ESR-2311 - ICC-ES

Most Widely Accepted and Trusted 0 ICC‐ES Report ESR‐2311
ICC‐ES | (800) 423‐6587 | (562) 699‐0543 | www.icc‐es.org
000 Reissued 09/2016
This report is subject to renewal 09/2017.
DIVISION: 09 00 00—FINISHES SECTION: 09 22 26—SUSPENSION SYSTEMS REPORT HOLDER: WORTHINGTON ARMSTRONG VENTURE (WAVE) 101 LINDENWOOD DRIVE, SUITE 350 MALVERN, PENNSYLVANIA 19335 EVALUATION SUBJECT: SHORTSPAN DRYWALL GRID SYSTEM (DGS) Look for the trusted marks of Conformity! “2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence” ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not
specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a
recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved.
A Subsidiary of ICC-ES Evaluation Report
ESR-2311
Reissued September 2016
This report is subject to renewal September 2017.
www.icc-es.org | (800) 423-6587 | (562) 699-0543
DIVISION: 09 00 00—FINISHES
Section: 09 22 26—Suspension Systems
A Subsidiary of the International Code Council ®
accordance with ASTM A653. Table 1 and Figure 1 specify
the part numbers, dimensions and lengths.
3.2.2 Angle Moldings: The angle moldings are provided
as either Locking Angle Molding (LAM-12) or as Knurled
Angle Molding (KAM-10 or KAM-12). The steel used to
form the angle moldings complies with ASTM A568
Designation 1010, and has a minimum G40 galvanization
coating designation in accordance with ASTM A653.
The angle moldings have 1.25-inch-by-1.25-inch-wide
(32 by 32 mm) flanges. Both flanges have knurled surfaces
and reverse hems along the edges. The angle moldings
have locking tabs punched into the bottom flange at
8 inches (203 mm) on center. Table 1 and Figure 1 specify
the part numbers, dimensions and lengths.
REPORT HOLDER:
WORTHINGTON ARMSTRONG VENTURE (WAVE)
101 LINDENWOOD DRIVE, SUITE 350
MALVERN, PENNSYLVANIA 19335
(610) 722-1218
www.armstrong.com
[email protected]
EVALUATION SUBJECT:
SHORTSPAN DRYWALL GRID SYSTEM (DGS)
1.0 EVALUATION SCOPE
Compliance with the following codes:
®
 2012, 2009 and 2006 International Building Code (IBC)
 2013 Abu Dhabi International Building Code (ADIBC)
†
†
The ADIBC is based on the 2009 IBC. 2009 IBC code sections referenced
in this report are the same sections in the ADIBC.
Property evaluated:
Structural
2.0 USES
The ShortSpan DGS (drywall grid system) described in this
report is used as a ceiling framing system for screwattached gypsum panel products in interior applications, in
nonfire-resistance-rated construction.
3.0 DESCRIPTION
3.1 General:
The ShortSpan DGS (drywall grid system) is a ceiling
framing system that extends from wall to wall, and provides
support for screw-attached gypsum boards. The system
consists of tees that extend from wall to wall, and are
supported on angle moldings that are attached to gypsum
wallboard–faced steel wall framing. Supports for tees are
provided by StrongBack Supports or QuikStix Locking
Pocket Mains, which are attached to supporting
construction using QuikStix Uptight Clips.
3.2.3 StrongBack Support: The StrongBack support
measures 2 inches (51 mm) high, and is notched along
the bottom edge at 8 inches (203 mm) on center to
allow connections with ShortSpan Tees. The steel used to
form the StrongBack support complies with ASTM A568
Designation 1008 or 1010, and has a minimum G40
galvanization coating designation in accordance with
ASTM A653. Table 1 and Figure 1 specify the part
numbers, dimensions and lengths.
3.2.4 QuikStix Locking Pocket Main: The QuikStix
Locking Pocket Main member has an inverted T-shape,
and locking tabs punched into the bottom flanges at
8 inches (203 mm) on center. The steel used to form the
members complies with ASTM A568 Designation 1010,
and has a minimum G40 galvanization coating designation
in accordance with ASTM A653. Table 1 and Figure 1
specify the part numbers, dimensions and lengths.
3.2.5 Quikstix Uptight Clip: The QuikStix Uptight Clip is
a 1.75-inch-wide (44.4 m) L-shaped clip, with a 1.42-inch
(36 mm) short leg and a 4.42-inch (112 mm) long leg. The
clip is used to fasten StrongBack Support members and
QuikStix Locking Pocket Main members to structural
support members. The steel used to form the QuikStix
Uptight Clip complies with ASTM A568 Designation 1008
or 1010, and has a G90 galvanization coating designation
in accordance with ASTM A653.
3.2 Components:
3.2.6 Gypsum Board: Gypsum panel products must
comply with ASTM C36 or C1396, and must have a
maximum thickness of 5/8 inch (15.9 mm) and a maximum
2
weight of 2.5 pounds per square foot (12.3 kg/m ).
3.2.1 ShortSpan Tee: The ShortSpan Tee has an
inverted T-shape, a rotary-stitched double web and a
knurled lower flange that has a reverse hem along the
entire length of the bottom flange. The steel used to form
the tee complies with ASTM A568 Designation 1010, and
has a minimum G40 galvanization coating designation in
3.2.7 Screws: Screws used to fasten angle moldings to
framing, and QuikStix Uptight Clips to tees, StrongBack
1
or QSLPM members, must be No. 8 by 1 /4-inch-long
(32 mm), wafer-head, steel-framing, self-drilling tapping
screws complying with SAE J78 and ASTM C1002, and
must be recognized in a current ICC-ES evaluation report.
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved.
Page 1 of 4
ESR-2311 | Most Widely Accepted and Trusted
4.0 DESIGN AND INSTALLATION
4.1 Design:
The ceiling assembly is designed to support one layer of
5
/8-inch-thick (15.9 mm) gypsum board having a maximum
2
weight of 2.5 psf (12.3 kg/m ). Since the ShortSpan DGS
system consists of gypsum boards screwed to suspended
framing members, and the ceiling is supported on one level
extending between laterally braced walls, the ShortSpan
DGS system is not within the scope of the lateral load
design requirements of ASTM E580 (for the 2012 IBC and
ASCE 7-10) and CISCA 3-4 (for the 2009 and 2006 IBC
and ASCE 7-05). Therefore, the ShortSpan DGS system
must be designed for seismic loads as required under
Chapter 13 of ASCE 7.
4.2 Installation:
4.2.1 General: The ceiling system must be installed in
accordance with this report and the manufacturer’s
published installation instructions.
4.2.2 Angle Moldings: The angle moldings must be
screw-attached to No. 25 or No. 20 gage steel wall studs
spaced a maximum of 24 inches (610 mm) on center, with
1
the No. 8 by 1 /4-inch-long (32 mm), wafer-head, steelframing, self-drilling tapping screws described in Section
3.2.7.
4.2.3 ShortSpan Tees: ShortSpan Tees must be
installed to span between angle moldings or QuickStix
Locking Pocket Main members, as applicable. The tees
1
must be cut within /8 inch (3.2 mm) of the vertical leg of
the molding, and both ends must be fixed in the locking
tabs of either the Angle Moldings or the QuickStix Locking
Pocket Main members. ShortSpan Tees must be installed
at a maximum of 16 inches (406 mm) on center, and
1
leveled to within /4 inch in 10 feet (6.4 mm in 3048 mm).
The maximum length of tees between bearing end
supports is 14 feet (4 267 mm), and must be based on
the length of the tees, as noted in Table 1. The
maximum unsupported length between clips, hanger
wires or QuickStix Locking Pocket Main members is 7 feet
(2.13 m).
4.2.4 StrongBack Support: When used, the StrongBack
support must be installed by opening the lock tabs and
sliding the support over the bulb of the ShortSpan Tees,
then closing the lock tab to the original position. The
StrongBack support must be leveled to within 1/4 inch in
10 feet (6.4 mm in 3048 mm). Vertical supports for the
StrongBack Support that consist of vertical hangers and
perimeter hangers must be designed and installed in
accordance with the code. The maximum span of the
StrongBack support between vertical supports is 36 inches
(914 mm).
4.2.5 QuickStix Locking Pocket Mains (QSLPM): When
used, the QuickStix Locking Pocket Main members must
be installed parallel to the braced walls. The members
must be cut within 1/8 inch (3.2 mm) of the vertical leg of
the end supports, and both ends must be fixed in the
locking tabs. ShortSpan Tees must be installed as
described in Section 4.2.3. Vertical supports for the
QSLPM members that consist of vertical hangers and
perimeter hangers must be designed and installed in
accordance with the code. The maximum span of a
QSLPM member between vertical supports is 36 inches
(914 mm).
4.2.6 Quikstix Uptight Clip: When used, the QuikStix
Uptight Clip must be fastened to StrongBack and QuickStix
Locking Pocket Main members, as applicable, at a
maximum spacing of 36 inches (914 mm) on center, with
Page 2 of 4
four of the No. 8 by 11/4-inch-long (32 mm), wafer-head,
steel-framing, self-drilling tapping screws described in
Section 3.2.7. Attachment of the QuikStix Uptight Clip must
be with the short offset radius end of the clip facing the
member, to allow correct alignment between the clip and
member due to the offset between the bulb and web of the
member. The opposite end of the clip must be fastened to
the supporting structure in accordance with the approved
construction documents, prepared by a registered design
professional where required by statutes of the jurisdiction
in which the project is to be constructed.
5
4.2.7 Gypsum Board Attachment: Maximum /8-inchthick gypsum board must be installed and fastened to the
ceiling framing system (tees, main members and angle
moldings) in accordance with IBC Section 2508.
4.2.8 Lighting Fixtures: Lighting fixtures, when used,
must be independently supported by the structure.
5.0 CONDITIONS OF USE
The ShortSpan DGS (drywall grid system) described in this
report complies with, or is a suitable alternative to what is
specified in, those codes listed in Section 1.0 of this report,
subject to the following conditions:
5.1 The ceiling framing members must be fabricated, and
the drywall system with gypsum board must be
installed in accordance with, this report and the
manufacturer’s published installation instructions. In
the event of a conflict, this report governs.
5.2 The connection of the ceiling system to supporting
construction has not been evaluated and is outside
the scope of this report. The code official must
approve the floor, wall and/or roof construction
supporting the ceiling system.
5.3 Installation is limited to dry, interior conditions.
5.4 The ceiling system must be designed for seismic
loads in accordance with Chapter 13 of ASCE 7. The
documents must be prepared by a registered design
professional where required by statutes of the
jurisdiction in which the project is to be constructed.
5.5 Periodic special inspections must be provided in
accordance with ASCE 7-10 Section 11A.1.3.9, Item
2, and as required in ASCE 7-05, Section 13.5.6.2.2,
Item h. A statement of special inspection must be
provided for use in Seismic Design Categories D, E
and F as required in 2012 IBC Section 1704.3.2 (2009
and 2006 IBC Section 1705.3).
5.6 For installations in Seismic Design Category C, D, E
or F, a quality assurance plan complying with ASCE
7, Section 11A, must be submitted to the code official.
5.7 Design calculations for loads outside the scope of this
report must be submitted to the code official at the
time of permit application. The calculations must be
prepared by a registered professional where required
by the statutes of the jurisdiction in which the project
is to be constructed.
5.8 The ceiling system is limited to ceilings not
considered accessible in accordance with Item 28
(2012 IBC), Item 31 (2009 IBC) or Item 32 (2006 IBC)
of IBC Table 1607.1, titled, “Minimum Uniformly
Distributed Live Loads and Minimum Concentrated
Live Loads.”
6.0 EVIDENCE SUBMITTED
Data in accordance with portions of the ICC-ES
Acceptance Criteria for Suspended Ceiling Framing
Systems (AC368), dated February 2012.
E
ESR-2311 | Most
M
Widely Acc
cepted and Tru
usted
P
Page 3 of 4
7
7.0 IDENTIFIC
CATION
Bundles/carto
ons of framing members are identified with the
t
name and address of Armsttrong World Ind
dustries, Inc.; the
t
part number; the evaluatio
on report number (ESR-2311);
and the word “WAVE.”
TABLE 1—D
DESCRIPTION OF
O FRAMING SY
YSTEM COMPO
ONENTS
MINIMUM BASE
E-METAL THICK
KNESS (in)
LE
ENGTH (in)
KAM-10
0.0180
120
KAM-12
0.0180
144
LAM-12
0.0180
144
S7708
0.0180
96
S7710
0.0180
120
S7712
0.0180
144
S7714
0.0180
168
0.0340
144
0.0180
144
0.0480
4.5
PA
ART NUMBER
L
Locking Angle Molding/Knurled Angle
A
Molding
S
ShortSpan Tee
S
StrongBack Supp
port
SB12
L
Locking Pocket Main
M
QSLPM12
Q
QuikStix Uptight Clip
QSUTC
F
For SI: 1 inch = 25.4
2
mm.
ORTSPAN TEE
SHO
STRONG BACK SUPPORT
T
A
ANGLE MOLDIN
NG
QUIKSTIX LOC
CKING POCKET
T MAIN
FIGURE 1—SHORTSPAN DR
RYWALL GRID S
SYSTEM COMPO
ONENTS
E
ESR-2311 | Most
M
Widely Acc
cepted and Tru
usted
Page 4 of 4
QUIKST
TIX UPTIGHT CL
LIP
For SI: 1 inch
h = 25.4 mm.
URE 1—SHORTS
SPAN DRYWAL
LL GRID SYSTE M COMPONENT
TS (Continued)
FIGU
ICC-ES Evaluation Report
ESR-2311 CBC Supplement
Reissued September 2016
This report is subject to renewal September 2017.
www.icc-es.org | (800) 423-6587 | (562) 699-0543
A Subsidiary of the International Code Council ®
DIVISION: 09 00 00—FINISHES
Section: 09 22 26—Suspension Systems
REPORT HOLDER:
WORTHINGTON ARMSTRONG VENTURE (WAVE)
101 LINDENWOOD DRIVE, SUITE 350
MALVERN, PENNSYLVANIA 19335
(610) 722-1218
www.armstrong.com
[email protected]
EVALUATION SUBJECT:
SHORTSPAN DRYWALL GRID SYSTEM (DGS)
1.0 EVALUATION SCOPE
Compliance with the following codes:
2013 and 2010 California Building Code (CBC), Chapters 8, 16, 16A and 25
2.0 PURPOSE OF THIS SUPPLEMENT
This supplement is issued to indicate that the Shortspan Drywall Grid System, recognized in ICC-ES master evaluation
report ESR-2311, complies with the CBC, when design and installation are in accordance with the master evaluation report
with the following modifications:
Modify Section 4.1 as follows: The ceiling assembly is designed to support one layer of 5/8-inch-thick (15.9 mm) gypsum
2
board having a maximum weight of 2.5 psf (12.3 kg/m ). The ShortSpan DGS system must be designed for seismic loads as
required under Chapter 13 of ASCE 7-10 as referenced in 2013 CBC Sections 1613, 1613A and 2506.2.1, and modified by
2013 CBC Sections 1616.10.16 and 1616A.1.20 (Chapter 13 of ASCE 7-05 as referenced in 2010 CBC Sections 1613,
1613A and 2506.2.1, and modified in 2010 CBC Sections 1615.10.13 and 1615A.1.16), as applicable.
Modify Section 4.2.7 as follows: Revise reference from IBC Section 2508 to CBC Section 2508.
Modify Section 5.5, as follows: Periodic special inspections must be provided in accordance with 2013 CBC Sections
1704.3, 1704A.3, 1705.11.5, 1705A.11.5 and ASCE 7-10 Section 11A.1.3.9, Item 2 (Section 13.5.6.2.2, Item h of ASCE
7-05, and 2010 CBC Sections 1704.1.1, 1704A.1.1, 1705.3 and 1705A.3). A statement of special inspection must be
provided for use in Seismic Design Categories D, E and F as required in 2013 CBC Sections 1704.3.2 and 1704A.3.2 (2010
CBC Sections 1705.3 and 1705A.3).
Modify Section 5.6, as follows: For installations in Seismic Design Category C, D, E or F, a quality assurance plan
complying with CBC Chapters 17 and 17A, as applicable, must be submitted to the code official.
Modify Section 5.8, as follows: The ceiling system is limited to ceilings not considered accessible in accordance with
Item 28 of 2013 CBC Tables 1607.1 and 1607A.1(Item 31 of 2010 CBC Tables 1607.1 and 1607A.1).
This supplement expires concurrently with the master report, reissued September 2016.
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved.
Page 1 of 1