This document applies primarily to the net metering of • With a two-meter adapter, the meter that is directly in line residential and light commercial Class 1 installations. with the meter socket is the normal billing meter. The Larger meter off to the side (or above or below) measures the and/or more complex installations require a coordinated effort between the customer, the generator vendor and UI. energy that the customer sells back to UI. • meters have multiple channels that can be read by the customer. (“Class 1 renewable” customers are provided with ABB or Elster meters.) These meters are pre-programmed to record energy flow in only one direction so that the energy There are several physical constraints that must be met in order generator applications, UI requires the use of two meters. to use a two-meter adapter. • One meter is used solely to record energy delivered from • Service size is limited to not more than 200 Amps. UI to the customer • Existing meter socket must be of the “ringless” type. (The flowing out of the customer’s site and into UI will not be inadvertently charged to the customer instead of credited. adapter will not fit properly onto a “ring type” socket.) Second meter is used solely to record energy received • Existing meter socket does not have a “bypass” mechanism. (The bypass mechanism’s clamping action The use of two meters is needed in order to assure that the will not allow the adapter to be pushed into the socket.) outgoing power is properly credited to the customer under all • circumstances. electronic meters must be used. The digital displays on these charge for the installation. In order to accommodate net metering for Class 1 renewable from the customer into UI. For net metering of Class 1 renewable generators, fully The two-meter adapter is installed by UI and there is a METERING REQUIREMENTS • READING THE METERS Two-meter adapters cannot be combined with other adapter-type meter accessories such as a meter-mounted whole-house surge protector. METERING METHODS This meter is recording energy flow. Note the arrow pointing to the right. There are several methods used to accomplish the two-meter arrangement and the method chosen will depend on technical 1. 3. The third method of connecting the second meter applies only to 400 Amp (Metering Class 320) services. dynamics of the application. One method is for the customer’s electrician to install This method involves the installation of current transformers a second meter socket in line with the first. (CTs) over the load side power conductors in the main meter The second meter is used to measure the energy that the customer sells to UI. For “transformer rated” metering, the on the meter nameplate. The display on a transformer rated meter increments at a much slower pace than that of an equivalent self-contained meter. That is because the display on This work must be performed as a coordinated effort between a self-contained meter increments once for every kWh of energy UI and the customer’s electrician. The “transformer rated” meter while the display of a transformer rated meter increments once measures the energy that the customer sells to UI. The for every one kWh times the multiplier (typically 40 or 80 on advantage of this method of net residential meters). metering for 400 Amp services is mounted next to the original socket. that it reduces the costs and The second method is to install a two-meter adapter. unsightliness of having two full- This is the most common method used by sized 320 Amp meter sockets. homeowners with a service of 200 Amps or However, before considering this less. method, the customer’s electrician should consult with Utility Meter the town electrical inspector. Generator Meter display must be multiplied by a value that is written (in marker) socket. second meter socket is simply 2. Note: For “Transformer Rated” meters, the value on the There will be an arrowhead or a sequence of bars on the meters that display the instantaneous direction of power flow. As you go from importing power from UI to exporting power to UI, the arrows will change direction. The meter with the arrow pointing to the right is the one currently recording energy. The one with the left-pointing arrow is recording nothing. The arrows on the two meters should always be pointed in opposite directions. METER DISPLAY ELECTRONIC METER DISPLAY CHANNELDESIGNATIONS Meter Type ABB / ELSTER CH1 Date (DD/MM/YY) CH2 Time NET METERING CH3 This meter is not recording energy flow. Note the arrow pointing to the left. (The 'generator' meter is wired backwards so that it spins forward when you are selling power back into the UI system.) If you want to conduct a test, while the generator is in service, CH4 Total kWH CH5 Rate A kWH CH6 Rate A Demand CH7 Rate B kWH CH8 Rate B Demand CH9 Rate C kWH CH10 Rate C Demand CH11 Program ID CH12 try turning on electrical devices (oven, a/c, etc.) in your house CH13 until you see the arrow on the billing meter point to the right CH14 K' value ( ) and the arrow on the 'generator' meter point to the left (↖). Once the above is true, start turning off electrical devices until you see the arrow on the billing meter point to the left Rate A = On Peak Rate B = Off Peak Rate C = Shoulder (Not used in all cases.) (↖) and the arrow on the 'generator' meter point to the right ( ). In each case, the total kWh reading will only increase on the meter with the arrow pointing to the right. The above table represents a ‘Time of Use and Demand” rate structure. Not all channels will be utilized for all rate structures, but the channel number of the channels that are used will still match that of the table. UI’s generator meter is measuring something different from the meter provided by the generator vendor. The vendor's meter measures the total production of the Class 1 generator system. UI's 'generator' (we call it 'outflow') meter records only the excess power that is back-fed to UI. The rest of your system's CLASS 1 RENEWABLE GENERATION (Primarily Solar & Wind) output is used to reduce the energy consumed from UI. There is no way to do a direct comparison between the two meters. The best check for most people (with a prior billing history on the same location) is to compare the kWh numbers (not dollars) on today's bill with those from a similar prior billing period. Note: Please consider any significant additions or removals of electrical equipment done during the comparison period when doing this comparison. UNITED ILLUMINATING COMPANY Distributed Generation 801 Bridgeport Avenue Shelton, CT 06484 email: [email protected] • • • Meter Requirements Metering Methods Reading The Meters & Display
© Copyright 2026 Paperzz