RADON SCREENING SURVEY – FOLLOW-UP RACHEL CARSON ELEMENTARY SCHOOL 100 Tschiffely Square Road, Gaithersburg, Maryland 20878 EXECUTIVE SUMMARY Date of Test Report: Round of Testing: 3/15/16 Follow-Up Initial Follow-up Post Remediation # Rooms Tested # Rooms > 4.0 pCi/L: Low Value: High Value: Confirmed Rooms ≥ 4.0 pCi/L US EPA Action Level 1 0 <0.3 <0.3 0 Summary of Sampling Events ≥ 4.0 pCi/L Room 100 Result (pCi/L) 2/4/16 (Rev 1 Initial) <0.3 Tampered Result (pCi/L) 3/15/16 Follow-Up <0.3 Average Result (pCi/L) <0.3 E NGIN E E R S • P LAN NE R S • S C I E N TI S T S • C ON S TR UC TI ON M AN AG ER S 936 RIDGEBROOK ROAD • SPARKS, MD 21152 • 410-316-7800 • (FAX) 410-316-7935 MCPS RADON TESTING Executive Summary: Rachel Carson Elementary School Date of Test Report: Round of Testing: # Rooms Tested: # Rooms ≥ 4.0 pCi/L: Low Value: High Value: 3/15/2016 Initial Follow-up Post Remediation 1 0 < 0.3 < 0.3 Project Status: Retesting completed; no further action at this time. KC I T E C H N O L O G I E S , I N C . www.kci.com Employee-Owned Since 1988 E NGIN E E R S • P LAN NE R S • S C I E N TI S T S • C ON S TR UC TI ON M AN AG ER S 936 RIDGEBROOK ROAD • SPARKS, MD 21152 • 410-316-7800 • (FAX) 410-316-7935 March 15, 2016 Mr. Richard Cox Indoor Air Quality Team Leader Montgomery County Public Schools 850 Hungerford Drive Rockville, MD 20850 Re: Radon Testing Services KCI Job # 12146341.29 Location: Rachel Carson Elementary School 100 Tschiffely Square Road Gaithersburg, MD 20878 Dear Mr. Cox: KCI Technologies, Inc. (KCI) is pleased to submit the following report to the Montgomery County Public Schools (MCPS) pursuant to completing a “short-term” 3 day radon test for the Rachel Carson Elementary School, located at 100 Tschiffely Square Road in Gaithersburg, Maryland 20878 (subject site). Scope of Services: KCI conducted radon testing at the subject site to evaluate indoor radon levels relative to the USEPA's recommended action level of 4.0 picocuries per Liter (pCi/L) - the level at which EPA recommends that schools take action to reduce the level. KCI conducted the radon testing in accordance with American Association of Radon Scientists and Technologists (AARST) Protocol for Conducting Measurements of Radon and Radon Decay Products in Schools and Large Buildings. A National Radon Safety Board (NRSB) Radon Measurement Specialist (certification #14SS056) supervised the testing. Additional information on radon management and the health effects of radon exposure is available from www.montgomerycountymd.gov/dep/air/radon or www.epa.gov/radon. KCI visited the site on February 23, 2016 and deployed four (4) activated charcoal (AC) radon test kits. KCI deployed radon test kits in frequently-occupied ground contact rooms, and other areas, (if applicable) in accordance with AARST guidance. A floor plan map of the building with the test locations is included as Attachment A of this report. As a quality control measure, KCI included duplicate samples, field blanks, lab transit blanks, and office blanks in accordance with AARST recommendations. In addition, KCI submitted six (6) test kits to Bowser-Morner, Inc. as spike samples. The spiked tests were exposed to a known radon concentration by Bowser-Morner prior to being returned to the laboratory for analysis. KCI returned to the site on February 26, 2016 to retrieve the radon sampling test kits. KCI shipped all radon tests via overnight delivery to Airchek, Inc. for analysis by gamma-ray spectroscopy. Airchek, Inc. KC I T E C H N O L O G I E S , I N C . www.kci.com Employee-Owned Since 1988 Mr. Richard Cox March 15, 2016 Page 3 is a NRSB certified analytical laboratory for radon analysis (certification # ARL1402) located at 1936 Butler Bridge Road, Mills River, North Carolina. Evaluation of Testing Conditions: The operating condition that represents the greatest amount of significantly occupied time for this building is; heating active, with outdoor temperature averages ≤ 65° F. KCI concludes that the test period reasonably represents normal conditions when the building is significantly occupied. Clear characterization of the radon hazard is most likely to be observed under this normal operating condition. Based on the evaluation of test conditions, this test should reasonably characterize radon hazards. KCI also conducted observations of field conditions which could affect the results of the test and compiled weather data for the testing period. Note that strong storms and heavy rainfall were recorded during the test period. The unusual weather conditions may have resulted in atypical radon test results for this facility. KCI recorded observations of the following conditions in each room at the time of deployment and collection of the radon test kits: • • • • • • Indoor temperature, HVAC Operation, Dehumidifier operation, Humidifier operation, Ceiling fan operation, and Open windows or doors. Results: The results of the radon test analysis indicated the following: Radon Concentration ≥4.0 piC/L <4.0 piC/L Room none Result n/a See Attachment B Notes: D- Duplicate sample The field blank, office blanks, and lab transit blanks had test results of less than the laboratory detection limit of 0.3 pCi/L. Review of the duplicate sample analysis indicates that adequate laboratory measurement precision was achieved. The Spike sample analysis results indicate the laboratory is operating within statistical control limits. The sampling locations, field observations, and analytical results are listed on Table 1 (Attachment B). The laboratory analytical results are also attached (Attachment C). Laboratory results and exposure data for the spike samples are also included in Attachment C. Our professional services have been performed in accordance with customary principles and practices in the field of industrial hygiene and engineering. If you have any questions or comments regarding this report, please feel free to contact me at (410) 316-7800. KC I T E C H N O L O G I E S , I N C . www.kci.com Employee-Owned Since 1988 Mr. Richard Cox March 15, 2016 Page 4 Sincerely, James M. Moulsdale Radon Measurement Specialist KCI Technologies, Inc. Attachments: A- Floor Plan with Test Locations B- Table 1-Radon Test Summary Spreadsheet C- Laboratory Analytical Results KC I T E C H N O L O G I E S , I N C . www.kci.com Employee-Owned Since 1988 ATTACHMENT A Floor Plan With Test Locations ATTACHMENT B Radon Test Summary Spreadsheet Table Notes: AC- Activated Charcoal ACI- Air Chek, Inc. D- Duplicate FB- Field Blank KCI- KCI Technologies, Inc. OB- Office Blank* PM- Project Manager QC- Quality Control *Office blanks were submitted at a rate of 1% for all samples deployed in Phase 9 testing. Office blanks were not submitted under each school individually. Radon Testing Results Rachel Carson Elementary School Test Period: 02/23/16-02/26/16 Kit Number 7729914 7729916 Table Note: * Missing or Compromised Sample Room / Area 100 100 Result < 0.3 < 0.3 Radon Testing Results Rachel Carson Elementary School Test Period: 02/23/16-02/26/16 Kit Number 7732167 7729921 Table Note: * Missing or Compromised Sample QC Type D (100) FB (100) Result < 0.3 < 0.3 ATTACHMENT C Laboratory Analytical Results March** LABORATORY ANALYSIS 8, REPORT ** 2016 Radon test result report for: RACHEL CARSON ELEMENTARY SCHOOL MAIN Kit # 7729914 7729916 7729921 7732167 Room Id 100 100 100 100 Started 2016-02-23 @ 10:00 am 2016-02-23 @ 10:00 am 2016-02-23 @ 10:00 am 2016-02-23 @ 10:00 am Ended 2016-02-26 @ 8:00 am 2016-02-26 @ 8:00 am 2016-02-26 @ 8:00 am 2016-02-26 @ 8:00 am pCi/L < 0.3 < 0.3 < 0.3 < 0.3 Analyzed 2016-03-01 2016-03-01 2016-03-01 2016-03-01 Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498 March** LABORATORY ANALYSIS 9, REPORT ** 2016 Radon test result report for: MCPS Phase 9 Office Blanks Kit # 7712568 7712584 7719460 7719481 7719497 7719498 Room Id 0 0 0 0 0 0 Started 2016-02-22 @ 6:00 pm 2016-02-22 @ 6:00 pm 2016-02-22 @ 6:00 pm 2016-02-22 @ 6:00 pm 2016-02-22 @ 6:00 pm 2016-02-22 @ 6:00 pm Ended 2016-02-25 @ 3:00 pm 2016-02-25 @ 3:00 pm 2016-02-25 @ 3:00 pm 2016-02-25 @ 3:00 pm 2016-02-25 @ 3:00 pm 2016-02-25 @ 3:00 pm pCi/L < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 Analyzed 2016-02-29 2016-02-29 2016-02-29 2016-02-29 2016-02-29 2016-02-29 Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498 March** LABORATORY ANALYSIS 9, REPORT ** 2016 Radon test result report for: MCPS Phase 9 Office Blanks Kit # 7731626 7731633 7735204 Room Id 0 0 0 Started 2016-02-23 @ 2:00 pm 2016-02-23 @ 2:00 pm 2016-02-23 @ 2:00 pm Ended 2016-02-26 @ 3:00 pm 2016-02-26 @ 3:00 pm 2016-02-26 @ 3:00 pm pCi/L < 0.3 < 0.3 < 0.3 Analyzed 2016-03-01 2016-03-01 2016-03-01 Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498 February 23, ** LABORATORY ANALYSIS REPORT ** 2016 Radon test result report for: TRANSIT- PHASE 7, 8, 9 NONE Kit # 7734937 7734946 7734955 7734956 7734959 7734930 7734953 7734954 7734940 7734949 7734948 7734939 7734942 7734929 7734933 7734934 7734936 7734943 7734944 7734935 7734928 7734952 7734947 7734931 7734932 7718520 7718523 7718522 7718521 7734945 7734960 7734958 7734951 7734957 7734938 Room Id 1 10 11 12 13 14 15 16 17 18 19 2 20 21 22 23 24 25 26 27 28 29 3 30 31 32 33 34 35 4 5 6 7 8 9 Started 2016-02-19 @ 3:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 3:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 3:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 3:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm 2016-02-19 @ 4:00 pm Ended 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am 2016-02-22 @ 11:00 am pCi/L < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 Analyzed 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 2016-02-23 Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498 February 15, ** LABORATORY ANALYSIS REPORT ** 2016 Spike Sample Laboratory Results Radon test result report for: MCPS Kit # 7718273 7718281 7718282 7718288 7718289 7718291 Room Id 101A 102B 103C 104D 105E 106F Started 2016-01-30 @ 9:00 am 2016-01-30 @ 9:00 am 2016-01-30 @ 9:00 am 2016-01-30 @ 9:00 am 2016-01-30 @ 9:00 am 2016-01-30 @ 9:00 am Ended 2016-02-01 @ 9:00 am 2016-02-01 @ 9:00 am 2016-02-01 @ 9:00 am 2016-02-01 @ 9:00 am 2016-02-01 @ 9:00 am 2016-02-01 @ 9:00 am pCi/L 6.5 ± 0.6 6.4 ± 0.6 6.3 ± 0.6 6.7 ± 0.6 6.6 ± 0.6 6.5 ± 0.6 Analyzed 2016-02-04 2016-02-04 2016-02-04 2016-02-04 2016-02-04 2016-02-04 Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498 Note: Spike samples are test canisters that are deliberately exposed to a controlled high level of radon in a laboratory. They provide a quality control measure in the testing process and do NOT reflect radon levels in the building being tested. E NGIN E E R S P LAN NE R S S C I E N TI S T S C ON S TR UC TI ON M AN AG ER S 936 RIDGEBROOK ROAD SPARKS, MD 21152 410-316-7800 (FAX) 410-316-7935 MCPS RADON TESTING Executive Summary: Rachel Carson Elementary School Date of Test Report: Round of Testing: # Rooms Tested: # Rooms ≥ 4.0 pCi/L: Low Value: High Value: 2/04/2016 (Rev 1) Initial Follow-up Post Remediation 58 0 < 0.3 0.6 Project Status: Initial testing completed; compromised samples need re-test. KC I T E C H N O L O G I E S , I N C . www.kci.com Employee-Owned Since 1988 E NGIN E E R S P LAN NE R S S C I E N TI S T S C ON S TR UC TI ON M AN AG ER S 936 RIDGEBROOK ROAD SPARKS, MD 21152 410-316-7800 (FAX) 410-316-7935 February 4, 2016 (Rev 1) Mr. Richard Cox Indoor Air Quality Team Leader Montgomery County Public Schools 850 Hungerford Drive Rockville, MD 20850 Re: Radon Testing Services KCI Job # 12146341.24 Location: Rachel Carson Elementary School 100 Tschiffely Square Road Gaithersburg, MD 20878 Dear Mr. Cox: KCI Technologies, Inc. (KCI) is pleased to submit the following report to the Montgomery County Public Schools (MCPS) pursuant to completing a “short-term” 3 day radon test for the Rachel Carson Elementary School, located at 100 Tschiffely Square Road in Gaithersburg, Maryland 20878 (subject site). Scope of Services: KCI conducted radon testing at the subject site to evaluate indoor radon levels relative to the USEPA's recommended action level of 4.0 picocuries per Liter (pCi/L) - the level at which EPA recommends that schools take action to reduce the level. KCI conducted the radon testing in accordance with American Association of Radon Scientists and Technologists (AARST) Protocol for Conducting Measurements of Radon and Radon Decay Products in Schools and Large Buildings. A National Radon Safety Board (NRSB) Radon Measurement Specialist (certification #14SS056) supervised the testing. Additional information on radon management and the health effects of radon exposure is available from www.montgomerycountymd.gov/dep/air/radon or www.epa.gov/radon. KCI visited the site on January 11, 2016 and deployed sixty-nine (69) activated charcoal (AC) radon test kits. KCI deployed radon test kits in frequently-occupied ground contact rooms, and other areas, (if applicable) in accordance with AARST guidance. A floor plan map of the building with the test locations is included as Attachment A of this report. As a quality control measure, KCI included duplicate samples, field blanks, lab transit blanks, and office blanks in accordance with AARST recommendations. In addition, KCI submitted six (6) test kits to Bowser-Morner, Inc. as spike samples. The spiked tests were exposed to a known radon concentration by Bowser-Morner prior to being returned to the laboratory for analysis. KCI returned to the site on January 14, 2016 to retrieve the radon sampling test kits. KCI shipped all radon tests via overnight delivery to Airchek, Inc. for analysis by gamma-ray spectroscopy. Airchek, Inc. KC I T E C H N O L O G I E S , I N C . www.kci.com Employee-Owned Since 1988 Mr. Richard Cox February 4, 2016 Page 3 is a NRSB certified analytical laboratory for radon analysis (certification # ARL1402) located at 1936 Butler Bridge Road, Mills River, North Carolina. Evaluation of Testing Conditions: The operating condition that represents the greatest amount of significantly occupied time for this building is; heating active, with outdoor temperature averages ≤ 65° F. KCI concludes that the test period reasonably represents normal conditions when the building is significantly occupied. Clear characterization of the radon hazard is most likely to be observed under this normal operating condition. Based on the evaluation of test conditions, this test should reasonably characterize radon hazards. KCI also conducted observations of field conditions which could affect the results of the test and compiled weather data for the testing period. KCI recorded observations of the following conditions in each room at the time of deployment and collection of the radon test kits: Indoor temperature, HVAC Operation, Dehumidifier operation, Humidifier operation, Ceiling fan operation, and Open windows or doors. Results: The results of the radon test analysis indicated the following: Radon Concentration ≥4.0 piC/L <4.0 piC/L Room none Result n/a See Attachment B Notes: D- Duplicate sample All field blanks, office blank, and lab transit blanks had test results of less than the laboratory detection limit of 0.3 pCi/L. Review of the duplicate sample analysis indicates that adequate laboratory measurement precision was achieved. The Spike sample analysis results indicate the laboratory is operating within statistical control limits. The sampling locations, field observations, and analytical results are listed on Table 1 (Attachment B). The laboratory analytical results are also attached (Attachment C). Laboratory results and exposure data for the spike samples are also included in Attachment C. Our professional services have been performed in accordance with customary principles and practices in the field of industrial hygiene and engineering. If you have any questions or comments regarding this report, please feel free to contact me at (410) 316-7800. KC I T E C H N O L O G I E S , I N C . www.kci.com Employee-Owned Since 1988 Mr. Richard Cox February 4, 2016 Page 4 Sincerely, H. Allen Bennett Certified Industrial Hygienist KCI Technologies, Inc. Attachments: A- Floor Plan with Test Locations B- Table 1-Radon Test Summary Spreadsheet C- Laboratory Analytical Results KC I T E C H N O L O G I E S , I N C . www.kci.com Employee-Owned Since 1988 ATTACHMENT B Radon Test Summary Spreadsheet Radon Testing Results Rachel Carson Elementary School Test Period: 01/11/16-01/14/16 Kit Number 7719367 7719322 7719352 7719350 7719348 7719355 7719342 7719341 7719325 7719345 7719346 7719339 7719358 7719332 7719333 7719363 7719312 7719327 7719310 7719323 7719336 7719320 7719304 7719356 7719324 7719328 7719313 7719337 7719334 7719329 7719347 7719359 7719330 7719361 7719369 7719360 7719331 7719385 7719371 7719382 7719383 7719378 7719375 7719380 7719377 7719374 Table Note: * Missing or Compromised Sample Room / Area 100 101 102 103 108 110 112 114 114 119 120 121 122 122 123 124 126 127 128 129 130 131 132 138 139 140 141 142 143 144 145 146 147 148 149 150 151 201 203 227 228 236 914 1033 1081 1086 Result < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 0.5 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 Radon Testing Results Rachel Carson Elementary School Test Period: 01/11/16-01/14/16 Kit Number 7719384 7719372 7719381 7719376 7719379 7719321 7719368 7719366 7719353 7719354 7719349 7719362 7719335 7719338 7719344 Table Note: * Missing or Compromised Sample * Room / Area 1087 1089 1090 1093 1094 1982 100 (Tampered) 100A 101A 101B 101C 102A 108A 121A 122B Result < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 0.6 Radon Testing Results Rachel Carson Elementary School Test Period: 01/11/16-01/14/16 Kit Number 7719364 7719373 7719326 7719351 7719357 7719343 7719340 7719370 Table Note: * Missing or Compromised Sample QC Type D (100A) D (1089) D (110) D (123) D (131) FB (121A) FB (129) OB (0) Result < 0.3 < 0.3 0.6 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 Table Notes: AC- Activated Charcoal ACI- Air Chek, Inc. D- Duplicate FB- Field Blank KCI- KCI Technologies, Inc. OB- Office Blank PM- Project Manager QC- Quality Control ATTACHMENT C Laboratory Analytical Results February ** LABORATORY ANALYSIS 1, REPORT ** 2016 Radon test result report for: RACHEL CARSON ELEMENTARY SCHOOL MAIN Kit # 7719367 7719368 7719364 7719366 7719322 7719353 7719354 7719349 7719352 7719362 7719350 7719348 7719335 7719326 7719355 7719342 7719325 7719341 7719345 7719346 7719339 7719338 7719343 7719358 7719332 7719344 7719351 7719333 7719363 7719312 7719327 7719310 7719323 7719340 7719336 7719357 7719320 Room Id 100 100 100A 100A 101 101A 101B 101C 102 102A 103 108 108A 110 110 112 114 114 119 120 121 121A 121A 122 122 122B 123 123 124 126 127 128 129 129 130 131 131 Started 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 12:00 pm 2016-01-11 @ 12:00 pm 2016-01-11 @ 12:00 pm 2016-01-11 @ 12:00 pm 2016-01-11 @ 12:00 pm 2016-01-11 @ 12:00 pm 2016-01-11 @ 12:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm Ended 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 11:00 am 2016-01-14 @ 11:00 am 2016-01-14 @ 11:00 am 2016-01-14 @ 1:00 pm 2016-01-14 @ 11:00 am 2016-01-14 @ 11:00 am 2016-01-14 @ 11:00 am 2016-01-14 @ 11:00 am 2016-01-14 @ 11:00 am 2016-01-14 @ 11:00 am 2016-01-14 @ 11:00 am 2016-01-14 @ 11:00 am 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm pCi/L < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 0.6 ± 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 0.6 ± 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 Analyzed 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-18 2016-01-19 2016-01-19 2016-01-18 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-18 2016-01-19 2016-01-19 2016-01-18 2016-01-19 2016-01-18 2016-01-19 2016-01-19 2016-01-18 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498 February ** LABORATORY ANALYSIS 1, REPORT ** 2016 Radon test result report for: RACHEL CARSON ELEMENTARY SCHOOL MAIN Kit # 7719304 7719356 7719324 7719328 7719313 7719337 7719334 7719329 7719347 7719359 7719330 7719361 7719369 7719360 7719331 7719385 7719371 7719382 7719383 7719378 Room Id 132 138 139 140 141 142 143 144 145 146 147 148 149 150 151 201 203 227 228 236 Started 2016-01-11 @ 2:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 1:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm Ended 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm pCi/L < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 0.5 ± 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 Analyzed 2016-01-19 2016-01-18 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-18 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-19 2016-01-18 2016-01-19 2016-01-18 Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498 February ** LABORATORY ANALYSIS 1, REPORT ** 2016 Radon test result report for: RACHEL CARSON ELEMENTARY SCHOOL PORTABLE Kit # 7719370 7719380 7719377 7719374 7719384 7719373 7719372 7719381 7719376 7719379 7719321 7719375 Room Id 0 1033 1081 1086 1087 1089 1089 1090 1093 1094 1982 914 Started 2016-01-11 @ 4:00 pm 2016-01-11 @ 3:00 pm 2016-01-11 @ 3:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 3:00 pm 2016-01-11 @ 3:00 pm 2016-01-11 @ 3:00 pm 2016-01-11 @ 3:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 2:00 pm 2016-01-11 @ 3:00 pm 2016-01-11 @ 3:00 pm Ended 2016-01-14 @ 4:00 pm 2016-01-14 @ 1:00 pm 2016-01-14 @ 1:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 12:00 pm 2016-01-14 @ 1:00 pm 2016-01-14 @ 12:00 pm pCi/L < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 Analyzed 2016-01-19 2016-01-19 2016-01-19 2016-01-18 2016-01-19 2016-01-18 2016-01-19 2016-01-18 2016-01-19 2016-01-18 2016-01-19 2016-01-19 Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498 February ** LABORATORY ANALYSIS 2, REPORT ** 2016 Radon test result report for: MCPS PHASE 5 & 6 TRANSIT BLANKS Kit # 7722194 7718494 7718475 7718495 7718496 7718497 7718498 7718499 7718500 7718296 7718295 7722195 7716789 7716785 7716791 7716786 7716793 7718274 7716792 7718294 7718293 7718292 7722197 7718290 7722198 7722199 7722211 7718491 7718476 7718479 Room Id 1 10 11 12 13 14 15 16 17 18 19 2 20 21 22 23 24 25 26 27 28 29 3 30 4 5 6 7 8 9 Started 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm 2016-01-19 @ 12:00 pm Ended 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm 2016-01-22 @ 12:00 pm pCi/L < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 < 0.3 Analyzed 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-26 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-27 2016-01-26 2016-01-27 Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498 December 23, ** LABORATORY ANALYSIS REPORT ** 2015 Spike Sample Laboratory Results Radon test result report for: MCPS Kit # 7706380 7706381 7706208 7705132 7706366 7706211 Room Id 101 102 103 104 105 106 Started 2015-12-18 @ 9:00 am 2015-12-18 @ 9:00 am 2015-12-18 @ 9:00 am 2015-12-18 @ 9:00 am 2015-12-18 @ 9:00 am 2015-12-18 @ 9:00 am Ended 2015-12-21 @ 9:00 am 2015-12-21 @ 9:00 am 2015-12-21 @ 9:00 am 2015-12-21 @ 9:00 am 2015-12-21 @ 9:00 am 2015-12-21 @ 9:00 am pCi/L 25.2 26.5 27.7 28.6 26.5 26.1 Analyzed 2015-12-23 2015-12-23 2015-12-23 2015-12-23 2015-12-23 2015-12-23 Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498 Note: Spike samples are test canisters that are deliberately exposed to a controlled high level of radon in a laboratory. They provide a quality control measure in the testing process and do NOT reflect radon levels in the building being tested.
© Copyright 2026 Paperzz