GEO16-531.6 5H0839220000 March, 2015 O RV BS IC O E LE US TE E ON L Y MODINE CONTROL SYSTEM MANUAL Orb Controller geothermal systems Table of Contents ! WARNING 1. Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment. 2. Improper control adjustments and manual mode control can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before making adjustments. 3. Disconnect power supply before installing accessories to prevent the unit from operating during installation. SE IMPORTANT 1. The use of this manual is specifically intended for a qualified installation and service agency. All installation and service of this unit must be performed by a qualified installation and service agency. 2. These instructions must also be used in conjunction with the Installation and Service Manual originally shipped with the appliance, in addition to any other accompanying component supplier literature. Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Orb Controller Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Connections and Field Wiring . . . . . . . . . . . . . . . . . . . . . . .4 Orb Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Startup Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Forced Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Water to Water. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Orb Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 Menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 Internal Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 Mechanical Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 Thermostat Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 System Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Run Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21 Forced Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 Tank Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 Combination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 Forced Air Zoning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 Control Board Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 Real Time Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 Orb Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Appendix A - Orb Display Mounting Kit. . . . . . . . . . . . . . . . . . .32 Commercial Warranty. . . . . . . . . . . . . . . . . . . . . . . . Back Cover THIS MANUAL IS THE PROPERTY OF THE OWNER. PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB. MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Model Nomenclature 2 MT 3 UC 4,5,6 MBH 7 DS 8 CC 9,10 PC DIGIT 1 - UNIT APPLICATION (UA) G - RESIDENTIAL E - COMMERCIAL DIGIT 2 - MODEL TYPE (MT) DIGIT 3 - UNIT CONFIGURATION (UC) V - VERTICAL (COMBINATION, FORCED AIR, AND AIR HANDLER) H - HORIZONTAL (FORCED AIR AND AIR HANDLER) R - REVERSIBLE (WATER TO WATER) W - NON REVERSIBLE (WATER TO WATER) I - INDOOR SPLIT CONDENSING UNIT DIGITS 4, 5, 6 - NOMINAL CAPACITY (MBH) 018 024 036 048 060 066 096 120 132 14 HM 15 HWG 16 MT 17 SA 3 - ORB DIGIT 12 - AIR COIL (AC) N - NONE R - R410A DIGIT 13 - GEO (SOURCE) COIL MATERIAL (GM) X - NONE C - COPPER N - CUPRO NICKEL DIGIT 14 - HYDRONIC (LOAD) COIL MATERIAL (HM) X - NONE C - COPPER N - CUPRO NICKEL DIGIT 15 - DESUPERHEATER (HWG) 0 - NONE 1 - HOT WATER GENERATOR DIGIT 17 - SUPPLY AIR CONFIGURATION (SA) SE 0 - NONE 1 - SINGLE STAGE 2 - TWO STAGE 3 - SINGLE STAGE WITH SOFT START 4 - TWO STAGE WITH SOFT START 18 RA DIGIT 11 - CONTROLLER TYPE (CT) N - NONE E - ECM DIGIT 8 - COMPRESSOR CONFIGURATION (CC) N - NONE T - TOP (VERTICAL) B - BOTTOM (VERTICAL) S - SIDE (HORIZONTAL) E - END (HORIZONTAL) DIGIT 18 - RETURN AIR CONFIGURATION (RA) N - NONE L - LEFT R - RIGHT B - BOTTOM DIGITS 9, 10 - POWER CODE (PC) 02 - 208V/60Hz/1ph 03 - 208-230V/60Hz/1ph 04 - 208V/60Hz/3ph 05 - 208-230V/60Hz/3ph 2 13 GM DIGIT 16 - MOTOR TYPE (MT) DIGIT 7 - DESIGN SEQUENCE (DS) C 12 AC O RV BS IC O E LE US TE E ON L F - FORCED AIR UNIT H - WATER TO WATER UNIT A - AIR HANDLER UNIT C - COMBINATION UNIT S - SPLIT CONDENSING UNIT 11 CT Y 1 UA GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Orb Controller Overview • Simple Interface - Easy to understand menus and settings • Temperature Display - Real time display of water and air temperatures • Simple Troubleshooting - All alarms are displayed in full text - A snapshot of temperature values is saved when an alarm comes on • Zone Control - Control up to 4 forced air zones is standard The Modine Controls System Orb Controller is a combination of a control board located inside the equipment and the touchscreen display. The display location is based on the type of equipment that is installed. The touchscreen is an intuitive device that allows the user to interact with the system. Some of the features of the Orb Controller include: • LCD Display - Full color 320 x 240 pixel touchscreen • Quick Startup - Performed solely from the display Y Orb Control Board Connector Layout O RV BS IC O E LE US TE E ON L Figure 3.1 - Orb Control Board Revision D Connector Layout P7 P6 P15B P16 P15A P20 P17 P26 P2 P27 ORB CONTROL BOARD ETHERNET JACK 24V OUTPUTS USB P14 24V POWER SUPPLY P25 P13 P24 P9 P23 P10 P11 P12 240V INPUTS/ OUTPUTS Table 3.1 - Orb Board Connection Descriptions REFERENCE 24V POWER SUPPLY REFERENCE 240V INPUTS/ OUTPUTS DESCRIPTION P15A Zone 1 Thermostat Connections A 24V outputs: Compressor Contactor & Reversing Valve P15B Zone 1 Thermostat Connections B SE 24V OUTPUTS DESCRIPTION 24V Power input from transformer 240V Section of Board: FLC Pump, Fan, DHW & HYD Pump P16 Zone Control Connector P17 LCD/ Touchscreen Connector P2 ECM Control Connection P20 AUX Heat Control Connector P6 Hydronic Buffer Tank Cold Sensor Input P7 P23 High Pressure Switch Connector Hydronic Buffer Tank Hot Sensor Input P9 AUX OUT 2 P24 Low Pressure Switch Connector P10 AUX OUT 1 P25 Condensate Switch Connector P11 AUX IN 1 P26 Sensor Block A P12 AUX IN 2 P27 Sensor Block B P13 AUX OUT 3 P14 AUX OUT 4 GEO16-531.6 3 8 MODINE CONTROL SYSTEM MANUAL 11 12 13 ORB CONTROLLER Connections/Field Wiring Thermostat/Temperature Sensor Connections Figure 4.1 - Thermostat Wiring Connection on ORB Board W2/E DHM R W1 G R C Y2 Y1 The following thermostats have been tested and are recommended for use with the Orb controller: • Honeywell Prestige (YTHX9421R5051) • Emerson Blue (1F95-1291) • Emerson Blue (1F98EZ-1421) • Emerson Inspire (1HDEZ-1521) NOTE: The NEST thermostat is incompatible with the Orb controller. O L O RV BS IC O E LE US TE E ON L Y THERMOSTAT CONNECTIONS Table 4.1 - Thermostat Connections SYSTEM FORCED AIR UNIT: SINGLE STAGE THERMOSTAT CONNECTIONS DHM W2/E W1 C R R G Y1 Y2 L O De-hum Common 24 VAC 24 VAC Fan Compressor Stage 1 FORCED AIR AND SPLIT UNIT: 2 STAGE De-hum Compressor Thermostat Cooling Common 24 VAC 24 VAC Fan Compressor Stage 1 Stage 2 Alarm FORCED AIR AND SPLIT UNIT: W/ 5KW ELECTRIC HEAT De-hum Electric Heat Stage 3 (5KW) Compressor Thermostat Cooling Common 24 VAC 24 VAC Fan Compressor Stage 1 Stage 2 Alarm FORCED AIR AND SPLIT UNIT: W/ 10KW ELECTRIC HEAT De-hum Electric Heat Stage 4 (5KW) Electric Heat Compressor Compressor Thermostat Cooling Stage 3 Common 24 VAC 24 VAC Fan Stage 1 Stage 2 Alarm (5KW) FORCED AIR AND SPLIT UNIT: W/ 15KW ELECTRIC HEAT De-hum Electric Heat Stage 4 (10KW) Electric Heat Compressor Compressor Thermostat Cooling Stage 3 Common 24 VAC 24 VAC Fan Stage 1 Stage 2 Alarm (5KW) FORCED AIR AND SPLIT UNIT: W/ 20KW ELECTRIC HEAT De-hum Electric Heat Stage 4 (10KW) Electric Compressor Compressor Thermostat Cooling Heat Stage 3 Common 24 VAC 24 VAC Fan Stage 1 Stage 2 Alarm (10KW) HYDRONIC USING AN AQUASTAT Common 24 VAC 24 VAC AUX AN IN 1 AUX AN IN 2 AUX IN 1 Thermostat Cooling Alarm Aquastat Input Stage 1 Cooling Hot Tank Cool Tank Sensor Sensor Input Input HYDRONIC USING 10K THERMISTORS STACKED HYDRONIC USING AN AQUASTAT Common 24 VAC 24 VAC Aquastat Input Stage 1 Aquastat Input Stage 2* Cooling Hot Tank Cool Tank Sensor Sensor Input Input STACKED HYDRONIC USING 10K THERMISTORS De-hum Compressor Thermostat Cooling Common 24 VAC 24 VAC Fan Compressor Stage 1 Stage 2 Alarm COMBINED USING 10K THERMISTORS De-hum Compressor Thermostat Cooling Common 24 VAC 24 VAC Fan Compressor Stage 1 Stage 2 Alarm SE COMBINED USING AN AQUASTAT Aquastat Input Stage 1* Hot Tank Sensor Input NOTE 1: For combined units with electric heat, use the same electric heat connections as a forced air unit. NOTE 2: For stacked hydronic units using an aquastat, connecting Y2 is optional. A Y2 call will interrupt the lead lag timer and step into stage 2 conditioning. NOTE 3: For combined units usings and aquastat, "AUX IN 1" is a dry contact that is reverse acting. A call for heat is generated when the contact is open. NOTE 4: If the DHM terminal is energized during a cooling call, the fan speed slows to -10% from nominal value (Y1 - 57%, Y2 - 80%). 4 GEO16-531.6 AUX OUT 4 3rd Stage Boiler Output 3rd Stage Boiler Output 3rd Stage Boiler Output 3rd Stage Boiler Output MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Return & Supply Air Sensors (Forced Air, Combination, and Air Handlers Power Code 03 Only) Air Handlers: The return and supply air sensors are factory installed. Forced Air and Combination: The supply air sensor is factory installed and the return air sensor is factory wired, field mounted. 10K Buffer Tank Temperature Sensors Outside Air Temperature Sensor O RV BS IC O E LE US TE E ON L (Optional for Water to Water Units) An outside air temperature sensor is optional for hydronic units (Modine Part # 5H0835240000). The sensor should be mounted on an outside north facing wall, under the eaves which will provide protection from direct sunlight. It is mounted by extending a threaded end of the ½" conduit used for wiring through the building wall so that it protrudes at least 1" from the wall face. The sensor can be threaded directly onto the conduit until the unit is tight and pointing towards the ground. Remove access cover, feed wires through and connect. Orange wire leads are provided on the Orb board for easy field connections. Y (Optional for Water to Water and Combination Units) 10K sensors are recommended to control buffer tank temperature (Modine Part # 3H0388160000). These sensors are field wired. See wiring diagram for more detail. Figure 5.1 – Typical Outside Air Temperature Sensor Installation SE North OAT Temperature Sensor GEO16-531.6 5 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Orb Display The touchscreen LCD Display is the user interface to the system. During operation, the screen will display various temperatures, operation modes, menus and alarms. The housing for the display has a green LED power light. This light shows the user there is power to the display and the equipment. For hydronic, horizontal forced air, and split systems, the display is shipped loose with a mounting bracket and must be connected to the Orb control board. The bracket/display can be fastened to the top of the unit using provided self-tapping sheet metal screws or to a nearby wall using provided drywall anchors. The supplied ribbon cable must be connected to the back of the display and the control board (see “P17” in Figure 3.1 or refer to Appendix A for more information). When using the system, the display shows various buttons. To push a button, use a quick, firm tap in the general location of that button on the screen. Only during Calibration and accepting all start-up values does the user need to press and hold on the screen. O RV BS IC O E LE US TE E ON L Y Figure 6.1 - Orb Display Layout Table 6.1 - Orb Display Button Descriptions FUNCTION DESCRIPTION SE BUTTON ACCEPT 6 Pressing ACCEPT will take the user to the next menu item. Or confirm a selection. NEXT Pressing NEXT will cycle through a menu, change a setting, or increase or decrease a set-point. MENU Pressing MENU will provide access to all menus that are available for the unit. (Operation only) BACK Pressing BACK will return the user to the previous menu item. (Startup only) GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Start-Up Guide Default Settings Forced Air and Split units are pre-programed from the factory for easier installation. If any installation parameters differ from the default settings, the user should enter the "MECHANICAL SETUP" or "FORCED AIR" menu items to make changes. See Table 7.1 for more detail for each parameter. Water to Water and Combined units are NOT pre-programmed from the factory and will need to be configured on startup. Table 7.1 - Forced Air and Split Systems Default Startup Settings FACTORY SETTING VALUES/ RANGE Calibrated NA Hour Current Hour 0 - 23 Minute Current Minute 0 - 59 Day Current Day 1 - 31 Month Current Month JAN, FEB, MAR, APR, MAY, JUN, JUL, AUG, SEP, OCT, NOV, DEC Year Current Year 2015 - 2038 Model Type Forced Air Forced Air, Water to Water Non-Reversing, Water to Water Reversing, & Combined Model Size Model Digits 4,5,6 018, 024, 036, 048, 060, 066 Fan G 0% -5% - +15% O RV BS IC O E LE US TE E ON L Y PARAMETER Display Calibration Fan Low 0% -5% - +5% Fan High 0% -5% - +5% Scale Range Fahrenheit °F, °C Freeze Protection Water (36°F) Water, Methanol, Ethanol, Propylene Glycol Flow Center Control Master Master, Slave Domestic Hot Water Pump OFF Off, On Compressor Type Name Plate Single, Dual Voltage 230 197 - 253 Zoning OFF Off, On Start-Up Water and Combined units are not pre-programmed from the factory and will require the user to complete the startup sequence. Prior to the startup sequence, the user will have to calibrate the touchscreen. Press and hold down firmly on the screen where the circle is located for 3-5 seconds. When the circle moves to a new position, press and hold firmly at the new location. If calibration is done improperly the Orb will not accept the values and return to the first calibration screen. SE Figure 7.1 - Screen Calibration Procedure GEO16-531.6 7 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER FORCED AIR WATER TO WATER REVERSING WATER TO WATER NON-REVERSING COMBINED NAME 1 2 3 • • • • • • • • • • • • HOUR MINUTE DAY 4 • • • • MONTH 5 • • • • YEAR 6 • • • • MODEL 7 • • • • MODEL SIZE • • • • • • • • • • 9 10 11 12 13 • • • • 14 • • • • 15 16 17 18 19 20 21 • • • • • • • • • • • • • • • • • • • • • • • 22 • • 23 24 25 • • • • • • 26 • 27 • • • 28 29 • 30 • 31 • -10% - +28% -10% - +10% -10% - +10% °F, °C WATER, METHANOL, ALCOHOL ETHANOL, P_ GLYCOL PERCENTAGE 10 - 38 FLC MASTER, SLAVE DHW PUMP OFF, ON DHW SETPT 110 - 140 COMPRSR SINGLE, DUAL VOLTAGE 197 - 263 ZONING OFF, ON Select the number of flow centers wired to a stacked hydronic unit. Increase or decreases airflow during a fan only call. Increase or decreases airflow when the compressor is in low stage. Increase or decreases airflow when the compressor is in high stage. Selects the temperature scale of user preference. Selects the anti-freeze solution in the ground loop. Selects the percentage of the alcohol solution in the ground loop, (not available if 14 is WATER). Select flow center pump control for the unit. Select if domestic hot water is enabled or disabled, (Plumb and fill desuperheater coil with water before enabling pump). Select domestic hot water tank setpoint ranging 110°F - 140°F (not available if 17 is OFF). Select depending if compressor is a single or two stage. Select incoming line voltage to the unit. Select if zoning is enabled. ZONES 2, 3, 4 Select the number of zones in the system, (not available if 21 is OFF). ZONE 2 CFM ZONE 3 CFM ZONE 4 CFM HYD THIRD STG 20 - 80 20 - 80 20 - 80 Select the percentage of airflow required for zone 2, (not available if 21 is OFF). Select the percentage of airflow required for zone 3, (not available if 21 is OFF). Select the percentage of airflow required for zone 4, (not available if 21 is OFF). SENSOR RELAY OFF, 10 - 45 AQUASTAT, 10K THERM MAKE, BREAK OFF, ON Select the amount of time the unit runs before the 3rd stage output turns on. Select if the the buffer tank sensor is a aquastat or a 10K thermistor. Select if the Aquastat connected to the ORB is normally open or normally closed, (only available if 27 is AQUASTAT). Select if an outside air temperature sensor is being used, (only available if 27 is 10K THERM). OAT HT MIN 35 - 70 OAT HT MAX ⁻30 - 32 COOL TANK MIN COOL TANK MAX 40 - 55 Select the heating buffer tank minimum setpoint ranging 75°F - 95°F (only available if 29 is ON). Select the heating buffer tank maximum setpoint ranging 100°F - 130°F (only available if 29 is ON). Select the outside air temperature when the heating buffer tank will be at minimum setpoint ranging 35°F - 70°F (only available if 29 is ON). Select the outside air temperature when the heating buffer tank will be at maximum setpoint ranging ⁻30°F - 32°F (only available if 29 is ON). Select the cooling buffer tank minimum setpoint ranging 40°F - 55°F (only available if 29 is ON). 60 - 70 Select the cooling buffer tank maximum setpoint ranging 60°F - 70°F (only available if 29 is ON). • OAT CL MIN 60 - 75 • OAT CL MAX 85 - 110 • TANK DEADBAND 5 - 15 CHANGE TEMP 55 - 85 • MODE HEAT SETPOINT COOL SETPOINT SE • • • 42 • 43 • 44 45 • SINGLE, DUAL 75 - 95 100 - 130 • • • • • FAN G FAN LOW FAN HIGH SCALE RANGE HOT TANK MIN HOT TANK MAX 36 • Selects the amount of time the lead unit runs before the lag unit turns on, ranging 5 to 30 minutes, (only available if 7 is 096, 120, 132, or 360). Select the cooling buffer tank setpoint ranging 30°F - 60°F (only available if 29 is OFF, or 30 is CHANGEOVER). • • Select the unit size according to the serial plate. 30 - 60 • 41 Selects the unit type: Forced Air, Water to Water Non-Reversing, Water to Water Reversing, & Combined. Select the heating buffer tank setpoint ranging 80°F - 125°F (only available if 29 is OFF, or 30 is CHANGEOVER). 35 40 Select the current year. 80 - 125 • • • 39 Select the current month. Select the initial operation mode of the unit. (CHANGEOVER only available on reversing hydronic units with 29 ON). • • 38 5 - 30 Select current hour in 24 hour format. Select current minute. Select the current day of the month. HEAT, COOL, AUTO, CHANGEOVER, OFF • • 37 FLC CNTRL OAT • 33 34 46 • • 32 8 LAG TIMER(MIN) 0 - 23 0 - 59 1 - 31 JAN, FEB, MAR, APR, MAY, JUN, JUL, AUG, SEP, OCT, NOV, DEC 2015 - 2038 FORCEDAIR, W2WNONRV, W2WREV, COMBINED 018, 024, 036, 048, 060, 066, 096, 120, 132, 144, 180, 360 DESCRIPTION O RV BS IC O E LE US TE E ON L 8 VALUES/ RANGE Y REFERENCE NUMBER Table 8.1 - Orb Parameters by Unit Type • • DEADBAND 2 - 12 PRIORITY POOL MODE HOLD ACCEPTSTART AIR, HYDRONIC OFF, ON Parameter is applicable to unit type. NA Select the outside air temperature when the cooling buffer tank will be at maximum setpoint ranging 60°F - 75°F (only available if 29 is ON). Select the outside air temperature when the cooling buffer tank will be at minimum setpoint ranging 85°F - 110°F (only available if 29 is ON). Select the buffer tank deadband ranging 5°F - 15°F (not available if 27 if AQUASTAT). Select the outside air temperature that a single buffer tank system changes between heating and cooling ranging 55°F - 85°F (only available if 30 is CHANGEOVER). Select the outside air temperature deadband for the change over ranging 2°F - 12°F (only available if 30 is CHANGEOVER). Select the priority heating system. Select if pool mode is enabled to allow hydronic heating in forced air cooling mode. Hold down the ACCEPT button to accept all startup values. GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER 1, 2, 3, 4, 5. HOUR, MINUTE, DAY, MONTH, YEAR – Select the current time for the clock. Figure 9.1 - Orb Master / Slave Flow Center Wiring 6. MODEL – Select the type of heat pump equipment installed. See digits 1, 2, & 3 of the model number located on the serial plate. • Forced Air – GFV, GFH, EFV, EFH, GSI, ESI • Combined – GCV, ECV • Hydronic Reversible – GHR, EHR • Hydronic Non-Reversible – GHW, EHW 7. MODEL SIZE – Select the size or tonnage of the unit. See digits 4, 5, & 6 of the model number located on the serial plate. O RV BS IC O E LE US TE E ON L 9. FLC CNTRL - For stacked hydronic units, one or two flow centers may be used. For one flow center, wire the pump to the top unit terminals and select “SINGLE”. For two flow centers, wire each pump to the respective unit terminals and select “DUAL”. 18. DHW SETPT – In order to assure the domestic hot water pump runs as much as possible it should be set at, or above the hot water heater set point. The Orb uses a 10°F static dead band below the set point to prevent the pump from short cycling. The location of the temperature sensor is on the return DHW line inside the heat pump. Y 8. LAG TIMER (MIN) – The Lead Lag Timer is used for stacked hydronic units only. This timer is used to start the second stage of the system if the set point cannot be met in that period of time. The timer can be set from 5 to 30 minutes. 10. FAN G – This allows for the adjustment of the fan when operating in “G” signal. (Fan only). The factory setting is 33% of the nominal airflow. The installer can adjust the fan setting -10% to +28% of the nominal airflow. 11. FAN LOW – This allows for the adjustment of the fan when operating in “Y1” signal. (Compressor low stage). The factory setting is 67% of the nominal airflow. The installer can adjust the fan setting +/-10% of the nominal airflow. 12. FAN HIGH – This allows for the adjustment of the fan when operating in “Y2” signal. (Compressor high stage). The factory setting is 90% of the nominal airflow. The installer can adjust the fan setting +/- 10% of the nominal airflow. 13. SCALE RANGE – Temperature readings during operation are displayed in the selected Scale Range: Fahrenheit or Celsius. SE 14 & 15. ALCOHOL & PERCENTAGE – The alcohol percentage is used to determine the freeze protection temperature during operation. The installer selects the type of alcohol and the percentage in the system, and then the Orb calculates the freeze protection. If the application is an open loop, the installer would select water and the freeze protection would be set to 36°F. • Water: Freeze protect 36°F • Methanol: 10 - 25% • Ethanol: 14 - 29% • Propylene Glycol: 15 - 38% 16. FLC – The Orb controller has the ability to communicate with another Orb unit for a two heat pump, single flow center application. The heat pump to which the flow center is wired is considered the “Master”, while the other is considered the “Slave”. The “Slave” will send a signal to the “Master” when the Flow Center is required to be on. When using flow center master/slave control with a water to water unit, the water to water unit must be configured as the master. 17. DHW PUMP – The domestic hot water pump is shipped electronically off. If the pump is started prior to being plumbed and filled with potable water, DAMAGE TO THE UNIT WILL OCCUR. 19. COMPRSR – The Compressor setting selects either a Single Stage Compressor or a Two Stage Compressor. To determine if the unit is a single or two stage, refer to digit 8 of the model number located on the serial plate. 20. VOLTAGE – The incoming line voltage to the unit must be input for accurate energy estimates. Measure across L1 and L2 and input the value. 21, 22. ZONING, ZONES – If more than one forced air zone is to be used, zoning must be enabled and the number of zones input. (see “Zoning” on page 24 for more information). 23, 24, 25. ZONE CFM – Enter the size of each zone which is represented as a percentage of total unit airflow in cfm (See “Zoning” on page 24 for more information). 26. HYD THIRD STG – A backup boiler can be connected to the ORB through terminal "AUX OUT 4" on hydronic units. The unit will run for the selected amount of time in minutes (10 - 45) before the backup boiler is turned on. “AUX OUT 4” (board location P14) is a normally open dry contact. 27. SENSOR – Select the type of control used for the hydronic buffer tank. An Aquastat provides an ON/OFF signal to the Orb controller, whereas the 10K Thermistor provides a resistance to the Orb controller. 28. RELAY – When using an aquastat with a Combined unit, the aquastat is connected through terminal "AUX IN 1". If the aquastat is normally open, select "MAKE". If the aquastat is normally closed, select "BREAK". “AUX IN 1” (board location P11) is a dry contact. 29. OAT – An outside air temperature sensor can be used on units with a hydronic buffer tank to achieve a variable set point for the tank. On reversing water to water units using a single buffer tank, the outside air sensor allows for automatic changeover of the buffer tank from heating to cooling or vice versa. 30. MODE – Conditioning Mode is used in Hydronic Reversible & Combined applications. This allows the user to select the initial type of conditioning that is desired. (See page 12 in Operation on how to change mode after startup). HEAT: 1 Tank System - The unit will maintain the tank temperature for heating only. GEO16-531.6 9 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Figure 10.2 - Cooling Mode Outside Air Temperature Hydronic Setpoint Y The cooling tank set point is maintained at the COOL TANK MAX until the outside air temperature increases to the OAT CL MIN temperature. As the outside air temperature increases from 70°F to 100°F, the cooling tank set point decreases linearly. At and above the OAT CL MAX, the tank is maintained at COOL TANK MIN temperature. 41. TANK DEADBAND – The tank deadband sets the differential for hydronic tanks that are controlled with 10K thermistors. Example: If a deadband of 10°F is selected with a heating buffer tank set point of 100°F, the unit will operate until the set point is reached. The unit will then be in standby until the tank temperature drops below 90°F. 42, 43. CHANGE TEMP, DEADBAND – The changeover point is the outside air temperature used to determine whether the system should be heating or cooling. This Temperature is used in conjunction with the Auto Changeover Dead Band to prevent quick switching between conditioning modes. Example: CHANGE TEMP: 70°F DEADBAND: 10°F If the unit is in heating mode, the outside air temperature would have to increase to 80°F before the unit changes the single tank from the heating set point to the cooling set point. The outside air temperature would then have to drop below 60°F for the tank to switch back to heating. 44. PRIORITY - Combination units allow the option to set the priority heating system to either hydronic or forced air. The priority heating system will override the secondary system if both are calling for heat at the same time. 45. POOL MODE – Pool mode allows the system to do forced air cooling and hydronic heating at the same time. The flow center shuts down and heat is rejected through the hydronic coil instead of into the loop field. Once the hydronic tank is satisfied, the flow center will engage and the hydronic pump will shut down until the forced air cooling call is satisfied. 46. HOLD ACCEPT TO START – Review all startup criteria and hold down the ACCEPT button to complete the startup process. O RV BS IC O E LE US TE E ON L 2 Tank System – The unit will maintain only the heating tank. COOL: 1 Tank System – The unit will maintain the tank temperature for cooling only. 2 Tank System – The unit will maintain only the cooling tank. AUTO: 1 Tank System – Do not use. 2 Tank System – The unit will maintain both the heating and cooling tanks at the same time. CHANGEOVER: 1 Tank System – Based on outside air temperature, the unit will maintain the tank for heating or cooling. 2 Tank System – Do not use. OFF: 1 Tank System – The unit will not maintain the tank. 2 Tank System – The unit will not maintain either tank. 31. HEAT SETPOINT – If using 10K thermistors and no outside air temperature sensor, select the fixed set point for the heating tank. 32. COOL SETPOINT – If using 10K thermistors and no outside air temperature sensor, select the fixed set point for the cooling tank. 33, 34, 35, 36. HOT TANK MIN, HOT TANK MAX, OAT HT MIN, OAT HT MAX – The Orb allows for a variable set point of the hydronic buffer tank based on the outside air temperature. Maintaining a lower heating tank set point increases energy efficiency of the system. Heating Example: • HOT TANK MIN 80°F • HOT TANK MAX 110°F • OAT HT MIN 60°F • OAT HT MAX 30°F Figure 10.1 - Heating Mode Outside Air Temperature Hydronic Setpoint SE The heating tank set point is maintained at the HOT TANK MIN until the outside air temperature drops to the OAT HT MIN temperature. As the outside air temperature drops from 60°F to 30°F, the heating tank set point increases linearly. At and below the OAT HT MAX, the tank is maintained at HOT TANK MAX temperature. 37, 38, 39, 40. COOL TANK MIN, COOL TANK MAX, OAT CL MIN, OAT CL MAX – The Orb allows for a variable set point of the hydronic buffer tank based on the outside air temperature. Maintaining a higher cooling tank set point increases energy efficiency of the system. Cooling Example: • COOL TANK MIN 30°F • COOL TANK MAX 60°F • OAT CL MIN 70°F • OAT CL MAX 100°F 10 GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Operation The LCD Touchscreen display is the window to the system. When in normal operating mode the screen displays temperatures, conditioning mode, conditioning staging, time, date and any specific setup information. The temperatures displayed are from various points throughout the equipment. This information can provide the temperature differential through the heat exchanger in the system for troubleshooting. The display will eventually power off when 100 seconds of inactivity have occurred. Every time a button is pressed, this resets the activity timer. If the screen is off, touch the display and the screen will turn on again. When the system has finished a run cycle, the compressor has a 5 minute delay to allow the pressure in the system to equalize. If a conditioning call occurs in this 5 minute window, the amount of time in seconds is counted down in the conditioning area of the display. Forced Air The Forced Air system works off of control signals from a conventional thermostat. These signals determine the type of conditioning and conditioning stage of the equipment. O RV BS IC O E LE US TE E ON L Y Figure 11.1 - Forced Air Screen Display Table 11.1 - Forced Air Screen Parameter Descriptions NAME 1 2 3 4 STAND BY, HEATING, COOLING, EMRG-HEAT, ALARM ON, LOCKOUT STAGE:1, STAGE:2, STAGE:3, STAGE:4, CFM Current CFM GWO Ground water out temperature GWI Ground water in temperature SE 5 STATUS STAGING MODE VALUE 6 RETURN 7 SUPPLY 8 DHW 9 AMPS 10 CONDITIONING TIME 11 POWER CONSUMPTION 12 DHM Return air temperature Supply air temperature Domestic hot water return temperature Total amp draw for the unit Start and stop time of current or most recent cycle Total power consumption of last cycle (STANDBY mode only) Shows if dehumidification is on (COOLING conditioning mode only) GEO16-531.6 11 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Water to Water To change the operation mode after startup go to: • MENU • TANK SETTING • MODE • Select either HEAT, COOL, AUTO, CHANGEOVER, or OFF • >>RETURN • >>RETURN - NOTE - The Orb controller will not change the mode unless both RETURN items are selected. With the 10K thermistor setting, the dead band and set point is used to determine the temperature for starting the system. For Heating, if the tank temperature is lower than the set point minus the dead band the system will turn on. The reverse is applicable for Cooling. Stacked hydronic systems work from one control panel. The staging for the system is based on a Lead system and a Lag system. The Lead-Lag can either start based on a timer or based on aquastat staging. The Lead-Lag system will be switched every 24 hours to allow for balanced run times for the equipment. Refer to the wiring diagram for wiring the aquastat control signals for a Lead Lag system. Y The Hydronic system works with either buffer tank thermistors or aquastats. The type of sensors dictates how the main display screen appears. The operating mode for the equipment will also determine system operation. If the operating mode to set to “HEAT” or “COOL”, the system will only heat or cool. If the system is in “AUTO”, the mode that is first to call will receive the conditioning. Once that conditioning mode is satisfied, if the opposite mode is also calling, it will start after the 5 minute compressor delay. If the operating mode is set to “CHANGEOVER”, the outside air temperature along with the dead band will determine if the system is in heating or cooling. “OFF” mode will disable operation. O RV BS IC O E LE US TE E ON L Figure 12.1 - Hydronic Screen Display Table 12.1 - Hydronic Screen Parameter Descriptions 2 3 4 5 6 7 MODE GWO GWI T B 8 AMPS 10 CL 9 11 HT HEATING TANK STATUS 12 COOLING TANK STATUS 14 LEAD LAG DELAY 13 12 STATUS STAGING MODE VALUE STAND BY, HEATING, COOLING, ALARM ON, LOCKOUT STAGE:1, STAGE:2 HEAT, COOL, AUTO, CHANGEOVER, OFF SE 1 NAME OAT Ground water out temperature Ground water in temperature Top unit status, black: STANDBY, red: HEATING, blue: COOLING (Stacked units only) Bottom unit status, black: STANDBY, red: HEATING, blue: COOLING (Stacked units only) Total amp draw for the unit Heating tank setpoint (Optional 10K thermistors only) Cooling tank setpoint (Optional 10K thermistors only) Heating tank temperature (optional 10K thermistors only), or Aquastat status (Aquastat only) Cooling tank temperature (optional 10K thermistors only), or Aquastat status (Aquastat only) Outside air temperature (Optional outside air sensor only) Time in seconds until the lag unit turns on (Stacked units only) GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Combination Units A combination unit will show a combination of items from both the forced air and hydronic system status screens. The combination system has a heat priority that will determine if the forced air or hydronic system should run if both are calling at the same time. The combination system has “Pool Mode”, or dual conditioning mode functionality. In this mode, when the system is forced air cooling, the heat can be rejected into the hydronic buffer tank instead of into the loop field. The system needs to be calling for cooling from the thermostat and calling for heating from the buffer tank for the equipment to run in this mode. O RV BS IC O E LE US TE E ON L Y Figure 13.1 - Combination Screen Display Table 13.1 - Combination Screen Parameter Descriptions NAME 1 2 3 4 STAGING MODE STAND BY, HEATING, HEAT-HYD, COOLING, EMRG-HEAT, ALARM ON, LOCKOUT STAGE:1, STAGE:2, STAGE:3, STAGE:4 MODE HEAT, COOL, AUTO, CHANGEOVER, OFF, CFM GWO Ground water out temperature GWI Ground water in temperature SE 5 STATUS VALUE 6 RETURN Return air temperature 7 SUPPLY Supply air temperature 8 AMPS Total amp draw for the unit 9 TANK Heating tank temperature (optional 10K thermistors only), or Aquastat status (Aquastat only) 10 ST PNT 11 OAT Heating tank setpoint (Optional 10K thermistors only) Outside air temperature (Optional outside air sensor only) GEO16-531.6 13 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Alarms Alarms are used to monitor various points of the equipment and prevent the equipment damage. There are 4 types of alarms associated with the equipment, “High Pressure”, “Low Pressure”, “Condensate” and “Freeze Protection”. The system can also perform a “Lockout”, which requires interaction from the user to restart the system. When an alarm occurs, the display will show the type of alarm that has occurred. If the system is operating, the alarm will stop the system and try to determine what caused the alarm. If the system was not operating when an alarm occurs, the alarm will still be displayed on the screen. O RV BS IC O E LE US TE E ON L Y Figure 14.1 - Alarm Screen Display When the system is in alarm mode, the display backlight will stay powered and show a snapshot of the temperatures in the system at the time the alarm occurred. The display will remain in “snapshot” mode, and nothing will change until the display is touched. This allows for quicker troubleshooting of the system. When an operational alarm occurs the following is displayed: • Alarm type • Mode the alarm occurred • Time and date alarm occurred • Run time for the system • Possible alarm information • The exact temperatures when the system had the alarm Table 14.1 - Alarm Screen Parameter Descriptions NAME STATUS 2 ALARM TYPE 3 RUNTIME 4 CURRENT STATUS 5 6 14 ALARM ON, LOCKOUT High Pressure-HT, High Pressure-CL, Low Pressure-HT, Low Pressure-CL, Condensate, Freeze Protect Previous cycle runtime Shows if emergency heat is on and if the user must touch the LCD before the system can restart SE 1 VALUE DIAGNOSIS TEMPERATURE FAULT Shows a potential cause of the problem “OUT” is displayed if a signal is not received from the temperature sensor GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER High Pressure Alarm The high pressure switch is located on the discharge line from the compressor. This switch will open above 600psi and reset at 450psi. If the system is operating in heating, it will stop and display HIGH PRESSURE-HT. If the system is operating in cooling, it will stop and display “HIGH-PRESSURE-CL”. The low pressure switch is located on the suction line from the compressor. This switch will open below 25psi and reset at 45psi. If the system is operating in Heating, it will stop and display LOW PRESSURE-HT. If the system is operating in cooling, it will stop and display “LOW-PRESSURE-CL”. Condensate Alarm O RV BS IC O E LE US TE E ON L The condensate float switch is located in the condensate pan. This switch will open when the drain pan is filled with water. Condensate alarms will always generate a LOCKOUT alarm to avoid overflow of the drain pan. Y Low Pressure Alarm Freeze Protect Warning The geo (source) water out temperature is monitored to ensure that the brine solution/water does not freeze. The temperature must be below this value for 60 seconds for the alarm to turn on. Once the temperature returns to above the freeze protection set point, the system will start again. Temperature Sensor – Out of Range If a temperature sensor is faulty, the display will show a “*” and “OUT” where the temperature is usually displayed. This indicates that the value for this sensor is not communicating with the control panel. Check the wiring or sensor for damage. Lockout SE Lockout occurs when the same alarm has occurred within a 2 hour time frame. A lockout requires the user to touch the display before the system can be restarted. Once a lockout has been reset, it will take 2 of the same alarm for lockout to occur again. GEO16-531.6 15 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Orb Diagnostics When an alarm occurs, the Orb tries to diagnose the problem based off of the temperature and airflow readings of the system. When the alarm occurs in a certain mode, the Orb checks set parameters consecutively until an error is found. COMBINED CHECK SEQUENCE ALARM HISTORY REFERENCE ALARM TEXT DISPLAY • • • 1 8 CHECK COMPRESSOR-TEST WINDINGS • • • 2 8 CHECK COMPRESSOR-OR ALARM WAS ON Geo (source) side temperature difference is below 2°F and Amp Draw is below 10. • 3 12 CHECK REVERSING-VALVE CONSTANT POWER Geo (source) water out temperature is greater than geo (source) water in, and return air temperature is greater than supply air temperature. • • HIGH PRESSURE • • COOLING HEATING LOW PRESSURE 4 4 CHECK AIRFLOW • 5 5 CHECK WATER FLOW-LOW FLOW The system was in hydronic heating. No other parameters have generated an error, hydronic (load) water flow is a potential problem. • 6 7 CHECK WIRING-AIRFLOW OK The system was in forced air heating. No other parameters have generated an error, wiring is a potential problem. • • • 1 11 CHECK REVERSING-VALVE NO POWER Geo (source) water in temperature is greater than geo (source) water out, and supply air temperature is greater than return air temperature. • • • 2 10 CHECK GEOFIELD-LOW WATER FLOW Geo (source) side temperature difference is greater than 12°F. • • • 3 13 CHECK R410A PRESS-CHECK WIRING • • • 1 14 CHECK R410A - POTENTIAL GAS LOSS Runtime below 30 seconds. • • • 2 15 CHECK FLC PUMP - LOW WATER FLOW Runtime between 30 and 120 seconds. • • • 3 6 CHECK GEOFIELD TEMP - COLD GEOFIELD Runtime above 120 seconds. • • 1A 11 CHECK REVERSING-VALVE NO POWER • • 2 4 CHECK AIRFLOW The cfm value is greater than zero, but less than 20% of the nominal value for stage 1, and less than 50 % of the nominal value for stage 2. • • 3 7 CHECK WIRING-AIRFLOW OK No other parameters have generated an error, wiring is a potential problem. 1B 5 CHECK WATER FLOW-LOW FLOW The system was in hydronic cooling. No other parameters have generated an error, hydronic (load) water flow is a potential problem. • CONDENSATE ALARM No other parameters have generated an error. High pressure switch or wiring is a potential problem. Geo (source) water in temperature is greater than Geo (source) water out, and supply air temperature is greater than return air temperature. • • • 1 10 CHECK GEOFIELD-LOW WATER FLOW Geo (source) side temperature difference is greater than 12°F. • • • 2 6 CHECK GEOFIELD TEMP-COLD GEOFIELD No other parameters have generated an error, loop field flow is a potential problem. COOLING • • • 1 9 CHECK FREEZE PROT-INCORRECT SETTING Freeze protection alarm should not occur during Cooling Mode HEATING • • 1 3 FAULTY CONDENSATE-OVERFLOW SWITCH Alarm should not occur during Heating Mode, the drain switch is most likely stuck COOLING • • 1 2 BLOCKED DRAIN HEATING • • • 1 1 CHECK WIRING More than 1 Alarm has occured, check wiring. COOLING • • • 1 1 CHECK WIRING More than 1 Alarm has occured, check wiring. SE FREEZE PROTECTION HEATING • Parameter is applicable to unit type. 16 The cfm value is greater than zero, but less than 20% of the nominal value for stage 1, and less than 50 % of the nominal value for stage 2. • COOLING MULTIPLE ALARMS Alarm occurs when runtime is less than 1 second. O RV BS IC O E LE US TE E ON L HEATING REASON FOR ALARM Y MODE WATER TO WATER ALARM FORCED AIR/ SPLIT Table 16.1 - Alarm Message Descriptions GEO16-531.6 The condensate drain is most likely blocked MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Menus (See Figure 17.1) The menus to the system provide access to all the various settings available on the system. Each menu either displays or allows access to edit that value. To navigate through the menus, use the “NEXT” button to cycle the blue highlighted option. This will then highlight the next menu option. To access the menu option that is highlighted press the “ACCEPT” button. To exit any menu highlight “>>RETURN”, then press the “ACCEPT” button. If a menu has no options to cycle through and no “>>RETURN”, press either the “NEXT” or “ACCEPT” button to return to the previous menu. The menus available for editing are based on the type of equipment. These menus are designed for a specific sequence of operations or specific conditioning modes for each type of equipment. Other types of equipment operations or modes will not be available. A forced air model will not have the ability to edit hydronic settings. SE O RV BS IC O E LE US TE E ON L Y Figure 17.1 - Menu Navigation GEO16-531.6 17 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Internal Setup (See Figure 18.1) The “INTERNAL SETUP” menu displays the current software version loaded onto the board and allows the user to update the clock. O RV BS IC O E LE US TE E ON L Y Figure 18.1 - Internal Setup Mechanical Setup (See Figure 18.2) The “MECHANICAL SETUP” menu allows for some of the parameters set on startup to be viewed or changed. To first enter the “MECHANICAL SETUP” menu, the installer must enter the correct password. If the incorrect password is used, the user is re-directed to the main operational screen for the equipment. The password is a 3 digit number that cannot be changed. Mechanical Setup Password: 724 When entering the password, the current password digit that is being edited is highlighted blue. When that value has been selected, the next value will be highlighted blue, and the previous value is highlighted red. To enter the password: • Change the first value with the Next button. • When the value reads the correct number, select the “ACCEPT” button, the number will go red and the next value will show blue. Once entered, the user can go in and out of the Mechanical Setup without re-entering the password until the screen times out. NOTE: When a change has occurred in the Mechanical Setup menu, the user must return to the system status screen for the change to take effect. SE Figure 18.2 - Mechanical Setup 18 GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Thermostat Signals (See Figure 19.1) The Thermostat Signals Menu will show the values for all the thermostat inputs (Main Zone) that are being monitored by the control panel. This menu is for display only. This is used to troubleshoot or verify the thermostat is sending the correct signals. System Monitoring (See Figure 19.2) The system monitoring menu saves data from the previous operating period for troubleshooting purposes. The electrical energy that is being consumed by the unit is estimated in kWh. This value is estimated by the amp draw from the system during operation (through a current sensor) and the voltage value entered by the installer during the commissioning process. The Delta T Geo Water and Delta T Air values display the change in temperature of the fluid or air across the respective heat exchanger. O RV BS IC O E LE US TE E ON L Y Figure 19.1 - Thermostat Signals Menu SE Figure 19.2 - System Monitoring Menu GEO16-531.6 19 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Alarms (See Figure 20.1) The Alarms Menu will show the values for all the alarms associated with the control panel. The status of the alarm is displayed along with the total time the alarm has been on. The History menu will display the previous 10 alarms that have occurred. SE O RV BS IC O E LE US TE E ON L Y Figure 20.1 - Alarms Menu 20 GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Run Timers (See Figure 21.1) The RUNTIMERS menu will show the amount of time each mechanical component has been on. These values are updated and recorded continuously by the control panel. It displays the time in the format of HH:MM:SS. These timers can be reset back to zero. The timers will reset to zero after 1,500,000 seconds. Tracking component usage over a known time frame can help troubleshoot incorrect settings or issues with the system. To reset the timers: • Highlight “RESET RUNTIMERS” blue with the Next button. • When highlighted, select the Accept button. • A second question confirms that the timers will be reset “RESET SETTINGS”. • If it is right, “RESET RUNTIMERS” is still highlighted blue, select the Accept button. • Run timers are set to 00:00:00. • “SETTINGS CHANGED” will appear. • Press any button to return to the main menu. SE O RV BS IC O E LE US TE E ON L Y Figure 21.1 - Run Timers Menu Navigation GEO16-531.6 21 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Forced Air (Forced Air and Split units only) (See Figure 22.1) The “FORCED AIR” menu shows and allows for changing of forced air unit specific startup parameters. See Startup on page 8 for detailed descriptions of each parameter. The status of all zone inputs, dehumidification and fan speed settings are shown. The zone timers menu shows the runtime for each individual zone if configured. (See Figure 22.2) The “TANK SETTINGS” menu shows and allows for changing of all the hydronic specific startup parameters. See Startup on page 8 for detailed descriptions of each parameter. All buffer tank set points, dead bands, and modes of operation are shown. When changing the operational mode or the type of buffer tank sensor, the user will have to press “>>RETURN” twice to get back to the system status screen. This is to prevent inadvertent editing of critical parameters that could affect the operation of the equipment during a menu change. O RV BS IC O E LE US TE E ON L Y Figure 22.1 - Forced Air Menu Navigation Tank Settings (Water to Water units only) SE Figure 22.2 - Tank Settings Menu Navigation 22 GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Combined (Combination units only) (See Figure 23.1) The “COMBINED” menu shows and allows for change for forced air and hydronic startup parameters. See Startup on page 8 for detailed descriptions of each parameter. All buffer tank set points, dead bands, modes of operation, and fan settings are shown. When changing the operational mode or the type of buffer tank sensor, the user will have to press “>>RETURN” twice to get back to the system status screen. This is to prevent inadvertent editing of critical parameters that could affect the operation of the equipment during a menu change. SE O RV BS IC O E LE US TE E ON L Y Figure 23.1 - Combination Menu Navigation GEO16-531.6 23 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER System Design O RV BS IC O E LE US TE E ON L The Orb controller is capable of controlling up to 4 forced air zones. Unit airflow and static pressure capabilities vary by unit type and size, refer to the Installation and Service (I&S) Manual for more information. Ductwork should be designed to allow each zone to handle at least 60% of the maximum unit airflow. If the smallest zone’s ductwork is not able to be sized to handle 60% of the unit airflow, a dump zone must be designed into the system. Modine recommends one of the following approaches to a dump zone in a residential application: 1. Use Attic or Crawl Space: If a well-insulated attic or crawl space is available, it must be included in the overall building load calculation. Return grilles must be located in the attic or crawlspace if this approach is used. 2. Use Minimum Position: If a well-insulated attic or crawl space is not available, the larger zone dampers must be set to stay open at a minimum position to compensate for the smaller zones. Bypass dampers are not recommended (barometric or powered) as they shorten the lifespan of the unit and can cause premature compressor failure. Components Required 1. Modine Controls System Orb Controller – Standard on Heat Pump 2. 24 Volt Zone Dampers (By Others) a. 4 Zone Dampers Maximum b. 40 VA Maximum Load for All Dampers 3. 24 Volt Heat Pump Zone Thermostats (By Others) a. Main Zone must be 4 Heat / 2 Cool b. Zone Stats must be 1 Heat / 1 Cool c. 3 Zone Thermostats Maximum, Plus Main Zone Thermostat d. All thermostats must be configured for Heat Pump Operation, per the manufacturer’s instructions A terminal block located in the control panel is included on forced air and combination units for easy field wiring of the zone connections. To make a connection in the terminal block, insert a small flat head screw driver into the square hole. Once the screw driver is inserted far enough a stripped wire can then be inserted in the round hole above it. Hold the wire in position while removing the screwdriver. Gently tug the wire to make sure the connection is tight. The Orb provides 2 damper outputs for each zone. For Zone 1 they are labeled “D1O” (damper 1 open), and “D1C” (Damper 1 closed). The Orb provides 24VAC to the “D1O” terminal to power the damper open, and 24VAC to the “D1C” terminal to power the damper closed. With the open and closed terminals, the dampers can be setup in 3 different ways: • Power Close / Spring Open (Recommended) • Power Open / Spring Close • Power Open / Power Close Y Forced Air Zoning Figure 24.1 - Zone Wiring Terminal Strip Table 24.1 - Zone Wiring Terminal Descriptions R LABEL DESCRIPTION 24VAC Z3O Zone 3: off heating, on cooling 24VAC Z4O Zone 4: off heating, on cooling Common D1O Damper 1 open Common D1C Damper 1 close Z2Y Zone 2 call for conditioning input D2O Damper 2 open Z3Y Zone 3 call for conditioning input D2C Damper 2 close R C C 24 DESCRIPTION SE LABEL Z4Y Zone 4 call for conditioning input D3O Damper 3 open Z2G Zone 2 call for fan only input D3C Damper 3 close Z3G Zone 3 call for fan only input D4O Damper 4 open Z4G Zone 4 call for fan only input D4C Damper 4 close Z2O Zone 2: off heating, on cooling GND Ground GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Sequence of Operation During commissioning, the installer enters the number of zones and the size of the zone, which is represented by a percentage of total unit airflow in CFM. (See startup items 16 through 20 for how to enter the zoning information to the Orb). These zone percentages do not control the speed of the fan. The speed of the fan is controlled by the compressor operating speed. Conditioning of zones operates on a first come first serve basis. If the unit is heating Zone 1 while Zone 2 calls for cooling, the unit will run in heating until the Zone 1 call is satisfied. Then the unit will delay for 5 minutes before starting in cooling mode to handle the Zone 2 call. Emergency Heat If the system is in Emergency Heat mode, only the Zone 1 thermostat can call for emergency heat. If the emergency heat is on, the zone dampers will open as needed. This will cause uneven heating of the zones to alert the homeowner as soon as possible that there is a problem. NOTE: The supply air temperature sensor is mounted below the electric heating element. The air temperature rise provided by the electric heat will not be captured on the system status display. Heating or Cooling O RV BS IC O E LE US TE E ON L Fan Only Y The compressor operating speed and airflow is based on the zones calling for heating or cooling and the percentage of airflow entered by the installer during the commissioning process. < 67% of total airflow called • 1st stage compressor operation • Low speed fan, 67% of full rated airflow delivered to zone(s) calling > 67% of total airflow called • 2nd stage compressor operation • High speed fan, 90% of full rated airflow delivered to zone(s) calling The Orb uses a common G terminal for all zone thermostats, if one zone calls for constant fan, all dampers will open and the fan will come on to 25% of total unit airflow. Zoning Example: SE A system with 4 zones is in standby (Zone 1 = 25%, Zone 2 = 25%, Zone 3 = 25%, Zone 4 = 25%). Zone 1 calls for heat. The compressor goes into 1st stage operation and 67% of the nominal airflow is delivered to Zone 1. While Zone 1 is being heated, Zone 2 calls for heat. The total percentage of the two zones is still less than 67%. Zone 2 damper opens while the compressor stays in 1st stage operation and 67% of the nominal airflow is delivered to both zones. Zone 3 calls for heat, so now the total percentage of airflow is above 67%. The unit goes into second stage operation, opens Zone 3 damper, and 90% of the nominal airflow is delivered to the 3 zones. Zone 4 calls for cooling. After all heating calls are satisfied, the compressor will go into a 5 minute delay then restart in cooling mode. GEO16-531.6 25 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER O RV BS IC O E LE US TE E ON L Y Figure 26.1 - Zone Screen Display Table 26.1 - Zone Screen Parameter Descriptions NAME 1 STATUS VALUE STAND BY, HEATING, COOLING, EMRG-HEAT, ALARM ON, LOCKOUT 2 STAGING MODE 3 1 Zone 1 status, black: STANDBY, red: HEATING, blue: COOLING, green: Fan Only, yellow: EMRG-HEAT 2 Zone 2 status, black: STANDBY, red: HEATING, blue: COOLING, green: Fan Only 3 Zone 3 status, black: STANDBY, red: HEATING, blue: COOLING, green: Fan Only 4 Zone 4 status, black: STANDBY, red: HEATING, blue: COOLING, green: Fan Only 4 5 SE 6 STAGE:1, STAGE:2, STAGE:3, STAGE:4, 26 GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Orb Control Board Hardware For all thermostat and buffer tank connections the Orb is outfitted with Wieland screw down connectors (see Figure 27.1). These connectors can be removed from the board for easier field wiring. Communication Ports (See Figure 27.2) USB Port Ethernet Port The RJ45 Ethernet jack is not used. Figure 27.3 - Real Time Clock Location On Display O RV BS IC O E LE US TE E ON L Figure 27.1 - Main Zone (Zone 1) Thermostat Connections (See Figures 27.3 & 27.4) The control panel uses a real time clock that can keep track of the current time. The clock is displayed at the top of the screen and also provides the day and month. To program the time for the control panel, connect a computer directly to the controller with an Ethernet cable and use a web browser to navigate to the IP address of the unit. The real time clock is used to determine conditioning cycles, run times and when alarms occurred. To ensure that the time is being kept, the control panel has a 3 volt lithium battery (CR2032) that provides power in the event of a power outage. To replace the battery, ensure all power is shut off to the unit and gently pry the battery out by hand. Y The USB mini port type B is used to connect a laptop computer to the Orb board. This port is used for field service programing. Time & Date – Real Time Clock Figure 27.4 - Battery for Real Time Clock on Orb Board SE Figure 27.2 - Communication Ports GEO16-531.6 27 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Fuses (See Figure 28.1) The control panel has 3 replaceable fuses on the board. Fuse kit 3H0387950000 includes 4 of each fuse and ships loose with each unit. The low voltage fuse is a 315mA replaceable fuse (Modine Part # 5H0836540000). This fuse is designed to protect the low level circuitry from damage. When this fuse blows, the board and the display will not power up (no green LEDs). When replacing a fuse, ensure all power is shut off to the equipment. The high voltage fuses are two 240V/10A slow blow fuses (Modine Part # 5H0836530000). These fuses are designed to protect the high voltage components that are connected to the control panel, which includes the flow center, blower motor, domestic hot water pump, and hydronic pump. These two fuses are housed in a black tower case. When replacing a fuse, ensure all power is shut off to the equipment. SE O RV BS IC O E LE US TE E ON L Y Figure 28.1 - Fuses on Orb Boards 28 GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Table 29.1 - Troubleshooting SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION Reset power. 2. Jumper in the “PROGRAM” position Move jumper to the “OPERATION” position. 3. Ribbon cable not connected properly or damaged Ensure ribbon cable connections are fully seated. Inspect ribbon cable for damage and replace if necessary. 1. Low voltage fuse blown Replace fuse. Assure correct power is connected to unit and secondary transformer voltage is not greater than 28 VAC. 2. Trace burnt between blue and silver cylinder Contact factory. 3. Transformer trip Reset transformer switch (White Rodgers transformer only). 1. Display not plugged in Connect control board to the display with the ribbon cable. 2. Bad ribbon cable Inspect cable for damage and replace. 3. Bad display Contact factory. 1. Screws holding LCD to plastic bezel too tight Loosen screws. 2. Display bad Contact factory. 1. Screws holding LCD to plastic bezel too tight Loosen screws. 2. Display bad Contact factory. Combined unit won’t stop calling for hydronic heat 1. Normally closed aquastats are to be used Replace aquastat for normally closed action or wire in a relay. Values changed in menus don’t change the system 1. Orb display has timed out due to inactivity Must select “>>RETURN” twice to get to the system status screen before changes are saved. Fan does not run when zones 2, 3, or 4 make a call 1. “G” terminal not connected Connect each zone “G” terminal to the zone 1 “G” terminal according to the wiring diagram. 1. Antifreeze type and percent set incorrectly Verify alcohol type in “MECHANICAL SETUP” menu. 2. Temperature sensor bad/ not connected Verify all temperature sensors are installed and accurate according to the resistance charts. 3. Low flow through source coil Verify correct flow through the coil. 1. Improper thermostat Install thermostat that supports 4 stages of heat. 2. Improper thermostat wiring Verify thermostat connections to the control board. 3. AUX heat control harness not connected Connect Aux heat control harness according to wiring diagram. Display screen is all white O RV BS IC O E LE US TE E ON L No power to board, green light on board not on Y 1. Power needs to be reset No power to display, green light on display not on Display Buttons are too sensitive Display Buttons don’t respond Freeze protect alarm SE Aux heat won’t come on GEO16-531.6 29 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER °F RESISTANCE Ω °F RESISTANCE Ω -11.2 97490 57.2 15790 -9.4 92430 59 15130 -7.6 87660 60.8 14500 -5.8 83160 62.6 13900 -4 78910 64.4 13330 -2.2 74910 66.2 12790 -0.4 71130 68 12260 1.4 67570 69.8 11770 3.2 64200 71.6 11290 10.4 12.2 14 15.8 17.6 19.4 21.2 23 24.8 26.6 28.4 30.2 32 33.8 35.6 37.4 39.2 41 42.8 44.6 10840 10410 55170 77 10000 52480 78.8 9605 49940 80.6 9227 47540 82.4 8867 45270 84.2 8523 43110 86 8194 41070 87.8 7880 39140 89.6 7579 37310 91.4 7291 35570 93.2 7016 33930 95 6752 32370 96.8 6500 30890 98.6 6258 29490 100.4 6026 28150 102.2 5805 26890 104 5592 25690 105.8 5389 24550 107.6 5193 23460 109.4 5006 22430 111.2 4827 21450 113 4655 20520 114.8 4489 19630 116.6 4331 18790 118.4 4179 51.8 17980 120.2 4033 53.6 17220 122 3893 46.4 48.2 50 30 73.4 75.2 O RV BS IC O E LE US TE E ON L 8.6 61020 58012 SE 5 6.8 Y Table 30.1 - Type III 10k Thermistor Resistance vs. Temperature GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Table 31.1 - Service Parts MODINE PART# 5H0835950001 Orb Display 5H0835950002 Orb Ribbon Cable 5’ 5H0833070060 Orb Ribbon Cable 20’ 5H0833070240 Fuse Kit 3H0387950000 Low Voltage Fuse 315mA 5H0836540000 High Voltage Fuse 10A 5H0836530000 5H0835930000 3H0388160000 10K Outside Air Temperature Sensor 5H0835240000 SE O RV BS IC O E LE US TE E ON L Orb Backup Battery 10K Buffer Tank Temperature Sensor Y SERVICE PART Orb Control Board GEO16-531.6 31 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Appendix A: Orb Display Mounting Kit Instructions General Remove the front and right side access panels from the unit. The installer must determine where the Orb Display will be located. If the display will be mounted on top of the unit, remove the knock-out located in the top panel (see Figure 32.1 below). If the display will be mounted remotely, the installer has the choice of using either the knock-out located in the top panel or in the back panel. On GFH/EFH units, the only option is to exit the top panel. NOTE: The ribbon cable is 6 feet long. If the display is to be mounted remotely, the installer must ensure that the length of the ribbon cable will be adequate to reach the desired mounting location. If a longer cable is needed, see Table 33.1 for an accessory part number. SE O RV BS IC O E LE US TE E ON L Figure 32.1 - Knockout Locations Unit Location Y Modine Water to Water (GH/EH), Split Condensing Units (GS/ ES) and Horizontal Forced Air Units (GFH/EFH) are supplied with a mounting bracket assembly that allows the installer to mount the ORB LCD Display on top of the unit or remotely, such as, on a wall near the unit. All mounting hardware is provided. The units are built with knockouts that provide a location for the display ribbon cable to penetrate the casing. 32 GEO16-531.6 MODINE CONTROL SYSTEM MANUAL ORB CONTROLLER Bracket Orientation / Mounting Display If the bracket is to be mounted on a horizontal surface, the bracket orientation is shown in Figure 33.1. If the bracket is to be mounted on a vertical surface, the bracket orientation is shown in Figure 33.2. Secure the Orb display to the mounting bracket using the nylon screws provided in the kit. Do not over tighten the screws. Figure 33.1 - Horizontal Mounting Mount Bracket & Display If mounting remotely, secure to surface using hardware provided. If mounting to top of unit, position the mounting bracket over the top of the grommet. Rotate bracket to desired position and secure to top panel using self-tapping screws provided in kit. Connecting Ribbon Cable Remove control panel cover. Plug one end of ribbon cable into main PCB plug (see Figure 33.4). O RV BS IC O E LE US TE E ON L Y Figure 33.4 - Ribbon Cable Connection Figure 33.2 - Vertical Mounting Ribbon Cable Socket on PCB “LCD/TOUCHSCREEN”, P17 Take care not to cut, tear, crease or otherwise damage the ribbon cable. Route the ribbon cable through a bushing in the control panel. Install Ribbon Cable Grommet Install the grommet (provided in the kit) in the hole where the knockout was removed. Using a razor knife or similar tool, cut a single slit through the grommet per Figure 33.3. Figure 33.3 - Grommet If display is mounted on top of unit, route ribbon cable through grommet in top panel and plug ribbon cable into socket on back of display. Secure remaining ribbon cable inside of unit away from any discharge lines or sharp edges. For remote mounted displays, the ribbon cable may be routed through the top panel or back panel of the unit, depending on which knockout was chosen by the installer. Run ribbon cable to display and plug ribbon cable into socket on back of display. Secure ribbon cable ensuring it is protected from damage inside and outside of the unit. SE Table 33.1 - Orb Mounting Kit Replacement Parts GEO16-531.6 Item Modine Part Number Mounting Bracket 5H0832870000 Grommet, 1-½” 5H0836190003 Ribbon Cable, 20’ 5H0833070240 33 Y O RV BS IC O E LE US TE E ON L SE THIS PAGE INTENTIONALLY LEFT BLANK 34 GEO16-531.6 Y O RV BS IC O E LE US TE E ON L SE THIS PAGE INTENTIONALLY LEFT BLANK GEO16-531.6 35 (For Residential Warranty, see GEO16-510) Seller warrants its products to be free from defects in material and workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use of materials substituted under emergency conditions for materials normally employed. This warranty covers replacement of any parts furnished from the factory of Seller, but does not cover labor of any kind and materials not furnished by Seller, or any charges for any such labor or materials, whether such labor, materials or charges thereon are due to replacement of parts, adjustments, repairs, or any other work done. This warranty does not apply to any equipment which shall have been repaired or altered outside the factory of Seller in any way so as, in the judgment of Seller, to affect its stability, nor which has been subjected to misuse, negligence, or operating conditions in excess of those for which such equipment was designed. This warranty does not cover the effects of physical or chemical properties of water or steam or other liquids or gases used in the equipment. BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO BE FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP, AS LIMITED HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE, THERE ARE NO OTHER WARRANTIES, INCLUDING WARRANTY OF MERCHANTABILITY OR FITNESS FOR PURPOSE, WHICH EXTEND BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND SELLER AS OF THE DATE OF FINAL AGREEMENT. BUYER AGREES THAT IN NO EVENT WILL SELLER BE LIABLE FOR COSTS OF PROCESSING, LOST PROFITS, INJURY TO GOODWILL, OR ANY OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY KIND RESULTING FROM THE ORDER OR USE OF ITS PRODUCT, WHETHER ARISING FROM BREACH OF WARRANTY, NONCONFORMITY TO ORDERED SPECIFICATIONS, DELAY IN DELIVERY, OR ANY LOSS SUSTAINED BY THE BUYER. Component Applicable Models Heat Exchangers Gas-Fired Units These warranties are issued only to the original owner-user and cannot be transferred or assigned. No provision is made in these warranties for any labor allowance or field labor participation. Seller will not honor any expenses incurred in its behalf with regard to repairs to any of Seller’s products. No credit shall be issued for any defective part returned without proper written authorization (including, but not limited to, model number, serial number, date of failure, etc.) and freight prepaid. OPTIONAL SUPPLEMENTAL WARRANTY Provided a supplemental warranty has been purchased, Seller extends the warranty herein for an additional four (4) years on certain compressors. Provided a supplemental warranty has been purchased, Seller extends the warranty herein for an additional four (4) years or nine (9) years on certain heat exchangers. EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND SELLER’S CONTROL This warranty shall not be applicable to any of the following items: refrigerant gas, belts, filters, fuses and other items consumed or worn out by normal wear and tear or conditions beyond Seller’s control, including (without limitation as to generality) polluted or contaminated or foreign matter contained in the air or water utilized for heat exchanger (condenser) cooling or if the failure of the part is caused by improper air or water supply, or improper or incorrect sizing of power supply. O RV BS IC O E LE US TE E ON L This warranty is void if the input to the product exceeds the rated input as indicated on the product serial plate by more than 5% on gas-fired and oil-fired units, or if the product in the judgment of SELLER has been installed in a corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected to misuse, negligence, accident, excessive thermal shock, excessive humidity, physical damage, impact, abrasion, unauthorized alterations, or operation contrary to SELLER’S printed instructions, or if the serial number has been altered, defaced or removed. BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY COMPONENT WHICH SHALL, WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN AND UPON PRIOR WRITTEN APPROVAL, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER, BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR GAS-FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS, BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO TEN YEARS FROM DATE OF SHIPMENT FROM SELLER. Y commercial Warranty Heat Exchangers Low Intensity Infrared Units Compressors Condensing Units for Cassettes Burners Low Intensity Infrared Units Other Components excluding Heat Exchangers, Coils, Condensers, Burners, Sheet Metal SE Heat Exchangers/Coils Indoor and Outdoor Duct Furnaces and System Units, Steam/Hot Water Units, Oil-Fired Units, Electric Units, Cassettes, Vertical Unit Ventilators, Geothermal Units Compressors Vertical Unit Ventilators, Geothermal Units “APPLICABLE WARRANTY PERIOD” TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST Burners High Intensity Infrared Units Sheet Metal Parts All Products As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice. © Modine Manufacturing Company 2015 Modine Manufacturing Company 1500 DeKoven Avenue Racine, WI 53403 Phone: 1.877.679.4436 (4GEO) www.modinehvac.com
© Copyright 2026 Paperzz