HOUSING SERVICES GUIDANCE ON FIRE SAFETY REQUIREMENTS FOR HOUSES IN MULTIPLE OCCUPATION November 2009 November 2009 Page 1 of 24 Date of approval 25/11/09 1 Introduction 1.1 A house in multiple occupation (HMO) is a house or dwelling which is occupied by persons who do not form a single household as defined in Section 258 of the Housing Act 2004. The full definition can be found in Sections 77, 254, 257, 258 – 260 of the Housing Act 2004 (Housing Act 2004). 1.2 The Housing Act 2004 introduced a new method of assessing the conditions in residential accommodation, the Housing, Health and Safety Rating System (HHSRS). Applying these conditions to the various categories of HMO will help to ensure that the property is adequately protected from fire to avoid the presence of category 1 or 2 hazards which may otherwise result in legal action being taken by the Council. 1.3 These notes are for guidance only, a full inspection will be required to determine fire safety requirements for a particular property. The Housing Standards Team should be consulted before undertaking works. 2 2.1 Categories of HMOs covered by these standards Category A – Bedsits 2.1.1 These are houses occupied as individual rooms, bedsits and flatlets which are considered to have a number of rooms for exclusive occupation, not necessarily behind one door. There will be some sharing of amenities, usually bathrooms and/or toilets. In such a house, each occupancy would be rented separately (on a separate tenancy). 2.2 Category B – Shared houses 2.2.1 These are houses occupied on a shared basis. Some would be let to groups of friends on a shared/group tenancy, others will be occupied by individuals on separate tenancies. Each occupant will have their own bedroom, but will share the amenities with the other tenants. This accommodation is typically occupied by groups of students. 2.3 Category C – Lodgings 2.3.1 These are houses catering for not more than two lodgers where the owner is living as his main residence. This is the traditional house let in lodgings where the lodgers share family facilities and meals are provided from the family kitchen. If a property has more than two lodgers, it will be classed as a shared house for the purposes of this standard. 2.4 Category D – Self contained flats 2.4.1 This category includes most houses or buildings which, by erection or conversion, contain dwellings which are self contained and all such dwellings comprise accommodation which is behind one access door off a common area. The dwellings would normally contain all the standard amenities, although it would be possible for some to be unimproved self-contained flats lacking one or more standard amenities. There is no sharing of amenities with occupiers of other dwellings. November 2009 Page 2 of 24 Date of approval 25/11/09 2.4.2 If the house or building containing the self-contained flats is proven to meet modern building regulations, including the provision of appropriate active and passive fire safety measures, then they would not be considered to be within a category of HMO. 2.5 Category E – Hostels and supported housing These types of properties will be dealt with under the most appropriate category of HMO, usually being shared house HMOs. 2.6 Interpretation 2.6.1 The Council accept that not all properties will fall readily into one of the categories detailed above. Whilst these standards will be applied to all HMOs, the Council accept that it may be appropriate, on occasion, to treat a property as comprising a mix of the different Categories. The classification of individual lettings within an HMO and the interpretation of these standards in their application to a mixed Category property shall be at the discretion of the Public Protection Manager. 2.6.2 The Council accept that there cannot be hard and fast demarcation between categories of HMO and that a house might move between categories over a period of time. The classification of a HMO at any particular time will be at the discretion of the Public Protection Manager and the appropriate requirements will be enforced. 3 Fire Risk Assessment 3.1 The aims of the fire risk assessment are to identify the fire hazards; reduce the risk of those hazards causing harm and to decide what physical fire precautions and management arrangements are necessary to ensure the safety of people in the premises if a fire does start. 3.2 The responsible person must carry out a fire risk assessment for the purpose of identifying the general fire precautions and other measures needed to ensure the safe occupation of the property. Responsible person means “the person who has control of the premises”. In practice this will usually be the landlord or managing agent. For further information please refer to LACORS Guidance on fire safety provisions – sections 4 – 6. 4 4.1 General Management Hazards should be removed where it is practicable to do so such as replacing portable heating appliances with a whole house heating system; ensure electrical sockets are adequate in number and sited appropriately to avoid overloading and trailing leads; ensure all furniture complies with the Furniture and Furnishings (Fire)(Safety) Regulations 1988; ensure combustible items such as furniture and laundry are stored properly and are kept away from potential ignition sources such as cookers, heaters and boilers; ensure refuse is properly stored and November 2009 Page 3 of 24 Date of approval 25/11/09 disposed of. All escape routes must be kept free of obstruction at all times. Refuse must not be stored within the escape route. 4.2 • • • • • Information and training: Each occupier should be given specific advice on fire prevention and fire safety in the home. This should be provided at the start of each new tenancy and reviewed periodically. Information should include: an explanation of the escape routes, particularly where secondary means of escape is provided; how the fire detection and alarm system operates and what to do if it activates including how and when to re-set the fire alarm system, the avoidance of false alarms; how and when to call the fire brigade and how to report defects; where extinguishers or fire blankets are provided, there should be training in their application and safe use; the importance of maintaining clear escape routes, free of storage, and keeping fire doors closed, not propped or wedged open; smoking and cooking safety, gas safety advice; 4.3 Record keeping: It is recommended that a property log book is kept and all routine maintenance and servicing activity is recorded in it, along with all reported defects and remedial action taken – including false alarms. 4.4 Notices/ signage: In most residential premises of average size and risk, fire safety signs and notices will not be required. However, in larger premises or those with complicated layouts or with alternative exits, the fire risk assessment is likely to indicate some need for signage. The need for clear information should be balanced with the desire to maintain a homely environment. 4.5 The fire risk assessment will determine whether fire safety signage is required. The assessor should consider if all occupiers are likely to be familiar with the escape route; which route offers the shortest travel distance and are there any changes in direction in corridors or areas where confusion may occur when exiting the building. Any facilities or equipment provided for fire safety may need appropriate signage e.g. If it is obscured from view. 4.6 Fire-resisting doors should be marked ‘Fire door keep shut’. Where fire safety signs are provided they should be in accordance with BS 5499 and the Health and Safety (Safety Signs and Signals) Regulations 1996. All signs should be pictographic. For further information please refer to LACORS Guidance on fire safety provisions – section 27. 5 Escape Routes 5.1 Layout of accommodation units themselves must be considered. Poor layout within a unit of accommodation can compromise the means of escape in the event of a fire. Ideally, sleeping areas or rooms should be closer to the exit door to the accommodation than living areas or kitchen facilities. Escape from the premises should not be through a risk room. E.g. a kitchen. 5.2 There is usually no requirement to provide protection to bathrooms and shower rooms which open onto protected routes. Properly installed and maintained central heating boilers, electric showers or water heaters and room-sealed gas November 2009 Page 4 of 24 Date of approval 25/11/09 water heaters pose little additional risk. However, if the room contains open flame or electric bar space heaters, storage cupboards or other risk items then either the storage cupboards or the room itself, as appropriate, should be protected to the appropriate standard in the same way as the remainder of the route. 6 Escape windows 6.1 Any window provided for emergency escape purposes should have an unobstructed openable area that is at least 0.33m² and have a minimum 450mm height and 450mm width. The bottom of the openable area should not be more than 1,100mm above the floor. 6.2 Escape windows can only be considered if satisfied that it would be safe to use them in an emergency and they serve rooms whose floor level is no more than 4.5m from the ground. 6.3 The occupiers of those rooms must be able-bodied individuals and there must be no basement well or other encumbrance beneath the window such as railings or a conservatory. 7 Exit doors 7.1 All doors to lettings and each final exit doors from the premises should be fitted with locks/catches which are openable by the occupiers from the inside without the use of a removable key. Wherever key-operable locks are fitted they should be of the type with a suitable internal thumb-turn to facilitate this. 7.2 Electrically operated locks must fail to safety (open) or have a manual over-ride in the event of power failure. 8 Fire separation and compartmentation 8.1 In addition to providing a protected escape route, it is necessary to restrict the spread of fire and smoke from one unit of accommodation to another. Fireresisting construction enclosing each unit of accommodation creates a compartment that will contain fire and smoke within it - generally 30 minutes. 8.2 Where the fire risk assessment identifies specific higher risks, then a higher standard of fire resistance may be required (usually 60 minutes) or additional fire safety measures should be installed. 8.3 Examples of 60-minute requirement will include walls, ceilings and doors separating commercial uses from residential parts; walls, ceilings and doors separating areas of high fire risk such as commercial kitchens, large boiler rooms or large stores; and separating walls between buildings. 8.4 Attention should be paid to any ductwork that passes through the separation. This will require protecting to the same standard of fire resistance as the partition itself. 8.5 Floor/ ceiling partitions between any basement or cellar and the ground floor escape route should provide 30 minutes resistance. November 2009 Page 5 of 24 Date of approval 25/11/09 8.6 Inspection of the floors/ceilings as part of the fire risk assessment will determine the suitability of existing construction. Generally, ceilings constructed with 12.5mm plasterboard with skim coat and in sound condition will be adequate. 8.7 Ceilings constructed from 9mm plasterboard or lath and plaster (in sound condition) can be expected to provide a lower standard of fire resistance. However, this should be acceptable as part of an overall fire risk assessment in lower risk premises such as single household occupancy and shared houses of no more than three storeys with no specific higher risk factors present. 8.8 Ceilings which are not in sound condition particularly lath and plaster type should be replaced or upgraded to provide 30 minutes resistance. 8.9 This can be achieved by removal and replacement of the existing ceiling with standard 12.5mm plasterboard and skim or alternative product/construction providing 30 minutes resistance and subject to a satisfactory fire test report. 8.10 It may be possible to provide additional protection below the ceiling; or by providing additional protection within the floor space above the ceiling. 8.11 Only upgrading methods accompanied by a valid test report can be accepted. The report will specify the fire resistance which will be achieved by the upgrading method. This is essential for all upgrading methods, but particularly so where proprietary products are being considered. 9 Fire doors/ door sets 9.1 Where fire-resisting partitions are required, any doorways within them must be fitted with fire resisting door assemblies (door and frame set) providing fire resistance at least to the same standard as the partition itself. E.g. 30-minute partitions will require a 30-minute fire-resisting door set. 9.2 30-minute doorsets are specified as FD30 (or E 30) and 60-minute doorsets are specified as FD60 (or E 60). 9.3 Most timber fire doors will need intumescent seals fitted. In most situations fireresisting doors should be fitted with smoke seals, as these restrict the passage of smoke into the escape route from the room where the fire is situated. 9.4 The exception to this is where fire doors are fitted to rooms in premises where the fire detection system is restricted to the escape route. This will often be the case in three-storey shared houses. In these cases smoke seals should not be fitted, as their benefit will be outweighed by the fact that the smoke detectors in the escape route will only activate when the fire is at an advanced stage and beginning to breach the fire door. 9.5 Where smoke detection is sited within rooms the alarm will sound very early in the development of the fire and the smoke seals will be of benefit in keeping smoke out of the escape route. 9.6 Fire doors should be installed and maintained in accordance with BS 8214:1990. In multi-occupancy situations, fire-resisting doors should be fitted with approved self-closing devices. November 2009 Page 6 of 24 Date of approval 25/11/09 9.7 Doors to rooms within larger flats in multiple occupation and larger shared houses may require self-closers within the context of an overall fire risk assessment. Entrance doors to flats and bed-sit rooms will always require them. 9.8 In lower risk premises (as determined by the enforcing authority), where a full 30minute protected route is not required, it should be possible to accept existing, well fitted and constructed solid doors, providing they are in sound condition. Solid timber doors and panelled doors of substantial construction may be adequate in these lower risk situations. Non fire-resisting glazed doors, doors of flimsy construction or hollow infill-type doors (commonly known as ‘egg box’) should not be accepted. 9.9 When new fire doors are to be provided, ideally an entire doorset construction should be fitted, overcoming problems with fitting doors to frames of a different specification. However, it is recognised that in some existing buildings of substantial construction this may cause practical difficulties. It may be possible to fit new fire doors to existing frames provided that the frames are of sound construction, in good condition, and of adequate material and dimensions to meet requirements. 9.10 Not all doors are suitable for upgrading, so before undertaking upgrading the door must be assessed for suitability by a qualified person. For further information please refer to LACORS Guidance on fire safety provisions – section 21.9/ 10. 10 Emergency Lighting 10.1. When a fire occurs, people will be escaping in haste and in a probable state of distress or even panic therefore the staircase and escape route must be adequately lit at all levels. 10.2 In HMOs (including shared houses) of three or four storeys, it may be appropriate to provide emergency lighting throughout the escape route if the route is long or complex or where there is no effective borrowed light. 11 Fire fighting equipment (portable) 11.1 The provision of fire blankets and simple fire extinguishers can be useful in restricting the development and spread of small fires in their early stages. However, unless a fire is very small, the best advice is to evacuate the building to a place of safety and call the fire and rescue service. 11.2 In order to provide a facility for extinguishing small fires in their early stages, a simple multi-purpose extinguisher in compliance with BS EN 3-7 is recommended on each floor in the common parts of HMOs and buildings containing flats. It will not usually be practical to train tenants in the use of these, but basic advice should be offered at the start of each new tenancy. 11.3 Water extinguishers are not suitable for location within kitchens or for use on electrical fires. All portable fire fighting equipment shall be wall mounted by the use of suitable brackets, so that the handle or other carrying device is about 1.1m from floor level. November 2009 Page 7 of 24 Date of approval 25/11/09 11.4 Fire blankets will be required in certain kitchens and bed-sit rooms. Fire blankets should comply with BS 6575 and be mounted on the wall approximately 1.5m high and closer to the room exit than the cooking facility. 12 Automatic fire detection and alarm systems 12.1 The presence of a suitable, properly installed and maintained automatic fire detection and warning system will alert occupiers to the presence of a fire in its early stages and enable them to evacuate. The system should wake people who are sleeping. It should also alert the presence of a developing fire in any hidden areas before that fire affects the escape route. 12.2 The type of system to be provided in a particular premises is dependent upon risk. The type of system installed should be in accordance with the recommendations of BS 5839: part 6. This details different grades of system and extent of coverage and recommends an appropriate system based on the risk the premises presents. Relatively simple systems will be satisfactory for smaller, lowrisk premises, but larger houses and HMOs will require a more sophisticated automatic system. For more detailed information on grades of fire alarm system please refer to LACORS Guidance on fire safety provisions – section 22. Please note: These notes are for guidance only it will be necessary to refer to British Standard – Fire detection & fire alarm systems for buildings. BS: 5839 -1:2002 and BS: 5839 -6:2002 for full details on component compliance. November 2009 Page 8 of 24 Date of approval 25/11/09 13 Bed-sit type HMO of no more than two storeys to final exit 13.1 Escape routes It is necessary to create a protected route as provision of a safe means of escape from the property, i.e. all doors, walls and screens forming staircase enclosures shall be constructed or repaired to provide a minimum period of fire resistance of thirty minutes. NOTE: The protected means of escape must be kept free from obstruction at all times meaning articles and items of furniture must not be placed or stored on the escape route at any time. 13.1.1 All doors and frames to risk rooms and those which open onto the protected route, should must be FD30s (including the door to the cellar). This should include the correct installation of intumescent strips, cold smoke seals and correctly adjusted self-closing devices. All doors to lettings and each final exit door from the premises should be fitted with locks/catches which are openable by the occupiers from the inside without the use of a removable key. Wherever keyoperable locks are fitted they should be of the type with a suitable internal thumbturn to facilitate this. 13.1.2 Gas & Electric meters within the protected route should be boxed in with fire resisting material affording a minimum of one half hour fire protection. 13.2 Fire separation No requirement for additional fire-resisting separation between units, but walls and floors should be of sound, traditional construction. However: 13.2.1 Occupied basement Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm gypsum plaster skim to provide 30 minutes fire resistance. Alternatively use 12mm plasterboard and skim joints. A separate escape route is required from occupied basements. If this is not possible escape windows must be installed to all habitable rooms and occupants must be able bodied. Where there is no external access to the basement any rooms off the basement corridor must be fitted with 30 minute fire resisting doors and frames, including the correct installation of intumescent strips and correctly adjusted self-closing devices. (Cold smoke seals must not be fitted). NOTE: If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. All overlaid boards should be laid with staggered joints. All ducting and large pipe work passing through ceilings/ floors is to be fitted with intumescent collars. All holes in brickwork to party walls must be sealed. November 2009 Page 9 of 24 Date of approval 25/11/09 13.2.2 Unoccupied cellar Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Note; Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm skim. Alternatively use 12mm plasterboard and skim joints to provide a minimum of 30 minutes fire protection. If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. An FD 30S fire door and frame with smoke seals must be provided to the head of the cellar stairs, where this door leads into the protected route. Rubbish and materials should not be stored within the cellar; 13.3 Fire detection and alarm system 13.3.1 Mixed system Grade D, LD2 system • Interlinked mains wired smoke alarms with integral battery back-up located in the escape route at each floor level. • Interlinked smoke alarms with integral battery back-up located in any cellar. 13.3.2 Where cooking facilities are sited within the bed-sit: • Interlinked heat alarms with integral battery back-up located in each bed-sit; and additional non-interlinked smoke alarm with integral battery back-up located in each bed-sit. 13.3.3 Where cooking facilities are sited in shared kitchen, not within bed-sit: • Interlinked smoke alarms with integral battery backup located in each bed-sit; • interlinked heat alarms with integral battery back-up located in each communal kitchen; 13.4 Emergency Lighting Conventional artificial lighting is required. Emergency lighting (which is to be independent of all other systems), in compliance with B.S. 5266 should be installed - one light to each level to illuminate all escape routes, except where there is adequate borrowed light. 13.5 Fire fighting equipment 13.5.1 Fire blanket to be provided in each bed-sit with cooking facilities and in shared kitchens. 13.5.2 A simple multi-purpose extinguisher on each floor in the common parts recommended. 13.6 Fire safety signs Signage along escape route to the final exit is required, if the escape route is complex. 13.7 Management and maintenance of fire safety Please refer to “General Management” page 1 November 2009 Page 10 of 24 Date of approval 25/11/09 14 Bed-sit-type HMO of three or four storeys to final exit 14.1 Escape routes It is necessary to create a protected route as provision of a safe means of escape from the property, i.e. all doors, walls and screens forming staircase enclosures shall be constructed or repaired to provide a minimum period of fire resistance of thirty minutes. NOTE: The protected means of escape must be kept free from obstruction at all times meaning articles and items of furniture must not be placed or stored on the escape route at any time. 14.1.1 All doors and frames to risk rooms and those which open onto the protected route, should must be FD30s (including the door to the cellar). This should include the correct installation of intumescent strips, cold smoke seals and correctly adjusted self-closing devices. All doors to lettings and each final exit door from the premises should be fitted with locks/catches which are openable by the occupiers from the inside without the use of a removable key. Wherever keyoperable locks are fitted they should be of the type with a suitable internal thumbturn to facilitate this. 14.1.2 Gas & Electric meters within the protected route should be boxed in with fire resisting material affording a minimum of one half hour fire protection. 14.2 Fire separation No requirement for additional fire-resisting separation between units, but walls and floors should be of sound, traditional construction. However: 14.2.1 Occupied basement Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm gypsum plaster skim to provide 30 minutes fire resistance. Alternatively use 12mm plasterboard and skim joints. A separate escape route is required from occupied basements. If this is not possible escape windows must be installed to all habitable rooms and occupants must be able bodied. Where there is no external access to the basement any rooms off the basement corridor must be fitted with 30 minute fire resisting doors and frames, including the correct installation of intumescent strips and correctly adjusted self-closing devices. (Cold smoke seals must not be fitted). NOTE: If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. All overlaid boards should be laid with staggered joints. Please note all ducting and large pipe work passing through ceilings/ floors is to be fitted with intumescent collars. All holes in brickwork to party walls must be sealed. November 2009 Page 11 of 24 Date of approval 25/11/09 14.2.2 Unoccupied cellar Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Note; Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm skim. Alternatively use 12mm plasterboard and skim joints to provide a minimum of 30 minutes fire protection. If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. An FD 30S fire door and frame with smoke seals must be provided to the head of the cellar stairs, where this door leads into the protected route. Rubbish and materials should not be stored within the cellar; 14.3 Fire detection and alarm system 14.3.1 Mixed system Grade A, LD2 system: • Smoke detectors located throughout the escape route • Additional interlinked smoke detectors located in any cellar. • Control panel. 14.3.2 Where cooking facilities are sited within the bed-sit: • Interlinked heat detectors located in each bed-sit; and additional Grade D, noninterlinked smoke alarm with integral battery back-up located in each bed-sit. 14.3.3 Where cooking facilities are sited in shared kitchen, not within bed-sit: • Interlinked smoke detectors located in each bed-sit; • Heat detectors located in each kitchen; and 14.4 Emergency Lighting Conventional artificial lighting is required. Emergency lighting (which is to be independent of all other systems), in compliance with B.S. 5266 should be installed - one light to each level to illuminate all escape routes, except where there is adequate borrowed light. 14.5 Fire fighting equipment 14.5.1 Fire blanket to be provided in each bed-sit with cooking facilities and in shared kitchens. 14.5.2 Simple multi-purpose extinguisher on each floor in the common parts recommended. 14.6 Fire safety signs Signage along escape route to the final exit is required, if the escape route is complex. 14.7 Management and maintenance of fire safety Please refer to “General Management” page 1 November 2009 Page 12 of 24 Date of approval 25/11/09 15 Building converted into self-contained flats – up to two storeys to final exit (Converted self contained flats not meeting 1991 building regulations or not suitably maintained) 15.1 Escape routes It is necessary to create a protected route as provision of a safe means of escape from the property, i.e. all doors, walls and screens forming staircase enclosures shall be constructed or repaired to provide a minimum period of fire resistance of thirty minutes. NOTE: The protected means of escape must be kept free from obstruction at all times meaning articles and items of furniture must not be placed or stored on the escape route at any time. 15.1.1 All entrance doors and frames to flats which open onto the protected route, should must be FD30s (including the door to the cellar). This should include the correct installation of intumescent strips, cold smoke seals and correctly adjusted self-closing devices. All doors to lettings and each final exit door from the premises should be fitted with locks/catches which are openable by the occupiers from the inside without the use of a removable key. Wherever key-operable locks are fitted they should be of the type with a suitable internal thumb-turn to facilitate this. 15.1.2 It is not required for existing doors within the flats to be FD30; however it is necessary for the doors to be in a sound condition and well constructed – please refer to section 9 - fire doors and door sets. 15.1.3 If any door within the flat is to be changed, or in new conversions, FD30 doors must be fitted. 15.1.3 Gas & Electric meters within the protected route should be boxed in with fire resisting material affording a minimum of one half hour fire protection; 15.2 Fire separation No requirement for additional fire-resisting separation between units, but walls and floors should be of sound, traditional construction. However: 15.2.1 Occupied basement Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm gypsum plaster skim to provide 30 minutes fire resistance. Alternatively use 12mm plasterboard and skim joints. A separate escape route is required from occupied basements. If this is not possible escape windows must be installed to all habitable rooms and occupants must be able bodied. Where there is no external access to the basement any rooms off the basement corridor must be fitted with 30 minute fire resisting doors and frames, including the correct installation of intumescent strips and correctly adjusted self-closing devices. (Cold smoke seals must not be fitted). November 2009 Page 13 of 24 Date of approval 25/11/09 NOTE: If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. All overlaid boards should be laid with staggered joints. Please note all ducting and large pipe work passing through ceilings/ floors is to be fitted with intumescent collars. All holes in brickwork to party walls must be sealed. 15.2.2 Unoccupied cellar Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Note; Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm skim. Alternatively use 12mm plasterboard and skim joints to provide a minimum of 30 minutes fire protection. If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. An FD 30S fire door and frame with smoke seals must be provided to the head of the cellar stairs, where this door leads into the protected route. Rubbish and materials should not be stored within the cellar; 15.3 Fire detection and alarm system 15.3.1 Common Parts Grade D, LD2 system A hard wired fire alarm system, interlinked and consisting of self-contained smoke/ heat detectors complying with B.S. 5446. • Interlinked mains wired smoke alarms with integral battery back-up located in the escape route at each floor level; and • Interlinked heat alarm with integral battery back-up located within the hallway to each flat; and • Interlinked smoke alarms with integral battery back-up located in any cellar. 15.3.1 Within each dwelling Grade D, LD3 system A hard wired fire alarm system consisting of self-contained smoke/ heat detectors complying with B.S. 5446: • Non-interlinked mains wired smoke alarms with integral battery back-up located in the room / lobby opening onto the escape route; NOTE: Additional detection may be required in high fire risk rooms if higher than normal risk is identified. E.g. where kitchens are next to the final exit door. 15.4 Emergency Lighting Conventional artificial lighting is required. Emergency lighting (which is to be independent of all other systems), in compliance with B.S. 5266 should be installed - one light to each level to illuminate all escape routes, except where there is adequate borrowed light. 15.5 Fire fighting equipment Fire blanket to be provided in each kitchen or kitchen area. Simple multi-purpose extinguisher on each floor in the common parts required. November 2009 Page 14 of 24 Date of approval 25/11/09 15.6 Fire safety signs Signage along escape route to the final exit is required, if the escape route is complex. 15.7 Management and maintenance of fire safety Please refer to “General Management” page 1 November 2009 Page 15 of 24 Date of approval 25/11/09 16 Building converted into self-contained flats - three-four storeys to final exit (Converted self contained flats not meeting 1991 building regulations or not suitably maintained) 16.1 Escape routes It is necessary to create a protected route as provision of a safe means of escape from the property, i.e. all doors, walls and screens forming staircase enclosures shall be constructed or repaired to provide a minimum period of fire resistance of thirty minutes. NOTE: The protected means of escape must be kept free from obstruction at all times meaning articles and items of furniture must not be placed or stored on the escape route at any time. 16.1.1 All entrance doors and frames to flats which open onto the protected route, should must be FD30s (including the door to the cellar). This should include the correct installation of intumescent strips, cold smoke seals and correctly adjusted self-closing devices. Note: All doors to lettings and each final exit door from the premises should be fitted with locks/catches which are openable by the occupiers from the inside without the use of a removable key. Wherever key-operable locks are fitted they should be of the type with a suitable internal thumb-turn to facilitate this. 16.1.2 It is not required for existing doors within the flats to be FD30; however it is necessary for the doors to be in a sound condition and well constructed – please refer to section 9 - fire doors and door sets. 16.1.3 If any door within the flat is to be changed, or in new conversions, FD30 doors must be fitted. 16.1.4 Gas & Electric meters within the protected route should be boxed in with fire resisting material affording a minimum of one half hour fire protection. 16.2 Fire separation No requirement for additional fire-resisting separation between units, but walls and floors should be of sound, traditional construction. However: 16.2.1 Occupied basement Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm gypsum plaster skim to provide 30 minutes fire resistance. Alternatively use 12mm plasterboard and skim joints. A separate escape route is required from occupied basements. If this is not possible escape windows must be installed to all habitable rooms and occupants must be able bodied. Where there is no external access to the basement any rooms off the basement corridor must be fitted with 30 minute fire resisting doors and frames, including the correct installation of intumescent strips and correctly adjusted self-closing devices. (Cold smoke seals must not be fitted). November 2009 Page 16 of 24 Date of approval 25/11/09 NOTE: If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. All overlaid boards should be laid with staggered joints. Please note all ducting and large pipe work passing through ceilings/ floors is to be fitted with intumescent collars. All holes in brickwork to party walls must be sealed. 16.2.2 Unoccupied cellar Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Note; Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm skim. Alternatively use 12mm plasterboard and skim joints to provide a minimum of 30 minutes fire protection. If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. An FD 30S fire door and frame with smoke seals must be provided to the head of the cellar stairs, where this door leads into the protected route. Rubbish and materials should not be stored within the cellar; 16.3 Fire detection and alarm system 16.3.1 Common Parts Grade A, LD2 system A hard wired fire alarm system, interlinked and consisting of self-contained smoke/ heat detectors complying with B.S. 5446. I.e. • interlinked mains wired smoke alarms with integral battery back-up located in the escape route at each floor level; and • interlinked heat alarm with integral battery back-up located within the hallway to each flat; and • interlinked smoke alarms with integral battery back-up located in any cellar; • Manual call points to be located at each final exit. • Control panel 16.3.2 Within each dwelling Grade D, LD3 system A hard wired fire alarm system consisting of self-contained smoke/ heat detectors complying with B.S. 5446. • Non - interlinked mains wired smoke alarms with integral battery back-up located in the room / lobby opening onto the escape route; NOTE: Additional detection may be required in high fire risk rooms if higher than normal risk is identified. E.g. where kitchens are next to the final exit door. 16.4 Emergency Lighting Conventional artificial lighting is required. Emergency lighting (which is to be independent of all other systems), in compliance with B.S. 5266 should be installed - one light to each level to illuminate all escape routes, except where there is adequate borrowed light. November 2009 Page 17 of 24 Date of approval 25/11/09 16.5 Fire fighting equipment Fire blanket to be provided in each kitchen or kitchen area. Simple multi-purpose extinguisher on each floor in the common parts required. 16.6 Fire safety signs Signage along escape route to the final exit is required, if the escape route is complex. 16.7 Management and maintenance of fire safety Please refer to “General Management” page 1 November 2009 Page 18 of 24 Date of approval 25/11/09 Individual tenancies 17 Shared house of no more than 2 storeys to final exit 17.1 Escape routes It is necessary to create a protected route as provision of a safe means of escape from the property, i.e. all doors, walls and screens forming staircase enclosures shall be constructed or repaired to provide a minimum period of fire resistance of thirty minutes. The protected route must not be used for furniture or storage/rubbish and must be kept clear of obstacles. 17.1.1 All door frames and doors opening onto the protected route i.e. hall, landing and staircase enclosures, should afford 30 minutes fire protection (including the door to the cellar; generally excluding bathroom doors). This should include the correct installation of intumescent strips and correctly adjusted self-closing devices. (Cold smoke seals must not be fitted) Note: All doors to lettings and each final exit door from the premises should be fitted with locks/catches which are openable by the occupiers from the inside without the use of a removable key. Wherever key-operable locks are fitted they should be of the type with a suitable internal thumb-turn to facilitate this. 17.1.2 Gas & Electric meters within the protected route should be boxed in with fire resisting material affording a minimum of one half hour fire protection; 17.2 Fire separation No requirement for additional fire-resisting separation between units, but walls and floors should be of sound, traditional construction. However: 17.2.1 Occupied basement Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm gypsum plaster skim to provide 30 minutes fire resistance. Alternatively use 12mm plasterboard and skim joints. A separate escape route is required from occupied basements. If this is not possible escape windows must be installed to all habitable rooms and occupants must be able bodied. Where there is no external access to the basement, any rooms off the basement corridor must be fitted with 30 minute fire resisting doors and frames, including the correct installation of intumescent strips and correctly adjusted self-closing devices. (Cold smoke seals must not be fitted). NOTE: If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. All overlaid boards should be laid with staggered joints. Please note all ducting and large pipe work passing through ceilings/ floors is to be fitted with intumescent collars. All holes in brickwork to party walls must be sealed. November 2009 Page 19 of 24 Date of approval 25/11/09 17.2.2 Unoccupied cellar Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Note; Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm skim. Alternatively use 12mm plasterboard and skim joints to provide a minimum of 30 minutes fire protection. If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. An FD 30S fire door and frame with smoke seals must be provided to the head of the cellar stairs, where this door leads into the protected route. Rubbish and materials should not be stored within the cellar; 17.3 Fire detection and alarm system Grade D, LD3 system: i.e. • interlinked mains wired smoke alarms with integral battery back-up located in the escape route at each floor level; and • Interlinked heat alarm with integral battery back-up located in the kitchen; and • Interlinked smoke alarm with integral battery back-up located in the lounge; and • Interlinked smoke alarms with integral battery back-up located in any cellar. 17.4 Emergency Lighting Conventional artificial lighting is required. Emergency lighting (which is to be independent of all other systems), in compliance with B.S. 5266 should be installed - one light to each level to illuminate all escape routes, except where there is adequate borrowed light. 17.5 Fire fighting equipment A fire blanket to be provided in the kitchen and a simple multi-purpose fire extinguisher in the hallway. 17.6 Fire safety signs Signage only required if the escape route is complex 17.7 Management and maintenance of fire safety Please refer to “General Management” page 1 November 2009 Page 20 of 24 Date of approval 25/11/09 Individual tenancies 18 Shared house of 3 – 4 storeys to final exit 18.1 Escape routes It is necessary to create a protected route as provision of a safe means of escape from the property, i.e. all doors, walls and screens forming staircase enclosures shall be constructed or repaired to provide a minimum period of fire resistance of thirty minutes. The protected route must not be used for furniture or storage/rubbish and must be kept clear of obstacles. 18.1.1 All door frames and doors opening onto the protected route i.e. hall, landing and staircase enclosures, should afford 30 minutes fire protection (including the door to the cellar; generally excluding bathroom doors). This should include the correct installation of intumescent strips, cold smoke seals and correctly adjusted self-closing devices. Note: All doors to lettings and each final exit door from the premises should be fitted with locks/catches which are openable by the occupiers from the inside without the use of a removable key. Wherever key-operable locks are fitted they should be of the type with a suitable internal thumb-turn to facilitate this. 18.1.2 Gas & Electric meters within the protected route should be boxed in with fire resisting material affording a minimum of one half hour fire protection; 18.2 Fire separation No requirement for additional fire-resisting separation between units, but walls and floors should be of sound, traditional construction. However: 18.2.1 Occupied basement Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm gypsum plaster skim to provide 30 minutes fire resistance. Alternatively use 12mm plasterboard and skim joints. A separate escape route is required from occupied basements. If this is not possible escape windows must be installed to all habitable rooms and occupants must be able bodied. Where there is no external access to the basement, any rooms off the basement corridor must be fitted with 30 minute fire resisting doors and frames, including the correct installation of intumescent strips and correctly adjusted self-closing devices. (Cold smoke seals must not be fitted). NOTE: If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. All overlaid boards should be laid with staggered joints. Please note all ducting and large pipe work passing through ceilings/ floors is to be fitted with intumescent collars. All holes in brickwork to party walls must be sealed. November 2009 Page 21 of 24 Date of approval 25/11/09 18.2.2 Unoccupied cellar Ceilings, staircase soffits and spandrels should be upgraded to afford a minimum of 30 minutes fire protection. Note; Existing ceilings in poor condition should be removed and replaced with a minimum of 9.5mm plasterboard + 5mm skim. Alternatively use 12mm plasterboard and skim joints to provide a minimum of 30 minutes fire protection. If the existing ceiling is in good condition it may be possible to underdraw the ceiling using plasterboard with skimmed joints. An FD 30S fire door and frame with smoke seals must be provided to the head of the cellar stairs, where this door leads into the protected route. Rubbish and materials should not be stored within the cellar; 18.3 • Fire detection and alarm system Grade A, LD2 system: i.e. interlinked mains wired smoke alarms with integral battery back-up located in the escape route at each floor level and located in each bedroom; and • interlinked heat alarm with integral battery back-up located in the kitchen; and • interlinked smoke alarm with integral battery back-up located in any lounge/ living rooms; and • interlinked smoke alarms with integral battery back-up located in any cellar; • Manual call points to be located at each final exit. • Control panel 18.4 Emergency Lighting Conventional artificial lighting is required. Emergency lighting (which is to be independent of all other systems), in compliance with B.S. 5266 should be installed - one light to each level to illuminate all escape routes, except where there is adequate borrowed light. 18.5 Fire fighting equipment A fire blanket to be provided in the kitchen and a simple multi-purpose fire extinguisher on each landing is recommended. 18.6 Fire safety signs Signage only required if the escape route is complex. 18.7 Management and maintenance of fire safety Please refer to “General Management” page 1 November 2009 Page 22 of 24 Date of approval 25/11/09 19 Single family dwellings of no more than two storeys to final exit 19.1 Escape routes etc. The level of protection for single family dwellings will again depend on the risk factors. There are generally no requirements for a protected escape route, fire doors, fire separation or emergency lighting. Two different standards are set out below and the risk factors present will determine which standard should be applied. 19.2 Average property: Where there are no particular risk factors; and Stairs do not pass through a risk room; and There is a substantial door on the kitchen Then the following will apply: Grade D, LD3 alarm system • Interlinked mains wired smoke alarms with integral battery back-up located in the escape route at each floor level; and • Interlinked heat alarm with integral battery back-up located in the kitchen; and • Interlinked smoke alarms with integral battery back-up located in any basement/cellar. If there are operational, sealed detectors (with 10 year battery enclosed) in the escape route, with no additional risk factors, this may be acceptable. An inspection of the property will determine this. 19.3 Additional risk factors present: These could include stairs coming into the kitchen; or Stairs coming into an open plan lounge/kitchen, where a door cannot be fitted to the kitchen. Then the following will apply: At least one escape window to the first floor – see section 6 for details (may need two if the travel distances are excessive eg. large rear extension). Grade D, LD3 alarm system • Interlinked mains wired smoke alarms with integral battery back-up located in the escape route at each floor level; and • Interlinked heat alarm with integral battery back-up located in the kitchen; and • Interlinked smoke alarms with integral battery back-up located in any basement/cellar. 19.4 Fire fighting equipment It is recommended that a fire blanket be provided in the kitchen. 19.5 Management and maintenance of fire safety It is recommended that all doors are kept closed at night. 19.6 If other high risk factors are present, such as means of escape through kitchen at first floor level, alterations to the layout may be required. An inspection will be required to determine if work is required. November 2009 Page 23 of 24 Date of approval 25/11/09 Contact details: Housing Standards, Trafford Town Hall, Talbot Road, Stretford, Trafford, Manchester, M32 0YJ. Tel. 0161 912 4509 Fax. 0161 912 1113 E-mail. [email protected] November 2009 Page 24 of 24 Date of approval 25/11/09
© Copyright 2025 Paperzz