Waldo 09/03/2013 reinspection

NOTICE OF FIRE SAFETY
INSPECTION
OREGON STATE UNIVERSITY
Facility Inspected: WALDO HALL
Inspection Date: 09/03/2013
Reinspect Date/Time: 00/00/0000
A fire safety inspection of the facility listed above was performed by the Corvallis Fire Prevention
Bureau. These fire safety deficiencies could result in a fire or jeopardize the safety of those occupying
the facility. Please see that these items are corrected immediately. If you have any questions regarding
this inspection, please phone me at 737-3066. Thank you for your cooperation and support for fire
safety. Jim Patton, Fire Prevention Officer, [email protected]
Note: Deficiencies that are bold and underlined remain uncorrected from the last fire/life safety
inspection(s) and should be corrected immediately.
* Annotates a deficiency identified by OSU Environmental Health and Safety Department. Direct any
questions regarding these items to that office (737-2273).
Indicated on the report are items which should be correct by the Departments (DEPT) that occupy this
building, Facilities Services (FS), Environmental Health and Safety (EHS), and Recycling (RECY).
Please forward a copy of this report to the responsible group(s) and begin corrective action to be
completed no later than the reinspection date.
Facilities Services Priority Codes:
Priority 1: (p1) items are considered immediate safety hazards and should be corrected within 48 hours
of notification if possible. If repairs cannot be made immediately, temporary measures may be taken.
Priority 2: (p2) items should be corrected within the five-week period before the scheduled reinspection.
Priority 3: (p3) items are long term fixes that should be either added to an ongoing work list (such as
annual testing of building sprinkler systems) or to the capital improvement list for campus upgrades.
The due date is listed at the top of this page. If you have any questions, require additional information,
or feel the items have been improperly assigned, feel free to contact Jim Patton (Corvallis Fire
Department) at 737-3066. If assistance is required from Facilities Services to estimate or correct an item
assigned to a Department, contact the Work Coordination Center at ext. 7-2969. MS Excel format is
available upon request.
Completed? Priority
[]
[]
[]
[X]0
[X]
[]
2
2
2
FS
2
2
Responsible
Location
Party
FS
DEPT
Description
Code Reference Notes
Change out
red core
locks or
provide red
core key for
Knox box
South
Stairwell
Keys
0413
Discontinue the use
of non-fuse
protected extension
cords in place of
CFC 605.4,
permanent wiring. 605.5
Fuse protected
power strips are
acceptable.
Post State
pressure
vessel permit
if applicable
FS
0408
Pressure vessel
0433
A sprinkler
box, with
spare heads
and a
wrench, is
required.
Provide
sprinkler head
CFC 901.6, NFPA
wrench, and
13
adaptor if
necessary
FS
FS
0433
4th Floor
South and
East Exits
Provide/maintain
exit sign.
OFC 3807.3
Secure metal
hydraulic
calc plates
on riser
CFC 1011
Relocate
EXIT signs
to be visible.
This was
identified at
final.
Completed? Priority
[X]
[]
[]
[]
[X]
2
1
1
2
2
Responsible
Location
Party
Description
Code Reference Notes
DEPT
Near 456
Remove storage
and obstructions
from exits, aisles,
corridors, and
stairs. EXITWAYS
SHALL BE KEPT
CLEAR AT ALL
TIMES.
CFC 315.2.2,
Remove box
1027, htt
from
p://surplus.oreg
hallway
onstate.edu/spr
Third Floor
North
Stairwell
Remove storage
and obstructions
from exits, aisles,
corridors, and
stairs. EXITWAYS
SHALL BE KEPT
CLEAR AT ALL
TIMES.
CFC 315.2.2,
1027,
http://surplus.or
egonstate.edu/sp
r
North
Stairwell at
3rd Floor
Fire protection or
detection systems
shall be extended,
altered, or repaired CFC 901.4
as necessary to
maintain
protection.
Remove tape
from
sprinkler
head
immediately
0330
Fire protection or
detection systems
shall be extended,
altered, or repaired CFC 901.4
as necessary to
maintain
protection.
Remove
cord from
sprinkler
pipe
0301
Discontinue the use
of non-fuse
protected extension
cords in place of
CFC 605.4,
permanent wiring. 605.5
Fuse protected
power strips are
acceptable.
DEPT
FS
DEPT
DEPT
Remove
display
board from
stairwell
Completed? Priority
[]
[X]
[]
[]
[]
2
1
2
2
2
2
Responsible
Location
Party
Description
RECY
Near 321
Combustible
recycling
containers shall not
be placed in
CFC 316.5
exitways.
Containers may be
placed in non
hazardous rooms.
Near 321
Remove storage
and obstructions
from exits, aisles,
corridors, and
stairs. EXITWAYS
SHALL BE KEPT
CLEAR AT ALL
TIMES.
DEPT
DEPT
RECY
DEPT
DEPT
Code Reference Notes
Remove
cardboard
CFC 315.2.2,
from
1027,
hallway.
http://surplus.or
Discontinue
egonstate.edu/sp
placing
r
material in
hallways
0308
Halogen lamp
Near 207
Combustible
recycling
containers shall not
be placed in
CFC 316.5
exitways.
Containers may be
placed in non
hazardous rooms.
0214
Discontinue the use
of non-fuse
protected extension
cords in place of
CFC 605.4,
permanent wiring. 605.5
Fuse protected
power strips are
acceptable.
0214
Plug power strips
directly into outlet.
CFC 605.4.2
Do not chain one to
another.
Remove
halogen
lamp
Multiple
Completed? Priority
[]
[X]
[X]
[X]
[]
2
2
2
2
2
Responsible
Location
Party
Description
DEPT
0214
Fire protection or
detection systems
shall be extended,
altered, or repaired CFC 901.4
as necessary to
maintain
protection.
0238
Discontinue the use
of non-fuse
protected extension
cords in place of
CFC 605.4,
permanent wiring. 605.5
Fuse protected
power strips are
acceptable.
DEPT
FS
DEPT
DEPT
0201A
Code Reference Notes
Remove
items from
fire sprinkler
pipe
OFC 3807.3Post
room capacity at
49. This should
be shared with
campus
classroom
scheduler.
Near 242
Remove
Remove storage
furniture
and obstructions
from
CFC 315.2.2,
from exits, aisles,
hallway or if
1027,
corridors, and
it is to
http://surplus.or
stairs. EXITWAYS
remain
egonstate.edu/sp
SHALL BE KEPT
secure to
r
CLEAR AT ALL
wall
TIMES.
appropriately
.
0282A
Cords shall not be
affixed to, or
extend through,
walls, ceilings,
CFC 605.5
floors, under doors,
and shall not be
subject to physical
damage.
Also remove
ext. cord
Completed? Priority
[X]
[]
[]
[]
2
1
2
2
Responsible
Location
Party
Description
Code Reference Notes
DEPT
Remove storage
and obstructions
from exits, aisles,
corridors, and
Near 251 A
stairs. EXITWAYS
SHALL BE KEPT
CLEAR AT ALL
TIMES.
DEPT
Near 276
Remove storage
and obstructions
from exits, aisles,
corridors, and
stairs. EXITWAYS
SHALL BE KEPT
CLEAR AT ALL
TIMES.
CFC 315.2.2,
1027,
http://surplus.or
egonstate.edu/sp
r
Discontinue
placing
material all
along this
hallway.
Near 262
Remove storage
and obstructions
from exits, aisles,
corridors, and
stairs. EXITWAYS
SHALL BE KEPT
CLEAR AT ALL
TIMES.
CFC 315.2.2,
1027,
http://surplus.or
egonstate.edu/sp
r
Remove
material
from
hallway.
0121
Fire doors/smoke
barriers shall be
maintained and
kept free of
CFC 703.2
obstructions. Doors
shall close and
latch unaided.
DEPT
FS
CFC 315.2.2,
1027,
Remove
http://surplus.or desk from
egonstate.edu/sp hallway
r
As this
office opens
directly into
a 4 story
stairwell,
install a door
closer on the
door.
Completed? Priority
[]
[]
[X]
[X]
[]
2
2
2
2
2
Responsible
Location
Party
FS
FS
RECY
DEPT
FS
Description
Code Reference Notes
Near 100
Fire doors/smoke
barriers shall be
maintained and
kept free of
CFC 703.2
obstructions. Doors
shall close and
latch unaided.
Provide
correct door
hardware on
this door so
it can latch
when it
closes. Panic
hardware
should not
be latched
down.
0145A
Provide cover
plates on all
electrical outlets,
switches, and
junction boxes.
Ceiling
junction
boxes
Near 116
Combustible
recycling
containers shall not
be placed in
CFC 316.5
exitways.
Containers may be
placed in non
hazardous rooms.
Near 115
Remove storage
and obstructions
from exits, aisles,
corridors, and
stairs. EXITWAYS
SHALL BE KEPT
CLEAR AT ALL
TIMES.
Near 141
Fire doors/smoke
barriers shall be
maintained and
kept free of
CFC 703.2
obstructions. Doors
shall close and
latch unaided.
CFC 605.6
CFC 315.2.2,
1027,
http://surplus.or Move ladder
egonstate.edu/sp
r
Adjust both
stairwell fire
doors to
latch upon
closing
Completed? Priority
[X]
[X]
[]
[]
2
2
2
1
Responsible
Location
Party
Description
Code Reference Notes
DEPT
Near 124
Remove storage
and obstructions
from exits, aisles,
corridors, and
stairs. EXITWAYS
SHALL BE KEPT
CLEAR AT ALL
TIMES.
Remove
CFC 315.2.2,
green
1027,
recycling bin
http://surplus.or from
egonstate.edu/sp hallway.
r
Store inside
room.
0130B
Discontinue the use
of non-fuse
protected extension
cords in place of
CFC 605.4,
permanent wiring. 605.5
Fuse protected
power strips are
acceptable.
0139
Discontinue the use
of non-fuse
protected extension
cords in place of
CFC 605.4,
permanent wiring. 605.5
Fuse protected
power strips are
acceptable.
Near 117
Remove storage
and obstructions
from exits, aisles,
corridors, and
stairs. EXITWAYS
SHALL BE KEPT
CLEAR AT ALL
TIMES.
DEPT
DEPT
DEPT
Multiple
cords
CFC 315.2.2,
1027,
Remove
http://surplus.or items from
egonstate.edu/sp hallway
r