Building Standards Advisory Promoting construction of safe, healthy, habitable buildings Fire Alarm Monitoring Question “Does a fire alarm system in a building need to be monitored?” “Under what circumstances does an existing alarm system in a building need to be updated?” Answer Fire alarm system monitoring, described within the National Building Code (NBC) as “Signals to Fire Department” may be required depending on the type of alarm system required if any. Fire alarm updates are only required when: • the original system has been changed since it was designed and installed. • the original system has been expanded since it was designed and installed. • the original system cannot be repaired without it being changed. Background The NBC does not use the term, “monitored”. The term “notify the fire department” is found in NBC 2010 Division B, Article 3.2.4.8., Signals to Fire Department. NBC 2010, Division B, Article 3.2.4.8 Signals to Fire Department 1) A single-stage fire alarm system installed in a building of assembly occupancy that has an occupant load more than 300 shall be designed to notify the fire department, in conformance with Sentence (4), that an alarm signal has been initiated. saskatchewan.ca/buildingstandards | 306-787-4113 2) A fire alarm system that includes waterflowindicating devices shall be designed to notify the fire department in conformance with Sentence (4) when an alarm is initiated. 3) A 2-stage fire alarm system shall be designed to notify the fire department, in conformance with Sentence (4), that an alert signal has been initiated. 4) Notification of the fire department, as required by Sentences (1), (2) and (3), shall be provided in conformance with CAN/ULC-S561, “Installation and Services for Fire Signal Receiving Centres and Systems.” 5) Where a single-stage fire alarm system is installed in a building that is not sprinklered throughout and Sentence (1) does not apply, a legible notice that is not easily removed shall be affixed to the wall near each manual station stating a) that the fire department is to be notified in the event of a fire emergency, and b) the emergency telephone number for the municipality or for the fire department. The requirement for signals to fire department has been found in the NBC since the NBC 1965 was published. Fire alarm systems in assembly occupancy classifications were required to be connected directly to the fire department via municipal alarm systems. This requirement was essential for the timely notification of the fire department. Today, direct connection is more likely through an outside “Signal Receiving Centre”. Direct connection to the fire department is no longer practical. Fire Alarm Monitoring The notification of the fire department, where required shall be provided in conformance with CAN/ULC-S561, “Installation and Services for Fire Signal Receiving Centres and Systems.” Existing Buildings and Existing Fire Alarm Systems Earlier codes, such as the NBC 1995 required large occupancies with single-stage fire alarm systems, waterflow detecting devices, and 2-stage fire alarm systems to notify the fire department at actuation of the alarm system. NBC 1995 allowed the signal to the fire department to be by way of: • independent central station, National Fire Protection Association (NFPA) 71, “Standard for the Installation, Maintenance and Use of Central Station Protective Signaling Systems for Watchman Fire Alarm and Supervisory Service”;or, • a proprietary control centre NFPA 72: “National Fire Alarm and Signaling Code” . Where the above facilities are not available in a municipality, this article allows for: • an independent system to transmit signals to the fire department. Lastly, where a single-stage fire alarm system or a local group of sprinklers is installed, the occupancy is not an assembly occupancy, and the occupant load is not greater than 300, a permanent legible notice shall be affixed to the wall near each manual “pull” station, stating to notify the fire department or 911. The Underwriters Laboratories of Canada (ULC) standard CAN/ULC-S536, “Inspection and Testing of Fire Alarm Systems”, referenced in the National Fire Code (NFC), fire alarm systems shall be inspected and tested in conformance with CAN/ULC-S536 which requires actions on a daily, monthly, and annual basis. The NFC indicates that the system needs be maintained, tested, and work to its original design. Unless it is found that the system is not working as originally intended, it does not need to be updated. saskatchewan.ca/buildingstandards | 306-787-4113 Application of New Code Requirements to Fire Alarm Systems that are Being Upgraded or Replaced Building owners, designers, and the local authority (municipality) should determine the original design parameters and standards for an existing fire alarm system. When dealing with existing conditions, the authority having jurisdiction may determine if other measures are needed to provide an acceptable degree of fire alarm system reliability. In cases where fire alarm systems are being expanded or replaced due to the modernization of a building, all provisions of the current adopted code would apply. Analysis Procedure Several factors need to be considered when determining if an alarm system and proposed changes to the system continue to meet the needs of the building in which it is installed and complies with the applicable standards: 1. Is the alarm system in safe and operable working condition? 2. What year was the building constructed? 3. What regulations or code applied to the building at time of construction or when the alarm system was installed? 4. What upgrading is being done to the building and to what standard? 5. Have changes to the building affected the design or safety of the original system? 6. Determining the extent of new code requirements applicable in providing an acceptable degree of safety. When the original components of a fire alarm system fail, become outdated, or obsolete, these components need to be replaced. This may cause the working ability of the entire system to be reviewed. It is also possible that components are no longer available for older systems. If the system is expanded the new portions need to communicate with the existing system. Should the expansion or should replacement parts affect the ability of the entire system to function as intended the system may need to be updated or replaced. Fire Alarm Monitoring If a fire alarm system has not been changed since it was originally installed and it was not required to notify the fire department at that time, upgrading the system to notify the fire department is not required. If a fire alarm system has been modified since it was installed then the system would need to meet all provisions of the code currently adopted and in effect. Building Standards and Licensing Branch Building Standards Advisory 100 - 1855 Victoria Avenue Fire Alarm Monitoring Regina, Saskatchewan S4P 3T2 October 2015 (306) 787-4113 Phone (306) 798-4172 Fax [email protected] Original approved and signed by: www.saskatchewan.ca/buildingstandards Wm. Hawkins, Executive Director/Chief Building Official This advisory is published by the Saskatchewan Ministry of Government Relations for purposes of providing information to users on the topic contained herein. In case of conflict between The Uniform Building and Accessibility Standard Act (the UBAS Act), the National Building Code of Canada 2010 (NBC 2010) and this advisory, provisions of the UBAS Act and NBC 2010 shall apply. 3
© Copyright 2025 Paperzz