INTERNAL GUTTER DETAIL GUIDE

TRA double
with selected
cification.
NOTES
ALL SHEETS LAID LONGITUDINALLY WHERE PRACTICAL.
ANY CROSS SEAMS TO BE WELL AWAY FROM DRAINAGE OUTLETS
plywood
ZBC. Glue
ALL EXTERNAL CORNERS TO BE ARRISED.
r support
ALL INTERNAL CORNERS TO BE FILLETED.
pported.
JAYDEX DOUBLE LAYER
MEMBRANE SYSTEM WITH
JAYDEX POLIBIT CAP SHEET &
JAYDEX NOVAFLEX BASE
SHEET.
ALL 3D CORNERS MUST HAVE TRIPLE THICKNESS MEMBRANE.
ALL 2D TRANSITIONS MUST HAVE DOUBLE THICKNESS MEMBRANE.
rebate in
INTERNAL GUTTER SHALL BE SIZED TO SUIT ROOF CATCHMENT AREA.
ip.
SUBSTRATE LAID TO FALLS
SUBSTRATE LAID TO FALLS
1.5° FALL
(MIN)
50mm MIN.
(OVERLAP)
1.5° FALL
(MIN)
H3 CCA TREATED "C" FACED
PLYWOOD GUTTER
UPSTANDS.
GUTTER HIGH POINT
MINIMUM FREEBOARD 50mm
TO NZBC E2/AS1 FIGURE 64c.
JAYDEX POLIBIT CAP
SHEET.
20mm H3 TREATED ANGLE FILLET.
300mm MIN.
APPLICATION
UNIT 3C-3 MARKEN PLACE,
GLENFIELD, AUCKLAND
FINISH
MINERAL or COATED FINISH
ROOF SOLUTION
POLIBIT/NOVAFLEX DOUBLE LAYER TORCH-ON MEMBRANE SYSTEM
SYSTEM
DRAWING NAME
PO BOX 100 000
NORTH SHORE MAIL CENTRE
BRANZ Appraised
GSPublisherEngine 294.0.97.100
Appraisal N o. 647 [2009]
PHONE: 444 1751 FAX: 444 0132
EMAIL: [email protected]
SCALE
DATE
REVISION
NTS (A4 SHEET)
JAN 2015
INTERNAL GUTTER DETAIL GUIDE
DISCLAIMER
DRAWING No.
THE DETAILED DRAWINGS AS OUTLINED ARE BASED ON EXPERIENCE AND APPLICATION PROCEDURES
AND REPRESENT THE LATEST INFORMATION AVAILABLE. NO RESPONSIBILITY IS TAKEN FOR USES TO
WHICH THIS INFORMATION MAY BE PUT, BUT WE ADVISE WHERE TH APPLICATION IS IN COMPLETE
CONFORMITY WITH THE APPROPRIATE SPECIFICATION A WARRANTY MAY BE AVAILABLE.
WE RESERVE THE RIGHT TO ALTER OR UPDATE THE INFORMATION AT ANY TIME WITHOUT PRIOR NOTICE.
COPYRIGHT ©
R07