AC90-0611-R1 #18 8385 White Oak Avenue Rancho Cucamonga, CA 91730 909.483.0250 ph. | 909.483.0336 fx. May 27, 2011 Michael Merrigan, P.E. ICC Evaluation Service 5360 Workman Mill Road Whittier, CA 90601 RE: Proposed Revisions to AC90 Dear Mr. Merrigan, QAI submits the following comments regarding the proposed revisions to AC90, Proposed Revisions to the Acceptance Criteria for Fiber Cement Siding Used as Exterior Wall Siding, Subject AC90-0611-R1 (MM/MB), dated May 4, 2011 as posted on the ICC-ES website. We have 3 points to comment in reference to the rewording of Section 4.1. 1. The first sentence reads that the air pressure difference is to be “applied to the back of the siding.” In reading further in the paragraph it stipulates that the air pressure be applied by a plastic film installed in between the siding and the sheathing and/or framing. This test set up will apply a pressure to the siding in only one direction, which we would describe as the negative pressure direction (meaning the direction of a negative wind pressure). A positive pressure applied in this manner would exert no load on the siding material as the film would be pulled in to the sheathing and/or framing, leaving the siding untouched. The positive pressure application requires the film to be applied on the front of the siding. We recommend that the test set-up for positive and negative loading be described separately in the criteria, with language presented further on in this letter. 2. The second sentence reads to apply a “2-mil (0.058 mm) maximum thickness” plastic film in accordance with ASTM E330. As the plastic film is already described in the E330 standard, it is not necessary to repeat this in the criteria. We recommend striking the specifics of the film thickness. 3. The third sentence describes holes that are to be cut in the sheathing to allow pressure through to the plastic film. There are several conflicts with this requirement: a) This would apply only in negative pressure loading when the film is between the sheathing and siding, b) The holes are only necessary in the negative wind pressure loading direction if you are pushing the air pressure through the film on to the siding, many test chambers would align the test specimen so that the film is pulling against the siding, in which case the holes would be facing in to the open air and serving no purpose, c) The vertical spacing of the holes of the holes is not specified, which leaves out instruction to ensure the pressure is distributed all the way across the test specimen in both directions. The following page includes our recommended language for section 4.1. WWW.QAI.ORG [email protected] Recommendation on AC90 May 27, 2011 Page 2 of 2 4.1 Transverse Load Tests: Transverse load tests of the siding material shall be in accordance with ASTM E 330, Procedure B. For negative load direction tests, the air pressure difference shall be applied to the back of the siding through a plastic film, in accordance with Section 11.1.1 of ASTM E 330, installed between the siding and the studs or sheathing and sealed to the perimeter of the test frame. If sheathing is applied to the exterior of the studs and the test chamber applies air pressure from the back of the sheathing through to the siding, 2-inch (50.8 mm) minimum diameter holes shall be cut through the sheathing, centered horizontally between studs and spaced 24-inches (610 mm) vertically from each end and through the center, to allow an even pressure application to the plastic film. For positive load direction tests, the plastic film is to be applied on the outer face of the siding and sealed to the perimeter of the test frame. At least three positive and three negative load tests shall be conducted with the siding material fastened to the framing system in accordance with the published installation instructions. Test assemblies shall be a minimum of 4 feet by 8 feet (1219 mm by 2438 mm). Test assemblies of the siding material shall include vertical joints. Test assemblies of panel products shall include at least one vertical joint and one horizontal joint. Application of loads to failure shall be in at least six increments with a 10-second load duration for each increment. Test assemblies shall be mounted according to ASTM E 330. Relative movement between the siding material and any part of the test assembly or test apparatus shall not be restricted during testing. Framing supporting the panel shall be located at the maximum spacing on which recognition is desired. ICC-ES shall approve any variations from these spans prior to commencement of tests. Load deflection readings at the midpoint of panel spans shall be reported. Conditions of acceptance shall be based on the following: 1. Allowable loading shall be based on a factor of a safety of 3.0 applied to the ultimate load, if all of the following are satisfied: a. No single test result varies by more than 15 percent from the average of three tests. Variations exceeding this limit will result in larger safety factors. b. Allowable load does not exceed established values for mechanical connectors such as nails, screws and staples. 2. Other factors of safety can be considered based on unique conditions of installation or material used. If there are any questions or comments on this recommendation, please feel free to contact me at (909) 4830250 or [email protected]. Sincerely, QAI Laboratories, Inc. Chris Bowness, P.E. General Manager WWW.QAI.ORG [email protected]
© Copyright 2026 Paperzz