XFEL.EU TN-2013-005-02 TECHNICAL NOTE Control System for the Photon Beamlines July 2015 T. Korsch for the X-Ray Optics and Beam Transport group (WP73) at European XFEL European X-Ray Free-Electron Laser Facility GmbH Albert-Einstein-Ring 19 22761 Hamburg Germany Contents Revisions ..................................................................................................................... 4 Preface ......................................................................................................................... 5 1 Communication ................................................................................................. 6 1.1 1.2 1.3 1.4 2 Protection ......................................................................................................... 15 2.1 2.2 2.3 3 PLC ........................................................................................................ 6 1.1.1 Bus terminals............................................................................. 6 1.1.2 Bus terminals for additional controller ....................................... 7 Operating parameters ............................................................................ 8 1.2.1 Vacuum pressure ...................................................................... 8 1.2.2 Cooling water flow ..................................................................... 8 1.2.3 Cooling water conductance ....................................................... 8 1.2.4 Compressed air ......................................................................... 8 1.2.5 Temperatures ............................................................................ 8 1.2.6 Beam shutter ............................................................................. 9 1.2.7 Valve ......................................................................................... 9 1.2.8 Motors ....................................................................................... 9 Software ................................................................................................. 9 1.3.1 PLC software ............................................................................. 9 1.3.2 GUI software ............................................................................. 9 1.3.3 GUI for a control system ......................................................... 10 1.3.4 Emergency system .................................................................. 10 Graphical user interface ....................................................................... 10 1.4.1 Symbols................................................................................... 10 1.4.2 Buttons .................................................................................... 13 1.4.3 Service pages.......................................................................... 13 1.4.4 Log book .................................................................................. 14 1.4.5 Archive .................................................................................... 14 1.4.6 Automatic email ....................................................................... 14 Safety during power failure .................................................................. 15 2.1.1 Power blackout ........................................................................ 15 2.1.2 Switch over .............................................................................. 15 Vacuum control and machine protection systems ............................... 15 2.2.1 Beam dump ............................................................................. 16 2.2.2 Machine stop ........................................................................... 17 Service work ......................................................................................... 17 Hardware .......................................................................................................... 18 3.1 PLC ...................................................................................................... 18 3.1.1 Bus coupler to controller ......................................................... 18 3.1.2 Bus terminals........................................................................... 18 July 2015 2 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines 3.2 3.3 3.4 3.5 4 PLC topology ........................................................................................ 19 Power concept...................................................................................... 21 3.3.1 Power for bus coupler ............................................................. 21 3.3.2 Power for components ............................................................ 22 Connectors ........................................................................................... 22 3.4.1 Stepper motor.......................................................................... 22 3.4.2 Encoder ................................................................................... 22 Cable .................................................................................................... 23 3.5.1 Labels for cables ..................................................................... 24 3.5.2 Cable for valves ...................................................................... 25 3.5.3 Cable for ion pumps ................................................................ 25 3.5.4 Cable for sensor fast valve...................................................... 25 3.5.5 Cable for temperature measurement ...................................... 25 3.5.6 Cable for creates / bus coupler ............................................... 26 PLC program logic .......................................................................................... 27 4.1 4.2 4.3 Global variables.................................................................................... 27 4.1.1 Global variables ...................................................................... 27 4.1.2 Main global .............................................................................. 27 4.1.3 Low global ............................................................................... 27 Main functions ...................................................................................... 27 4.2.1 PLC lock .................................................................................. 28 Logic functions for components ........................................................... 28 4.3.1 Logic for valves ....................................................................... 28 4.3.2 Ion pump controller ................................................................. 29 4.3.3 Experiments ............................................................................ 29 4.3.4 Fast valve ................................................................................ 30 A Abbreviations .................................................................................................. 31 B Cabling connection guidelines ...................................................................... 32 B.1 B.2 Cable for ion pumps ............................................................................. 32 B.1.1 Seven-part connector .............................................................. 32 B.1.2 Six-part connector ................................................................... 34 Pin array ............................................................................................... 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 3 of 35 Revisions Version Date Description 1.1 23 Jul. 2015 Second release: Added all components with motion to the control systems Separated equipment protection from vacuum control 1.0 10 Dec. 2013 First release July 2015 4 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines Preface In the European XFEL tunnel, X-ray light will be transported in beamlines from the source point to the experiment. The main objective of the control system for beam transport and optics is to enable the machine to run free of imperfections in time for end-user operation. The control system is divided into three subsystems: vacuum, motion, and equipment protection. The main goal of the vacuum control system is to take care of the vacuum in the beamline and to protect the accelerator for vacuum. The motion control system is for any movable device that is not vacuumrelated. For the optical characteristics of the light, monochromators, mirrors, shutters, slit systems, apertures, and other parts will be installed. These optical devces are typically movable in the beam. Motion control system hardware and software is suitable for all electric or pneumatic moving parts that are not relevant to vacuum. The equipment protection control system is designed to ensure the secure operation of the beam for the experiments. It takes care of correct water cooling, air compression, and other supply media. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 5 of 35 1 Communication Communication in the context of the control system means the information exchange between the PLC, bus coupler, and controller for components, as well as the information that will be shown to the control person. 1.1 PLC The PLC will be a Beckhoff system with EtherCAT Bus. The system will be built in a ring structure (see Figure 1) for each control part. The PLC is outside the tunnel and connected to a bus coupler inside the tunnel. With an optical fiber to decouple any grounding or shielding problems, the EtherCAT signal is transferred to a patch panel in the electronic rack. The optical fiber is a single-mode fiber. The signal will transfer from one coupler to the next coupler on wire with a cable in RJ45 geometry if the distance is less than 100 m. Tunnel Bus coupler Master PLC LWL single-mode EtherCAT – Rj45 Cable < 100 m Figure 1: EtherCAT Terminals and PLC 1.1.1 Bus terminals The bus coupler provides an EtherCAT line for different terminals. The terminals read physical signals, switch voltage, open or close contacts, or send and read data protocols. July 2015 6 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines Bus coupler with terminals Digital Limit switch Analog Vacuum pressure RS485 Pump controller Figure 2: Bus coupler and terminals for different signals Table 1: Function of the terminals Function Type Low High Range Signal Digital input ES1008 0V 24 V — — Digital output ES2008 0V 24 V — — Digital output (fast < 3 ms) ES2202 0V 24 V — — Analog input ES3164 — — 0–10 V — ES3054 — — 4–20 mA — EL6002 — — — 2 x RS232 EL6022 — — — 2 x RS485 ES3314 — — — Type K ES3202 — — — PT100 Communication Temperature Relay output ES2624 Bus coupler EK1101 EtherCAT coupler EK1122 Two-port EtherCAT junction EK1501-0010 EtherCAT coupler for single mode fibre junction EK1521-0010 One-port EtherCAT fibre optic junction 1.1.2 4 x NO contacts Bus terminals for additional controller The control system and its terminals provide a lot of communication protocols, such as RS232, RS485, and RS422. RS485 communication is used for the following: Ion pump controller (Agilent Technologies, Type 4UHV Ion Pump Controller) Turbo pump controller (Pfeiffer TCP 350) XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 7 of 35 1.2 Operating parameters 1.2.1 Vacuum pressure The ion pump controller is from Agilent, Type 4 UHV, with a negative high voltage of up to 7 kV. There are two types of controllers: one can provide four pumps with 80 W (Model 9299400); the other can control two pumps with 200 W (Model 9299020). The current for an ion pump is in relation to the vacuum pressure, so the information about the vacuum can be read out by the controller for the ion pumps. The controller provides the standard RS485 protocol and a threshold for an adjustable vacuum pressure. With a wire connection between the controller and the terminals, the PLC can read the vacuum pressure information and alarms. The vacuum pressure is read out via RS485, and alarm signals are read out by the contact threshold in the controller to digital input terminals. 1.2.2 Cooling water flow With additional boxes, the flow rate can be measured. The box gives a 4–20 mA signal according to the flow. The cooling water is also measured with a temperature switch. If the temperature is too high, a contact will open. 1.2.3 Cooling water conductance The conductance is measured in the cooling water. 1.2.4 Compressed air The compressed air is measured with a pressure device. The box gives a 4–20 mA signal according to the pressure. For some devices, a sensor with a simple switchpoint opens an electrical contact if the pressure is below the set value. Minimimum compressed air will be measured in every tunnel. 1.2.5 Temperatures For temperatures, a PT 100 (platinum with a resistor of 100 Ω by 0°C) should be used. Only in some special cases is a thermocouple Type K allowed. July 2015 8 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines 1.2.6 Beam shutter The signal for the open and closed position of the beam shutter must be read out by an end switch with a positive opening operation. 1.2.7 Valve The limit switch in the open and closed position provides the signal for the valve position. The switch closes if the valve is in the end position. 1.2.8 Motors 1.2.8.1 Encoder The encoder is for motors work with a separate cable in SSI or incremental technique. 1.2.8.2 Switches A limit switch immediately stops the moving and allows just a turn in direction to the other side. A homing or calibration switch cannot be used for an emergency stop. 1.3 Software 1.3.1 PLC software The PLC runs with TwinCAT 3. Logic functions and tasks are programmed there. 1.3.2 GUI software For the graphical user interface (GUI), a Karabo server is connected to the PLC. It allows the display of all main data. Actions can be performed at this level to the PLC, but the logic in the PLC program can override the actions. For example, if you create a macro to open a value, but the pressure is not OK, the PLD blocks the command. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 9 of 35 Display PC PC Master Karabo PLC server Network PC USB,DVI Figure 3: GUI for the interlock 1.3.3 GUI for a control system The GUI is based on Karabo software. User operations are split into five levels of access rights: Admin, Expert, Operator, User, and Observer. 1.3.4 Emergency system For the main tasks, a display is directly connected to the PLC. It allows a simple diagnostic for the complete system and control components without any network. 1.4 Graphical user interface The main goal of a good GUI is provide an intuitional use and understanding of the system. Without a lot of explantion, the GUI must provide a simple way to open and close valves without any risk. The GUI is defined in the “XFEL User Interface Style Guide”: https://xfel-wiki.desy.de/XFEL_User_Interface_Style_Guide 1.4.1 Symbols Symbols for components are based on the International Electrotechnical Commission “Graphical Symbols for Use on Equipment” (IEC 60417) and the European Committee for Electrotechnical Standardization “Safety of July 2015 10 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines Machinery – Electrical Equipment of Machines – Part 1: General Requirements” (EN 60204-1:2006). In addition, the following symbols are used: Beamline Single solid line in black (Figure 4). Aperture Isosceles triangle with the small side to the experiment side (Figure 8). If there is a temperature alarm, it switches from white to red. The small side is half the length of the side. The inner angle is 70° and 120°. Figure 4: Beamline Figure 5: Open (vertical back line) and closed (vertical red line) valve XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 11 of 35 Figure 6: In-range (white circle) and failed (red circle) vacuum pressure 2.5e-8 on off XDT2, 75m, Controller 4 Figure 7: Ion Getter pump with vacuum pressure and an on/off button Figure 8: Low (white) and high (red) aperture temperature July 2015 12 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines Figure 9: GUI for the vacuum interlock at the PETRA III beamline 1.4.2 Buttons Buttons are visible in different rules to the user. For experts, all buttons are visible. For guests, no buttons are visible. Buttons are visible only if the user role enables the user to switch them. The caption of a button is black or grey if it cannot be used or is out of order. A single button can have only one function. That is, there are two buttons for any given valve: one for open and one for closed. A single button cannot switch between open and closed. 1.4.3 Service pages A service page is useful for a quick and efficient search for problems. This page includes all backup information, all hidden properties, and a log book. The service page shows information such as cooling water, compressed air, hardware status, power supplies status, counter for valves, and so on. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 13 of 35 1.4.4 Log book All activities on the PLC must be logged with a time stamp and shown in a text field. Every action is logged in text format (without any special characters or symbols): “component, action, time”. The component defines kind and place. The action is the change of the component. The time is defined as year, month, day, hour, minute, and second in the format YYYY.MM.DD.hh.mm.ss (e.g. Valve V3102, closed, 2015.03.12.13.43.21). 1.4.5 Archive Some data will be saved for several years with a low frequency. The following data must be stored 10 times a minute: 1.4.6 Vacuum pressure, readout of the controller Cooling water temperature Compressed air Configuration of each ion pump controller Automatic email For some tasks, an automatically generated email will be sent. For minor tasks, an SMS will be sent. July 2015 14 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines 2 Protection For all control systems, faultless operation of the system is essential. Any minor fault, which can stop the machine, causes a delay in the experiments. Any major fault must be protected by hardware and software components. 2.1 Safety during power failure 2.1.1 Power blackout Power failure means a complete disruption of the supply voltage in the whole system, or a failure in one unit without a bridge to the redundancy module. If a power failure occurs, the system must switch to Save status. In Save status, the following occurs: 2.1.2 All valves close without power connection. Machines dump to protect the valves. Switch over If the mains voltages switch off for less than 100 ms the System must run without a failure. For this kind of power failure, each power supply bridges a gap of 30 ms. This provides the section of the beamline with power, using a redundancy system in which each power supply runs with a normal load of 50% total operating performance. 2.2 Vacuum control and machine protection systems The machine protection system (MPS) is the process used to maintain the safety of the accelerator and to shut down and stop the system, if needed. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 15 of 35 The vacuum control system is responsible stopping the accelerator if something happens that threatens the safety of the controlled beamlines. The shutdown will activate with a change of one bit via the RS422 protocol. Figure 10: Communication between vacuum PLC and MPS 2.2.1 Beam dump In some cases, the accelerator must be pumped to protect the beamline and its components. These cases are: Tripping of a fast shutting valve. Unexpected non-opening of a valve. In this case, the activator is active, and the open end switch is lost. In each of these cases, an alarm is sent to the user. The alarm indicates which case produced the shutdown. July 2015 16 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines 2.2.1.1 Hardware for beam dump The machine shutdown is possible on a separate RS422 line. The beam dump will activate with a change of one bit via the RS422 protocol. Two elements are directly connected to this line: Fast valve The control unit for a fast shutting valve is directly connected to this line. Software identification of a failure The PLC shutdown will switch on separate Beckhoff ES2202 terminals with a fast output of < 1 μs. 2.2.2 Machine stop The accelerator must stop to protect the beamline and its components in the following cases: Temperature alarm Cooling water flow Failure of a global variable (see Section 2.1, “Safety during power failure”, on page 15) Valve closed by PLC Hardware failure — A power supply is not working. — No compressed air. 2.3 Service work For service or repair of components in the tunnel that are controlled by the PLC, a safety key can be removed from the panel at the control station. Without this key, the PLC does not allow movement of any device. The PLC indicates that the key is missing. Workers are responsible for their own work and safety. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 17 of 35 3 Hardware The hardware of the PLC, bus coupler, terminals, and power supply is defined in this chapter. The systems with PLC, bus coupler, and bus terminals use a modular technique. In this modular structure, the interpolation of new components can be done quickly and easily. 3.1 PLC For the control system, the Advanced Electronics group will program the PLC. In most of the systems, a Beckhoff PLC with EtherCAT protocol is to be used. 3.1.1 Bus coupler to controller The bus coupler and additional terminals provide a lot of communication protocols, such as BiSS-C, RS232, RS485, and RS422. 3.1.2 Bus terminals The bus coupler provides an EtherCAT line for different terminals. The terminals read physical signals, switch voltage, or send and read data protocols. Table 2: Function of the terminals Function Digital input Digital output Analog input Communication Stepper motor SinCos encoder Temperature Bus coupler RS 485 July 2015 18 of 35 Type ES1008 ES2008 ES3164 ES3054 EL6002 EL6022 ES 7041 ES 5021 ES3314 ES3202 EK1122 EK1521 High Range Low 24 V — 0V 24 V — 0V — 0–10 V — — 4–20 mA — — — — — — — — — — — — — — — — — — — Two-port EtherCAT junction One-port EtherCAT fibre optic junction EL6022 2-channel serial interfaces RS485, D-sub connection Signal — — — — RS232 RS485 — — Type K PT100 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines 3.2 PLC topology For each SASE tunnel, one PLC each is responsible for the vacuum, motion, and equipment protection control systems. For example, SASE 1 has three PLCs, and these PLCs controls Experiments 10–12. Figure 11: SASE tunnel definition All PLCs work in the same hierarchy without a master PLC. They communicate via EtherCAT with each other and each PLC in the Karabo system. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 19 of 35 Karabo Server EtherCAT XFEL network PLC PLC PLC 1 2 n Bus coupler 1 Bus coupler 1 Bus coupler 1 Bus coupler 2 Bus coupler 2 Bus coupler 2 Bus coupler n Bus coupler n Bus coupler n Figure 12: Topology July 2015 20 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines PLC 1 EtherCAT Bus coupler Switch contacts Fast valve controller MPS RS 422 Figure 13: Signal communication 3.3 Power concept The system works with 24 V DC. Other voltages must be provided with different power supplies and need extra terminals. 24 V are also provided for the components. The 24 V circuit is protected with a glass fuse. The power supply is protected against short circuits and overloads. All wires must connect to the terminals without screws; only spring terminals are allowed. If another voltage is required (e.g. 12 V), a separate power supply can be requested from the X-Ray Optics and Beam Transport group. 3.3.1 Power for bus coupler For each bus coupler in the tunnel, there are two power supplies with a power balance module that provides the 24 V. The two power supplies are on different phases (L1, L2) and get their own fuse. The power supplies and the balance module have alarm contacts for temperature and overcurrent, which are read out. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 21 of 35 3.3.2 Power for components The components for the vacuum interlock, such as actuators for valves, end switches, gauges, and so on are served by the power supply of the bus coupler. 3.4 Connectors The list of connectors is defined by the Advanced Electronics group. Components in the tunnel are hard installations. On the PLC side, no connector is provided. A patchboard is at the device and not at the electronic rack. Cables are fixed at one end on the PLC terminals and attached at the other end to the patchboard at the component. 3.4.1 Stepper motor For the stepper motor, LEMO Type 3B is defined with 8 pins and the key system G. Limit switches are “normally closed” contacts. For more information about the pin array, see Section B.2, “Pin array”. 3.4.2 Encoder For the encoder, Lemo Type 1B is defined with 8 pins and the key system C. For more information about the pin array, see Section B.2, “Pin array” July 2015 22 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines 3.5 Cable For cable inside the tunnel, the DESY specifications are obligatory. Name: “Technische Spezifikation Energieversorgung Nr. 13/2005 über brandschutztechnische Anforderungen an halogenfreie und flammwidrige Kabel und Leitungen in den Anlagen von DESY” The respective DIN VDE 0100 references apply. Connections to cable cores to crimp are always preferred before screwing and before soldering. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 23 of 35 3.5.1 Labels for cables One side of the cable includes a label with the distance in the tunnel in metres. The other side includes the rack number. Table 3: Label system for cables Letter / Number L N N NN N L Sample V 1 0 15 0 G Component type • Gauge – C = Cold cathode – F = Full range – P = Pirani – S = Spinning rotor • Pump – I = Ion P. – M = Membran P. – N = NEG P. – R = Rootsp. – S = Scroll P. – T = Turbo P. • Valve – A = Angel V. – D = Dosing V. – F = Fast V. – G = Gate V. – M = All Metal V. – V = Vatterfly V. Future upgrades Strart 0..9 Component counter Two numbers 00..99 Beamline zone • 0 = From hand-over point with WP19 up to separation chamber • 1 = Center • 2 = Left • 3 = Right Beamline number • 1 = SASE 1 • 2 = SASE 2 • 3 = SASE 3 Component category • G = Gauge • P = Pump • V = Valve July 2015 24 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines 3.5.2 Cable for valves For a valve, a cable with 5 cores with a M12 connector (female straight) is available for use. On the PLC side, this cable is directly connected to the terminals. On the other side, it has a connector. 3.5.3 Cable for ion pumps For the cable from the ion pumps to the high voltage controller, a cable of the following type should be used: DESY HV-CABLE 0.9/3.2 + 1x0.35mm² - DRAKA – yyyy – ZERO HALOGEN 09 3211173 207171642 nnn m Where “yyyy” is the year of manufacturing and “nnn” is the lineal meter. This cable type includes a core for high voltage that is shielded and a second core for the interlock connection. For detailed information about this cable, see Appendix B.1, “Cable for ion pumps”. 3.5.4 Cable for sensor fast valve The cable for the senor fast valve is similar to the cable for ion pumps. The only difference is that a different connector is used. 3.5.5 Cable for temperature measurement For a temperature measurement with PT 100, a three-core cable should be used. Figure 14: Temperature measurement with PT100 in a three-port cable For thermocouple Type K, a cable of IEC standard must be used, with green coat, red (+), and white (-) isolation. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 25 of 35 3.5.6 Cable for creates / bus coupler The cable colours inside the create are define in Table 4. These colours should be used tor additional boxes or wiring. Table 4: Cable colours for creates Signal Colour L1, L2, L3 Brown, grey, black N Light blue PE Green / yellow +24 V Red 0V Dark blue Digital in / out Red Analog in / out Red Relay signal extern Black RS232, RS422, RS485 Tx White Rx Brown July 2015 26 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines 4 PLC program logic The various parts of essential PCL program logic are described in this chapter. 4.1 Global variables In general, some variables must be provided. 4.1.1 4.1.2 4.1.3 4.2 Global variables Machine status: shut down / run Beamshutter: open / close Main global Compressed air: n.n bar Cooling water flow: nnn l/h Temperatures in range: nn°C Low global Power supply for each bus coupler: operate and temperature in range Vacuum pressure for each pump: n.n e–n mbar Valve position: open / closed Main functions This section describes the main functions. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 27 of 35 4.2.1 PLC lock In accordance with EN60204-1: For safe work at a component or part of a system, it is necessary to switch off the system and get a status that no moving parts can be dangerous to people. This lock closes all valves and beam shutters, and prevents them from reopening even if someone attempts to switch from the GUI. If the lock is relocked, all valves and beam shutters must opened by hand in the GUI PLC PLC PLC PLC PLC SASE 1 SASE 2 SASE 3 SASE 4 SASE 5 TO LOCK UNPLUG THE KEY Figure 15: Key–lock layout for the PLCs 4.3 Logic functions for components 4.3.1 Logic for valves Valves are normally open. They close when one of the following conditions (failures) occurs: Vacuum pump fails in a section Global variable fails in the section User can close a valve by clicking a button in the GUI July 2015 28 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines Activator is active but the open end switch is not active after three seconds A valve can close only when the beam shutter is closed before the valve. If one pump controller fails for ≤ 3 seconds, the valves does not close the section. The open and closed cycles are counted for each valve. Valves can be opened when: Vacuum pressure on both sides of the valve is in range. The open and closed positions are registered with end switches. If both end switches are not active for more than three seconds, the PLC must create an alarm. 4.3.2 Ion pump controller The ion pump controller can be switched on and off by clicking in the GUI. Switching off is possible only when the valve has closed the section. Switching on is possible in expert mode The ion pump controller provides the vacuum pressure information of the pump. A operation time counter have to run for each pump and for the controller. The configuration for connected pumps, set points, alarms, and steps of fixed voltage must be adjusted, saved to the archive, loaded to the controller, and backed up to the Karabo server. The information can then be loaded onto new controllers, overriding their standard configurations. 4.3.3 Experiments For all experiments, an ion pump on the side of the experiment is necessary to make sure the vacuum pressure is adequate to open a valve. XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 29 of 35 Figure 16: Signal interchanges for the experiment and vacuum interlock 4.3.4 Fast valve These valves close directly with their own controller. The PLC gets the status of the valve. The valve can be opened and closed in normal operation through the GUI and can be reset if it closes for safety reasons. Signals of the sensors are read out and shown in the GUI. July 2015 30 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines A Abbreviations GUI graphical user interface MPS machine protection system ms milliseconds PLC programmable logic control RGA residual gas analyser SASE self-amplified spontaneous emission UPS uninterrupted power supply XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 31 of 35 B Cabling connection guidelines B.1 Cable for ion pumps B.1.1 Seven-part connector Figure 17: Seven connector parts: (a) collet nut, (b) collet, (c) reducing cone, (d) split insert carriers, (e) contact, (f) insulator + contact, and (g) housing subassy To prepare the cable for ion pumps with a seven-part connector, follow these steps: 1 Strip off 45 mm of red cable coating. 2 Cut the white string. 3 Strip off 25 mm of white cable coating. 4 Strip off 20 mm of clear cable coating. 5 Prepare the 5 mm core. July 2015 32 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines 6 Put the collet nut (a), collet (b), and reducing cone (c) on the cable. 7 Solder the contact (e) on the core. 8 Solder the red “interlock” core on both contacts at the insulator + contact (f). 9 Insert the split insert carriers (d) and fix the housing subassy (g). XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 33 of 35 B.1.2 Six-part connector Figure 18: Six connector parts: (a) collet nut, (b) collet, (c) elbow outlet, (d) contact, (e) insulator + contacts, and (f) housing subassy To prepare a cable for ion pumps with a six-part connector, follow these steps: 1 Strip off 40 mm of red cable coating. 2 Cut the white string. 3 Strip off 20 mm of white cable. 4 Strip off 15 mm of clear cable coating on 15mm. 5 Prepare the 5 mm core. 6 Put the collet nut (a), collet (b), and reducing cone (c) on the cable. 7 Solder the contact (f) onto the core. 8 Solder the red “interlock” core onto one contact at the insulator + contact (f). 9 Solder the plate between the two contacts. July 2015 34 of 35 XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines 10 Fix the housing subassy(g). B.2 Pin array Table 5: Connectors use for stepper motors and encoders Pin array Pin Motor Encoder Encoder SSI 1 2 3 4 5 6 7 8 A1 A2 GND Ub+ B1 B2 CW Limit CCW Limit A+ AB+ BI+ IUb+ GND D+ DC+ CDIR STAT V+ GND XFEL.EU TN-2013-005-02 Technical Note: Control System for the Photon Beamlines July 2015 35 of 35
© Copyright 2026 Paperzz