on an aluminum surface submerged in water was measured as shown in Figure 2. Al CPC θ Water Figure 2: Contact angle measurement of CPC against aluminum submerged in water A test was also performed to determine if the CPC were capable of forming stable emulsions. Three mL of water and about six mL of CPC were slowly added to a glass vial. Then the vial was shaken to form an emulsion. The stability of the emulsion was monitored visually and recorded with photographs. 11 3.4 3.4.1 Wicking Tests Assembly Of Wicking Specimens The same simulated lap joint was used for the first set of wicking tests and consisted of two sheets, one of Plexiglas, the other of AA2024-T3. As illustrated in Figure 3, grooves were machined into the aluminum to secure the fiber optic sensor while minimizing the sensors influence on the flow front. The grove was machined to precisely hold the fiber whose diameter is 250 µm. The empty space above the optical fiber was filled with 400-mesh silica. The powder ensured that when the CPC flow front reached the grove, the CPC wicked into the groove and wet the sensor. The bulb at the end of the sensor groove housed a reflector for the fiber optic system. The sensor was ½” long and was located about ¼” behind the bulb. The 3” by 5” plates were assembled with hilok fasteners to insure consistent torque and fit up between tests. Three plates were fastened together—a Plexiglas plate followed by and aluminum plate followed by another offset aluminum backing plate. Before each test, the aluminum plates were initially cleaned with acetone, alcohol or toluene to ensure a clean, organic-free surface. The AV8 and AV30 products were best cleaned with toluene. LPS3 and Amlguard were best removed with alcohol and acetone respectively. After solvent cleaning the plates were washed with Alconox detergent until water broke off the surface with a streak free finish. The Plexiglas sheets were cleaned with Alconox to remove CPC from the previous tests. Toluene was occasionally used when the CPC became difficult to remove. The face sheets were dried with a heat gun before testing. 12 Sensor 3 1.00 in. Sensor 2 0.50 in. Sensor 1 1.50 in. 250 µm 250 µm Silica Filler Optical Fiber Sensor Groove Pool of CPC Optical Fiber Leads Flow front under plexiglas, sensor two is activated Figure 3. Sketches of simulated lap joints and optical fiber placement from power point wicking of CPC 3.4.2 Wicking Into Wet And Dry Simulated Lap Joints Immediately before each test, about 4 mL of CPC were sprayed into a container. CPC was placed on to the aluminum backing plate with a dropper and allowed to wick between the aluminum and the Plexiglas. By adding additional CPC, the pool of CPC was maintained during the test. When the wicking test was conducted on a wet joint, several drops of water were placed at the edge of the faying surface. The water was allowed to wick in and the excess was wiped with a chemwipe. Then the CPC was added to the backing plate. The sides were not masked as masking the edges seemed to cause problems with preferential wicking. The sensors were placed near the center of the joint to avoid edge effects and the need for masking. The flow front was monitored visually and with the sensors. The time required for the CPC to reach the sensors was recorded along with the sensor response. When the Plexiglas sheet was replaced with an aluminum sheet only the sensor data were recorded. If the flow front advanced uniformly across the joint, then the sensors would wet out in the following order– sensor 2, sensor 3 and sensor 1. The test was allowed to continue until all of the sensors wetted out or until the flow front stopped moving. 13 3.4.3 Fiber Optic Sensor Instrumentation and Data Reduction The fiber optic sensor measures refractive index, which changes from that of air to that of CPC or that of water as the flow front passes the sensor. Infrared light is directed through the fiber. When the light reaches the sensor light of a specific wavelength is coupled out of the optical fiber. The remaining light is reflected back to the instrument. The wavelength of the light that was coupled out of the fiber is determined. That wavelength is a function of the refractive index of the environment surrounding the sensor. Figure 4 contains typical spectra returned from the sensor when the sensor was dry, wet with water, wet with CPC or a combination of water and CPC. The instrumentation collects the spectra and the software finds the minima in the spectra. The graphs in Figure 4 consist of light intensity on the y-axis and wavelength on the x-axis. Light coupled out of the sensor appears as a dip in the intensity known as a loss peak. During the test the instrumentation record the wavelength of the loss peak as a function of time as illustrated in Figure 5. When the sensor is wet out completely with CPC, the loss peak moves off the scale and the instrumentation returns a loss peak of 1492 nm or 1570 nm. The moment the water or CPC reaches the start of the sensor, the wavelength starts rising and that time is recorded as the wet out time. The vertical lines in Figure 5 indicate when the CPC reached the CPC as determined from visual observation. 14 Air has a refractive index of one. For these sensors, light of Water has a refractive index of 1.33. For these sensors, light of wavelength of 1510 nm is coupled out of the fiber when the wavelength of 1530 nm is coupled out of the fiber when the environment surrounding the sensor has a refractive index of one. environment surrounding the sensor has a refractive index of 1.33. CPC has a refractive index of 1.4 to 1.5. When CPC When water and CPC are present or if only a portion of the completely wets the sensor, the refractive index is out of range of 1/2:” long sensor is surrounded with CPC, a loss will occur the instrumentation. As a result no loss peak is detected and the between 1530 and 1560 cm. software returns a value of 1492 nm or 1570 nm. Figure 4: Typical spectra encountered during the wicking process 15 Wave Length, nm 1525 Sensor 1 Sensor 2 Sensor 3 1520 1515 1510 1505 1500 1495 1490 100 150 200 250 300 350 400 450 500 Time, sec. Figure 5. Wicking of Protector 100 into a dry simulated lap joint. (Protector 100 is a CPC that was used early in the project to develop the technique). The vertical lines mark when the CPC first touches the sensor. When the sensor is fully wetted the response drops off the scale and reads 1492 nm. 3.4.4 Wicking Into CPC-Treated Lap Joints In this set of tests, dry lap joints instrumented with fiber optic sensors were treated with CPC. Four simulated lap joints were assembled with two sensors located at either 0.5”, 1.0” or 1.5” from the edge of the faying surface. AV8, AV30, LPS3 and Amlguard were each applied to one simulated lap joint. The CPC were sprayed directly on the simulated lap joints and allowed to dry over night. Special effort was taken to ensure the spray reached the interface between the faceplates. The amount of CPC applied exceeded that which one would expect to be applied in the field. Wetting of the sensor with CPC was verified before immersing the joint in water. The joint was immersed in tap water to the position at which the fiber optic leads exited the joint (Figure 6). The water level was limited to this point to avoid having to seal the fiber ingress points. The water was not agitated or stirred except to replace water lost through evaporation. The sensor response was recorded with time to determine if water had compromised the inside of the joint. 16 Two baseline measurements were taken. The first was of the dry, untreated lap joint and is labeled untreated in the results. This baseline verified that the sensor was functioning properly and allowed a comparison for a wetted sensor. The second baseline, called treated baseline, was taken after the joint was treated with CPC and dried. This baseline determines if CPC wicked into the inside of the joint when CPC was sprayed on the outside of the joint. Fiber egress point connectors Immersion level Potential water ingress Figure 6 Treated lap joint showing immersion level and potential water ingress areas. For scale the joint is 3” wide. 4 Results 4.1 4.1.1 Constant Immersion AA7075-T6 Figure 7 shows the interfacial impedance change with exposure time. For all CPC, interfacial impedance decreased with increasing exposure time. Among the four CPC tested in constant immersion, Amlguard failed first at about 110 days as indicated by a sharp drop in interfacial impedance. Compared with untreated AA7075-T6, the interfacial impedance for CPC-treated samples is at least 2 orders of magnitude higher, indicating protection against corrosion. 17 Interfacial Impedance (Mohms.cm 2) 10 10 10 10 10 10 2 1 0 -1 Amlguard AV30 AV8 LPS3 Bare AA7075 -2 -3 0 50 100 150 200 250 300 Exposure Time (Days) Figure 7 Interfacial impedance vs. exposure time for AA7075-T6 constant immersion 4.1.2 Clad AA2024-T3 Figure 8 is the interfacial impedance vs. exposure time for clad AA2024-T3 under constant immersion. AV30 failed at about 60 days whereas the other CPC still work well after > 200 days exposure. The interfacial impedance for CPC treated samples is one or two order magnitude higher than that for untreated AA2024-T3. Interfacial Impedance (Mohms.cm 2) 10 10 10 10 10 2 1 0 Amlguard AV30 AV8 LPS3 Bare AA2024 -1 -2 0 50 100 150 200 250 Exposure Time (Days) Figure 8 Interfacial impedance vs. exposure time for clad AA2024-T3 constant immersion 18 4.1.3 Precorroded AA7075-T6 The interfacial impedance changes with exposure time for AA7075-T6 samples precorroded before being treated with CPC are shown in Figure 9. All CPC applied samples had higher interfacial impedance than CPC untreated sample. Among them, the interfacial impedances on AV30, AV8 and LPS3 applied samples were about 2 orders of magnitude higher, but Amlguard provided only one order magnitude higher protection. In general the interfacial impedance decreased with the increase of exposure time and were lower than for samples treated with CPC before corrosion (section 4.1.1). Figure 9 Interfacial impedance vs. exposure time for Precorroded AA7075-T6, constant immersion 19 4.1.4 Precorroded Clad AA2024-T3 Interfacial Impedance (Mohms.cm 2) 10 10 10 10 10 2 Amlguard AV30 AV8 LPS3 1 0 -1 -2 0 20 40 60 80 100 120 Exposure Time (Days) Figure 10 Interfacial impedance vs. exposure time for precorroded clad AA2024T3, constant immersion The interfacial impedance for precorroded clad AA2024-T3 is shown in Figure 10. At the beginning of the test, there are some differences of the interfacial impedance on all samples. With the exposure time, however, this difference became negligible. 4.2 4.2.1 Alternate immersion AA7075-T6 Figure 11 shows the change on interfacial impedance for AA7075-T6 during alternate immersion exposure. For all samples, the interfacial impedance decreases with the increase of exposure time. Amlguard failed after 55 days exposure and AV8 failed after exposed 120 days. For LPS3 and AV30, after the observation of a portion of the film floating in solution, the tests were stopped. 20 Interfacial Impedance (Mohms.cm2) Exposure Time (Days) Figure 11 Interfacial impedance vs. exposure time for AA7075-T6, alternate immersion 4.2.2 Clad AA2024-T3 Figure 12 shows the relation between the interfacial impedance and the exposure time for AI-exposed, precorroded clad AA2024-T3. AV30 and AV8 failed in 100 days and Amlguard failed at about 240 days. LPS3 is still performing well after 260 days. The general tendency was for the interfacial impedance to decrease for all CPC. The LPS3treated sample had the highest interfacial impedance for exposures longer than 20 days. 2 2 Interfacial Impedance (Mohms.cm ) 10 10 10 10 10 1 0 -1 -2 0 Amlguard AV30 AV8 LPS3 50 100 150 200 250 Exposure Time (Days) Figure 12 Interfacial impedance vs. exposure time for clad AA2024-T3, alternate immersion 21 4.2.3 Precorroded AA7075-T6 Figure 13 Interfacial impedance vs. exposure time for precorroded AA7075-T6, alternate immersion The interfacial impedance for precorroded AA7075-T6 alternate immersion is shown in Figure 13. At the beginning of exposure, all CPC treated samples had higher interfacial impedance than untreated sample. The impedance decreased with time. After 100 days, the interfacial impedances for Amlguard and AV8 were slightly lower than that of the untreated sample. 4.2.4 Precorroded Clad AA2024-T3 Figure 14 shows the interfacial impedance for precorroded clad AA2024-T3 exposed to alternate immersion. At most times, AV30 had the highest interfacial impedance and Amlguard had the lowest interfacial impedance. The interfacial impedance changed little with time. 22 Interfacial Impedance (Mohms.cm 2) 10 10 10 10 2 1 0 Amlguard AV30 AV8 LPS3 -1 0 20 40 60 80 100 120 Exposure Time (Days) Figure 14 Interfacial impedance vs. exposure time for precorroded clad AA2024T3 alternate immersion 4.3 Proof of Remnant CPC After Apparent Loss of Film For some samples, large pieces of CPC film appeared to detach from the surface and were found floating in the solution. Thinking that this meant total failure of the CPC, the samples were removed from testing. However, inspection of the areas from which the film was lost showed no initiation of corrosion. Further investigations demonstrated that although the majority of the CPC film was detached, protection of the surface continued. 4.3.1 FTIR The FTIR measurement was taken on two types of surfaces: a bare area on exposed AA7075-T6 on which portion of the film has peeled off, and an area on pristine AA7075-T6 with the same CPC (AV30) applied and cured. The results are shown in Figure 15. Solid and dot line represents bare area on exposed AA7075-T6 and pristine AA7075-T6 respectively. Both lines are the result after background absorbance due to the AA7075-T6 substrate has been subtracted. The two lines have very similar characteristics, showing peaks relating to bond stretching from organic species on the surface. 23 0.35 Bare Area on Exposed AA7075 CPC on Pristine AA7075 0.3 Absorbence 0.25 0.2 0.15 0.1 0.05 0 500 1000 1500 2000 2500 3000 3500 4000 4500 Wavenumber 4.3.2 Figure 15 FTIR for bare area on exposed AA7075-T6 (red line) and CPC on pristine AA7075-T6 (Blue line) Cyclic Polarization Scan To determine the extent to which the remnant CPC provided protection to the AA7075-T6 surface, cyclic polarization scans were generated for both pristine AA7075T6 and AA7075-T6 that had lost the majority of its CPC film during exposure. Tests were conducted in borate solution with 10-5 M Cl-. The results are shown in Figure 16. The solid line is for pristine AA7075-T6 and the dotted line is for exposed AA7075-T6. From the figure, the pitting potential for exposed AA7075-T6 is much higher than pristine AA7075-T6 and also, the passive current density for exposed samples is lower than for the pristine sample. 24 0 Potential (V vs. SCE) -0.2 -0.4 -0.6 -0.8 -1 -1.2 -1.4 -9 AA7075 Pristine AA7075 Exposed (AV30) -8 -7 -6 -5 logi (A/cm 2) -4 -3 -2 Figure 16 Cyclic polarization scan for pristine AA7075-T6 and exposed AA7075-T6 in borate solution. 4.4 Leaching Figure 17. Interfacial impedance vs. leaching time for different CPC. Figure 17 shows the interfacial impedance of clad AA2024-T3 exposed to solutions produced after different times of exposure of the CPC-coated Pt-Nb meshes to the LJSS. Within the first two weeks of leaching, the inhibitors leached from the AV30, AV8 and Amlguard all increased the interfacial impedance of the AA2024-T3. The LPS3 leachate had no effect. After two weeks of leaching, the AV30 continued to leach inhibiting species, leading to an interfacial resistance of more than an order of magnitude higher 25 than that of the baseline sample. The other CPC had a more limited effect. It should be noted that these results are for clad AA2024-T3 and repetition of the experiments are planned for unclad AA2024-T3 and AA7075-T6. 4.5 Surface Properties of CPC, AA2024-T3 and Al2O3 Using the pendant drop technique, the overall surface tensions of the CPC were obtained and the results are shown in Table 2. Contact angle measurements were also taken for each CPC against poly(tetrafluoroethylene), PTFE, as required by the Fowkes theory. Substituting these contact angles and the overall surface tensions into the Fowkes theory results in the component surface tension data shown Table 2. Table 2 Overall and component surface tension data for CPC obtain from the pendant drop in technique and the Fowkes, respectively. Surface Tension Amlguard LPS 3 AV30 AV8 (mN/m) (mN/m) (mN/m) (mN/m) Overall 22.86 22.55 24.15 24.22 Polar 2.48 5.70 8.05 3.83 Dispersive 20.38 16.85 16.10 20.39 % Surface Polarity 10.9 25.3 33.3 15.8 The overall surface tensions are similar for the Amlguard and LPS 3 products, but the surface polarities are quite different (10.9% for Amlguard versus 25.3% for LPS 3). The same type of situation exists for the two AV CPC. They have very similar overall surface tensions, which are higher than those of the other two CPC. However, their surface polarities differ widely (33.3% for AV30 and 15.8% for AV8). A clean AA2024-T3 aluminum alloy surface was characterized for overall surface energy by the Fowkes method using water and ethylene glycol as the probe liquids. Applying Fowkes method to the average contact angle data yielded the following surface energy information for the AA2024-T3 surface. 26 Table 3. Overall surface energy for AA2024-T3 and Al2O3 obtained with the Fowkes method and with Washburn adsorption method[need reference] Surface Energy Al (mJ/m2) Al2O3 (mJ/m2) Overall 34.04 44.95 Polar 3.43 27.79 Dispersive 30.61 17.16 % Surface Polarity 10.07 61.81 Al has a relatively low surface energy (34.04 mJ/m2) and surface polarity (10.07%) compared to Al2O3, which has a surface energy of 44.95 mJ/m2 and a surface polarity of 61.81%. For the Al2O3 powder the necessary contact angle values were obtained (in duplicate) by the Washburn adsorption method using a Tensiometer which measure the weigh to liquid wicking into a powder packed column. Hexane was used as to determine the void volume of the column. 4.6 Water Displacement From the surface characterization data of the aluminum and aluminum oxide, one can calculate interfacial tension values between each of the CPC and water, against the two solid surfaces using Good’s equation.[7] σ SL =σ S +σ L − 2 (σ D L σ D S ) 1 / 2 − 2 (σ P L σ P S )1 / 2 where σ is the over all surface energy and the letters L, S, D, P refer to liquid, solid, dispersive and polar respectively. The results of these calculations are given in Table 4. Table 4 Liquid/Solid Interfacial Tensions, σSL, between CPC and Water and Al and Al2O3 surfaces Amlguard LPS3 AV30 AV8 Water (mN/m) (mN/m) (mN/m) (mN/m) (mN/m) AA2024-T3 1.11 2.32 3.28 1.04 24.76 Al2O3 13.80 8.32 5.95 11.13 3.36 27 The interfacial tensions for all of the CPC against the aluminum surface were calculated to be less than the interfacial tension for water against the surface (i.e., σSL for CPC against AA2024-T3 is less than σSL of water against AA2024-T3). This relationship was found for every CPC on a clean, non-corroded AA2024-T3 surface, but for none of CPC on an Al2O3 surface (model oxidized Al surface). The CPC with the lowest interfacial tension on the Al surface were the low surface polarity CPC (Amlguard and AV8). On the Al2O3 surface, the leading CPC, in terms of low interfacial tension, were the ones with higher surface polarity (LPS3 and AV30). However, none of the CPC matched the surface polarity of the Al2O3 as well as water (63.7% surface polarity). When a CPC interacts with water on an aluminum surface three interfaces are formed—CPC/aluminum, Water/aluminum and CPC/water. The surface energies of Water/aluminum and CPC/aluminum interfaces are given in Table 4 while the surface energy between water and CPC needs to be measured. Interfacial tensions were measured between CPC and water by the pendant drop method and the results are shown in Table 5 Table 5 Interfacial Tensions for CPC Against Water Measured by the Pendant Drop Technique Amlguard LPS 3 AV30 AV8 (mN/m) (mN/m) (mN/m) (mN/m) Average 7.80 3.42 3.03 4.76 Std. Dev. 0.05 0.07 0.05 0.04 Finally, with the CPC/water interfacial tension, the free energies for water displacement were calculated. These free energies were calculated by adding the CPC/Water interfacial tension (Table 5) and the CPC/surface interfacial tension (Table 4) to give the final condition, following the water displacement process. Then the relevant water/surface interfacial tension, the initial condition was subtracted from the final condition. Free energy of water displacement results for each of the CPC for Al and Al2O3 are listed in Table 6: 28 Table 6 Free Energies for Water Displacement by CPC Amlguard LPS 3 AV30 AV8 (mJ/m2) (mJ/m2) (mJ/m2) (mJ/m2) AA2024-T3 -15.85 -19.02 -18.45 -18.96 Al2O3 18.24 8.38 5.62 12.53 All four CPC have negative free energies for displacing water from Al7075, but the free energy for displacing water from Al2O3 are all positive. To measure, in part, the ability of a CPC to penetrate a lap joint, the contact angle of CPC on an aluminum surface submerged in water was measured as shown in Figure 1. Such contact angles for CPC displacing water from an aluminum surface were measured with the results given in Table 7. Table 7 Contact Angles for CPC on Aluminum Submerged in Water Amlguard LPS 3 AV30 AV8 (degrees) (degrees) (degrees) (degrees) Average 32.6 13.6 23.6 17.3 Std. Dev. 0.5 0.7 0.7 0.5 All of the contact angles are fairly low (less than 90û). Furthermore the contact angle trend does follow the free energy trend: Amlguard (-15.85, 32.6o)> AV30 (-18.45, 23.6o)> AV8 (-18.96, 17.3o)> LPS 3 (19.02, 13.6o) None of the angles was found to be particularly dynamic in nature. They all developed an equilibrium values as soon as the CPC was applied. So the dynamic aspect of this study was not completed. The same trend on the Al2O3 cannot be checked because there is no method to measure the contact angle for CPC displacing water from a powder. 4.7 Water Emulsification Each of the four CPC was shaken with water to form an emulsion. The LPS3 adhered to the glass and a portion of the Amlguard appeared to have been extracted into 29 the water. Photographs of the experiment are shown Figure 18. The Amlguard/water mixture separated immediately. After ten minutes all of the emulsions were gone and the water and CPC had separated. CPC and Water before being shaken CPC immediately after shaking The AV8, AV30 and LPS3 form an emulsion 30 All of the emulsions are unstable. After 10 minutes the CPC and water have all separated Figure 18: CPC from left to right AV8, AV30, LPS3 and Amlguard were shaken to form emulsion then allowed to stand to determine if the CPC formed stable emulsions. None of the CPC formed stable emulsions. 4.8 Wicking into Dry Lap Joints The CPC were wicked into a simulated lap joint with two dry AA 2024 face sheets. The time to reach sensors located 0.5”, 1.0” and 1.5” inside the joint was recorded. The Table 8 Average wicking time to sensors 0.5”, 1.0” and 1.5” from the edge and standard deviation of wicking times for three replicates Time to sensor, sec Std. Dev., sec 0.5 in. 1.0 in 1.5 in 0.5 in. 1.0 in. 1.5 in. Amlguard 20 63 87 Amlguard 3.9 18.5 17.3 LPS 105 214 259 LPS 70.9 99.4 146.9 AV8 57 186 166 AV8 2.8 109.2 47.3 AV30 124 341 332 AV30 95.8 116.9 46.7 results of three replicates are tabulated in Table 8 Average wicking time to sensors 0.5”, 1.0” and 1.5” from the edge and standard deviation of wicking times for three replicates and illustrated in Figure 19. The CPC were not observed to selectively wick along the 31 machined groove well ahead of the local flow front. The average wicking time is different for each CPC. The standard deviations, however, are quite large making it difficult to quantify differences between the CPC. In general the sensor wet out in the expected order, however, this was not always the case. Overall Amlguard wicks the fastest. Time to Sensor, sec. 500 400 0.5 in. 300 1.0 in. 1.5 in. 200 100 0 Amlguard LPS AV8 AV30 Figure 19 Wicking into a dry lap joint. The error bars represent one standard deviation taken from three replicates. Table 7 contains pictures of AV8 wicking into a dry lap joint. AV8 is used because it is very dark and thus provides excellent contrast. The orange line highlights the flow front. The flow front was not uniform, but did not preferentially wick along the sensor groove. Bare spots or non-wetted areas remained after the flow front passed. This phenomenon was not unique to AV8. If given sufficient time, the CPC would wick into the entire faying surface of a dry joint. 32 Table 9: Photographs of AV8 wicking into a simulated lap joint. The orange line indicates the location of the flow front AV8 wicking into a dry lap joint 5 second after the CPC was applied AV8 wicking into a dry lap joint 1 minute after the CPC was applied AV8 wicking into a dry lap joint 3 minutes after the CPC was applied AV8 wicking into a dry lap joint 4 minutes after the CPC was applied 33 Figure 20 through Figure 23 are representative data used to obtain the wicking times in Figure 19. Typically the moment the sensor first wet out there was a slight increase in the wavelength. Shortly afterward when the sensor was completely wet out the wavelength would move to either 1492 nm or 1570 nm. The initial increase in the wavelength was marked as the wet out time. 1570 loss peak, nm 1560 1550 1540 0.5" 1530 1.0" 1520 1.5" 1510 1500 0 100 200 300 400 Time, sec Figure 20 Sensor trace of Amlguard wicking into a dry aluminum lap joint. 1570 loss peak, nm 1560 1550 1540 0.5" 1530 1.0" 1520 1.5" 1510 1500 0 100 200 300 400 Time, sec Figure 21 Sensor trace of LPS-3 wicking into a dry aluminum lap joint. 34 1550 loss peak, nm 1540 1530 1520 0.5" 1510 1.0" 1500 1.5" 1490 1480 0 100 200 300 400 Time, sec Figure 22 Sensor trace of AV8 wicking into a dry aluminum lap joint. 1560 loss peak, nm 1550 1540 1530 1520 0.5" 1510 1.0" 1500 1.5" 1490 1480 0 100 200 300 400 Time, sec Figure 23 Sensor trace of AV30 wicking into a dry aluminum lap joint. 4.9 Wicking into Wet Lap Joints The CPC were wicked into a simulated lap joint that had water entrained between the two face sheets. To allow visual observation, one face sheet was Plexiglas and the other was AA2024-T3. The time for the CPC to reach sensors located 0.5”, 1.0” and 1.5” inside the joint was recorded visually and with imbedded fiber optic sensors. The results of four replicates are tabulated in Table 10 and illustrated in Figure 29 and Figure 30. The data in Figure 29 are from sensors behind the Plexiglas. The data in Figure 30 are 35 from visual observation through the Plexiglas. Figure 31 shows the wicking times for CPC wicking into a simulated lap joint with two AA2024-T3 face sheets for which only the sensor data are available. Whenever a wicking time is not recorded, either the CPC did not reach the sensor or the sensor reading was spurious because of a broken sensor. The average wicking time was different for each CPC. Amlguard wicked the fastest and most thoroughly followed (in order of decreasing speed) by AV8, LPS3 and AV30 under the Plexiglas. The standard deviations, however, were quite large making it difficult to quantify differences between the CPC. The wicking time for the wet lap joint was an order of magnitude slower than the wicking times for a dry lap joint as report above. When two aluminum face sheets are used, the Amlguard does not appear to be the fastest. All of the wicking rates are roughly the same. Wicking of CPC into a wet lap joint appears to be an inherently variable process. Visual observations of wicking into the Al-Plexiglas joint, shown in Figure 24, indicated very non-uniform flow fronts. In some cases the flow front at one location advanced two to three times farther than at other locations within the same amount of time. The CPC were not observed to selectively wick along the machined groove well ahead of the local flow front. Edge effects and fastener location do influence the flow front as shown in the series of photos in Figure 24. Some pockets of water remained after the CPC flow front had passed through the faying surfaces The fiber optic sensor data were consistent with the visual observations. The variability associated with sensor data was higher than the visual observations. Figure 25 through Figure 28 are representative of the output from the sensors. Amlguard and LPS3 gave a definitive response whereas the AV8 and AV30 gave less obvious responses when they reach the sensor. In each case the sensors started out dry with the loss peak at ~1510 nm. When the water reached the sensor, the sensor response goes to ~1530 nm. The water wicked very quickly compared to CPC in a dry lap joint. Finally, if the CPC reaches the sensor the wavelength again increased. The wicking time for the joint with two aluminum face sheets is shown in Figure 31. The data for these tests have more scatter and the wicking times do not agree with the wicking times determined from the test using a Plexiglas face sheet, indicating the importance of the embeddable fiber optic sensor. 36 Table 10 Average wicking time to each sensors 0.5”, 1.0” and 1.5” from the edge. Times were recorded visually and with the sensors during the experiment Time to sensor (visual reading), sec 0.5 in. 1.0 in. 1.5 in. Amlguard 473 667 833 AV8 620 1853 LPS 1200 AV30 1583 Time to sensor (sensor reading), sec 0.5 in. 1.0 in. 1.5 in. Amlguard 825 683 1300 2830 AV8 870 2400 2405 1900 3400 LPS 2213 3783 4450 7000 4700 AV30 5038 5367 1950 Table 11 Standard deviation of wicking times. Four tests were conducted. Zero to four observations were made at each sensor location. Std. Dev. (visual reading), sec 0.5 in. Std. Dev., (sensor reading), sec 1.0 in. 1.5 in. Amlguard 197 125 125 AV8 275 486 LPS 216 AV30 388 0.5 in. 1.0 in. 1.5 in. Amlguard 460 437 505 130 AV8 410 0 955 - - LPS 1500 1710 2299 2777 - AV30 4466 3668 0 AV8 wicking into a wet lap joint 4 minutes after the CPC was applied 37 AV8 wicking into a wet lap joint 15 minutes after the CPC was applied AV8 wicking into a wet lap joint 40 minutes after the CPC was applied Figure 24: AV8 wicking into a wet simulated lap joint Loss Peak wavelength, nm 1570 1560 1550 1.5 inches 1540 0.5 inches 1530 1.0 inches 1520 1510 1500 0 500 1000 1500 2000 2500 3000 time, seconds Figure 25. Wicking of Amlguard into a wet lap joint. At time 0 the sensor is dry. The first jump in wavelength is water wicking into the joint. The second increase in wavelength indicates the presence of CPC. 38 Loss Peak Wavelength, nm 1570 1560 1550 1.5 inches 1540 0.5 inches 1530 1.0 inches 1520 1510 1500 0 2000 4000 6000 8000 time, seconds Loss peak Wave Length, nm Figure 26. Wicking of LPS3 into a wet lap joint. At time 0 the sensor is dry. The first jump in wavelength is water wicking into the joint. The second increase in wavelength indicates the presence of CPC. 1550 1545 1540 1535 1.5 inches 1530 0.5 inches 1525 1.0 inches 1520 1515 1510 0 2000 4000 6000 8000 10000 Time, seconds Figure 27. Wicking of AV8 into the lap joint. Note that the response to the CPC is weaker than LPS3 and Amlguard. 39 Loss Peak Wavelength, nm 1545 1540 1535 1530 1.5 inches 1525 0.5 inches 1520 1.0 inches 1515 1510 1505 0 2000 4000 6000 8000 10000 12000 Time, seconds Figure 28 Wicking of AV30 into the lap joint. Note that the response to the CPC is weaker than LPS3 and Amlguard. CPC never reached the 1.0 inch sensor. Figure 29. Wicking into a wet lap joint. Data is from sensors imbedded in a Plexiglas lap joint. 40 Figure 30: Wicking into a wet lap joint. Data is from visual observations through Plexiglas. Figure 31 Wicking into a wet aluminum lap joint. All of the data were collected from the sensors. 41 4.10 Wicking into CPC-Treated Lap Joints Lap joints were treated with CPC and then immersed in water. The sensor responses over time are shown in Figure 32 through Figure 35. For the joint treated with LPS3 (Figure 32), the sensor located 0.5” from the edge immediately gave a loss peak of 1570 nm after treatment. The other senor responded the same way after one day. After 13 days the response dropped to 1560 nm on both sensors. An oil film appeared on the surface of the immersion solution. For the joint treated with AV8 (Figure 33) the treated baseline is missing. After one day, however, both sensors gave a loss peak of 1570. After 13 days the response of the 0.5” sensor remained at 1570 nm while the 1.0” sensor dropped 1555nm. For the joints treated with AV30 (Figure 34) and Amlguard (Figure 35) the sensors do not respond after treatment. Both sensors remain at 1510 nm. After one day immersed in water, the sensors gave a loss peak of 1530nm, which remained roughly constant through 33 days. AV30 got paler in color. The Amlguard specimen began corroding with black spots on boldly exposed surfaces and foamy bubbles coming from one of the fasteners. An oily film also appeared on the surface of the immersion solution. 1700 wavelength, nm 1650 1600 1550 1500 0.5" 1450 1.0" 1400 untreated treated baseline day 1 day 13 day 33 Figure 32. Sensor response in a simulated lap joint treated with LPS3 and immersed in water. 42 1700 Wavelength, nm 1650 1600 1550 1500 0.5" 1450 1.0" 1400 untreated treated baseline day 1 day 13 day 33 Figure 33. Sensor response in a simulated lap joint treated with AV8 and immersed in water. 1700 wavelength, nm 1650 0.5" 1600 1.0" 1550 1500 1450 1400 untreated treated baseline day 1 day 13 day 33 Figure 34. Sensor response in a simulated lap joint treated with AV30 and immersed in water. 43 1700 wavelength, nm 1650 1.5" 1600 0.5" 1550 1500 1450 1400 untreated treated baseline day 1 day 13 day 33 Figure 35. Sensor response in a simulated lap joint treated with Amlgurad and immersed in water. 5 Discussion 5.1 5.1.1 Testing Protocol Development For Boldly Exposed Surface Assessment Vs. Prediction of CPC Performance by Test Protocol All of the commercial CPC tested do provide some protection for aluminum alloys in LJSS as demonstrated by the higher interfacial impedance for treated samples relative to an untreated sample. This protection degraded with time. During the EIS testing, it was found that a decrease in interfacial impedance was correlated to the observation of visible corrosion on the sample surface for most CPC. However samples treated with AV30 or LPS3 were also likely to lose a portion of the CPC film after a long exposure times. In AA2024-T3 alternate immersion (Figure 11), the observation of a portion of the film floating in solution was initially assumed to indicate imminent failure although no corrosion was observable. On the other hand, the observation of good performance CPC was always correlated to higher interfacial impedance. Therefore, interfacial impedance can be used as one parameter to assess CPC performance. As mentioned above, samples treated with AV30 or LPS3 tended to lose a portion of the film after exposure for a long time. One example picture is shown below in Figure 36 An example of film loss sample (Substrate: AA7075-T6; CPC: AV30). It is a sample of AA7075-T6 with AV30 after exposure ten months. 44 No visible corrosion was observed on those film loss areas, however, if these samples were continued to expose to LJSS. There are two possibilities for this phenomenon: either protection developed from modification of the solution by species leached from CPC, or; there was still some CPC left on the film loss area. To decide if the protection was from the solution, impedance spectra on both fresh LJSS and CPCexposed LJSS were generated (Figure 37). It was found the impedance results in both solutions were very similar, which indicated that the protection on film loss area was not from the solution. In Figure 15, the FTIR results show similarities on pristine AA7075T6 with CPC and the bare area on exposed AA7075-T6, which indicates that there was still CPC remain on the aluminum alloy surface after the bulk of the film appeared to fall off. Intact CPC Film (AV30) Area of Film Loss Figure 36 An example of film loss sample (Substrate: AA7075-T6; CPC: AV30) 45 10 4 LJSS (Without Exposed) CPC Exposed LJSS 3 |z| 10 10 2 1 10 -2 10 10 0 10 2 Frequency (Hz) 10 4 10 6 Figure 37 results on both fresh LJSS and CPC exposed LJSS using AA7075-T6 The cyclic polarization results on pristine AA7075-T6 and exposed AA7075-T6 also support the assertion that the protection on film loss area is from the remaining CPC (Figure 16). From Figure 16, the corrosion on exposed AA7075-T6 was inhibited due to remaining CPC relative to pristine AA7075-T6. In addition, after cyclic polarization scan, pits were observed on the surface of the pristine AA7075-T6, but not on the exposed AA7075-T6. Table 12. A CPC ranking method Time to Failure (Days) Approximate percentage of corrosion area when failure Failure mode No. of failed samples to date/total exposed Ranking when consider all factors Amlguard AV30 AV8 LPS3 55 55 120 85 25% 3% 5% 0 Blistering Breaching of film Blistering 3/3 3/3 0/3 0/3 1 2 3 Breaching of film 46 4 (the best one) Figure 38 A correlation between CPC ranking and short-term interfacial impedance. A ranking method for CPC performance was developed and applied to the CPC tested as shown in Table 12. This ranking method was based on the impedance test results of AA7075-T6 alternate immersion as well as the exposure performance of CPC treated samples. A relationship between CPC ranking after 120 days exposure and interfacial impedance was found as shown in Figure 38, which shows that at 40 days, a CPC with higher interfacial impedance will have better performance after 120 days exposure. Using data from before 40 days, however, no such correlation was found between ranking and interfacial impedance. A correlation between short-term test data and long-term performance was not found on CPC applied to clad AA2024-T3. The reason for that is due to that the clad layer is sufficiently corrosion resistant that the gains by the CPC application are minimal. 5.1.2 Relative Corrosivity of Exposure Protocols Alternate immersion and constant immersion were used in this work for both alloys. Comparing CPC performances in both environments, it was found that alternate immersion is more aggressive than constant immersion. For example, for AA7075-T6 alternate immersion, Amlguard failed in 55 days and for AA7075-T6 constant immersion, Amlguard failed after 100 days exposure. Again, for clad AA2024-T3 47 alternate immersion, Amlguard failed at around 200 days exposure but in constant immersion, it still goes well after 240 days. 5.1.3 Ranked Performance of CPC a. Ranked performance of CPC and alloys CPC performance is different for different alloys and different exposure environments. Based on measurements in this work, the following ranking was obtained: For AA7075-T6: 1) AA7075-T6 constant immersion: AV8>LPS3>AV30>Amlguard 2) AA7075-T6 alternate immersion: LPS3>AV8>AV30>Amlguard 3) Precorroded AA7075-T6 constant immersion: AV30>LPS3>AV8>Amlguard 4) Precorroded AA7075-T6 alternate immersion: LPS3>AV30>AV8≈Amlguard Total ranking for pristine aluminum: LPS3, AV8>AV30>Amlguard; Total ranking for corroded aluminum: AV30, LPS3>AV8≈Amlguard; Total ranking for AA7075-T6: LPS3>AV30, AV8>Amlguard. For clad AA2024-T3: 1) Clad AA2024-T3 constant immersion: AV8>Amguard>LPS3>AV30 2) Clad AA2024-T3 alternate immersion: LPS3>Amlguard>AV30>AV8 3) Precorroded clad AA2024-T3 constant immersion: alternate immersion: AV8>Amlguard≈LPS3≈AV30 4) Precorroded clad AA2024-T3 AV30>LPS3>AV8>Amlguard Total ranking for pristine clad AA2024-T3: Amlguard, LPS3>AV30, AV8; Total ranking for corroded clad AA2024-T3: AV8, LPS3>AV8, Amlguard; Total ranking for clad AA2024-T3: LPS3>AV8, AV30, Amlguard. 5.1.4 Failure Mode Two different CPC failure modes were found in this work: blistering and breaching of film. The pictures in Figure 39 show these two failure modes. Breaching of film is local region where corrosion occur due to losing of film protection and Blistering 48 means failure of film by blisters formation, which are local regions where adherence between the film and the substrate has been lost. Breaching of film Blistering of film Figure 39 CPC failure modes. Failure modes were controlled by CPC (e.g., Amlguard vs. AV30) not by type of immersion (e.g., Alternate vs. Constant). 5.2 5.2.1 Precorrosion Effects Effect of Prior Corrosion on Effectiveness of CPC for Boldly Exposed Aluminum As shown by the interfacial impedance measurements for the precorroded samples, the CPC can slow or inhibit the initiated corrosion sites on both clad AA2024-T3 and AA7075-T6. The interfacial impedance values for precorroded samples were lower than 49 those for pristine samples. For example, the interfacial impedance for precorroded AA7075-T6 under constant immersion was 2 order magnitudes lower than that for pristine AA7075-T6 constant immersion. In addition, the relative poor CPC adherence ability on precorroded aluminum was another factor to make CPC perform worse on precorroded samples. For AV30, the film started to peel off from the precorroded sample in the first week of exposure whereas the film started to peel off from the pristine sample after 6 weeks. 5.3 Wicking The discussion of the wicking studies will show that fundamental surface chemistry measurements can predict if a CPC will wick in between two pristine aluminum plates. The surface chemistry shows that the CPC would wick into a dry simulated lap joint and a simulated lap joint containing entrained water. The surface chemistry also suggests that CPC would not wet out and displace water from a completely oxidized aluminum surface (as modeled by Al2O3). Wicking test on pristine aluminum plates verified the former but experiments were not available to verify the latter. 5.3.1 CPC Surface Chemistry CPC and AA2024-T3 Surface Energy. The differences in the overall surface tension of the CPC and the differences in their polar and dispersive components will affect their interaction with pristine aluminum surfaces and heavily corroded surfaces. What this is likely to mean to their relative interactions with surfaces, as well as to water, is the following: 1. The two higher surface polarity CPC—LPS-3 and AV30—will have greater adhesion to highly polar surfaces, like the Al2O3 powder when compared to Amlguard and AV8. When two materials adhere to one another the interfacial tension between them is low. The high surface polarity CPC will likely have lower interfacial tensions with water, since water is very polar (63.7% surface polarity). When two liquids easily form an emulsion the interfacial tension between them is low. 2. The two lower surface polarity CPC, Amlguard and AV8, may have the advantage of stronger adhesion to (lower interfacial tensions against) Al. 50 3. The fully oxidized aluminum oxide had a higher surface polarity than the uncorroded alloy. This trend represents the expected effect of oxidizing a surface. It should be noted that the alloy used in service does have a thick oxide coating and that two different methods were used to obtain the contact angle of the AA2024-T3 and the Al2O3 powder. The next experiment would be to corrode the alloy surface under different conditions such as high and low pH and then measure the surface properties. The first two hypotheses described above were verified by measuring the CPC/water interfacial tension and the contact angle of CPC on aluminum submerged in water. Water displacement. The best adhesion (lowest interfacial tensions) occurs when the liquid and solid in question have very similar surface polarities. Thus, Amlguard (10.9% surface polarity) and AV8 (15.8% surface polarity) are more compatible with the low surface polarity AA2024-T3 (10.1% surface polarity) while LPS3 (25.3% surface polarity) and AV30 (33.3% surface polarity) are more compatible with high surface polarity Al2O3 (61.8% surface polarity). These trends are illustrated in Figure 40. The lower the surface polarity of the CPC the lower its surface energy with the less polar AA2024-T3 surface. The higher the surface polarity of the CPC, the lower its surface energy with the more polar Al2O3 surface would be. The lower the energy between the CPC and the surface the more tightly bound they are. 51 35 14 30 12 10 8 25 CPC/Al CPC/Al2O3 % polarity 20 15 6 10 4 Surface polarity, % Surface energy, J/m2 16 5 2 0 0 So Sure Amlguard AV8 LPS3 AV30 Figure 40: Surface polarity of CPC and surface energy between CPC and AA2024-T3 and Al2O3 surfaces The affinity water has for the aluminum surface affects the CPC ability to displace the water from that surface. The water had a strong affinity for the polar Al2O3 surface. Demonstrated by the low surface tension between water and the Al2O3. In cases where the interfacial tension for a CPC against a surface is calculated to be less than the interfacial tension between water and that same surface, it is thermodynamically favorable to replace a water/surface interface with a CPC/surface interface. When a CPC interacts with water on an aluminum surface, three interfaces are formed—CPC/aluminum, water/aluminum and CPC/water. The surface energy between water and CPC was measured to determine if the CPC could displace water from aluminum. From high to low, the trend in the interfacial tension with water, is: Amlguard > AV8 > LPS 3 > AV30 These results were expected, based on the relative surface polarities of the CPC, which follow the inverse trend as illustrated in Figure 41 52 35 30 8 25 6 20 4 15 10 CPC/WATER 2 % polarity Surface Polarity, % Surface Tension, J/m2 10 5 0 0 So Sure Amlguard AV8 LPS3 AV30 Figure 41. Surface polarity of CPC and surface tension between CPC and water. The higher the surface polarity of the CPC the surface tension between it and water. The more surface polarity a CPC has, the more compatible with water (surface polarity of 63.7%) it would be expected to be. Finally, using the CPC/water interfacial tension, the free energies for water displacement can be calculated. This free energy characterizes the ability of each CPC to displace water from Al and Al2O3 surfaces. These free energies were calculated by adding the relevant CPC/Water interfacial tension and the CPC/surface interfacial tension. This sum described the final condition following the water displacement process. The initial condition, which is the relevant water/surface interfacial tension, was subtracted from the final condition to give the free energy for water displacement. Negative free energy results indicate that water displacement from the surface is thermodynamically favored. Positive results indicate that displacement of water is unfavorable. All four CPC are favored to displace water from Al, but not from Al2O3, since water adheres strongly to Al2O3. This conclusion can be justified experimentally and related to water displacement in lap joints. To have any chance of penetrating a lap joint and displacing water in such a joint a CPC must exhibit, at the very least, a less than 90o contact angle on an aluminum surface submerged in water. A 90o contact angle, in this situation, defines the condition under which the free energy for water displacement by a CPC is equal to 0 mJ/m2 . In other words, in cases where the free energy for water displacement by a CPC is negative, the contact angle should be less than 90o. Furthermore, the actual contact angle measured in such an experiment, and the magnitude 53 of the free energy for water displacement, should have a trend-wise relationship. The more negative (favorable) the free energy of the displacement – the lower the contact angle should be. Such contact angles for CPC displacing water from an aluminum surface are given in Table 7 All of the contact angles are fairly low, such that the displacement of water is very favorable – which would portend well for lap joint penetration. The lower the angle, the better capillary-based penetration into lap joints should be. The contact angle trend does follow the free energy trend: Amlguard (-15.85, 32.6o)> AV30 (-18.45, 23.6o)> AV8 (-18.96, 17.3o)> LPS 3 (-19.02, 13.6o) Emulsification. A good CPC might very well also need to be a good emulsifier of water, in addition to having good water displacement properties, and capillary spreading action. The CPC/water interfacial tension values characterize the emulsification abilities. Lower interfacial tension is better –since interfacial tension is a direct measure of the amount of work necessary to create interface (emulsify). Listed from best to worst emulsifier the results were as follows: AV30 (3.03 mN/m) > LPS3 (3.42 mN/m) > AV8 (4.76 mN/m) > Amlguard (7.80 mN/m) The interfacial tension trend follows inversely the surface polarity trend for the CPC. More surface polarity = better compatibility with water = better emulsification ability. The Amlguard did not emulsify water at all which fits the trend above. No real distinction could be made between the other three CPC. When water is entrained in a lap joint or crevice and the CPC removes the water from the surface, if the water is not emulsified, then the question of where does the water go remains unanswered. 5.3.2 Wicking Into Dry and Wet Lap Joints Wicking of CPC into a lap joint appears to be an inherently variable process. Visual observations of wicking into an Al-Plexiglas joint indicated very non-uniform flow fronts. In some cases the flow front at one location advanced two to three times farther than at other locations within the same amount of time. The presence of the machined grooves did not appear to influence the wicking. Because of the variability, it is not surprising that for a given CPC, the distribution of measured penetration rates was 54 relatively large, as indicated by the relative standard deviation (RSD = standard deviation / mean x 100 %). RSD ranged from 5% for AV8 at 0.5“ to 78 % for AV30 at 0.5”. Typical RSD values were ~ 40 %. The fiber optic sensor data were consistent with the visual observations. The variability associated with sensor data was comparable with visual observations. All of the CPC tested exhibited comparable wicking ability into a dry aluminum lap joint. Differences in performance, if any, may come down to differences in other properties such as water displacement and/or emulsification, film formation and self-healing ability. The visual observation is subjective and the observer is inclined to mark the time based on previous data consequently the variability appears smaller. Variability in the sensor data is associated with variability in how the sensor is packed into the grooves and judging when the sensor has responded. Variation in the surface properties of the aluminum and the Plexiglas may also contribute to the variability in the results. Furthermore, the dimensions of the occluded region were probably not uniform between the fasteners. As a result wicking near the fastener is different than wicking between fasteners. All of the CPC tested exhibited comparable wicking ability into a dry aluminum lap joint. The contact angle of all of the CPC against aluminum in air was nearly zero, and the overall surface energies of the CPC were nearly equal. (Amlguard 22.86 mN/m, LPS3 22.55 mN/m, AV30 24.15 mN/m, AV8 24.22 mN/m) Therefore, the driving forces for wicking were about the same. In the case of a wet joint, however, differences in surface properties of the CPC/water/aluminum interface would potentially indicate differences in wicking rates. Thermodynamically, the surface measurements did predict that all of the CPC would wet the aluminum, which they did. As seen in Table 13, the contact angles of the CPC against aluminum in water were not zero and the surface energy of the water-CPC interface were different for each CPC. The resultant of the surface energy and the contact angle could be considered a driving force for wicking and if so Amlguard (resultant 6.57mN/m) would wick the fastest and AV30 (resultant 2.78) would wick the slowest. In the case of the CPC wicking through the joint containing a Plexiglas face sheet this trend seemed to be the case. When two aluminum face sheets were used, however, 55 the surface property measurements were not a good indication of wicking rate, although they were a good indicator of whether or not the CPC would wick into a wet joint. Table 13: CPC surface properties and contact angles CPC surface energy against water, mN/m contact angle against aluminum in water degrees Resultant, mN/m Amlguard 7.8 32.6 6.57 Av8 4.76 17.3 4.54 Lps3 3.42 13.6 3.32 Av30 3.03 23.6 2.78 The CPC wicked much faster into a dry joint than into a wet joint. This result would be expected thermodynamically by comparing the overall surface tension of the CPC to the resultants in Table 13. Because the contact angle on a dry aluminum surface was nearly zero then the resultant on the dry surface would be equal to the overall surface tension of the CPC which were about 24 mJ/m2 the resultant for the wet surface was about an order of magnitude lower as was the wicking rate. By itself wicking rate is not important until the wicking time become so long that the CPC on the outside of the occluded region dries up and stops any wicking. These tests were very forgiving in that the CPC was not allowed to dry. There are two significant issues related to CPC and corrosion in occluded regions (1) the wicking is not uniform or complete which will leave some areas exposed to corrosive environments and essentially untreated and (2) Although the CPC removes the water from the surface it may only be trapped in the faying surfaces or forced to another area where corrosion will continue to occur. 5.3.3 Wicking Into a Pretreated Lap Joint Water wicking into a pretreated joint would be an indicator of how the CPC would hold up to the environment once it is applied. Given that the wicking process is inherently variable, it is not surprising that each of the CPC behave differently when exposed to water after treatment. Only one lap joint was tested for each CPC, therefore, 56 the effects of variability in wicking rate or coverage are not assessed. These experiments show that water will penetrate past the CPC by passing through fastener holes, by wicking around CPC or by softening the CPC and diffusion through it. These experiments do not differentiate between the wicking paths or wicking mechanisms. They only measure that water has penetrated the joint and affected the sensor. Recall that a dry sensor has a loss peak of 1510 nm, a water wet sensor has a loss peak of 1530 nm. A sensor wet by CPC has a loss peak off the scale and the instrument returns a value of 1570 or 1492 nm. In the lap joint treated with LPS3, the 0.5” sensor wetted out with CPC as expected. The second sensor did not wet out until one day later, which may have occurred because the LPS3 is a soft waxy film and could potentially continue to wick into the joint. The peak location dropping to 1560 nm may indicate that water had diffused into the LPS3 or water had wicked into the joint and part of the sensor was wetted with water while the other part remained wet with CPC. The former is more likely because both sensors behaved the same way. The AV8 appeared to wet out both sensors. After 13 days the 1.0” sensor had dropped to 1560 nm indicating that the water had in some way affected the sensor. Presumably the water reached the sensor by diffusion or directly by wicking into regions that the CPC did not reach. The AV8 kept the water away form the 0.5” sensor for at least 33 days. The AV30 and the Amlguard behaved in the same manner. Neither CPC appeared to wet out the sensors. After one day water had reached both sensors in each lap joint. The water had definitely affected the integrity of the AV30 judging by the color change of the boldly exposed surface. The Amlguard became completely ineffective since corrosion has appeared even on the boldly exposed surfaces and water had infiltrated the occluded regions. If the CPC does not reach all of the occluded regions it is safe to say that when exposed to a salt solution the occluded regions are likely to corrode. 6 Conclusions The objectives of this project are (a) to develop a quantitative testing protocol that allows discrimination of CPC performance and allows selection of the most effective CPC for a particular component, and (b) to test the effectiveness of several commercial 57 CPC on both boldly exposed and occluded regions on aircraft. In this annual report, progress has been described on both objectives with a focus on boldly exposed surfaces for the corrosion testing. An investigation of the surface thermodynamic properties and wicking kinetics was also conducted. 6.1 Development of Quantitative Testing Protocol • Alternate immersion in LJSS is more aggressive than constant immersion leading to failure of CPC at much earlier times (e.g., 55 days for Amlguard on AA7075T6 in alternate immersion vs. 111 days for Amlguard on AA7075-T6 in constant immersion). • A means of CPC ranking was defined using the EIS results and visual assessment of CPC performance. • Generally a substantial decrease in the interfacial impedance (ca. a factor of 5) correlated to the observation of visible corrosion on the substrate, except for those samples for which a portion of the CPC film was lost. In those cases, the decrease in interfacial impedance did not presage a loss in protection. • CPC fail via two different modes: blistering and breaching of film. • The assessment/prediction methods that have been successful for organic coating cannot be directly transferred for use in studying CPC. The barrier properties of the CPC (as measured at high frequency) are low and do not predict corrosion performance. • CPC can somewhat suppress the initiated corrosion on precorroded sample for some time period as demonstrated by the increased interfacial impedance of precorroded samples subsequently treated with CPC before re-exposure to solution. The protection of CPC on precorroded sample is not as good as that of CPC on pristine sample, with interfacial impedance being 2 orders of magnitude lower than for pristine 7075 samples treated with CPC. • The CPC adherence ability on pristine sample is better than that on precorroded sample (e.g. for AV30, the film started to peel off from the precorroded sample in 58 the first week of exposure and the film started to peel off from the pristine sample after 6 weeks). 6.2 Relative Effectiveness of Several Commercial CPC • The CPC ranking for AA7075-T6 exposed to alternate immersion was found to be LPS3 > AV8 > AV30 > Amlguard) • All of the CPC tested can provide substantial protection of AA7075-T6, albeit for a limited time period. In the constant immersion testing, the interfacial impedance of the intact CPC-coated AA7075-T6 was approximately three to four orders of magnitude higher than those for untreated, bare AA7075-T6. • AV30-treated samples were more likely to lose a portion of their film after a longtime exposure. Over these areas, it appeared that the vast majority of the CPC film detached and was found floating in the solution. Nonetheless, there was remnant CPC left on the apparently bared regions, and this remaining CPC still protected the substrate for some (as yet undetermined) time period. 6.3 Surface Thermodynamic Properties and Wicking into Occluded Regions • The ability of the different CPC to wick into dry and wet simulated lap joints was predictable by fundamental surface chemistry measurements. • Wicking is much slower in wet joints due to larger contact angles on the wet joint. Wicking rates into wet joints requires the displacement of water and was found to take as much as ten times longer to move to a given position. • The surface polarity of the CPC appeared to dominate the wetting and moisture displacement capability of CPC. A low surface tension promotes spreading whereas high surface polarity promotes water displacement from oxidized surfaces. • Wicking is a spatially and temporally variable process depending on local geometry and surface properties. In both dry and wet joints, areas of surface behind the CPC front were left unprotected, leaving behind air and water pockets, respectively. This observation could have importance on the initiation of corrosion within occluded regions. 59 7 Future Work • CPC testing and analysis on unclad AA2024-T3 in order to assess their effectiveness on the base alloy ands comparison to the effectiveness of the clad. • Exposure of samples with intentional scratches through a CPC film to accelerate corrosion on constant immersion samples. • Further investigate CPC performance in occluded regions. We have simulated lap joints of both AA2024-T3 and AA7075-T6 pretreated with CPC and being exposed to LJSS. Samples are being removed every three months for analysis. • Determination of test method for determination of reapplication time. • Surface chemistry measurement of aluminum alloy surfaces that have been corroded as part of lap joints in order to better simulate the relevant surface chemistry. • Wicking measurements for water and CPC into precorroded, simulated lap joints to better assess the effects of corrosion product surface chemistry and porosity on water and CPC transport. 8 Acknowledgements Technical interactions with L. B. Simon (S & K Technologies), J. Dante (Univ. of Dayton Research Institute), and R. C. Kinzie (Air Force Corrosion Program Office) are gratefully acknowledged. Financial support provided through the Air Force Research Lab (Dr. B. T. Peeler) via NCI Contract (NCI Subcontract Number: NCI-USAF-9191010), Garth Cooke, Program Manager is gratefully acknowledged. 60 9 Appendix—Kruss Report January 29, 2002 Keith Furrow Luna Innovations P.O. Box 11704 Blacksburg, VA 24062-1704 Dear Keith, We have completed our characterizations of your corrosion prevention compounds (Dinotrol AV8, Dinotrol AV30, LPS-3, and SoSure Amulguard) with regard to their interaction capabilities with Al, Al2O3, and water. The work was performed according to our statement of work proposal of 12/10/01, with the objectives discussed, both in that proposal and in this document, in mind. Background Information from the Statement of Work CPC’s are sprayed onto metal structures to slow corrosion. On boldly exposed surfaces they are effective. However, their functionality inside occluded regions can be disputed. The purpose of this investigation is to develop test methods that will quantify the ability a CPC to penetrate lap joints and displace water. The testing will specifically evaluate: 4. The surface properties of the CPC’s, and the surfaces to which they are applied, (specifically Al and Al2O3). 5. The ability of various CPC’s to displace water from surfaces to which they are applied (both in an equilibrium sense, and in a dynamic sense). 6. The propensity of various CPC’s to form emulsions with water (which might be found to be an advantage, in that it gives the displaced water somewhere to reside, away from the protected surface). Item 1 – Surface Properties Each of the following four CPC’s (Dinotrol AV8, Dinotrol AV30, LPS-3, and So Sure Amulguard) were characterized for overall surface tension (energy) by the pendant drop technique. The overall surface tension was then divided into polar and dispersive components according to the Fowkes approach, which is discussed in mathematical detail on pages 11 through 14 of the enclosed technical note entitled, “So You Want to Measure Surface Energy?” - with a special note on liquids appearing on page 9. The pendant drop technique works as follows. A drop of liquid to be studied for surface tension is formed on the end of a downward-pointing capillary tip. The drop is typically formed to about 90% of its detachment volume (from the capillary). The drop is then 61 digitally imaged. The drop’s image is fit by a robust mathematical approach to determine the drop’s mean curvature at over 300 points along its surface. The curvature of a drop that is pendant to a capillary tip, at any given point on its surface, is dependent on two opposing factors (or forces). Gravity works to make the drop elongated or “drip-like”. The greater the difference in density between the liquid and the outside gas (in this case air), the greater this force. Surface tension works to keep the drop spherical- since a sphere has the lowest surface to volume ratio of any shape, and surface tension is by definition the amount of work necessary to create a unit area of surface. Pendant drop surface tension evaluation involves observing the balance that exists between these two forces on a pendant drop, in the form of the drop’s mean curvature at various points along its surface. Lower surface tension means a more “drip-like” drop shape, higher surface tension means a more spherical drop shape. The actual mathematics of pendant drop analysis are based on the Laplace equation which says that pressure differences exist across curved surfaces. The pressure difference at any given point on the surface (∆P) is equal to mean curvature of the surface at that point ((1/r1 +1/r2), where r1 and r2 are the principal radii of curvature) multiplied by twice the tension (σ) contained in the surface. ∆P = (1/r1 +1/r2) 2 σ For a pendant drop, the pressure difference within the drop between any two vertical positions is: ∆ρ g Z where ∆ρ = the difference in density between the liquid that is forming the drop and the bulk gas, g = gravity, and Z = the vertical distance between the two positions, as shown below. A z B The measurement of surface tension is actually made by determining the mean curvature on the drop at over 300 points (like those labeled A and B above). Those points are then 62 used in pairs, with the equations given above, to solve for surface tension. In the following manner: ( (1/r1 +1/r2)at A - (1/r1 +1/r2)at B ) 2 σ = ∆ρ g Zbetween A and B Therefore, from one drop image, surface tension is determined at least 150 times. These surface tension values are averaged to give a single value for the overall surface tension of the drop. This technique has been found to be extremely accurate for determining surface tensions of liquids with known surface tension (typical errors of less than 0.1%). Of course, the disadvantage of the pendant drop method is that the densities of all liquids studied have to be predetermined to the same level of accuracy one expects for the surface tension data being measured. For your CPC’s, we determined densities by the most simple of approaches – weighing controlled volumes of each CPC. The following results were obtained: Sample Density (g/cm3) So Sure 0.8452 LPS 3 0.8079 AV30 0.9017 AV8 0.8768 Using these density values, and running pendant drop experiments, with five drops tested for each condition, we obtained the following overall surface tension values for your CPC’s: Overall Surface Tension Results for CPC’s So Sure LPS 3 AV30 AV8 Drop # (mN/m) (mN/m) (mN/m) (mN/m) 1 22.68 22.52 24.18 24.19 2 22.65 22.50 24.17 24.23 3 22.69 22.58 24.14 24.24 4 22.67 22.53 24.15 24.22 5 22.69 22.63 24.12 24.22 Average 22.86 22.55 24.15 24.22 63 Std. Dev. 0.02 0.05 0.02 0.02 Contact angle measurements were also taken for each CPC against poly(tetrafluoroethylene), PTFE, as described by the Fowkes theory. The contact angle work on PTFE, was also performed with five drops being tested, and gave the following results: Contact Angles for CPC’s Against PTFE So Sure LPS 3 AV30 AV8 Drop # (degrees) (degrees) (degrees) (degrees) 1 47.6 57.1 65.4 54.5 2 47.7 57.2 65.8 54.3 3 47.3 57.1 66.2 54.7 4 47.9 57.2 65.8 54.4 5 47.2 56.3 65.8 54.2 Average 47.5 57.0 65.8 54.4 Std. Dev. 0.3 0.4 0.3 0.2 Combining these data with Fowkes theory then produced the following component surface tension data for the CPC’s: Component Surface Tension Data for CPC’s Surface Tension So Sure LPS 3 AV30 AV8 (mN/m) (mN/m) (mN/m) (mN/m) Overall 22.86 22.55 24.15 24.22 Polar 2.48 5.70 8.05 3.83 Dispersive 20.38 16.85 16.10 20.39 % Surface Polarity 10.9 25.3 33.3 15.8 At this point, it is worthwhile to draw some preliminary conclusions concerning the relative natures of the various CPC’s. You can see from the data directly above that the overall surface tensions are similar for the So Sure and LPS 3 products, but the surface polarities are quite different (10.9% for So Sure versus 25.3% for LPS 3). The same type of situation exists for the two AV CPC’s. They have very similar overall surface tensions, 64 which are higher than those of the other two CPC’s. However, their surface polarities differ widely (33.3% for AV30 and 15.8% for AV8). What this is likely to mean to their relative interactions with surfaces, as well as to water, is the following: 1. The two higher surface polarity CPC’s, LPS 3 and AV30, will have greater adhesion to (lower interfacial tensions against) highly polar surfaces, like your Al2O3 would be expected to be, versus their counterparts, SoSure and AV8. They will also likely have lower interfacial tensions with water, since water is very polar (63.7% surface polarity) – meaning that they would emulsify water more easily. The emulsification of water is, of course, a possible water displacement mechanism in lap joints – as we have discussed. 2. The two lower surface polarity CPC’s, So Sure and AV8, may have the advantage of stronger adhesion to (lower interfacial tensions against) Al (the surface of which is often found to be less than 20% polar). We will discuss these aspects in more detail shortly. First, however, I will discuss characterization of the Al and Al2O3 surfaces. The aluminum surface you provided was characterized for overall surface energy by the Fowkes method described in the enclosed application note, with water and ethylene glycol used as the probe liquids. Five drops each of water and ethylene glycol were placed on the surface of the Al, and the following contact angles were obtained, by the goniometer method. Contact Angles for Water and Ethylene Glycol Drops on Al Water Ethylene Glycol Drop # (degrees) (degrees) 1 82.4 55.8 2 82.6 55.7 3 81.9 55.9 4 81.9 55.8 5 82.1 55.7 Average 82.2 55.8 Standard Deviation 0.3 0.1 Applying Fowkes method to the average contact angle data, given that water has an overall surface tension of 72.8 mN/m, with 46.4 mN/m being polar component, and ethylene glycol has an overall surface tension of 47.7 mN/m, with 21.3 mN/m being polar 65 component (as discussed on page 9 of the enclosed application note), yields the following surface energy information for the Al surface. Al - Surface Energy Components Surface Energy Al(mJ/m2) Overall 34.04 Polar 3.43 Dispersive 30.61 % Surface Polarity 10.07 The Al2O3 powder you provided was likewise be characterized for surface energy components using ethylene glycol and water, and applying Fowkes theory to the resultant contact angle data. However, a different contact angle determination method is applied to powders. The necessary contact angle values were obtained (in duplicate) by the Washburn adsorption method using a Kruss Processor Tensiometer K12, with an FL12 powder cell accessory. Hexane was used as the material constant determination liquid, and all experiments were performed exactly according to the protocol described on pages 9 and 10 of the enclosed Kruss application note #302, with 1.6 grams of Al2O3 used for each experiment. The following properties of hexane, and the probe liquids, were important for this work: Liquid Overall Surface Tension (mN/m) Polar Component Dispersive Component (mN/m) (mN/m) Density Viscosity (g/cm3) (cp) n-Hexane 18.4 0.0 18.4 0.661 0.33 Ethylene Glycol 47.7 21.3 26.4 1.109 15.1 Water 72.8 46.4 26.4 0.998 1.00 And, the following material constant and contact angle values were obtained (raw mass2 versus time data from all experiments also attached in graphical form). 66 Test # Material Constant and Contact Angle Values for Al2O3 1.6 gram packs in a Standard FL12 Contact Angle Contact Angle Material Constant With With With Hexane Water Ethylene Glycol (cm5) (degrees) (degrees) 1 6.9301 x 10-5 19.3 53.4 2 6.8575 x 10-5 18.7 53.6 Average 6.8938 x 10-5 19.0 53.5 Applying the Fowkes method to these data yields the following surface energy values for the Al2O3 powder: Al2O3 - Surface Energy Components Surface Energy Al2O3(mJ/m2) Overall 44.95 Polar 27.79 Dispersive 17.16 % Surface Polarity 61.81 So, what we have learned from the surface energy characterizations on Al and Al2O3 is that Al has a relatively low surface energy (34.04 mJ/m2) and surface polarity (10.07%) compared to Al2O3, which has a surface energy of 44.95 mJ/m2 and a surface polarity of 61.81%. This trend represents the expected effect of oxidizing a surface. Item 2 – Water Displacement by CPC’s From the surface characterization data given above, it is now possible to calculate interfacial tension values between each of the CPC’s, as well as water, and the two solid surfaces we have studied. This is done using Good’s equation (first equation on page 7 of my “So You Want to Measure Surface Energy?” technical note), with the following results: Liquid/Solid Interfacial Tensions Between CPC’s and Water and Al and Al2O3 Al So Sure LPS3 AV30 AV8 Water (mN/m) (mN/m) (mN/m) (mN/m) (mN/m) 1.11 2.32 3.28 1.04 67 24.76 Al2O3 13.80 8.32 5.95 11.13 3.36 In cases where the interfacial tension for a CPC against a surface is calculated to be less than the interfacial tension between water and that same surface, it is thermodynamically favorable to replace a water/surface interface with a CPC/surface interface. Please note, that this is the case for every CPC on a fresh Al surface, but for none of CPC’s on an Al2O3 surface (model oxidized Al surface). Also note that, the leading CPC’s, in terms of low interfacial tension on the Al surface, are, of course, the low surface polarity CPC’s (So Sure and AV8). And, on the Al2O3 surface, the leading CPC’s, in terms of low interfacial tension, are the ones with higher surface polarity (LPS3 and AV30). This is due to surface polarity matching. The best adhesion (lowest interfacial tensions) occur when the liquid and solid in question have very similar surface polarities. Thus, So Sure (10.9% surface polarity) and AV8 (15.8% surface polarity) are more compatible with the Al surface (10.1% surface polarity). And, LPS3 (25.3% surface polarity) and AV30 (33.3% surface polarity) are more compatible with Al2O3 (61.8% surface polarity). However, none of the CPC’s matches the surface polarity of the Al2O3 as well as water (63.7% surface polarity) does. What does this mean to the actual displacement of water from these surfaces by the CPC’s? To answer that question completely, we actually need one more piece of information, which we will follow with a direct measurement of the displacement capabilities of each CPC, as justification that all this theory still makes good sense! The other piece of information necessary is the interfacial tension between water and each of the CPC’s, since when water is displaced by a CPC, there is not just an exchange of a water/surface interface for a CPC/surface interface. There is also a CPC/water interface created, during displacement. Interfacial tensions were measured between each of your CPC’s and water by the pendant drop method. The measurement procedure for this work was equivalent to that used for the pendant drop surface tension experiments described above – except that instead of a drop of CPC being formed air (to measure surface tension), it is formed on the end of an upward facing capillary tip submerged in water (so that interfacial tension is measured). In five-drop experiments, the following data was collected: 68 Interfacial Tensions for CPC’s Against Water Measured by the Pendant Drop Technique Drop # So Sure LPS 3 AV30 AV8 (mN/m) (mN/m) (mN/m) (mN/m) 1 7.78 3.35 3.00 4.77 2 7.85 3.51 3.08 4.80 3 7.73 3.38 3.07 4.69 4 7.83 3.38 2.96 4.77 5 7.79 3.47 3.06 4.75 Average 7.80 3.42 3.03 4.76 Std. Dev. 0.05 0.07 0.05 0.04 You will note that the trend in the interfacial tension values, from high to low, is: So Sure > AV8 > LPS 3 > AV30 This is completely expected, based on the relative surface polarities of the CPC’s, which follow the inverse trend: So Sure (10.9%) < AV8 (15.8%) < LPS 3 (25.3%) < AV30 (33.3%) The more surface polarity a CPC has, the more compatible with water (surface polarity of 63.7%) it would be expected to be. Finally, with the CPC/water interfacial tension information in hand, we can calculate what I believe is the definitive data characterizing how capable each CPC is of displacing water from Al and Al2O3 surfaces. That is, free energies for water displacement. These free energies can be calculated by adding together the relevant CPC/Water interfacial tension and the CPC/surface interfacial tension given above (to give the final condition, following the water displacement process) and subtracting the relevant water/surface interfacial tension (initial condition). Negative free energy results indicate that it is thermodynamically favorable for a CPC to displace water from the surface. Positive results indicate that displacement of water is unfavorable. And, the magnitude of the result indicates the magnitude of the favorability or unfavorability, relative to the other values calculated. 69 Example: To calculate the free energy for So Sure displacing water from Al, we take the interfacial tension between So Sure and water (7.80 mN/m), add the interfacial tension between So Sure and Al (1.11 mN/m), and subtract the interfacial tension between water and Al (24.76 mN/m) – to find that So Sure is favored to displace water from Al by (15.85 mN/m). Free energy of water displacement results for each of the CPC’s for Al and Al2O3 are as follows: Free Energies for Water Displacement by CPC’s So Sure 2 LPS 3 AV30 2 2 AV8 (mJ/m ) (mJ/m ) (mJ/m ) (mJ/m2) Al -15.85 -19.02 -18.45 -18.96 Al2O3 18.24 8.38 5.62 12.53 From this data, you see that all four CPC’s are favored to displace water from Al, but not from Al2O3, since water adheres strongly to Al2O3, because Al2O3 has a surface polarity very similar to that of water. You should also note that the magnitude of disfavorability for water displacement from Al2O3 follows inversely the trend on CPC surface polarity. So Sure (10.9%) > AV8 (15.8%) > LPS 3 (25.3%) > AV30 (33.3%) Some statements about the relative utility of each CPC, with regard to how extensively oxidized of an aluminum surface each CPC, should be able to coat (displace water from) can be developed from this data - without a whole lot of imagination. And, I will develop such a thought for you shortly. However, first let’s justify the values calculated above, with some experimental data. One of original purposes of this project was to consider water displacement in lap joints. And, I said that, to have any chance of penetrating a lap joint (and of displacing water in such a joint) a CPC must exhibit, at the very least, a less than 90o contact angle on an aluminum surface submerged in water – as per the diagram below. Al CPC θ Water What may have gotten lost, in the mathematics of the free energy calculations that I presented above, is another fact that a 90o contact angle, in this situation, is also the 70 condition under which the free energy for water displacement by a CPC is equal to 0 mJ/m2 . In other words, in cases where the free energy for water displacement by a CPC is negative, the contact angle, measured as shown above, should be less than 90o. And, furthermore, the actual contact angle measured in such an experiment, and the magnitude of the free energy for water displacement, should have a trend-wise relationship. The more negative (favorable) the free energy of the displacement – the lower the contact angle should be. We actually measured such contact angles for each of your CPC’s displacing water from an aluminum surface, with the following results. Contact Angles for CPC’s on Aluminum Submerged in Water So Sure LPS 3 AV30 AV8 Drop # (degrees) (degrees) (degrees) (degrees) 1 32.7 13.8 23.2 17.2 2 33.0 13.8 24.0 17.5 3 32.8 13.6 24.1 17.6 4 32.3 13.6 23.4 16.9 5 32.3 13.2 23.5 17.2 Average 32.6 13.6 23.6 17.3 Std. Dev. 0.5 0.7 0.7 0.5 I am pleased to note that all of the contact angles are fairly low, such that the displacement of water is very favorable – which seems good for lap joint penetration, with LPS 3 leading the pack with the lowest angle. The lower the angle, the better capillary-based penetration into lap joints should be. (None of the angles was found to be particularly dynamic in nature. They all developed an equilibrium values just as soon as the CPC was applied. So the dynamic aspect of this study was not completed.) However, I am maybe even more pleased to observe that the contact angle trend does follow the free energy trend: So Sure (-15.85, 32.6o)> AV30 (-18.45, 23.6o)> AV8 (-18.96, 17.3o)> LPS 3 (-19.02, 13.6o) We cannot, of course, check the same trend on the Al2O3 , because there is no good way to measure the contact angle for CPC’s displacing water from a powder – particularly since the surface energy data tells us that the CPC’s will have contact angles of greater than 90o, in this situation. 71 However, verifying the trend with Al gives me enough confidence to make some statements about the relative utility of each CPC, with regard to how extensively oxidized of an aluminum surface each CPC should be able to coat (displace water from). Using the data above, and assuming that there is a linear progression from the surface properties of unoxidized Al to Al2O3 (which I will assume to be representative of complete oxidation) with % oxidation, one can easily develop the following table. Free Energies for Water Displacement by CPC’s on Theoretical Surfaces Oxidation So Sure LPS 3 AV30 AV8 % (mJ/m2) (mJ/m2) (mJ/m2) (mJ/m2) Al (0%) -15.85 -19.02 -18.45 -18.96 5% -14.15 -17.65 -17.24 -17.38 10% -12.44 -16.28 -16.04 -15.81 15% -10.74 -14.91 -14.84 -14.24 20% -9.03 -13.54 -13.63 -12.66 25% -7.33 -12.17 -12.43 -11.09 30% -5.62 -10.80 -11.23 -9.51 35% -3.92 -9.43 -10.02 -7.94 40% -2.22 -8.06 -8.82 -6.36 45% -0.51 -6.69 -7.62 -4.79 50% 1.19 -5.32 -6.41 -3.21 55% 2.90 -3.95 -5.21 -1.64 60% 4.60 -2.58 -4.01 -0.07 65% 6.31 -1.21 -2.80 1.51 70% 8.01 0.16 -1.60 3.08 75% 9.71 1.53 -0.40 4.66 80% 11.42 2.90 0.81 6.23 72 85% 13.12 4.27 2.01 7.81 90% 14.83 5.64 3.21 9.38 95% 16.53 7.01 4.42 10.95 Al2O3 (100%) 18.24 8.38 5.62 12.53 This table implies that So Sure is capable of displacing water from aluminum that is up to 45% oxidized. LPS 3 is capable of displacing water from aluminum that is up to 65% oxidized. AV30 is capable of displacing water from aluminum that is up to 75% oxidized. And, AV8 is capable of displacing water from aluminum that is up to 60% oxidized. However, penetration into lap joints will require free energy values lower than 0 mJ/m2. The lower the better, to promote capillary joint penetration. Item 3 – Water Emulsification in a CPC We had talked about the idea that a good CPC might very well also need to be a good emulsifier of water, in addition to having good water displacement properties, and capillary spreading action. At this point, we actually have already collected data on the emulsification abilities of CPC’s, in the process of looking at other aspects. This data takes the form of the CPC/water interfacial tension values. And, lower interfacial tension is to be considered better –since interfacial tension is a direct measure of the amount of work necessary to create interface (emulsify). The results were as follows (listed from best to worst emulsifier): AV30 (3.03 mN/m) > LPS3 (3.42 mN/m) > AV8 (4.76 mN/m) > So Sure (7.80 mN/m) And, of course, the interfacial tension trend follows inversely the surface polarity trend for the CPC’s. More surface polarity = better compatibility with water = better emulsification ability. Conclusions So, which is the best CPC? Overall, I’d say the data predict that AV30 is the most versatile. It has the lowest interfacial tension with water (3.03 mJ/m2) due having the highest surface polarity, so it can emulsify water the best. It is predicted to be able to displace water on Al surfaces all the way up to 75% oxidized. And, it has a fairly reasonable displacement angle for joint penetration on water covered Al (23.6o). However, in certain situations, LPS3 and AV8 also have their merits, based on the data. The oxidation state chart, as well as the water displacement contact angle values measured, indicate that LPS3 (13.6o contact angle for water displacement on Al) may well be a superior joint penetrator to AV30, at least for Al surfaces that are oxidized less than about 20%. AV8 (17.3o contact angle for water displacement on Al) may also be preferable to AV30 up to about 10% surface oxidation, again for its superior joint 73 penetration. However, in both cases water emulsification ability is sacrificed, relative to AV30. In the end, however, if you were to design a new CPC, the bulk of this data suggests that surface polarity of the CPC is the overriding aspect. You want a low surface tension (to promote wetting and spreading), but high surface polarity (to promote water emulsification and water displacement from oxidized surfaces) product. I hope this data proves useful for you. If you have questions or comments about it, or if you wish to contract for further analyses, please let me know. The charge for this work is $2500 (4 liquid surface tension component experiments @ $200 each, 1 solid surface energy determination @ $200, 1 powder surface energy determination @ $500, 4 three-phase contact angle experiments @ $150 each, and 4 liquid/liquid interfacial tension experiments @ $100 each). That sum will be invoiced against your P.O. number P11212F. Best Regards, Christopher Rulison, Ph.D. Laboratory Manager 1 B. Hinton, et al., 4th International Aerospace Corrosion and Control Symposium, Jakarta, Indonesia, June 1996 2 L. B. Simon, J. L. Elster, R. G. Kelly, “Quantitative Studies of the Effectiveness of Corrosion Protection Compounds Used in Lap Splice Joints, “ Proc. of 2000 ASIP Conference, San Antonio (2000). 3 Karen S. Lewis, Determination of the Corrosion Conditions Within Aircraft Lap-Splice Joints, Master Thesis, University of Virginia, 1999 4 J. A. Gonzalez, E. Otero, A. Bautista, E. Almeida, M. Morcillo, “Use of electrochemical impedance spectroscopy for studying corrosion at overlapped joints”, Progress in Organic Coatings, 33, 61, (1998) 5 Hermenz, C. Paul, Rajagopalan, Raj; Principles of Colloid and Surface Chemistry, 3rd edition; 1997 6 Fowkes, F.M.; Industrial and Engineering Chemistry, 56,12,40, (1964) 7 Good, R.J.; Firifalco, L.A.; J. Phys. Chem., 64, 561, (1960) 74
© Copyright 2026 Paperzz