MULTISTACK 1065 Maple Ave PO Box 510 Sparta, WI 54656 Service Bulletin Number: 1-012 Date: 1/9/2012 Topic: Head Pressure Control for Air Cooled Splits On any air cooled split modules shipped as of 1/1/2012 the “LAC” head pressure control valve (or valves) have been replaced by an electronic stepper “CDS “ valve along with a fixed “ORD” valve. Both valves are shipped loose with the module and need to be field installed. Each circuit will have 1 “CDS” valve and 1 “ORD” valve. The “CDS” needs to be wired back to the valve control panel on the module. A schrader needs to be installed in the discharge line and the (supplied) discharge transducer installed on and wired back to the control panel as well. The “CDS” valve should be located in the liquid line within 10’ of the Valve Control Panel. The HP transducer and cable should also be installed within this distance. The “ORD” Valve should go between the discharge line and the inlet to the receiver on the liquid line. The “ORD” Valve should go between the “CDS” valve outlet and receiver inlet. For wiring of the “CDS” valve and HP Transducer please see the module wiring diagrams supplied with the submittal or service manual. CDS Valve ORD Valve Valve Control Panel with EVD Board HP Transducer and cable PHONE: (608) 366-2400 ▌▌▌FAX: (608) 366-2450 MULTISTACK 1065 Maple Ave PO Box 510 Sparta, WI 54656 Service Bulletin Display for EVD Board Parts supplied by MS and Factory Installed: Compressor, Evaporator, TXV, Sight Glass, Solenoid Valve, Drier, Receiver. Part supplied by MS and field installed: Condenser, CDS Valve, ORD Valve, Parts not supplied but recommended: Liquid and Discharge Isolation valves at module to system piping connections (not shown in flow diagram) Setting Up Valve The setting for the CDS Valve are set up in the EVD board at the Valve Control Panel prior to shipment. 1 Display for the EVD board is provided for all modules. To modify settings the Display will need to be connected to each EVD. The settings can be uploaded and saved into the Display and then downloaded to the next board or settings can be manually adjusted. The full parameter listings as well as instruction for upload and download are available from Multistack if needed. For any questions on this issue please contact Multistack Service / Product Support Department at 608-366-2400. PHONE: (608) 366-2400 ▌▌▌FAX: (608) 366-2450 Remote Air Cooled Condenser Application EVD Evolution Twin for Sporlan CDS Valves Controller Setpoints Configuration Network Address 198 Refrigerant R410A Valve user defined 3 Probe S1 user defined Main Regulation EPR back pressure 4 Probe S2 not used Auxiliary Regulation user defined 5 Probe S3 user defined Relay Configuration disabled 6 Probe S4 not used DI2 Configuration regulation start/stop 7 Display Main Var. 1 S1 Probe Measurem Display Main Var. 2 S3 Probe Measurem 8 S1 Probe Alarm Manag. valve @ fixed pos. S2 Probe Alarm Manag. no action 9 S3 Probe Alarm Manag. valve @ fixed pos. S4 Probe Alarm Manag. no action 10 Unity Measure Imperial (°F, psig) DI1 Configuration regulation start/stop 11 Language English Probes 1 S1 calibrat offset 0 psi S1 calibrat gain on 4-20mA 1.0 2 S1 pressure MINIMUM value 0 psi S1 pressure MAXIMUM value 653 psi 3 S1 alarm MIN pressure 0 psi S1 alarm MAX pressure 653 psi 4 S2 calibrat offset 0 °F S2 calibrat gain on 0-10V 1.0 5 S2 alarm MIN temperat -58.0 °F S2 alarm MAX temperat 221 °F 6 S3 calibrat offset 0 psi S3 calibrat gain on 4-20mA 1.0 7 S3 pressure MINIMUM value 0 psi S3 pressure MAXIMUM value 653 psi 8 S3 alarm MIN pressure 0 psi S3 alarm MAX pressure 653 psi 9 S4 calibrat offset 0 °F S4 alarm MIN temperat -58.0 °F S4 alarm MAX temperat 221 °F Regulation 1 Superheat setpoint --Valve opening at start-up 10% 2 Valve opened in stand-by 1 start-up delay after defrost --Pre-position time 6 s (not adjustable) Press "Help" and "<-" to Switch Between Valves A & B 1 2 Regulation continued Hotgas bypass temp setpoint --Hotgas bypass press setpoint --EPR pressure setpoint 300 psi 4 PID proport gain 415 PID intergral time 150 s PID derivative time 5.0 s 5 LowSH protect threshold --LowSH protect intergral time --6 LOP protection threshold --LOP protection intergral time --7 MOP protection threshold --MOP protection integral time --8 Enable manual valve position 0 Manual valve position 0 stp 9 Discharge SH setpoint --Discharge temp setpoint --Advanced 1 High Tcond threshold --High Tcond integral time --2 Modul thermost setpoint --Modul thermost differential --Modul thermost Shset offset --3 CO2 regul 'A' coefficient --CO2 regul 'B' coefficient --4 Start manual tuning 0 Tuning method 0 Network settings 2 5 Power supply mode 0 Alarm Config 1 Low superheat alarm timeout 300 s Low evap temp alarm timeout 300 s High evap temp alarm timeout 600 s 2 High cond temp alarm timeout --Low suct temp alarm thresh -58.0 °F Low suct temp alarm timeout 300 s Valve 1 EEV minimum steps 200 stp EEV maximum steps 6386 stp EEV closing steps 6500 stp 2 EEV nominal step rate 400 Hz EEV nominal current 210 mA EEV holding current 20 mA 3 EEV duty cycle 70% EEV opening synchroniz. 0 EEV closing synchroniz. 1 Multistack Part # BOARD131 Press "Prg" Button and Enter 0066 for Password 3
© Copyright 2026 Paperzz