67 5 GENERAL DISCUSSION The absorbtion refrigeration system differs from the more prevalent compression chillers in that its cooling performance is driven by heat energy, rather than by mechanical energy (heat-operated cycle). This cooling system is regarded as environmentally friendly method due to the uses of safe refrigerant and absorbent substances i.e. LiBr-H2O and NH3-H2O, respectively. The other advantage of this method is the utilization of heat energy for energy source. Heat is the end product of energy conversion which is considered as low grade energy and can be produced from solar energy, biomass, animal husbandry and agricultural waste and also industrial waste. In absorbtion refrigeration system, heat is used for regeneration process which specifically used to separate the refrigerant from the absorbent. The separatedrefrigerant in vapor phaseis condensed into liquid refrigerant in condenser. The liquid refrigerant is then evaporated in evaporator by absorbing heat from the environment which produces cooling effect. The generated water vapor is then absorbed by high concentration of LiBr-H2O in absorber. Regeneration process in generator requires higher temperature than 85°C (Ma, et al., 1998).In addition, traditional single-effect of LiBr-H2O can’t operate effectively when driven by heat resource below 80°C because of low COP (Vargas et al., 2009). Gu et al. (2006) used a solar lithium bromide absorbtion chiller system whose temperature scope was from 80 to 93°C. The average COP of the system was 0.725. Sumathy et al. (2002) introduced a twostage lithium bromide absorbtion refrigeration system which could apply low temperature heater from 70 to 85°C. However, the COP was only 0.39. Kim et al. (2008) added that the large contact area needed to separate water vapor from aqueous lithium bromide solution makes traditional generator too bulky. Therefore, membrane technology is introduced to deal with the uses of high temperature for refrigerant and absorbent separation. However, the application of membrane technology in absorbtion refrigeration system has been previously reported by several researchers although still focus on the membrane performance. Riffat and Su (1998) used centrifuge reverse osmosis (RO) membrane in a refrigeration system to reduce the utilization of high pressure pump. The research found that rate higher than 10.000 rpm at r = 50 mm was required in order to obtain 64% of solution concentration. The disadvantage of this system was the uses of high velocity which corresponds to the increasing of mechanical energy used in the system. Wang Z.S. et al., (2009) used membrane distillation technology based on PVDF-hollow fiber module for LiBr-H2O separation process. In this research, several parameters i.e. feed flux, temperature in lumen side and vacuum pressure in shell lumen were observed. It was found that the increasing of feed temperature and feed flux will increase the water vapor permeation flux. Ahmed H. and Peter S., (2009) conducted an experiment to analyze the effect of membrane characteristic towards the absorbtion process in absorber. A good absorbtion performance was obtained by membrane characteristic which has high permeability upon water vapor, uses high pressure hydrophobic membrane to avoid membrane pore wetness, and no water vapor capillary condensation to avoid membrane pore block. While the problem 68 which associates with low value of COP in absorbtion refrigeration system should analyze the effectiveness of energy utilization and exergy analysis. The study of water vapor absorbtion by LiBr-H2O solution was to determine the influence of concentration, temperature and water vapor pressure toward water vapor absorbtion process. This result was used to determine the optimum condition of absorber to absorb water vapor. The concentration value of end product produced from separation process was very important factor in determining the absorbtion performance. The result discussed in Chapter 2 mentioned that higherconcentration of LiBr-H2O solution increased the absorbtion rate. In addition, higher concentration reduced water vapor pressure which then increased the rate of absorbtion process. The temperature influenced the pressure of absorbent and water vapor. The increasing of temperature increased the pressure of water vapor and absorbent which tend toreducethe water vapor absorbtion rate. Similar condition also occurred for relative humidity. The increasing of relative humidity increased the water vapor volume contained in the air. Higher rate of water vapor absorbtion is a response of higher relative humidity. An equation to predict the amount of water vapor pressure was developed from water vapor absorbtion rate which a function of temperature, concentration and relative humidity. The separation process of LiBr-H2O solution was conducted to produce pure refrigerant to reduce the uses of heat energy in traditional absorbtion chiller system. This process was performed by applying reverse osmosis (RO) membrane and vacuum membrane distillation (VMD). The experiment which used RO membrane Dow Filmtech TW30-1812-50 module generated big effect on the purity ofthe permeate and retentate. This was indicated by rejection value. Table 5.1.shows the data on separation experiment using RO membrane under different concentration and pressure operation. Tabel 5.1. Change of concentration during separation process using RO membrane Concentration (% w/w) Initial Retentate 30 31.2 30 31.6 30 32 25 25.4 25 26 25 26.2 20 23 20 22.4 20 22.2 Permeat 9 9.4 10 9 8.4 8.2 7.4 7.6 8.2 According to Table 5.1, it can be seen that the permeate still contained LiBr compound. The condition of salt compound that could diffuse the membrane indicated that RO membrane had small rejection value. In other words, it could be said that increasing pressure would reduce the performance of a membrane to reject certain compound. The result showed that RO membrane Dow Filmtech 69 TW30-1812-50 was not suitable for LiBr-H2O separation. This suggested that other RO membrane with better selectivity performance for LiBr-H2O separation should be found. Separation process using VMD was conducted under the solution’s boiling temperature. The experiment resulted pure H2O which was indicated by the permeate value of 1.330oBrix. The highest flux permeate reached up to 930.068 (kg/m2h). 10-3which was obtained at the initial process i.e. concentration 47.5%, temperature 80°C and flow rate 1.9 L/min. The retentat concentration was 48.404%. Regarding the permeate generated from RO and VMD method, it can be concluded that VMD resulted better performance for LiBr-H2O separation and produced pure refrigerant. According to the retentate value, it also demonstrated that VMD resulted better performance than RO membrane in producing strong solution. Taken retentate and permeate value together, it suggested that VMD could produce better performance for absorbtion process. This condition would influence cooling temperature and cooling time. The determination of water vapor absorbtion in absorber was conducted using equations cited in Chapter 2. The result of separation process shows that higher concentration would increase the absorbtion rate. However, some improvements of membrane application still need to be taken place. An improvement of RO membrane which specifically designed for LiBr-H2O separation could be an interesting study. The design should consider the amount of pressure and rejection factor. Meanwhile, the direct application of VMD on absorbtion refrigeration system should consider the temperature, concentration and flow rate in order to obtain good cooling effect. Fouling factor should also be considered as it can reduce the permeate produced during separation process. Form the economic point of view, RO membrane has lower cost than VMD due to the elimination of condenser unit. Condenser unit is not used in the system based RO membrane as the absence of phase changes of weak solution before entering membrane and strong solution after passing the membrane. The analysis on exergy efficiency in absorbtion refrigeration system using RO membrane showed that evaporator unit had the smallest efficiency compared to membrane and absorber unit. In the application of VMD, the average value of exergy destroy was small which tended to increase the efficiency value. From the experiments, the efficiency energy at temperature 80°C was 98% while remain was 99%. According to the result of separation process, VMD application had higher performance than RO membrane. In the application of RO membrane, the presence of salt compound caused low cooling effect as discussed in Chapter 3. This condition could be improved by adjusting the design of RO membrane and using similar concentration applied in traditional absorbtion refrigeration system. Other consideration was the pressure leaving the RO membrane. The decrease of this pressure will decrease the chilling temperature.
© Copyright 2026 Paperzz