4 205 120 V02 MA 7-Uno-3 (320-360) EN.indd

Technical information
Assembly instructions
Uno-3 (320, 360)
Oil/gas boilers
These instructions are applicable to the
following types:
7-Uno-3 (320, 360)
7-Uno-3 b-i * (320, 360)
* = Burner integrated
Hoval products must be installed and commissioned only
by appropriately qualified experts. These instructions
are intended exclusively for the specialist. Electrical
installations may only be carried out by a qualified
electrician.
Subject to modifications
|
4 205 120 / 02 - 12/13
Uno-3 (320, 360) boilers are suitable and licensed for
use as heat generators for hot water heating systems
with a permissible flow temperature of up to 100 °C1).
They are designed for closed-circuit systems, but can
also be installed in open systems as per EN 12828.
1)
See chapter 3.2
EN
TABLE OF CONTENTS
1.
Important notes
1.1
Other instructions................................................................................................................................................................3
1.2
Safety instructions...............................................................................................................................................................3
1.3
Regulations, official approvals............................................................................................................................................3
1.4Warranty................................................................................................................................................................................4
2.Installation
2.1
2.2
2.3
2.4
2.5
2.6
3.
Installation position..............................................................................................................................................................5
Setting up, levelling..............................................................................................................................................................5
Fitting the thermal insulation...............................................................................................................................................6
Fitting the casing..................................................................................................................................................................8
Fitting the boiler controller on the side...............................................................................................................................8
Fitting the boiler controller at the top...............................................................................................................................10
Technical information
3.1
Description of the boiler....................................................................................................................................................12
3.1.1
The Uno-3 (320, 360) complies with the following directives + standards.........................................................................12
3.2
Technical data Uno-3 (320, 360).........................................................................................................................................13
3.3Dimensions.........................................................................................................................................................................14
3.3.1
Overall dimensions and space requirements....................................................................................................................14
4.Installation
4.1
Boiler installation room requirements...............................................................................................................................17
4.2
Flue connection and dimensioning...................................................................................................................................17
4.3
Installing the burner...........................................................................................................................................................19
4.3.1
Noise damping.................................................................................................................................................................19
4.4Fuel.....................................................................................................................................................................................20
4.5
Electrical connection..........................................................................................................................................................20
4.5.1
Electrical connection of burner.........................................................................................................................................20
4.6
Flue gas and performance diagrams.................................................................................................................................20
4.7
Flow mixing loop / minimum limitation of the boiler return temperature........................................................................21
4.8
Setting the temperature controllers...................................................................................................................................21
4.9
Safety valves......................................................................................................................................................................21
4.10
Charging pump (boiler with free-standing calorifier).......................................................................................................21
4.11
Heating pump.....................................................................................................................................................................21
5.Commissioning
5.1
Water quality.......................................................................................................................................................................22
5.1.1
Heating water..................................................................................................................................................................22
5.1.2
Filling and replacement water..........................................................................................................................................22
5.2
Filling the heating system..................................................................................................................................................23
5.3
Filling the water heater (if fitted).......................................................................................................................................23
5.4Commissioning...................................................................................................................................................................23
5.5
Oil/gas burners...................................................................................................................................................................23
5.6
Handover to the operator/storage......................................................................................................................................23
6.Maintenance
6.1
Information for combustion controller / chimney sweep regarding emission monitor key............................................24
6.2Cleaning..............................................................................................................................................................................25
6.2.1
Preparatory work.............................................................................................................................................................25
6.2.2
Cleaning (dry or wet method)...........................................................................................................................................25
6.2.3
Putting into operation again.............................................................................................................................................25
7.
7.1
7.2
2
Overview of settings
Table of parameters............................................................................................................................................................26
Overview of alarms TopTronic®T........................................................................................................................................37
4 205 120 / 02
IMPORTANT NOTES
1.
1.1
Important notes
Other instructions
All instructions relevant to your system can be found
in the Hoval system manual! In exceptional cases, the
instructions can be found enclosed with the components.
Further information sources
• Hoval catalogue
• Standards, regulations
1.2
Safety instructions
The system may only be placed in operation if all the
relevant standards and safety regulations have been
complied with. At least the following conditions must be
satisfied for a trial operation:
1. Safety valve installed (system sealed).
2. Control system in operation (connected to the
power supply).
3. Sensor for the safety temperature limiter mounted in
the immersion sleeve.
4. System filled with water.
5. Expansion tank connected.
6. Flue gas outlet with flue gas conduit connected to
flue gas system.
7. An adequate supply of fresh air must be guaranteed.
8. Burner preset.
1.3
Regulations, official approvals
The following regulations are to be complied with for
installation and operation:
Germany
• DIN EN 12831 Heating systems in buildings – Method
for calculation of the design heat load.
• EN 303 Heating boilers with forced draught burners.
• DIN EN 12828 Sheet 1 and 2
Heating systems in buildings – design of water-based
heating systems.
• DIN 4755 Oil-fired systems.
Design, construction and safety engineering
requirements.
• DIN 4756 Gas-fired systems; construction, execution,
technical safety requirements, planning and execution.
• DIN 18160 House chimneys; requirements, planning
and execution.
• TRD 702 Steam boiler plants with calorifiers of the
group II.
• DIN EN 13384 Flue gas systems – Calculation methods
in heat and flow engineering.
• TRD 721 Safety devices against excess pressures /
safety valves / for steam boilers of Group II.
4 205 120 / 02
• VDI 2035 Prevention of damage by corrosion and the
formation of scale in hot water heating systems.
• DIN 57 116 / VDI 0116 Electrical equipment for firing
systems (VDE Regulation).
• For further standards applicable in Germany, see
appendix N-430 020.
Austria
• ÖNorm 7550.
• ÖNorm B 8130 Open water heating systems;
safety devices.
• Norm B 8131 Closed water heating systems; safety,
execution and testing requirements.
• ÖNorm B 8133 Hot water production systems; technical
safety requirements.
• ÖNorm B 8136 Heating systems, space requirements
and other building requirements.
• ÖNorm M 7515 Calculations of dimensions of chimneys;
terminology, calculation procedure.
• ÖNorm H 5171 Heating systems, construction
engineering requirements.
• ÖVGW TR-Gas G1 Technical directives for low pressure
gas installations.
• ÖNorm M 7445 Gas blower burner.
Switzerland
• VKF – Association of Cantonal Fire Insurers
• Fire prevention authority regulations.
• Requirements of the SVGW Swiss Association of Gas
and Water Suppliers.
• SWKI 91-1 Aeration and ventilation of the boiler
installation room.
• SWKI 88-4 Water treatment for heating, steam and air
conditioning systems.
• SWKI 93-1 Safety engineering installations for heating
systems.
• KRW Corrosion caused by halogen compounds.
• KRW/VSO/FKR Plug-in electrical connections on
heating boilers and burners
and further regulations and standards issued by CEN,
CEN ELEC, DIN, VDE, DVGW, TRD and the legislative
body.
Also to be complied with are the regulations of the local
building authorities, insurance companies and chimney
sweeping operations. The regulations of the responsible
gas supply company are also to be complied with and any
necessary official approval obtained.
3
IMPORTANT NOTES
1.4
Warranty
Proper function is only guaranteed providing these
instructions are followed and the boiler is regularly
maintained by a licensed specialist. (Maintenance contract).
The rectification of faults and damage as a result of
contaminated operating materials (gas, water, combustion
air), unsuitable chemical additives and an inadmissibly high
lime content of the heating water, improper handling, faulty
installation, unauthorised modifications and damage due to
the use of force do not fall under our guarantee obligations,
this also applies to corrosion due to halogen compounds,
e.g. from spray cans, paints, adhesives, halogenated fluids,
solvents and cleanings agents.
4
4 205 120 / 02
ASSEMBLY
2.
2.1
Installation
Installation position
Where limited space is available, the Uno-3 can be
transported standing on the door. Hex nuts are mounted
behind the door as supports for this purpose. After
transport, they can simply be screwed back to the bracket.
Release and screw back 6 transport counter
nuts (1, Figure 01) before commissioning.
1
2.2
Setting up, levelling
A special foundation plate for the boiler is not an essential,
but it is recommended.
Space requirement
For mounting the thermal insulation and sheet metal
cladding:
at least 40 cm each on the left and right side of
the boiler.
If the space between the boiler and the wall is less,
all heat insulation and casing must be fitted before the
boiler can be pushed into its final position.
Do not connect lines until the heat insulation and
casing have been fitted to the boiler!
There must always be enough space
between the back of the boiler and the
wall to allow easy access to the cleaning
aperture in the flue gas collector.
There must be enough space to swing open the
boiler door, incl. the burner.
Figure 01
Levelling
Using a spirit level, align the upper edge of the boiler water
jacket (longitudinal axis of the boiler) until it is precisely
horizontal or sloping very slightly upwards towards the
rear by inserting the plinth rails correspondingly, to allow
the boiler to vent properly.
Before fitting the burner, first fit the double door
(8a, Figure 05) (door casing).
4 205 120 / 02
5
6
Fitting the thermal insulation
i
The remaining 2 insulation mats (12, Figure 05) are fitted after mounting the casing.
1. Mount the front retaining bracket (1, Detail A, Figure 02) with hexagon screws M8, nuts and U-washers, aligned horizontally, to the front wall of the boiler.
Attach C-clips.
2. Mount the rear retaining bracket (2, Detail B) with hexagon screws M8, nuts and U-washers aligned horizontally. Attach C-clips.
3. Place the insulation mat (3, 3a) around the boiler body (with the joint at the top, black side facing outwards, see Figure 3).
4. Attach the insulation mat (3, 3a) using 4 plastic straps (4) and strap fasteners (4a, Detail C):
-- tension springs (4b) serve for additional fixing
-- Do not overtighten the straps (reduced insulating value)
5. Attach the insulation mats (5/5a/5b) to the pins provided on the rear wall of the boiler and secure with retaining discs (ø 38). Wrap the insulation mats (5c)
around the connection fittings and secure with tension springs.
6. Attach insulation panels (6/6a/6b/6c/6d) to the pins welded onto the flue gas collector and secure with the retaining discs (ø 38).
7. Attach insulation panels (7/7a/7b/7c/7d) to the pins welded onto the front wall of the boiler and secure with the retaining discs (ø 38) provided.
2.3
ASSEMBLY
4 205 120 / 02
4 205 120 / 02
7c
7a
7
7d
4a
Detail C
4
7b
3
‌4b
3a
C-clips
6b
6
5a
6c
Detail A
5c
1
2
Figure 02
Detail B
5b
6a
5
6d
ASSEMBLY
7
8
Fitting the casing
Fitting the boiler controller on the side
17.Attach cover plate (15, Figure 05) with self-tapping screws ø3.5 x 6.5 and serrated washers.
18.Position cladding cover (18, 18a, 18b) and fix left and right with 2 self-tapping screws ø 4,8 x 38 each. (Model with
accessible covers, see separate instructions)
19.Fit cover plate (19, 19a) with self-tapping screws ø 3.5 x 9.5.
20.Affix labels and where applicable, mount manual holder on the side.
21.Remove transport lock (see chapter 2.1).
Attention: The capillaries must not be folded or kinked!
15.Remove the control box cover plate (15, Figure 05). Hook the switch control box (15a, Figure 03) into the side wall
(11a, Figure 05) with the recesses for the special screws and secure it with 2 self-tapping screws ø3.5 x 6.5 and
serrated washers (15b, Figure 4).
16.Pull the capillaries with the immersion sensors (16, Figure 04) through the opening (16, Figure 03) in the side wall,
insert them into the immersion sleeve (16b, Figure 05) as far as the stop and fix in position with retaining spring
(16c, Figure 04).
The controller must be mounted on the side of the Uno-3. If this causes problems due to limited space, it is also
possible to fit the controller on the top of the Uno-3. You will find a description of how to do this on the next page.
2.5
8. Fix bolts (8, Detail D, Figure 05) with hexagon nuts M8 and U-washers to the door and then mount door
cladding (8a).
9. Place support (9) on the hinge holder (Figure 6a). Attach 4 special screws (9a, Detail E) with counter nuts to the
side sections (9b/9c). Fit burner plug (9d) into the front left (or right) side section and route the burner cable (9e)
(possibly over the boiler) to the opening for the controller (cable routing as shown in Figure 05). Place right and
left side sections (9b/9c) into the support (9) and attach to the front brackets with self-tapping screws ø 4.8 x 38.
10.Mount support (10, Detail F) with hexagon bolts and nuts on the water jacket base (back wall of boiler). Important:
support (10) must be aligned so that top edge of support (9) and top edge of support (10) are at the same height.
11. Hook lower right and left side wall (11) into the side sections (9b/9c) and attach to the front and rear retaining
brackets with self-tapping screws ø 4.8 x 38. Hook upper right and left side wall (11a) into the side sections
(9b/9c) as well as into support (10) and attach to the front and rear retaining brackets with self-tapping screws
ø 4.8 x 38.
12.Place 2 insulating mats (12) left and right in longitudinal direction (to prevent vertical air circulation).
13.Only applies if mounting the controller on the side (see chapter 2.5): Fit 2 special screws (13, Figure 03) with
counter nuts to the side wall on which you are mounting the controller.
14.Attach rear wall (14, Figure 05) to the angled edges of the side walls (11, 11a) with self-tapping screws ø 4.8 x 38
and C-clips.
2.4
16
16c
16a
13
15b
Figure 04
Figure 03
15a
ASSEMBLY
4 205 120 / 02
4 205 120 / 02
8a
8
Detail D
9
Detail F
8a
9b
19
12
10
19a
18
9d
18a
16b
9c
9e
11
Detail E
9a
18b
Figure 05
15
11a
14
ASSEMBLY
9
ASSEMBLY
2.6
Fitting the boiler controller at the top
15.Remove the control box cover plate (15, Figure 05).
The control panel (15a, Figure 06) must be turned
around. To do this, remove the pressure lock sleeves
(15b, press together and pull off) and the earthing
screw and serrated washer (15c). Attach the special
screws (15d) in the casing cover (15e) with counter
nuts. Position switch control box (15f) on the casing
cover (15e) with the recesses for the special screws
and secure with 2 self-tapping screws ø3.5 x 6.5 and
serrated washers (15h). Fit casing cover (15e, Figure
07) and secure with self-tapping screws (ø4.8 x 38).
16.Pull the capillaries with the immersion sensors
(16, Figure 04) through the opening (16a, Figure 06)
in the cover, insert them into the immersion sleeve
(16b, Figure 07) as far as the stop and fix in position
with retaining spring (16c, Figure 04). Insert the
burner plug (16d, Figure 07).
17.Attach cover plate (15) with self-tapping screws
ø3.5 x 6.5 and serrated washers.
18.Position cladding cover (18, 18a) and fix left and
right with self-tapping screws ø 4,8 x 38. (Model with
accessible covers, see separate instructions)
19.Fit cover plate (19, 19a) with self-tapping screws
ø 3.5 x 9.5.
20.Affix labels and where applicable, mount manual
holder on the side.
21.Remove transport lock (see chapter 2.1).
Attention: The capillaries must not be folded
or kinked!
15b
18
15c
0°
15f
15h
15a
15d
Figure 06
15e
16a
10
4 205 120 / 02
ASSEMBLY
18
18a
16b
15
15e
16d
19a
Figure 07
19
4 205 120 / 02
11
TECHNICAL INFORMATION
3.
3.1
Technical information
Description of the boiler
The Uno-3 is a threepass boiler. At the end of the circular
cylindrical combustion chamber, the flame gases flow
through several cylindrical tubes arranged above the
combustion chamber and towards the front to the turning
chamber, from where they flow through rectangular ducts
(thermolytic heating surface) towards the rear and reach
the flue gas collector. The flue gas temperatures can be
varied within a specific range through the installation of
various regulator combinations.
3.1.1 The Uno-3 (320, 360) complies with the
following directives + standards
We hereby declare that the product described, as an
individual appliance, complies with the standards,
guidelines and technical specifications laid down.
Directives
90/396/EC
92/42/EC
73/23/EEC
89/336/EEC
97/23/EC
Regulations
Stability
Building
requirements
Low voltage
EMC
"Gas Equipment Directive"
"Efficiency directive"
"Low-voltage directive"
"Electromagnetic compatibility"
"Pressure Equipment Directive"
(PED)
prEN14394:2001
EN303-1, EN303-2, EN303-3
DIN VDE 0722/ Ed. 04.83
EN 50082 Part 1/ Ed. 01.92
Figure 08
12
4 205 120 / 02
TECHNICAL INFORMATION
3.2
Technical data Uno-3 (320, 360)
Type
(320)
(360) 1
kW
kW
kW
kW
320
220-320
140-320
344
360
220-360
140-360
390
• Maximum boiler operating temperature 2
• Safety temperature limiter setting (water side) 2
• Operating/test pressure at max. operating temperature 90 °C 1
°C
°C
bar
90
110
4.0/5.2
90
110
4.0/5.2
• Maximum boiler operating temperature 3
• Safety temperature limiter setting (water side) 3
• Operating pressure at max. operating temperature 105 °C 3
°C
°C
bar
105
120
4.0
105
120
4.0
• Minimum boiler operating temperature
• Minimum boiler return temperature
• Minimum flue gas temperature at boiler
°C
°C
°C
•
•
•
•
Nominal heat output at 80/60 °C
Heat output range (heating oil EL, natural gas H: variant 1 and 3)
Heat output range (heating oil EL, natural gas H: variant 2)
Maximum heat input
• Regulator set for 170 °C flue gas temperature
• Boiler efficiency at full load at 80/60 °C
(related to lower/upper calorific value (heating oil EL))
• Boiler efficiency at partial load 30 % at return 37 °C
(acc. to EN 303) (related to lower/upper calorific value (heating oil EL))
• Standard efficiency at 75/60 °C (DIN 4702 Part 8)
(related to lower/upper calorific value (heating oil EL))
• Standby losses qB at 70 °C
• Resistance on the heating gas side at nominal output
180 °C flue gas temperature, 12.5 % CO2, 500 m above sea level
(tolerance ±20 %)
• Flue gas mass flow at nominal output 12.5 % CO2 heating oil
see table of operating conditions (below)
see table of operating conditions (below)
see table of operating conditions (below)
-
-
%
93.5/ 88.2
92.5/87.3
%
95.5/90.1
95.0/89.6
%
96.6/ 91.1
95.8/ 90.4
Watts
670
670
mbar
2.5
3.4
kg/h
542
610
•
•
•
•
•
•
Maximum flue draught
Flow resistance boiler 4
Hydraulic resistance at 10K
Hydraulic resistance at 20K
Water flow rate at 10K
Water flow rate at 20K
Pa
z-value
mbar
mbar
m³/h
m³/h
20
0.022
16.51
4.10
27.43
13.71
20
0.022
20.94
5.2
30.86
15.43
•
•
•
•
Boiler water capacity
Boiler gas content
Insulation thickness of boiler body
Weight (incl. casing)
Litres
m³
mm
kg
625
0.402
80
920
625
0.402
80
920
mm
m³
ø488x1634
0.3056
ø488x1634
0.3056
Pa
30
• Combustion chamber dimensions Ø-inside x length
• Combustion chamber volume
• Dimensions
see dimensional drawing
• Maximum depression in flue gas system (boiler connection)
3
4
1
2
Not available in Switzerland
Controller U3.1 and T2.2
Controller U3.2 and T0.2
Flow resistance boiler in mbar = flow rate (m³/h)2 x z
Possible operating conditions
Fuel
Uno-3 type
min. flue gas temperature
min. boiler temperature
min. return temperature
Return maintenance
Boiler start-up protection 1
1
30
°C
°C
°C
Heating oil EL
(110-360)
Option 1
Variant 2
Option 3
130
48
35
110
50
38
yes
no
yes
no
130
52
No lower
limit
no
yes
Natural gas H
(110-360)
Option 1
Variant 2
Option 3
Heating oil L
(110-280) (320-360)
130
55
45
110
60
48
130
62
No lower limit
130
58
45
130
70
60
yes
no
yes
no
no
yes
yes
no
yes
no
If the boiler temperature is or drops below the minimum boiler temperature (variant 3) and there is no return maintenance then the load must be
switched off using a corresponding control function.
4 205 120 / 02
13
TECHNICAL INFORMATION
3.3
Dimensions
(All dimensions in mm)
1210
7
7
9
u
g
11
6
205
h
m
10
860
f
8
4
k
7
205
v
800
5
q
388
3 1
2
e
i
d
12
1
2
3
4
5
6
7
8
a
b
12
t
l
s
9 Boiler door attached on the right (on the left if desired)
10 Flue gas collector cleaning connection R 1"
11 Burner sound attenuation cowl; feet on rollers, height 50 mm,
adjustable up to 170 mm
12 Possible anti-vibration elements; width 80 mm, height 50 mm
Flow DN 80, PN 6
Return DN 80, PN 6
Thermostat immersion sleeve ¾″
Drain pipe R 1½″
Flue gas outlet Ø external, plate thickness 3 mm
Cleaning aperture 455/95 mm
Boiler controller on the right/left or top
Plinth rail, width 50 mm
Uno-3
Type
(320-360)
l
b
h
a
d
e
f
g
i
k
m
q
Ø
s
t
u
v
2070
910
1358
750
50
450
240
270; 4xM10
195
684
1100
249
178
1736
77
123
3.3.1 Overall dimensions and space requirements
Boiler (without calorifier) incl. swivel flange, connections and flue gas collector.
Uno-3
Type
(320.36)
14
Width
B
Length
L1
Length
L2
Height
H
Weight
kg
750
2114
1886
1481
800
4 205 120 / 02
TECHNICAL INFORMATION
Minimum overall unit dimensions boiler upright
Boiler (without calorifier) upright with swivel flange at
bottom, transport on trolley or rollers provided by the client.
Example calculation for the required corridor width
Door width T = 800
Uno-3 (320, 360)
K=
750
800
x 1481= Corridor width≥ 1389
Dimension of boiler door
Space for using a trolley
1
2
3
4
Transport board (by client)
Pipe as roller (by client)
Boiler door (can be removed)
Hinge bracket
Boiler height
Uno-3
Type
with
without
connection b.
connection b.
Flue gas collector Flue gas collector Width
H1
H2
B
(320, 360)
2114
1886
750
Max. width
for trolley
a
Uno-3
Type
Length
L
(320, 360)
Available ground clearance
with boiler door without boiler door
b
c
540
50
195
1481
Required minimum width of door and corridor for
bringing in the boiler
The following values are the calculated minimum values.
K=
T=
K
L
B
< 150
B
T
B
K
xL
T
K
B
L
Door width
Corridor width
Boiler width
Maximum boiler length
xL
Example calculation for the required corridor width
Door width T = 800
Uno-3 (320, 360)
K=
750
800
x 2114 = Corridor width≥ 1982
T
4 205 120 / 02
15
TECHNICAL INFORMATION
Tilting out of the boiler door and cowl dimensions
b
a
b
f
g
c
a
e
c
d
d
h
Type
Uno-3 (320)
Uno-3 (360)
1)
Sound reducing
cover
a
b
c
d
e 1)
f
g
depending on burner 606 depending on burner 400 depending on burner 2070
depending on burner 606 depending on burner 400 depending on burner 2070
d
h
600
600
Minimum distance 100 mm
16
4 205 120 / 02
INSTALLATION
4.
4.1
Installation
Boiler installation room requirements
Regarding the building specifications for boiler rooms
and their supply and extract air handling, the current
building supervisory office regulations specific to the
state or country are to be observed. In Germany the firing
regulations for the individual Bundesländer are to be
complied with.
Make sure there is an adequate supply of fresh air to
the boiler room,
to ensure that the combustion air supply necessary for
all the firing systems operated there can flow in without
hindrance and that no oxygen deficiency occurs for the
operating personnel.
Binding values for the size of supply air openings are not
generally specified in the relevant regulations; it is merely
required that no partial vacuum in excess of 3 N/m2
occurs. An opening or line leading into the open air of at
least 150 cm2. For every kW in excess of 50 kW, a further
2 cm2 must be calculated. In rectangular openings, the
ratio of the sides should not exceed 1.5:1; if a grid is fitted,
an appropriate allowance must be added so that the free
cross-section area reaches the amount given above.
In Austria ÖNorm H 5171 additionally stipulates a flue
air aperture. This must have a minimum cross section of
180 cm2 up to a rated heat output of 100 kW. For every
further kW, the cross-section must be increased by 1 cm2.
The flue gas system must be watertight,
acid-proof and approved for the
corresponding flue gas temperatures.
As a general rule, only one heat generator should
be connected to the chimney! When using two heat
generators, the corresponding regulations must
be observed.
4.2
Existing flue gas systems may require upgrading
or adjustment of the flue duct cross-section as
indicated by a chimney engineer.
The correct functioning of the flue duct, i.e. the generation
of the required delivery pressure depends on:
a) the type (nature) of the chimney (thermal insulation,
interior surface roughness, sealing etc.).
b) the connection of the boiler to the chimney according
to specification.
c) the correct chimney cross section dimensioning.
ref. a)
Chimneys according to EN 13384, part 2, execution
types I and II are appropriate for modern firing systems
(advice from the chimney specialist is necessary).
to b)
The flue gas pipe connecting the boiler to the flue gas
system must be as short as possible and placed at an
angle of 30-45°.
The entry location of the flue gas pipe must be carefully
sealed.
The introduction of the flue gas pipe into the chimney (A)
must be executed so that no condensate water can flow
from the chimney into the flue gas pipe and the boiler
(Figure 09).
A
Flue connection and dimensioning
To guarantee economic and fault-free operation, boiler
and chimney must be mutually adapted to create
a functional unit.
Moisture-resistant and acid-proof flue gas systems
must be used in new installations.
4 205 120 / 02
Figure 09
Where possible, avoid 90° bends in the flue gas system!
Flue gas pipes longer than 1 m are to be insulated.
17
INSTALLATION
Normally only one heat producer may be
connected to the chimney!
Flue gas pipes longer than 1 m are to be insulated. If an
adapter (reducer) from the flue gas outlet of the boiler to
the entry point into the flue gas system is required, it must
take the form of a slim cone.
to the chimney
zum
Schornstein
from
vom the
boiler
Kessel
Figure 10
to c)
Dimensioning the chimney cross section. The cross
sections are to be calculated for boilers without delivery
pressure requirement according to EN 13384. (Please
also observe DIN 18160, Part 1 "Domestic chimneys").
Take into consideration location-specific factors (hillside
location of the building, chimney position, slope of
the roof, chimney stack exit shape, etc.)!
In Switzerland, take note of SIA Recommendation 384/4!
In Austria, calculation is performed as prescribed by
ÖNorm M 7515.
Non-binding guide values for dimensioning of the flue
duct for boiler types Uno-3 (320, 360).
Inside diameter of flue duct in mm
Boiler type
Uno-3
kW *
Chimney height
11-15 m
(320)
320
~ 300
(360)
360
~ 350
*kW = maximum boiler output Based on:
Flue gas pipeline 5 m long, 2 90° elbows and 1 45° elbow,
outside air 15 °C, height above sea level max. 800 m,
flue gas pipeline same ø as flue gas connector on boiler.
You are recommended however to use the services of the
chimney specialist right from the planning stage!
18
4 205 120 / 02
INSTALLATION
4.3
Installing the burner
• Depending on the size of the burner flange, an
intermediate flange may be required to attach the burner.
• To allow the burner to be swung out 90° to the left
or right, the connections must be flexible and routed to
the burner in sufficiently large loops.
• The cavity between burner pipe and boiler flange must
be insulated with the fireproof fibre provided.
• In systems with ThermoCondensor, the burner
must additionally absorb the resistance of the
ThermoCondensor and the flue.
f
Uno-3
(320, 360)
Figure 11
Uno-3
(320, 360)
A
B
Ø
Ø
240
270; 4xM10
C
D
M
450
195
340
E
335
F
G
Ø
Ø
240
488
H
L max.
N
O
1649
630
33
133
4.3.1 Noise damping
• Gas pipelines are to be installed so that no vibrations
can be transferred to the building.
• A foundation plate under the boiler unit.
We recommend the following sound attenuation
components:
• Heat and sound attenuation cowl over the burner
• Flue gas silencer in the exhaust gas pipe
• Flexible exhaust gas pipe sleeves on the boiler exhaust
gas pipe
• Vibration elements for the plinth rail
4 205 120 / 02
19
INSTALLATION
4.4
Fuel
The boiler is only to be operated with the
fuel stated on the boiler rating plate.
4.6
Flue gas and performance diagrams
Uno-3 (320)
180
Uno-3 boilers are normally suitable for burning the following
fuels:
• Heating oil EL in accordance with DIN 51 603 / SN 181
160/2 / ÖNorm C 1109
• Heating oil L in accordance with ÖNorm C 1108
• All combustible gases in accordance with DVGW
Work sheet G 260
170
160
150
°C 140
130
120
110
100
140
4.5
160
180
200
For Switzerland, the following applies:
The system-related electrical circuit diagram must be
referred to when making the electrical connection!
For Austria only:
The diagram folder is located in the switch control box.
Please affix the correct connection diagram to the inside
of the terminal cover.
An electrical circuit diagram is supplied with the boiler
controls.
An all-phase main switch with a minimum contact spacing
of 3 mm must be fitted in the power supply line.
Applies only for Germany:
The diagram folder is located in the switch control box.
An electrical circuit diagram is supplied with the boiler
controls.
An all-phase main switch with a minimum contact spacing
of 3 mm must be fitted in the power supply line.
240
260
280
300
320
kW
Electrical connection
A qualified technician must install the electrical supply to
the equipment. The electrical circuit diagram is located in
the electrical box.
220
Uno-3 (360)
180
170
160
150
°C
140
130
120
110
100
120 140 160 180 200 220 240 260 280 300 320 340 360
kW
kW = Heat output
°C = Flue gas temperature with heating oil EL
Boiler flow 80 °C
Return flow 60 °C
CO2 = 13 %
During the combustion of natural gas or heating
oil L, the flue gas temperature is approx. 15 °C
higher
4.5.1 Electrical connection of burner
• The burner must be connected to the boiler with the
standard plug and socket connection.
• The burner cable must be shortened so that the plug-in
connection has to be parted to swing out the burner.
20
4 205 120 / 02
INSTALLATION
4.7
Flow mixing loop / minimum limitation of
the boiler return temperature
Hydraulic and control measures must be provided to
ensure that the operating conditions are complied with in
terms of boiler flow and return temperatures.
4.8
Setting the temperature controllers
Boiler temperature controller, selectable TR 50 °C – 85 °C
Basic setting of the controller is carried out by the heating
contractor. Selection and setting of the various heating
programmes in accordance with the operating manual.
If a calorifier is connected, the priority circuit
disables the boiler temperature regulator until the
temperature is reached. The boiler temperature can
rise to approx. 85 °C.
4.9
Safety valves
The heating system and hot water supply must each be
protected with one safety valve against impermissibly high
pressures. The discharge capacity of the heating system
safety valve must correspond to the boiler’s maximum
nominal heat output. The valve is installed in the safety
flow. In Germany, only safety valves with the code letter
"H" in the approval mark may be connected, and they
must always be connected at the boiler safety flow.
Water shortage protection in accordance with DIN 4751
Part 2 Section 9 is mandatory.
4.10 Charging pump (boiler with free-standing
calorifier)
Speed of rotation and output regulation must correspond
to the requirements of the free-standing calorifier. Setting
carried out by the heating installation engineer.
4.11 Heating pump
Speed of rotation and output regulation must correspond
to the requirements of the system and the regulations.
They are to be set by the heating installation engineer.
4 205 120 / 02
21
COMMISSIONING
5.
5.1
Commissioning
• Parts of the boiler which have contact with water are
made of ferrous materials.
Water quality
• On account of the danger of stress cracking corrosion
the chloride, nitrate and sulfate contents of the heating
water must not exceed 200 mg/l in total.
Heating Water
The European Standard EN 14868 and the
directive VDI 2035 must be observed.
• The pH value of the heating water should lie between
8.3 and 9.5 after 6-12 weeks of heating operation.
In particular, attention must be paid to the following stipulations:
• Hoval boilers and calorifiers are designed for heating
plants without significant oxygen intake (plant type I according to EN 14868).
• Plants with
- continuous oxygen intake (e.g. underfloor heating
systems without diffusion proof plastic piping) or
- intermittent oxygen intake (e.g. where frequent refilling is necessary)
must be equipped with separate circuits.
• Treated filling and replacement water must be tested at
least 1x yearly. According to the inhibitor manufacturer‘s
instructions, more frequent testing may be necessary.
• A refilling is not necessary if the quality of the heating
water in existing installations (e.g. exchange of boiler)
conforms to VDI 2035.
The Directive VDI 2035 applies equally to the replacement water.
• New and if applicable existing installations need to be
adequately cleaned and flushed befor being filled. The
boiler may only be filled after the heating system has
been flushed!
Filling and replacement water
• For a plant using Hoval boilers untreated drinking water
is generally best suited as heating medium, i.e. as filling and replacement water. However, as not all drinking
water is suitable for use as as filling and replacement
water the water quality must fulfil the standard set in
VDI 2035. Should the mains water available not be suited for use then it must be desalinated and/or be treated
with inhibitors. The stipulations of EN 14868 must be
observed.
• In order to maintain a high level of boiler efficiency and
to avoid overheating of the heating surfaces the values
given in the table should not be exceeded (dependent
on boiler performance ratings - for multi-boiler plants
rating of smallest boiler applies - and on the water content of the plant).
• The total amount of filling and replacement water which
is used throughout the total service life of the boiler
must not exceed three times the water capacity of the
plant.
Maximum filling capacity based on VDI 2035
Total hardness of the filling water up to ...
[mol/m ]
f°H
d°H
e°H
~mg/l
Conductance 2
Boiler size of the
individual boiler
50 to 200 kW
200 to 600 kW
3 1
1
2
<0,1
<1
<0,56
<0,71
<10
<20
0,5
5
2,8
3,6
50,0
100,0
1
10
5,6
7,1
100,0
200,0
1,5
15
8,4
10,7
150,0
300,0
2
20
11,2
14,2
200,0
400,0
2,5
25
14,0
17,8
250,0
500,0
3
30
16,8
21,3
300,0
600,0
>3,0
>30
>16,8
>21,3
>300
>600
maximum filling quantity without desalination
NO REQUIRE- 50 l/kW 20 l/kW 20 l/kW
MENT 50 l/kW 50 l/kW 20 l/kW
always desalinate
Sum of alkaline earths
If the conductance in µS/cm exceeds the tabular value an analysis of the water is necessary.
22
4 205 120 / 02
COMMISSIONING
5.2
Filling the heating system
Filling of the heating system must be carried out by
trained personnel. The filling and replacement water must
comply with the quality requirements in the relevant state
or country (VDI 2035 or SWKI 88-4 or ÖNORM H 5195).
5.3
Filling the water heater (if fitted)
The heating boiler may be put into operation even when
the calorifier is not filled.
5.4
Commissioning
Important:
On first commissioning, check that all safety and control
devices are functioning properly (in accordance with the
operating manual).
The operation and maintenance of the system must be
explained to the user in detail.
In some areas, gas or dual-fuel systems
may only be commissioned by an engineer
from the local gasworks.
Check with the local gasworks to make
sure.
5.5
Oil/gas burners
Setting the burner must also be carried out by a specialist,
and the setting must correspond to the heat demand of
the system.
Please see the technical information / assembly instructions
supplied with the burner.
5.6
Handover to the operator/storage
Have the operator confirm in writing that the operating and
maintenance procedures have been explained and that
he or she has received a copy of the relevant operating
manuals. (See sample on page 40). The manufacturer of
the unit is responsible for providing operating manuals
for the complete system. This technical information /
these installation instructions must not be destroyed after
completing the commissioning procedures, but should be
permanently stored with the unit.
4 205 120 / 02
23
MAINTENANCE
6.
6.1
Maintenance
Information for combustion controller / chimney sweep regarding emission monitor key
All other control elements of the control unit are described in the operating instructions.
The emission monitor key can also be used to change over to manual operating mode.
Emission monitor key / Manual operation
To protect under floor heating systems
against invalid overheating during emission monitoring / manual operation it is
necessary to implement appropriate safety
measures (e.g. safety temperature limiter
with pump switch-off). The duration of the
emission monitoring is limited to 20 minutes and shall be restarted, if necessary.
Scalding hazard due to hot water temperature, since the hot water temperature can
exceed the temperature setpoint!
Emissions metering


PRESS
SHORTLY
Immediate end
Remaining time display
REACTIONS for emissions metering
• Time unit automatically 20 min. – thereafter reverts
• Boiler temperature - > maximum temperature restriction
• Regulate to the maximum temperature… the heating circuits and the water heaters (at the direct heating circle only,
if the warm water mode of operation is adjusted to parallel operation)
• With 2-step heat generator both stages are in operation
Manual operation


Immediate end
PRESS
> 5 seconds
REACTIONS for manual operation
• Set reference boiler temperature with button!
• All heating pumps ON
• Mixer without current - manual setting necessary!
• Note the maximum permissible temperature of the floor heating!
• The hot water temperature reaches the set DHW maximum temperature (expert level standard 65°C).
24
4 205 120 / 02
MAINTENANCE
6.2
Cleaning
Cleaning should be performed at least twice per year.
Cleaning at intermediate intervals is necessary if the flue
gas temperature rises.
6.2.1 Preparatory work
• Switch boiler off (controller: set switch to "O", pull the
burner plug)
• Interrupt the fuel supply
• Open the boiler door
• Remove flue gas collector cleaning cover (back)
6.2.2 Cleaning (dry or wet method)
• Clean combustion chamber, 2-pass (cylindrical tubes),
3-pass (ribbed heating surface) thoroughly with a brush
or spray and then remove any combustion residue or
sprayed liquid from the flue gas collector and from the
combustion chamber.
For wet cleaning: Treat seals with graphite before
carrying out wet cleaning.
• Dispose of the cleaning fluid (scrubbing liquid) in
accordance with regulations.
6.2.3 Putting into operation again
• Mount the cleaning cover
• Close boiler door and reconnect burner plug.
Do not overtighten boiler door screws.
• Reconnect the fuel supply
• Where applicable, refit front cover
• Reset boiler switch to "I"
4 205 120 / 02
25
OVERVIEW OF SETTINGS
7.
7.1
Overview of settings
Table of parameters
Designation
Regulator
Factory
10
20
30
40
50
Setting range /
Setting values
Type of device:
DHW:
SW:
Address:
Surface operation
Key :
Heating curve HC
OFF
OFF, 0,20 .... 3,5
Heating curve MC1
1,0
OFF, 0,20 .... 3,5
Heating curve MC2
1,0
OFF, 0,20 .... 3,5
Daytime target temperature HC
*)
20°C
5 .... 30°C *)
Daytime target temperature MC1
*)
20°C
5 .... 30°C *)
Daytime target temperature MC2
*)
20°C
5 .... 30°C *)
Night-time target temperature HC
*)
16°C
5 .... 30°C *)
Night-time target temperature MC1 *)
16°C
5 .... 30°C *)
Night-time target temperature MC2 *)
16°C
5 .... 30°C *)
DHW target temperature
50°C
5 ... DHW-Max.
*) Depending on the setting of system parameters 03 OPERATING MODE
Remote operation/room stations
Type
26
Heating circuit
Address
HW
SW
4 205 120 / 02
OVERVIEW OF SETTINGS
Table for Time programs
DHW circuit
Time program P1
Tag
Cycle 1
from
to
Cycle 2
from
to
Time program P2
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Time program P3
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Cycle 3
from
to
Mo
Tu
We
Th
Fr
Sa
Su
Direct circuit
Time program P1
Tag
Cycle 1
from
to
Cycle 2
from
to
Time program P2
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Time program P3
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Cycle 3
from
to
Mo
Tu
We
Th
Fr
Sa
Su
Mixer Circuit 1
Time program P1
Tag
Cycle 1
from
to
Cycle 2
from
to
Time program P2
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Time program P3
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Cycle 3
from
to
Mo
Tu
We
Th
Fr
Sa
Su
Mixer Circuit 2
Time program P1
Tag
Cycle 1
from
to
Cycle 2
from
to
Time program P2
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Time program P3
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Cycle 3
from
to
Mo
Tu
We
Th
Fr
Sa
Su
4 205 120 / 02
27
OVERVIEW OF SETTINGS
HYDRAULIC
Par.
Designation
Factory
10
20
30
40
50
Lev.
2
Function allocation of the output DHW charging pump
1
HF
3
Function allocation of the output Mixer circuit 1
3
HF
4
Function allocation of the output Mixer circuit 2
3
HF
5
Function allocation of the output Direct circuit Pump
2
HF
6
Function allocation of the variable output 1
OFF
HF
7
Function allocation of the variable output 2
OFF/ 4/ 43
HF
8
Function allocation of the variable input 1
OFF
HF
9
Function allocation of the variable input 2
OFF
HF
10
Function allocation of the variable input 3
OFF/ 2/ 33
HF
11
Indirect return increase
OFF
HF
12
Maximum limit energy management
80 °C
HF
13
Activation cooling buffer
OFF
HF
14
Release contact cooling to KVLF
OFF
HF
SYSTEM
Par.
Designation
LANGUAGE Selection of the style-language
10
20
30
40
50
Lev.
EN
BE
P1
HF
1
HF
2
Number of cleared switching time programs
3
Clearing for separate operating mode
4
Limit temperature for summer disconnection
22 °C
HF
5
System frost protection
3 °C
HF
6
Demand contact module for VE1
1
HF
7
Demand contact module for VE2
1
HF
8
Demand contact module for VE3
9
Air conditioning zone
10
Building type
Automatic reversion time (surface end user level, except
info. level)
Pump and mixer compulsory operation
11
12
13
14
15
Logical fault signal
Automatic SET function
(after 24:00, is automatically set to OFF)
Blocking code for heating Installer
1
HF
-12 °C
HF
2
HF
5 min
HF
ON
HF
OFF
HF
ON/ OFF
HF
OEM
OFF
HF
30 min
HF
0
HF
OFF
HF
18
Release cycle temperature
19
Frost protection mode
21
RTC adjustment
23
Blocking code operator level
24
Temperature display in Fahrenheit
OFF
OEM
26
First commissioning date (after 24:00)
-
OEM
27
Fault report (only TTT/UG)
2
HF
28
Fault stack 2
ON
HF
29
Characteristic curve emergency operation
0 °C
HF
30
Thermostat function sensor allocation
31
Thermostat function reference value
32
33
RESET
28
Factory
AF
HF
1 °C
HF
Thermostat function switching difference
3K
HF
Thermostat function anti-blocking protection
Top: ArtNo - HW Index
Bottom: Code:REV - Software version
Reset parameter values
ON
HF
-----
OEM
BE
4 205 120 / 02
OVERVIEW OF SETTINGS
DHW
Par.
Designation
Factory
10
20
30
40
50
Lev.
40/ 45 °C
BE
2
DHW-legionella protection-day
OFF
HF
3
DHW-egionella protection-time
HF
4
DHW-legionella protection-temperature
5
DHW-temperature recording
6
DHW-maximum temperature limit
7
DHW-mode of operation
2:00
50/ 55/ 65/
70 °C
1
50/ 55/ 65/
70 °C
1
8
DHW-tank discharge protection
DHW-NIGHT DHW - economy temperature
9
DHW-charging temperature excess
10
DHW-switching difference
11
DHW-charging pump follow-on
12
ZKP-switching time program
13
ZKP-economy interval (pause)
14
ZKP-economy interval (period duration)
17
H-GEN behaviour during SLP follow-on time
18
DHW-parallel loading
19
DHW-time-out
20
PI-reference value control
21
PI-amplification factor, P-portion Xp
22
PI-scanning time Ta
23
PI -reset time Tn
HF
HF
HF
HF
ON/ OFF
HF
7/ 20 K
HF
5K
0.5/ 1/ 2/ 5
min
AUTO
OEM
0 min
HF
OEM
HF
20 min
HF
AUTO/ OFF
HF
OFF
OFF/
30 min
OFF
HF
HF
0,1 %/ K
OEM
20 s
OEM
600 s/ °C
OEM
HF
UNMIXED CIRC
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Type of reduced operation
ECO/ ABS
HF
2
Heating system (exponent)
DK= 1,30
HF
3
Room override (in connection with room sensor)
3
HF
4
Room factor
OFF
HF
5
Adaptation heating curve
OFF
HF
6
Switch-on optimisation
1
HF
7
Heating limit
0,5
OEM
8
Room frost protection limit
10 °C
HF
OFF
HF
0
HF
20 °C
HF
9
Room thermostat function
10
Outside temperature allocation
11
Constant temperature reference value
12
Minimum temperature limit
10 °C
HF
13
Maximum temperature limit
55/ 75 °C
HF
14
Temperature elevation Heating circuit
DK=0
HF
15
Pump follow-on
5 min
HF
16
Screed function
OFF
HF
23
Room control K-factor
8
HF
24
Room control Tn-factor
35 min
HF
25
Vacation mode
STBY
HF
36
Minimum value override
OFF
HF
XXXXX
HF
Name heating circuit (max. 5 letters)
4 205 120 / 02
29
OVERVIEW OF SETTINGS
MIX. VALVE-1
Par.
Designation
10
20
30
40
50
Lev.
1
Type of reduced operation
ECO/ ABS
HF
2
Heating system (exponent)
MK= 1,10
HF
3
Room override (in connection with room sensor)
4
Room factor
3
HF
100 %
HF
ON
HF
1
HF
5
Adaptation heating curve
6
Switch-on optimisation
7
Heating limit
0,5
OEM
8
Room frost protection limit
10 °C
HF
OFF
HF
0
HF
20 °C
HF
9
Room thermostat function
10
Outside temperature allocation
11
Constant temperature reference value
12
Minimum temperature limit
10 °C
HF
13
Maximum temperature limit
55/ 75 °C
HF
14
Temperature elevation/ abatement heating circuit
0/ 8 K
HF
15
Pump follow-on
5 min
HF
OFF
HF
2,0 %/ K
OEM
Scanning time Ta
20 s
OEM
I-portion Tn
270 s
OEM
21
Running time servomotor
150 s
HF
22
End position function, valve
1
OEM
23
Room control K-factor
8
HF
24
Room control Tn-factor
35 min
HF
25
Vacation mode
STBY
HF
36
Minimum value override
OFF
HF
37
Mixer lead time
OFF
HF
38
Regulation offset
0
HF
50
Cooling switch-on point, OT
OFF
HF
51
Cooling max. point, OT
35 °C
HF
52
Cooling reference flow temp. at switch-on point
18 °C
HF
53
Cooling reference flow temp. at max. point
24 °C
HF
54
Cooling reference room temp. at switch-on point
23 °C
HF
55
Cooling reference room temp. at max. point
28 °C
HF
18 °C
OEM
XXXXX
HF
16
Screed function
18
P-portion Xp
19
20
56
Min. temp. cooling
Name heating circuit (max. 5 letters)
30
Factory
4 205 120 / 02
OVERVIEW OF SETTINGS
MIX. VALVE-2
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Type of reduced operation
ECO/ ABS
HF
2
Heating system (exponent)
MK= 1,10
HF
3
Room override (in connection with room sensor)
4
Room factor
3
HF
100 %
HF
ON
HF
1
HF
5
Adaptation heating curve
6
Switch-on optimisation
7
Heating limit
0,5
OEM
8
Room frost protection limit
10 °C
HF
OFF
HF
0
HF
20 °C
HF
9
Room thermostat function
10
Outside temperature allocation
11
Constant temperature reference value
12
Minimum temperature limit
10 °C
HF
13
Maximum temperature limit
55/ 75 °C
HF
14
Temperature elevation/ abatement heating circuit
0/ 8 K
HF
15
Pump follow-on
5 min
HF
OFF
HF
2,0 %/ K
OEM
Scanning time Ta
20 s
OEM
I-portion Tn
270 s
OEM
21
Running time servomotor
150 s
HF
22
End position function, valve
1
OEM
23
Room control K-factor
8
HF
24
Room control Tn-factor
35 min
HF
25
Vacation mode
STBY
HF
36
Minimum value override
OFF
HF
37
Mixer lead time
OFF
HF
38
Regulation offset
0
HF
50
Cooling switch-on point, OT
OFF
HF
51
Cooling max. point, OT
35 °C
HF
52
Cooling reference flow temp. at switch-on point
18 °C
HF
53
Cooling reference flow temp. at max. point
24 °C
HF
54
Cooling reference room temp. at switch-on point
23 °C
HF
55
Cooling reference room temp. at max. point
28 °C
HF
18 °C
OEM
XXXXX
HF
16
Screed function
18
P-portion Xp
19
20
56
Min. temp. cooling
Name heating circuit (max. 5 letters)
4 205 120 / 02
31
OVERVIEW OF SETTINGS
HEAT GENER.
Par.
Designation
Factory
10
20
30
40
50
Lev.
1/ 2/ 5
HF
OFF/ 3
5/ 48/ 65/ 75
°C
75/ 85 °C
HF
HF
1
HF
1
H-GEN model
2
Start-up protection H-GEN
3
Minimum temperature limit H-GEN
4
Maximum temperature limit H-GEN
5
Mode of action minimum temperature limit H-GEN
6
Sensor mode operation for H-GEN
7
Minimum burner running time
8
9
10
11
12
DHW charging mode 1-2 stage
13
Lead time, boiler circuit pump
14
Follow-on time, boiler circuit pump or parallel boiler release
5 min
HF
15
Search time feed pump, primary pump
5 min
HF
16
Exhaust gas temperature monitoring
OFF
HF
17
Exhaust gas limit value
18
Boiler gradient
19
Modulation P-portion Xp
20
Modulation scanning time Ta
21
Modulation adjustment time Tn
22
Modulation running time
23
Modulation starting time
24
Modulation start-up output
25
Outside temperature block
26
Basic charge elevation
27
29
Minimum temperature limit, heating circuits
Switching difference, minimum temperature limit Heating
circuits
H-GEN forced discharge
30
OEM Maximum limit
110 °C
OEM
31
Minimum load control
OFF
OEM
34
Output limitation heating
100 %
HF
35
Output limitation hot water
100 %
HF
36
ET blocking 2.burner stage
OFF
HF
37
Running time meter
38
DHW release regulator (CD)
39
Emergency operation temperature H-Gen (e.g. for 70-8)
40
Heat balance (from V3.2)
41
Reset heat balance
28
HF
1
OEM
2 min
HF
Burner switching difference I
6K
HF
Burner switching difference II
12 K
HF
Time-out stage II
10
HF
Release mode stage II
1
HF
2
HF
1 min
HF
42
Volumetric flow rate
43
Density, medium
44
Specific thermal capacity, medium
200 °C
HF
OFF
OEM
5 %/ K
OEM
20 s
OEM
180 s/ °C
OEM
12 s
HF
200 s
HF
70
HF
OFF
OEM
0 K/ 10K
OEM
5/ 38/ 65 °C
HF
2K
OEM
OFF
HF
1
HF
ON
HF
70 °C
HF
ON
HF
HF
0,0 l/ min
0,0 l/ IMP
1,00 kg/ l
4,2
HF
HF
HF
RESET ST-1 Reset counters starts and running time, stage 1
OEM
RESET ST-2 Reset counters starts and running time, stage 2
OEM
32
4 205 120 / 02
OVERVIEW OF SETTINGS
RETURN CONTR
Par.
2
Designation
Minimum limit return temperature / reference value return
temperature
Switch-off difference
3
Pump follow-on time
1
Factory
10
20
30
40
50
Lev.
38 °C
HF
2K
HF
1 min
HF
SOLAR
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Switch-on difference
10 K
HF
2
Switch-off difference
5K
HF
3
Minimum running time SOP
3 min
HF
4
Solar collector maximum temperature
100 °C
HF
5
Solar tank maximum limit (KSPF)
65 °C
HF
6
Solar mode of operation
2
HF
7
Heat generator cycle lock (only when parameter 06=1,3,4)
0,5 h
HF
8
Solar priority parallel changeover
10 K
HF
Solar heat balance
OFF
HF
9
SOLAR
RESET
Reset heat balance
HF
0,0 l/ min
0,0 l/ IMP
1,05 kg/ l
11
Volumetric flow rate
12
Density, medium
13
Specific thermal capacity, medium
14
15
16
Switch-over temperature (SLVF)
60 °C
HF
17
Solar minimum temperature
OFF
HF
HF
HF
3,6 KJ/ kgK
HF
Final switching-off temperature
120 °C
HF
Test cycle solar charging switch-over
10 min
HF
SOLID FUEL
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Minimum temperature
60 °C
HF
2
Maximum temperature
95 °C
HF
3
Switch-on difference
10 K
HF
4
Switch-off difference
5K
HF
5
Clock block, heat generator
15
HF
4 205 120 / 02
33
OVERVIEW OF SETTINGS
BUFFER
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Minimum temperature
5/ 20 °C
HF
2
Maximum temperature
95 °C
HF
3
Temperature elevation, H-GEN
8/ 10/ 12K
HF
4
Switching difference
2/ 5/ 10K
HF
5
Forced discharge
OFF
HF
6
Skimming function switch-on difference
10 K
HF
7
Skimming function switch-off difference
5K
HF
8
Start-up protection
OFF
HF
9
Discharge protection
OFF
HF
10
Buffer mode of operation
2/ 3
HF
11
Pump follow-on time
3 min
HF
12
Switch-off reference value temp.
70 °C
HF
13
H-GEN release temp. skimming function
60 °C
HF
MAIN SUPPLY
Par.
Designation
Factory
10
Lev.
0 %/ K
HF
20 s
HF
600 s/ °C
HF
1
PI-amplification factor, P-portion Xp
2
PI-scanning time Ta
3
PI -reset time Tn
Designation
Factory
CASCADE
Par.
10
Lev.
1
Switch-off difference
3K
OEM
2
Connecting delay
20
OEM
3
Switch-off delay
5
OEM
4
Switching output stage sequence
65
OEM
5
Stage reversal
OFF
OEM
6
Control stage
1
BE
7
Peak load stage
OFF
OEM
8
Group switch-over
OFF
OEM
9
DHW fast activation
OFF
OEM
10
Peak load elevation
10 K
OEM
BUS
Par.
34
Designation
Factory
10
20
30
40
50
Lev.
1
Bus address central device
10
HF
2
Bus right RS direct circuit
1
HF
3
Bus right RS mixer circuit 1
1
HF
4
Bus right RS mixer circuit 2
1
HF
4 205 120 / 02
OVERVIEW OF SETTINGS
SERVICE
Par.
Designation
Factory
10
20
30
40
50
Lev.
Service 1 (Cleaning ST1 )
7
BE
Cleaning according to fixed date
OFF
BE
Cleaning according to fixed interval
OFF
BE
4
Cleaning according to cleaning counter
OFF
BE
5
Reset cleaning display 1
1
Suspend message «CLEANING ST-1» for X days
2
3
BE
Service 2 (Cleaning ST2)
7
BE
Cleaning according to fixed date
OFF
BE
Cleaning according to fixed interval
OFF
BE
9
Cleaning according to cleaning counter
OFF
BE
10
Reset cleaning display 2
6
Suspend message «CLEANING ST-2» for X days
7
8
BE
Service 3 (maintenance ST1 )
11
Suspend message «MAINTENANCE ST-1» for X days
7
HF
12
Maintenance according to fixed date
OFF
HF
13
Maintenance according to fixed interval
OFF
HF
14
Maintenance according to maintenance counter
OFF
HF
15
Reset maintenance display 1
HF
Service 2 (maintenance ST2 )
16
Suspend message «MAINTENANCE ST-2» for X days
7
HF
17
Maintenance according to fixed date
OFF
HF
18
Maintenance according to fixed interval
OFF
HF
19
Maintenance according to maintenance counter
OFF
HF
20
Reset maintenance display 2
HF
ALARM 1
Par.
Designation
10
20
30
40
50
Lev.
1
Alarm 1
OEM
2
Alarm 2
OEM
3
Alarm 3
OEM
4
Alarm 4
OEM
Alarm 5 - 20
OEM
Reset fault signals
OEM
5 ... 20
21
ALARM 2
Par.
(can ony be activated with H-Gen 5)
Designation
10
20
30
40
50
Lev.
1
Alarm 1
OEM
2
Alarm 2
OEM
3
Alarm 3
OEM
4
Alarm 4
OEM
Alarm 5 - 20
OEM
Reset fault signals
OEM
5 ... 20
21
4 205 120 / 02
35
OVERVIEW OF SETTINGS
FAULT REPORTING OVERVIEW TopTronic®T
Status
36
Designation
Fault type
Code
System
External sensor
Interruption
10-0
System
External sensor
Short-circuit
10-1
System
Boiler sensor
Interruption
11-0
System
Boiler sensor
Short-circuit
11-1
Remark
System
Flow sensor 1
Interruption
12-0
MC1=off, YK1=no current
System
Flow sensor 1
Short-circuit
12-1
MC1=off, YK1=no current
System
Storage sensor
Interruption
13-0
System
Storage sensor
Short-circuit
13-1
System
VE 2
Interruption
14-0
System
VE 2
Short-circuit
14-1
System
VE 2
Alarm
14-7
System
VE 3
Interruption
15-0
System
VE 3
Short-circuit
15-1
System
VE 3
Alarm
15-7
System
VE 1
Interruption
16-0
System
VE 1
Short-circuit
16-1
System
VE 1
Alarm
16-7
System
Solar tank sensor
Interruption (KSPF)
17-0
System
Solar tank sensor
Short-circuit (KSPF)
17-1
System
Flow sensor 2
Interruption
18-0
MC2=off, YK2=no current
System
Flow sensor 2
Short-circuit
18-1
MC2=off, YK2=no current
System
Collector sensor
Interruption (KVLF)
19-0
System
Collector sensor
Short-circuit (KVLF)
19-1
System
Room sensor (RS)
Interruption
20-0
System
Room sensor (RS)
Short-circuit
20-1
System
Burner 1
No switching off (1 min)
30-2
With par. log. alarm can be switched off
System
Burner 1
No switching on (10 min)
30-3
With par. log. alarm can be switched off
System
Burner 2
No switching off (1 min)
31-2
With par. log. alarm can be switched off
With par. log. alarm can be switched off
System
Burner 2
No switching on (10 min)
31-3
System
Exhaust gas temperature
Exceeding
33-5
System
Exhaust gas temperature
SLT triggered
33-8
System
Cleaning stage 1
Triggering by date
40-1
System
Cleaning stage 1
Triggering by interval
40-2
System
Cleaning stage 1
Triggering by counter
40-4
System
Maintenance stage 1
Triggering by date
41-1
System
Maintenance stage 1
Triggering by interval
41-2
System
Maintenance stage 1
Triggering by counter
41-4
System
Cleaning stage 2
Triggering by date
42-1
System
Cleaning stage 2
Triggering by interval
42-2
System
Cleaning stage 2
Triggering by counter
42-4
System
Maintenance stage 2
Triggering by date
43-1
System
Maintenance stage 2
Triggering by interval
43-2
System
Maintenance stage 2
Triggering by counter
43-4
4 205 120 / 02
OVERVIEW OF SETTINGS
FAULT REPORTING OVERVIEW TopTronic®T
Status
Designation
Fault type
Code
Logical
Boiler temperature
Not reached (90 min)
50-4
Logical
Tank temperature
Not reached (4 h)
51-4
Logical
Flow temperature MC1
Not reached (1 h)
52-4
Logical
Flow temperature MC2
Not reached (1 h)
53-4
Logical
Room temperature HC
Not reached (3 h)
54-4
Logical
Room temperature MC1
Not reached (3 h)
55-4
Logical
Not reached (3 h)
56-4
Address collision
70-0
System
Room temperature MC2
Lock by energy supply company
ST 2
Activity
No T2B signal
70-1
System
Activity
70-6
System
Activity
System
System
Activity
HP return sensor
No FA signal
Regulator with address 10 is
missing
Data bus error
Return min. temp. below setpoint
System
HP return sensor
85-5
System
QF
System
QF
Return max. temp. exceeded
Heat source min. temp. below
setpoint
Heat source max. temp. exceeded
(cooling operation)
System
System
QF
WPS
Fault heat source sensor
Variable input HP fault
-87-7
System
System
System
System
Pulse counter
Fault
Fault
Fault
No pulse (5 min)
Warning
Lock-out
Blocking
90-0
W:XX
E:XX
B:XX
System
Remark
70-8
70-9
85-4
No Hoval regulator
86-4
86-5
Standard signal «VE-x»
Warning in automatic firing device
Fault in automatic firing device
Fault in automatic firing device
SENSOR ALLOC.
Par.
1
Designation
Factory
10
20
30
40
50
Lev.
Balancing external sensor
0
OEM
Balancing room sensor (only adjustable with RS-T)
0
HF
2
Balancing heat generator
0
OEM
3
Balancing tank sensor
0
OEM
4
Balancing flow sensor 1
0
OEM
5
Balancing flow sensor 2
0
OEM
6
Balancing solar collector sensor
0
OEM
7
Balancing solar buffer sensor
0
OEM
8
Balancing variable input 1
0
OEM
9
Balancing variable input 2
0
OEM
10
Balancing variable input 3
0
OEM
RS-T
4 205 120 / 02
37
38
4 205 120 / 02
4 205 120 / 02
39
COPY FOR PLANT USER
Confirmation
The user (owner) of the system herewith confirms that
• he has received adequate instruction in the operating and maintenance of the installation,
• received and taken note of the operating and maintenance instructions and, where applicable other documents concerning the heat generator and any further components.
• and is consequently sufficiently familiar with the installation.
Installation address:
Type:
Serial number:
Year of manufacture:
Place, Date:
System installer:
System user:
COPY OF SYSTEM INSTALLER
Confirmation
The user (owner) of the system herewith confirms that
• he has received adequate instruction in the operating and maintenance of the installation,
• received and taken note of the operating and maintenance instructions and, where applicable other documents concerning the heat generator and any further components.
• and is consequently sufficiently familiar with the installation.
Installation address:
Type:
Serial number:
Year of manufacture:
Place, Date:
System installer:
System user: