RS-485 Ground Potential Differences or When Good Grounds turn Bad Thomas Kugelstadt October 2010 1 Industrial communication via field bus systems often take place over long transmission lines. Designers, unaware of the large Ground Potential Differences (GPD) between remote bus locations, either rely on the local earth ground as a reliable signal return path, or directly connect remote grounds with one another, thus creating noisy ground current loops. In both cases the integrity of the transmission signal is compromised, which can lead to system lock-down and worst case, destruction of the bus transceivers. To raise awareness of these design pitfalls, this session explains where in the electrical installation GPDs originate, how ground loops are created unintentionally, and how isolation circumvents both conditions yielding a robust data transmission system. Mains Supply System 2 The above slide shows a simplified diagram of a mains supply system to a commercial building or factory. The utility transformer, here represented through its secondary winding only, provides three live phases (L1, L2, L3) and a neutral conductor (N) to the supply system. All three phases are routed through an electrical meter, measuring the energy consumption of each phase, and through a circuit breaker, allowing for the shut-off of each phase for maintenance purpose, or during an emergency event. The mains supply strands end at a panel board, from where each phase supply is distributed through individual wiring to various loads. Electrical Installation Principle GPD1 Vs GND Supply System Vs GND Load A1 Load An Load B1 Load C1 Load Cn Load Bn L1 L2 L3 N PE Vs GND Vs GND GPD2 3 Slide 3 further simplifies the supply system through a simple box, but emphasizes on the various loading of the individual supply phases and the possible ground potential differences that can exist between the dc-outputs of various loads. With regards to data transmission, these loads can represent computers, printers, remote controlled lab-equipment, basically any type of communication nodes that might require data exchange between one another. The main questions now arising are: 1) How are these ground potential differences created? 2) And how do they affect the DC output ground through a, supposedly, isolated power supply ? DC-Output to Mains Connection Simplified low-cost, Switched-Mode Power Supply (SMPS) SMPS chassis connects Ground of DC output to Protective Earth (PE) conductor 4 Answering Question 2 first: The link between the DC ground of your local electronic circuit and the protective earth (PE) reference potential of the mains is often provided by the local power supply converting the line voltage into the required DC output. This slide shows a simplified block diagram of a low-cost switched-mode power supply (SMPS), widely used in personal computers, laser printers and lab equipment. Here the DC ground of the SMPS output is referenced to the protective earth conductor (PE) of the mains via the SMPS chassis. This direct link therefore acts as a sense conductor, establishing the voltage at PE as the local DC ground potential. Theoretically the PE conductor is assumed to be current free, hence there would be nothing wrong with referencing the output ground to this potential. In reality however, low-cost SMPS contain low-cost EMI filter, which leak non-linear currents into the earth wire. While the leakage current of one SMPS into the PE conductor is negligible, the fact that large buildings often have hundreds and thousands of these, non-linear loads leaking currents into the PE makes this wire a current carrying conductor. GPD Composition Linear Loads: small neutral current due to load imbalance Non-linear Loads: large neutral current due to distorted phase currents (several times larger than fundamental phase current) 5 Now starting with the answer to Question 1: A 2nd source for large PE currents comes, via the electrical installation, from the currents in the Neutral conductor. Firstly we look at the generation of neutral currents in a 3-phase system and then at the electrical installation, or wiring systems, connecting the Neutral to the PE conductor. Large office and industrial buildings operate a vast amount of non-linear loads, such as PCs, laser printers, solid-state heater controls, fluorescent tubes, uninterruptible power supplies (UPS), and variable speed drives (VSD). In comparison to linear loads such as incandescent lamps, whose phase currents maintain a sinusoidal waveform, non-linear loads distort phase currents, thus introducing large harmonic content. In other words: - applying a sinusoidal voltage to a linear load yields a sinusoidal phase current, - applying a sinusoidal voltage to a non-linear load results in a distorted, non-sinusoidal phase current. Linear versus Nonlinear Loads Fundamental current in comparison 6 Slide 6 gives a more detailed presentation of the phase and neutral currents. In the ideal case all neutral conductors merge into one neutral conductor of large diameter within the distribution panel running close to the utility transformer. In the case of linear loads the neutral currents of different phase systems cancel each other to a certain extent. Only a fraction of the total neutral current remains due to loading imbalance. For non-linear loads however, the individual currents add to a total neutral current primarily consisting of third harmonic content. Because any conductor possesses a finite resistance, the large neutral currents of non-linear loads cause significantly higher voltage drops across the line resistances of the electrical installation than those of linear loads. Phase Current Composition 100 90 120 80 80 Phase Current [A] 70 40 60 0 50 -40 40 -80 30 20 -120 0 90 180 Phase Angle [deg] 270 360 10 0 1 3 5 7 9 11 13 15 17 19 Order of Harmonics 7 Slide 7 shows the values and harmonic content of the phase currents measured at one of many distribution panels within a large office building. Note that phase L2 (blue) has higher loading then phase L1 (red) and L3 (black). While the 3rd and 5th harmonic of the fundamental line frequency (50 Hz or 60 Hz) make up the lion share of the harmonic content, the vector sum of all frequency components can reach peak values that exceed the amplitude of the fundamental phase current by more than 100%. Neutral Current Composition 100 90 120 80 80 70 40 60 0 50 -40 40 -80 30 -120 0 90 180 270 360 20 Phase Angle [deg] 10 0 1 3 5 7 9 11 13 15 17 19 Order of Harmonics 8 Slide 8 shows the total neutral current and its harmonic content measured at the same panel. With its peak values varying between 70 A and 90 A, the neutral current’s main harmonic content is made up by the 3rd harmonic of the fundamental mains frequency. It is these high neutral currents that, via the line resistances of the various installation systems, significantly contribute to the ground potential differences between the loads of different supply phases. Hence the characteristic frequency of a Ground Potential Difference is the 3rd harmonic of the fundamental mains frequency. Earthing System: TN-C 9 When investigating the root cause of ground potential differences, we cannot ignore the line resistance of installation wires, as they convert the high leakage and neutral currents into significantly varying voltage potentials. The most commonly applied electrical installation systems are TN-C and TN-C-S. TN stands for French Terre Neutral, and implies that the Neutral conductor is grounded to Earth potential at the transformer. The letter C indicates the combined use of Protective Earth (PE) and Neutral (N) via one conductor, designated as PEN. The PEN runs through the entire system up to a distribution point, (i.e. a sub-panel), close to the loads, where it splits into separate PE and Neutral conductors that directly connect to the loads. Although TN-C represents an old earthing system, it has regained in interest due to the cost-savings achieved by avoiding the run of an additional PE conductor. This method however, has a major drawback. Because the split into PE and Neutral occurs close to a load, the voltage potential at the local PE connection includes the large voltage drops across the line resistance, RL-N, of long neutral conductors, caused by high neutral currents from many non-linear loads. TN-C systems therefore, have the potential to cause large ground potential differences between remote grounds in the tens-of-volts. Earthing System: TN-C-S RL-N RL-N RL-PE RL-PE L1 N PE L1 L2 N PE L2 Load A1 RL-N Load Am RL-N L3 N PE L3 RL-PE RLS PEN N RL-PE Load B1 Load Bn PE 10 The TN-C-S system reduces GPDs by starting an extra PE-conductor within the distribution panel. In addition the star connection of the system’s Neutral and PE conductors receive a second grounding to earth, reducing the equipotential at this point and counteracting the otherwise large voltage drop at the PEN across the source line resistance RLS. As mentioned earlier, according to the National Electric Code (NEC), the PE is supposed to be a currentless conductor under normal operation. However, most non-linear loads leak currents in the lower milli-amps into the PE. This amount, although small for one unit, easily reaches amps when considering that hundreds of equipments contribute into the same strand. Although negligible in comparison with neutral currents, leakage currents do create potential differences between remote ground locations due to the voltage drops across the line resistance of the PE-conductors. These GPDs however, are in the lower volt range and thus significantly lower than in TN-C systems. Unfortunately, TN-C-S systems are mainly found in newer buildings, below a certain age. Older buildings often receive an installation upgrade due to the latest NEC code. In most of the cases however, only parts of the existing installation is upgraded. In some instances, new TN-C-S installations are simply added to existing TN-C systems. Making matters worse, additional Earth connecting rods are installed, or simply resembled by connecting the PE to a nearby metal water pipe (above shown as dotted Earthing symbols), thus complicating the Earth return path and worsening the GPD issue. Ground Potential Differences Ground Potential Difference [V] 30 20 10 0 -10 -20 -30 0 90 180 270 360 Phase Angle [O] 11 Ground potential differences are not a problem for data links whose bus nodes are powered by the same phase strand. Ground potential differences, as the ones above, become a concern when designing a communication link between bus nodes powered from different parts of the electrical installation. This holds true for long and short distance nodes. Because system designers don’t have control over the electrical installation supplying their data transmission design, one should always assume that Ground Potential Differences do exist. Design Pitfall: Ground Loops 2 3 d) Complex Earthing resistance network 1 12 Ground Potential Differences add as common-mode noise, Vn, to the transmitter output, and EIA/TIA485 specifies a maximum GPD of ±7V across which a data link must operate reliably. Figure a: Despite this specification, relying on the local earth ground as a stable ground reference is risky. Even if the total superimposed signal is within the receiver’s input common mode range, modifications to the electrical installation, (i.e. during maintenance work), are out of the designer’s control. The modifications can increase the GPD to the extent, that the receiver’s input common-mode range is either sporadically or permanently exceeded. Thus a data link which perfectly works today might stop operating sometimes in the near future. Figure b: Removing the ground potential difference by directly connecting remote grounds through a ground wire is also not recommended. Bear in mind that the electrical installation constitutes a highly complex resistance network, consisting of multiple, cross-connected line- and grounding resistances, which are caused by different phase systems, different cable lengths and various grounding electrode paths (Figure d). A direct connecting between remote grounds shunts this network and creates a current loop. The initial GPD tries to compensate its collapse by driving a large loop current through the low-impedance ground wire. The loop-current couples into the signal wires, generating a noise voltage that is superimposed on the transmission signal. This again carries the risk of a highly unreliable data transmission system. Figure c: In order to allow for a direct connection of remote grounds, the TSB89 application bulletin to EIA/TIA 485 recommends the separation of device ground and local system ground via the insertion of 100 Ω resistors. While this approach reduces loop current, the existence of a large ground loop keeps the data link sensitive to noise generated somewhere else within the loop. Single Ground Reference Signal Rate - Mbps 100 HVD23 -20V HVD20 10 +25V HVD24 HVD21 1 -7V HVD22 0.1 10 100 Cable Length - m +12V 1000 13 In order to support GPDs of up to ± 20V, Texas Instruments has released the SN65HVD2x family of Super RS-485 transceivers with an extended common-mode voltage range from 20 V to + 25 V. Single Ground Reference Isolated Node n ISO-GND 3 Local Processor Isolated Node 1 5V ISO-GND 3 Local Processor 5V Non-isolated Ref. Node 0 REF-GND 5V Local Processor Termination Plug Termination Plug 14 For even higher GPDs, such as hundreds and thousands of volts, a single ground reference approach is a must. However, this method requires the galvanic isolation of the signal and supply lines of all but one bus node, which actually presents the system ground reference node (see RS-485 Design Guide Lines).
© Copyright 2026 Paperzz