GEO16-531.6

GEO16-531.6
5H0839220000
March, 2015
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
MODINE CONTROL SYSTEM MANUAL
Orb Controller
geothermal systems
Table of Contents
!
WARNING
1. Improper installation, adjustment, alteration,
service or maintenance can cause property
damage, injury or death. Read the installation,
operating and maintenance instructions
thoroughly before installing or servicing this
equipment.
2. Improper control adjustments and manual
mode control can cause property damage,
injury or death. Read the installation, operating
and maintenance instructions thoroughly before
making adjustments.
3. Disconnect power supply before installing
accessories to prevent the unit from operating
during installation.
SE
IMPORTANT
1. The use of this manual is specifically intended
for a qualified installation and service agency.
All installation and service of this unit must be
performed by a qualified installation and service
agency.
2. These instructions must also be used in
conjunction with the Installation and Service
Manual originally shipped with the appliance, in
addition to any other accompanying component
supplier literature.
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Orb Controller Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Connections and Field Wiring . . . . . . . . . . . . . . . . . . . . . . .4
Orb Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Startup Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Forced Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Water to Water. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Orb Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Internal Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Mechanical Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Thermostat Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
System Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Run Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Forced Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Tank Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Combination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Forced Air Zoning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Control Board Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Real Time Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Orb Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Appendix A - Orb Display Mounting Kit. . . . . . . . . . . . . . . . . . .32
Commercial Warranty. . . . . . . . . . . . . . . . . . . . . . . . Back Cover
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Model Nomenclature
2
MT
3
UC
4,5,6
MBH
7
DS
8
CC
9,10
PC
DIGIT 1 - UNIT APPLICATION (UA)
G - RESIDENTIAL
E - COMMERCIAL
DIGIT 2 - MODEL TYPE (MT)
DIGIT 3 - UNIT CONFIGURATION (UC)
V - VERTICAL (COMBINATION, FORCED AIR, AND AIR
HANDLER)
H - HORIZONTAL (FORCED AIR AND AIR HANDLER)
R - REVERSIBLE (WATER TO WATER)
W - NON REVERSIBLE (WATER TO WATER)
I - INDOOR SPLIT CONDENSING UNIT
DIGITS 4, 5, 6 - NOMINAL CAPACITY (MBH)
018
024
036
048
060
066
096
120
132
14
HM
15
HWG
16
MT
17
SA
3 - ORB
DIGIT 12 - AIR COIL (AC)
N - NONE
R - R410A
DIGIT 13 - GEO (SOURCE) COIL MATERIAL (GM)
X - NONE
C - COPPER
N - CUPRO NICKEL
DIGIT 14 - HYDRONIC (LOAD) COIL MATERIAL (HM)
X - NONE
C - COPPER
N - CUPRO NICKEL
DIGIT 15 - DESUPERHEATER (HWG)
0 - NONE
1 - HOT WATER GENERATOR
DIGIT 17 - SUPPLY AIR CONFIGURATION (SA)
SE
0 - NONE
1 - SINGLE STAGE
2 - TWO STAGE
3 - SINGLE STAGE WITH SOFT START
4 - TWO STAGE WITH SOFT START
18
RA
DIGIT 11 - CONTROLLER TYPE (CT)
N - NONE
E - ECM
DIGIT 8 - COMPRESSOR CONFIGURATION (CC)
N - NONE
T - TOP (VERTICAL)
B - BOTTOM (VERTICAL)
S - SIDE (HORIZONTAL)
E - END (HORIZONTAL)
DIGIT 18 - RETURN AIR CONFIGURATION (RA)
N - NONE
L - LEFT
R - RIGHT
B - BOTTOM
DIGITS 9, 10 - POWER CODE (PC)
02 - 208V/60Hz/1ph
03 - 208-230V/60Hz/1ph
04 - 208V/60Hz/3ph
05 - 208-230V/60Hz/3ph
2
13
GM
DIGIT 16 - MOTOR TYPE (MT)
DIGIT 7 - DESIGN SEQUENCE (DS)
C
12
AC
O
RV BS
IC O
E LE
US TE
E
ON
L
F - FORCED AIR UNIT
H - WATER TO WATER UNIT
A - AIR HANDLER UNIT
C - COMBINATION UNIT
S - SPLIT CONDENSING UNIT
11
CT
Y
1
UA
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Orb Controller Overview
• Simple Interface
- Easy to understand menus and settings
• Temperature Display
- Real time display of water and air temperatures
• Simple Troubleshooting
- All alarms are displayed in full text
- A snapshot of temperature values is saved when an
alarm comes on
• Zone Control
- Control up to 4 forced air zones is standard
The Modine Controls System Orb Controller is a combination
of a control board located inside the equipment and the
touchscreen display. The display location is based on the type
of equipment that is installed. The touchscreen is an intuitive
device that allows the user to interact with the system.
Some of the features of the Orb Controller include:
• LCD Display
- Full color 320 x 240 pixel touchscreen
• Quick Startup
- Performed solely from the display
Y
Orb Control Board Connector Layout
O
RV BS
IC O
E LE
US TE
E
ON
L
Figure 3.1 - Orb Control Board Revision D Connector Layout
P7 P6
P15B
P16
P15A
P20
P17
P26
P2
P27
ORB
CONTROL
BOARD
ETHERNET
JACK
24V OUTPUTS
USB
P14
24V POWER SUPPLY
P25
P13
P24
P9
P23
P10 P11 P12
240V INPUTS/ OUTPUTS
Table 3.1 - Orb Board Connection Descriptions
REFERENCE
24V POWER SUPPLY
REFERENCE
240V INPUTS/
OUTPUTS
DESCRIPTION
P15A
Zone 1 Thermostat Connections A
24V outputs: Compressor Contactor &
Reversing Valve
P15B
Zone 1 Thermostat Connections B
SE
24V OUTPUTS
DESCRIPTION
24V Power input from transformer
240V Section of Board: FLC Pump, Fan,
DHW & HYD Pump
P16
Zone Control Connector
P17
LCD/ Touchscreen Connector
P2
ECM Control Connection
P20
AUX Heat Control Connector
P6
Hydronic Buffer Tank Cold Sensor Input
P7
P23
High Pressure Switch Connector
Hydronic Buffer Tank Hot Sensor Input
P9
AUX OUT 2
P24
Low Pressure Switch Connector
P10
AUX OUT 1
P25
Condensate Switch Connector
P11
AUX IN 1
P26
Sensor Block A
P12
AUX IN 2
P27
Sensor Block B
P13
AUX OUT 3
P14
AUX OUT 4
GEO16-531.6
3
8
MODINE
CONTROL
SYSTEM
MANUAL
11
12
13
ORB CONTROLLER
Connections/Field Wiring
Thermostat/Temperature Sensor Connections
Figure 4.1 - Thermostat Wiring Connection on
ORB Board
W2/E
DHM
R
W1
G
R
C
Y2
Y1
The following thermostats have been tested and are
recommended for use with the Orb controller:
• Honeywell Prestige (YTHX9421R5051)
• Emerson Blue (1F95-1291)
• Emerson Blue (1F98EZ-1421)
• Emerson Inspire (1HDEZ-1521)
NOTE: The NEST thermostat is incompatible with the
Orb controller.
O
L
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
THERMOSTAT CONNECTIONS
Table 4.1 - Thermostat Connections
SYSTEM
FORCED AIR UNIT:
SINGLE STAGE
THERMOSTAT CONNECTIONS
DHM
W2/E
W1
C
R
R
G
Y1
Y2
L
O
De-hum
Common 24 VAC 24 VAC Fan Compressor
Stage 1
FORCED AIR AND SPLIT UNIT:
2 STAGE
De-hum
Compressor Thermostat Cooling
Common 24 VAC 24 VAC Fan Compressor
Stage 1
Stage 2
Alarm
FORCED AIR AND SPLIT UNIT:
W/ 5KW ELECTRIC HEAT
De-hum
Electric
Heat
Stage 3
(5KW)
Compressor Thermostat Cooling
Common 24 VAC 24 VAC Fan Compressor
Stage 1
Stage 2
Alarm
FORCED AIR AND SPLIT UNIT:
W/ 10KW ELECTRIC HEAT
De-hum
Electric
Heat
Stage 4
(5KW)
Electric
Heat
Compressor Compressor Thermostat Cooling
Stage 3 Common 24 VAC 24 VAC Fan
Stage 1
Stage 2
Alarm
(5KW)
FORCED AIR AND SPLIT UNIT:
W/ 15KW ELECTRIC HEAT
De-hum
Electric
Heat
Stage 4
(10KW)
Electric
Heat
Compressor Compressor Thermostat Cooling
Stage 3 Common 24 VAC 24 VAC Fan
Stage 1
Stage 2
Alarm
(5KW)
FORCED AIR AND SPLIT UNIT:
W/ 20KW ELECTRIC HEAT
De-hum
Electric
Heat
Stage 4
(10KW)
Electric
Compressor Compressor Thermostat Cooling
Heat
Stage 3 Common 24 VAC 24 VAC Fan
Stage 1
Stage 2
Alarm
(10KW)
HYDRONIC USING AN
AQUASTAT
Common 24 VAC 24 VAC
AUX AN
IN 1
AUX AN
IN 2
AUX IN 1
Thermostat Cooling
Alarm
Aquastat
Input
Stage 1
Cooling
Hot Tank Cool Tank
Sensor
Sensor
Input
Input
HYDRONIC USING 10K
THERMISTORS
STACKED HYDRONIC USING
AN AQUASTAT
Common 24 VAC 24 VAC
Aquastat
Input
Stage 1
Aquastat
Input
Stage 2*
Cooling
Hot Tank Cool Tank
Sensor
Sensor
Input
Input
STACKED HYDRONIC USING
10K THERMISTORS
De-hum
Compressor Thermostat Cooling
Common 24 VAC 24 VAC Fan Compressor
Stage 1
Stage 2
Alarm
COMBINED USING 10K
THERMISTORS
De-hum
Compressor Thermostat Cooling
Common 24 VAC 24 VAC Fan Compressor
Stage 1
Stage 2
Alarm
SE
COMBINED USING AN
AQUASTAT
Aquastat
Input
Stage 1*
Hot Tank
Sensor
Input
NOTE 1: For combined units with electric heat, use the same electric heat connections as a forced air unit.
NOTE 2: For stacked hydronic units using an aquastat, connecting Y2 is optional. A Y2 call will interrupt the lead lag timer and step into stage 2 conditioning.
NOTE 3: For combined units usings and aquastat, "AUX IN 1" is a dry contact that is reverse acting. A call for heat is generated when the contact is open.
NOTE 4: If the DHM terminal is energized during a cooling call, the fan speed slows to -10% from nominal value (Y1 - 57%, Y2 - 80%).
4
GEO16-531.6
AUX
OUT 4
3rd Stage
Boiler
Output
3rd Stage
Boiler
Output
3rd Stage
Boiler
Output
3rd Stage
Boiler
Output
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Return & Supply Air Sensors
(Forced Air, Combination, and Air Handlers Power Code 03
Only)
Air Handlers: The return and supply air sensors are
factory installed.
Forced Air and Combination: The supply air sensor is
factory installed and the return air sensor is factory wired,
field mounted.
10K Buffer Tank Temperature Sensors
Outside Air Temperature Sensor
O
RV BS
IC O
E LE
US TE
E
ON
L
(Optional for Water to Water Units)
An outside air temperature sensor is optional for hydronic units
(Modine Part # 5H0835240000). The sensor should be mounted
on an outside north facing wall, under the eaves which will
provide protection from direct sunlight. It is mounted by
extending a threaded end of the ½" conduit used for wiring
through the building wall so that it protrudes at least 1" from the
wall face. The sensor can be threaded directly onto the conduit
until the unit is tight and pointing towards the ground. Remove
access cover, feed wires through and connect. Orange wire
leads are provided on the Orb board for easy field connections.
Y
(Optional for Water to Water and Combination Units)
10K sensors are recommended to control buffer tank
temperature (Modine Part # 3H0388160000). These sensors
are field wired. See wiring diagram for more detail.
Figure 5.1 – Typical Outside Air Temperature Sensor
Installation
SE
North
OAT
Temperature
Sensor
GEO16-531.6
5
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Orb Display
The touchscreen LCD Display is the user interface to the
system. During operation, the screen will display various
temperatures, operation modes, menus and alarms.
The housing for the display has a green LED power light.
This light shows the user there is power to the display and the
equipment.
For hydronic, horizontal forced air, and split systems, the
display is shipped loose with a mounting bracket and must be
connected to the Orb control board. The bracket/display can
be fastened to the top of the unit using provided self-tapping
sheet metal screws or to a nearby wall using provided drywall
anchors. The supplied ribbon cable must be connected to the
back of the display and the control board (see “P17” in
Figure 3.1 or refer to Appendix A for more information).
When using the system, the display shows various buttons.
To push a button, use a quick, firm tap in the general location
of that button on the screen. Only during Calibration and
accepting all start-up values does the user need to press
and hold on the screen.
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 6.1 - Orb Display Layout
Table 6.1 - Orb Display Button Descriptions
FUNCTION
DESCRIPTION
SE
BUTTON
ACCEPT
6
Pressing ACCEPT will take the user to the next menu item. Or confirm a selection.
NEXT
Pressing NEXT will cycle through a menu, change a setting, or increase or decrease a set-point.
MENU
Pressing MENU will provide access to all menus that are available for the unit. (Operation only)
BACK
Pressing BACK will return the user to the previous menu item. (Startup only)
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Start-Up Guide
Default Settings
Forced Air and Split units are pre-programed from the factory
for easier installation. If any installation parameters differ from
the default settings, the user should enter the "MECHANICAL
SETUP" or "FORCED AIR" menu items to
make changes. See Table 7.1 for more detail for each
parameter.
Water to Water and Combined units are NOT pre-programmed
from the factory and will need to be configured on startup.
Table 7.1 - Forced Air and Split Systems Default Startup Settings
FACTORY SETTING
VALUES/ RANGE
Calibrated
NA
Hour
Current Hour
0 - 23
Minute
Current Minute
0 - 59
Day
Current Day
1 - 31
Month
Current Month
JAN, FEB, MAR, APR, MAY, JUN, JUL, AUG, SEP, OCT, NOV, DEC
Year
Current Year
2015 - 2038
Model Type
Forced Air
Forced Air, Water to Water Non-Reversing, Water to Water Reversing, & Combined
Model Size
Model Digits 4,5,6
018, 024, 036, 048, 060, 066
Fan G
0%
-5% - +15%
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
PARAMETER
Display Calibration
Fan Low
0%
-5% - +5%
Fan High
0%
-5% - +5%
Scale Range
Fahrenheit
°F, °C
Freeze Protection
Water (36°F)
Water, Methanol, Ethanol, Propylene Glycol
Flow Center Control
Master
Master, Slave
Domestic Hot Water Pump
OFF
Off, On
Compressor Type
Name Plate
Single, Dual
Voltage
230
197 - 253
Zoning
OFF
Off, On
Start-Up
Water and Combined units are not pre-programmed from
the factory and will require the user to complete the startup
sequence. Prior to the startup sequence, the user will have to
calibrate the touchscreen. Press and hold down firmly on the
screen where the circle is located for 3-5 seconds. When the
circle moves to a new position, press and hold firmly at the new
location. If calibration is done improperly the Orb will not accept
the values and return to the first calibration screen.
SE
Figure 7.1 - Screen Calibration Procedure
GEO16-531.6
7
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
FORCED AIR
WATER TO WATER
REVERSING
WATER TO WATER
NON-REVERSING
COMBINED
NAME
1
2
3
•
•
•
•
•
•
•
•
•
•
•
•
HOUR
MINUTE
DAY
4
•
•
•
•
MONTH
5
•
•
•
•
YEAR
6
•
•
•
•
MODEL
7
•
•
•
•
MODEL SIZE
•
•
•
•
•
•
•
•
•
•
9
10
11
12
13
•
•
•
•
14
•
•
•
•
15
16
17
18
19
20
21
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
22
•
•
23
24
25
•
•
•
•
•
•
26
•
27
•
•
•
28
29
•
30
•
31
•
-10% - +28%
-10% - +10%
-10% - +10%
°F, °C
WATER, METHANOL,
ALCOHOL
ETHANOL, P_
GLYCOL
PERCENTAGE
10 - 38
FLC
MASTER, SLAVE
DHW PUMP
OFF, ON
DHW SETPT
110 - 140
COMPRSR
SINGLE, DUAL
VOLTAGE
197 - 263
ZONING
OFF, ON
Select the number of flow centers wired to a stacked hydronic unit.
Increase or decreases airflow during a fan only call.
Increase or decreases airflow when the compressor is in low stage.
Increase or decreases airflow when the compressor is in high stage.
Selects the temperature scale of user preference.
Selects the anti-freeze solution in the ground loop.
Selects the percentage of the alcohol solution in the ground loop, (not available if 14 is WATER).
Select flow center pump control for the unit.
Select if domestic hot water is enabled or disabled, (Plumb and fill desuperheater coil with water before enabling pump).
Select domestic hot water tank setpoint ranging 110°F - 140°F (not available if 17 is OFF).
Select depending if compressor is a single or two stage.
Select incoming line voltage to the unit.
Select if zoning is enabled.
ZONES
2, 3, 4
Select the number of zones in the system, (not available if 21 is OFF).
ZONE 2 CFM
ZONE 3 CFM
ZONE 4 CFM
HYD THIRD
STG
20 - 80
20 - 80
20 - 80
Select the percentage of airflow required for zone 2, (not available if 21 is OFF).
Select the percentage of airflow required for zone 3, (not available if 21 is OFF).
Select the percentage of airflow required for zone 4, (not available if 21 is OFF).
SENSOR
RELAY
OFF, 10 - 45
AQUASTAT, 10K
THERM
MAKE, BREAK
OFF, ON
Select the amount of time the unit runs before the 3rd stage output turns on.
Select if the the buffer tank sensor is a aquastat or a 10K thermistor.
Select if the Aquastat connected to the ORB is normally open or normally closed, (only available if 27 is AQUASTAT).
Select if an outside air temperature sensor is being used, (only available if 27 is 10K THERM).
OAT HT MIN
35 - 70
OAT HT MAX
⁻30 - 32
COOL TANK MIN
COOL TANK
MAX
40 - 55
Select the heating buffer tank minimum setpoint ranging 75°F - 95°F (only available if 29 is ON).
Select the heating buffer tank maximum setpoint ranging 100°F - 130°F (only available if 29 is ON).
Select the outside air temperature when the heating buffer tank will be at minimum setpoint ranging 35°F - 70°F
(only available if 29 is ON).
Select the outside air temperature when the heating buffer tank will be at maximum setpoint ranging ⁻30°F - 32°F
(only available if 29 is ON).
Select the cooling buffer tank minimum setpoint ranging 40°F - 55°F (only available if 29 is ON).
60 - 70
Select the cooling buffer tank maximum setpoint ranging 60°F - 70°F (only available if 29 is ON).
•
OAT CL MIN
60 - 75
•
OAT CL MAX
85 - 110
•
TANK
DEADBAND
5 - 15
CHANGE TEMP
55 - 85
•
MODE
HEAT
SETPOINT
COOL
SETPOINT
SE
•
•
•
42
•
43
•
44
45
•
SINGLE, DUAL
75 - 95
100 - 130
•
•
•
•
•
FAN G
FAN LOW
FAN HIGH
SCALE RANGE
HOT TANK MIN
HOT TANK MAX
36
•
Selects the amount of time the lead unit runs before the lag unit turns on, ranging 5 to 30 minutes, (only available
if 7 is 096, 120, 132, or 360).
Select the cooling buffer tank setpoint ranging 30°F - 60°F (only available if 29 is OFF, or 30 is CHANGEOVER).
•
•
Select the unit size according to the serial plate.
30 - 60
•
41
Selects the unit type: Forced Air, Water to Water Non-Reversing, Water to Water Reversing, & Combined.
Select the heating buffer tank setpoint ranging 80°F - 125°F (only available if 29 is OFF, or 30 is CHANGEOVER).
35
40
Select the current year.
80 - 125
•
•
•
39
Select the current month.
Select the initial operation mode of the unit. (CHANGEOVER only available on reversing hydronic units with 29 ON).
•
•
38
5 - 30
Select current hour in 24 hour format.
Select current minute.
Select the current day of the month.
HEAT, COOL, AUTO,
CHANGEOVER, OFF
•
•
37
FLC CNTRL
OAT
•
33
34
46
•
•
32
8
LAG
TIMER(MIN)
0 - 23
0 - 59
1 - 31
JAN, FEB, MAR, APR,
MAY, JUN, JUL, AUG,
SEP, OCT, NOV, DEC
2015 - 2038
FORCEDAIR,
W2WNONRV,
W2WREV, COMBINED
018, 024, 036, 048,
060, 066, 096, 120,
132, 144, 180, 360
DESCRIPTION
O
RV BS
IC O
E LE
US TE
E
ON
L
8
VALUES/ RANGE
Y
REFERENCE
NUMBER
Table 8.1 - Orb Parameters by Unit Type
•
•
DEADBAND
2 - 12
PRIORITY
POOL MODE
HOLD ACCEPTSTART
AIR, HYDRONIC
OFF, ON
Parameter is applicable to unit type.
NA
Select the outside air temperature when the cooling buffer tank will be at maximum setpoint ranging 60°F - 75°F
(only available if 29 is ON).
Select the outside air temperature when the cooling buffer tank will be at minimum setpoint ranging 85°F - 110°F
(only available if 29 is ON).
Select the buffer tank deadband ranging 5°F - 15°F (not available if 27 if AQUASTAT).
Select the outside air temperature that a single buffer tank system changes between heating and cooling ranging
55°F - 85°F (only available if 30 is CHANGEOVER).
Select the outside air temperature deadband for the change over ranging 2°F - 12°F (only available if 30 is
CHANGEOVER).
Select the priority heating system.
Select if pool mode is enabled to allow hydronic heating in forced air cooling mode.
Hold down the ACCEPT button to accept all startup values.
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
1, 2, 3, 4, 5. HOUR, MINUTE, DAY, MONTH, YEAR –
Select the current time for the clock.
Figure 9.1 - Orb Master / Slave Flow Center Wiring
6. MODEL – Select the type of heat pump equipment installed.
See digits 1, 2, & 3 of the model number located on the
serial plate.
• Forced Air – GFV, GFH, EFV, EFH, GSI, ESI
• Combined – GCV, ECV
• Hydronic Reversible – GHR, EHR
• Hydronic Non-Reversible – GHW, EHW
7. MODEL SIZE – Select the size or tonnage of the unit. See
digits 4, 5, & 6 of the model number located on the serial
plate.
O
RV BS
IC O
E LE
US TE
E
ON
L
9. FLC CNTRL - For stacked hydronic units, one or two flow
centers may be used. For one flow center, wire the pump
to the top unit terminals and select “SINGLE”. For two flow
centers, wire each pump to the respective unit terminals
and select “DUAL”.
18. DHW SETPT – In order to assure the domestic hot water
pump runs as much as possible it should be set at, or above
the hot water heater set point. The Orb uses a 10°F static
dead band below the set point to prevent the pump from
short cycling. The location of the temperature sensor is on
the return DHW line inside the heat pump.
Y
8. LAG TIMER (MIN) – The Lead Lag Timer is used for
stacked hydronic units only. This timer is used to start the
second stage of the system if the set point cannot be met
in that period of time. The timer can be set from 5 to 30
minutes.
10. FAN G – This allows for the adjustment of the fan when
operating in “G” signal. (Fan only). The factory setting is
33% of the nominal airflow. The installer can adjust the fan
setting -10% to +28% of the nominal airflow.
11. FAN LOW – This allows for the adjustment of the fan when
operating in “Y1” signal. (Compressor low stage). The
factory setting is 67% of the nominal airflow. The installer
can adjust the fan setting +/-10% of the nominal airflow.
12. FAN HIGH – This allows for the adjustment of the fan when
operating in “Y2” signal. (Compressor high stage). The
factory setting is 90% of the nominal airflow. The installer
can adjust the fan setting +/- 10% of the nominal airflow.
13. SCALE RANGE – Temperature readings during operation
are displayed in the selected Scale Range: Fahrenheit or
Celsius.
SE
14 & 15. ALCOHOL & PERCENTAGE – The alcohol
percentage is used to determine the freeze protection
temperature during operation. The installer selects the type
of alcohol and the percentage in the system, and then the
Orb calculates the freeze protection. If the application is an
open loop, the installer would select water and the freeze
protection would be set to 36°F.
• Water: Freeze protect 36°F
• Methanol: 10 - 25%
• Ethanol: 14 - 29%
• Propylene Glycol: 15 - 38%
16. FLC – The Orb controller has the ability to communicate
with another Orb unit for a two heat pump, single flow center
application. The heat pump to which the flow center is wired
is considered the “Master”, while the other is considered the
“Slave”. The “Slave” will send a signal to the “Master” when
the Flow Center is required to be on. When using flow center
master/slave control with a water to water unit, the water to
water unit must be configured as the master.
17. DHW PUMP – The domestic hot water pump is shipped
electronically off. If the pump is started prior to being
plumbed and filled with potable water, DAMAGE TO THE
UNIT WILL OCCUR.
19. COMPRSR – The Compressor setting selects either a
Single Stage Compressor or a Two Stage Compressor. To
determine if the unit is a single or two stage, refer to digit 8
of the model number located on the serial plate.
20. VOLTAGE – The incoming line voltage to the unit must be
input for accurate energy estimates. Measure across L1 and
L2 and input the value.
21, 22. ZONING, ZONES – If more than one forced air zone
is to be used, zoning must be enabled and the number
of zones input. (see “Zoning” on page 24 for more
information).
23, 24, 25. ZONE CFM – Enter the size of each zone which
is represented as a percentage of total unit airflow in cfm
(See “Zoning” on page 24 for more information).
26. HYD THIRD STG – A backup boiler can be connected to
the ORB through terminal "AUX OUT 4" on hydronic units.
The unit will run for the selected amount of time in minutes
(10 - 45) before the backup boiler is turned on. “AUX OUT 4”
(board location P14) is a normally open dry contact.
27. SENSOR – Select the type of control used for the hydronic
buffer tank. An Aquastat provides an ON/OFF signal to
the Orb controller, whereas the 10K Thermistor provides a
resistance to the Orb controller.
28. RELAY – When using an aquastat with a Combined unit, the
aquastat is connected through terminal "AUX IN 1". If the
aquastat is normally open, select "MAKE". If the aquastat is
normally closed, select "BREAK". “AUX IN 1” (board location
P11) is a dry contact.
29. OAT – An outside air temperature sensor can be used on
units with a hydronic buffer tank to achieve a variable set
point for the tank. On reversing water to water units using a
single buffer tank, the outside air sensor allows for automatic
changeover of the buffer tank from heating to cooling or vice
versa.
30. MODE – Conditioning Mode is used in Hydronic Reversible
& Combined applications. This allows the user to select the
initial type of conditioning that is desired. (See page 12 in
Operation on how to change mode after startup).
HEAT:
1 Tank System - The unit will maintain the tank
temperature for heating only.
GEO16-531.6
9
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Figure 10.2 - Cooling Mode Outside Air Temperature
Hydronic Setpoint
Y
The cooling tank set point is maintained at the COOL TANK
MAX until the outside air temperature increases to the OAT CL
MIN temperature. As the outside air temperature increases from
70°F to 100°F, the cooling tank set point decreases linearly. At
and above the OAT CL MAX, the tank is maintained at COOL
TANK MIN temperature.
41. TANK DEADBAND – The tank deadband sets the
differential for hydronic tanks that are controlled with 10K
thermistors.
Example: If a deadband of 10°F is selected with a
heating buffer tank set point of 100°F, the unit will
operate until the set point is reached. The unit will then
be in standby until the tank temperature drops below 90°F.
42, 43. CHANGE TEMP, DEADBAND – The changeover
point is the outside air temperature used to determine
whether the system should be heating or cooling.
This Temperature is used in conjunction with the Auto
Changeover Dead Band to prevent quick switching between
conditioning modes.
Example:
CHANGE TEMP: 70°F
DEADBAND: 10°F
If the unit is in heating mode, the outside air temperature
would have to increase to 80°F before the unit changes
the single tank from the heating set point to the cooling
set point. The outside air temperature would then have to
drop below 60°F for the tank to switch back to heating.
44. PRIORITY - Combination units allow the option to set the
priority heating system to either hydronic or forced air. The
priority heating system will override the secondary system if
both are calling for heat at the same time.
45. POOL MODE – Pool mode allows the system to do forced
air cooling and hydronic heating at the same time. The flow
center shuts down and heat is rejected through the hydronic
coil instead of into the loop field. Once the hydronic tank is
satisfied, the flow center will engage and the hydronic pump
will shut down until the forced air cooling call is satisfied.
46. HOLD ACCEPT TO START – Review all startup criteria
and hold down the ACCEPT button to complete the startup
process.
O
RV BS
IC O
E LE
US TE
E
ON
L
2 Tank System – The unit will maintain only the heating
tank.
COOL:
1 Tank System – The unit will maintain the tank
temperature for cooling only.
2 Tank System – The unit will maintain only the cooling
tank.
AUTO:
1 Tank System – Do not use.
2 Tank System – The unit will maintain both the heating
and cooling tanks at the same time.
CHANGEOVER:
1 Tank System – Based on outside air temperature, the
unit will maintain the tank for heating or cooling.
2 Tank System – Do not use.
OFF:
1 Tank System – The unit will not maintain the tank.
2 Tank System – The unit will not maintain either tank.
31. HEAT SETPOINT – If using 10K thermistors and no outside
air temperature sensor, select the fixed set point for the
heating tank.
32. COOL SETPOINT – If using 10K thermistors and no outside
air temperature sensor, select the fixed set point for the
cooling tank.
33, 34, 35, 36. HOT TANK MIN, HOT TANK MAX, OAT
HT MIN, OAT HT MAX – The Orb allows for a variable set
point of the hydronic buffer tank based on the outside air
temperature. Maintaining a lower heating tank set point
increases energy efficiency of the system.
Heating Example:
• HOT TANK MIN 80°F
• HOT TANK MAX 110°F
• OAT HT MIN
60°F
• OAT HT MAX
30°F
Figure 10.1 - Heating Mode Outside Air Temperature
Hydronic Setpoint
SE
The heating tank set point is maintained at the HOT TANK
MIN until the outside air temperature drops to the OAT HT MIN
temperature. As the outside air temperature drops from 60°F to
30°F, the heating tank set point increases linearly. At and below
the OAT HT MAX, the tank is maintained at HOT TANK MAX
temperature.
37, 38, 39, 40. COOL TANK MIN, COOL TANK MAX, OAT
CL MIN, OAT CL MAX – The Orb allows for a variable set
point of the hydronic buffer tank based on the outside air
temperature. Maintaining a higher cooling tank set point
increases energy efficiency of the system.
Cooling Example:
• COOL TANK MIN 30°F
• COOL TANK MAX 60°F
• OAT CL MIN 70°F
• OAT CL MAX 100°F
10
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Operation
The LCD Touchscreen display is the window to the system.
When in normal operating mode the screen displays
temperatures, conditioning mode, conditioning staging, time,
date and any specific setup information. The temperatures
displayed are from various points throughout the equipment.
This information can provide the temperature differential through
the heat exchanger in the system for troubleshooting.
The display will eventually power off when 100 seconds of
inactivity have occurred. Every time a button is pressed, this
resets the activity timer. If the screen is off, touch the display
and the screen will turn on again.
When the system has finished a run cycle, the compressor has
a 5 minute delay to allow the pressure in the system to equalize.
If a conditioning call occurs in this 5 minute window, the amount
of time in seconds is counted down in the conditioning area of
the display.
Forced Air
The Forced Air system works off of control signals from a
conventional thermostat. These signals determine the type of
conditioning and conditioning stage of the equipment.
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 11.1 - Forced Air Screen Display
Table 11.1 - Forced Air Screen Parameter Descriptions
NAME
1
2
3
4
STAND BY, HEATING, COOLING, EMRG-HEAT, ALARM ON, LOCKOUT
STAGE:1, STAGE:2, STAGE:3, STAGE:4,
CFM
Current CFM
GWO
Ground water out temperature
GWI
Ground water in temperature
SE
5
STATUS
STAGING MODE
VALUE
6
RETURN
7
SUPPLY
8
DHW
9
AMPS
10
CONDITIONING TIME
11
POWER CONSUMPTION
12
DHM
Return air temperature
Supply air temperature
Domestic hot water return temperature
Total amp draw for the unit
Start and stop time of current or most recent cycle
Total power consumption of last cycle (STANDBY mode only)
Shows if dehumidification is on (COOLING conditioning mode only)
GEO16-531.6
11
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Water to Water
To change the operation mode after startup go to:
• MENU
• TANK SETTING
• MODE
• Select either HEAT, COOL, AUTO, CHANGEOVER, or OFF
• >>RETURN
• >>RETURN - NOTE - The Orb controller will not change the
mode unless both RETURN items are selected.
With the 10K thermistor setting, the dead band and set point
is used to determine the temperature for starting the system.
For Heating, if the tank temperature is lower than the set point
minus the dead band the system will turn on. The reverse is
applicable for Cooling.
Stacked hydronic systems work from one control panel. The
staging for the system is based on a Lead system and a Lag
system. The Lead-Lag can either start based on a timer or
based on aquastat staging. The Lead-Lag system will be
switched every 24 hours to allow for balanced run times for the
equipment. Refer to the wiring diagram for wiring the aquastat
control signals for a Lead Lag system.
Y
The Hydronic system works with either buffer tank thermistors
or aquastats. The type of sensors dictates how the main display
screen appears.
The operating mode for the equipment will also determine
system operation. If the operating mode to set to “HEAT”
or “COOL”, the system will only heat or cool. If the system
is in “AUTO”, the mode that is first to call will receive the
conditioning. Once that conditioning mode is satisfied, if
the opposite mode is also calling, it will start after the 5
minute compressor delay. If the operating mode is set to
“CHANGEOVER”, the outside air temperature along with the
dead band will determine if the system is in heating or cooling.
“OFF” mode will disable operation.
O
RV BS
IC O
E LE
US TE
E
ON
L
Figure 12.1 - Hydronic Screen Display
Table 12.1 - Hydronic Screen Parameter Descriptions
2
3
4
5
6
7
MODE
GWO
GWI
T
B
8
AMPS
10
CL
9
11
HT
HEATING TANK STATUS
12
COOLING TANK STATUS
14
LEAD LAG DELAY
13
12
STATUS
STAGING MODE
VALUE
STAND BY, HEATING, COOLING, ALARM ON, LOCKOUT
STAGE:1, STAGE:2
HEAT, COOL, AUTO, CHANGEOVER, OFF
SE
1
NAME
OAT
Ground water out temperature
Ground water in temperature
Top unit status, black: STANDBY, red: HEATING, blue: COOLING (Stacked units only)
Bottom unit status, black: STANDBY, red: HEATING, blue: COOLING (Stacked units only)
Total amp draw for the unit
Heating tank setpoint (Optional 10K thermistors only)
Cooling tank setpoint (Optional 10K thermistors only)
Heating tank temperature (optional 10K thermistors only), or Aquastat status (Aquastat only)
Cooling tank temperature (optional 10K thermistors only), or Aquastat status (Aquastat only)
Outside air temperature (Optional outside air sensor only)
Time in seconds until the lag unit turns on (Stacked units only)
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Combination Units
A combination unit will show a combination of items from both
the forced air and hydronic system status screens.
The combination system has a heat priority that will determine if
the forced air or hydronic system should run if both are calling at
the same time.
The combination system has “Pool Mode”, or dual conditioning
mode functionality. In this mode, when the system is forced air
cooling, the heat can be rejected into the hydronic buffer tank
instead of into the loop field. The system needs to be calling
for cooling from the thermostat and calling for heating from the
buffer tank for the equipment to run in this mode.
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 13.1 - Combination Screen Display
Table 13.1 - Combination Screen Parameter Descriptions
NAME
1
2
3
4
STAGING MODE
STAND BY, HEATING, HEAT-HYD, COOLING, EMRG-HEAT, ALARM ON, LOCKOUT
STAGE:1, STAGE:2, STAGE:3, STAGE:4
MODE
HEAT, COOL, AUTO, CHANGEOVER, OFF, CFM
GWO
Ground water out temperature
GWI
Ground water in temperature
SE
5
STATUS
VALUE
6
RETURN
Return air temperature
7
SUPPLY
Supply air temperature
8
AMPS
Total amp draw for the unit
9
TANK
Heating tank temperature (optional 10K thermistors only), or Aquastat status (Aquastat only)
10
ST PNT
11
OAT
Heating tank setpoint (Optional 10K thermistors only)
Outside air temperature (Optional outside air sensor only)
GEO16-531.6
13
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Alarms
Alarms are used to monitor various points of the equipment
and prevent the equipment damage. There are 4 types of
alarms associated with the equipment, “High Pressure”, “Low
Pressure”, “Condensate” and “Freeze Protection”. The system
can also perform a “Lockout”, which requires interaction from
the user to restart the system.
When an alarm occurs, the display will show the type of alarm
that has occurred. If the system is operating, the alarm will stop
the system and try to determine what caused the alarm. If the
system was not operating when an alarm occurs, the alarm will
still be displayed on the screen.
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 14.1 - Alarm Screen Display
When the system is in alarm mode, the display backlight will
stay powered and show a snapshot of the temperatures in the
system at the time the alarm occurred. The display will remain
in “snapshot” mode, and nothing will change until the display is
touched. This allows for quicker troubleshooting of the system.
When an operational alarm occurs the following is displayed:
• Alarm type
• Mode the alarm occurred
• Time and date alarm occurred
• Run time for the system
• Possible alarm information
• The exact temperatures when the system had the alarm
Table 14.1 - Alarm Screen Parameter Descriptions
NAME
STATUS
2
ALARM TYPE
3
RUNTIME
4
CURRENT STATUS
5
6
14
ALARM ON, LOCKOUT
High Pressure-HT, High Pressure-CL, Low Pressure-HT, Low Pressure-CL, Condensate, Freeze Protect
Previous cycle runtime
Shows if emergency heat is on and if the user must touch the LCD before the system can restart
SE
1
VALUE
DIAGNOSIS
TEMPERATURE FAULT
Shows a potential cause of the problem
“OUT” is displayed if a signal is not received from the temperature sensor
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
High Pressure Alarm
The high pressure switch is located on the discharge line from
the compressor. This switch will open above 600psi and reset
at 450psi. If the system is operating in heating, it will stop and
display HIGH PRESSURE-HT. If the system is operating in
cooling, it will stop and display “HIGH-PRESSURE-CL”.
The low pressure switch is located on the suction line from
the compressor. This switch will open below 25psi and reset
at 45psi. If the system is operating in Heating, it will stop and
display LOW PRESSURE-HT. If the system is operating in
cooling, it will stop and display “LOW-PRESSURE-CL”.
Condensate Alarm
O
RV BS
IC O
E LE
US TE
E
ON
L
The condensate float switch is located in the condensate pan.
This switch will open when the drain pan is filled with water.
Condensate alarms will always generate a LOCKOUT alarm to
avoid overflow of the drain pan.
Y
Low Pressure Alarm
Freeze Protect Warning
The geo (source) water out temperature is monitored to ensure
that the brine solution/water does not freeze. The temperature
must be below this value for 60 seconds for the alarm to turn on.
Once the temperature returns to above the freeze protection set
point, the system will start again.
Temperature Sensor – Out of Range
If a temperature sensor is faulty, the display will show a “*”
and “OUT” where the temperature is usually displayed. This
indicates that the value for this sensor is not communicating with
the control panel. Check the wiring or sensor for damage.
Lockout
SE
Lockout occurs when the same alarm has occurred within a 2
hour time frame. A lockout requires the user to touch the display
before the system can be restarted. Once a lockout has been
reset, it will take 2 of the same alarm for lockout to occur again.
GEO16-531.6
15
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Orb Diagnostics
When an alarm occurs, the Orb tries to diagnose the problem
based off of the temperature and airflow readings of the system.
When the alarm occurs in a certain mode, the Orb checks set
parameters consecutively until an error is found.
COMBINED
CHECK
SEQUENCE
ALARM
HISTORY
REFERENCE
ALARM TEXT DISPLAY
•
•
•
1
8
CHECK COMPRESSOR-TEST
WINDINGS
•
•
•
2
8
CHECK COMPRESSOR-OR ALARM
WAS ON
Geo (source) side temperature difference is below 2°F and Amp
Draw is below 10.
•
3
12
CHECK REVERSING-VALVE
CONSTANT POWER
Geo (source) water out temperature is greater than geo (source)
water in, and return air temperature is greater than supply air
temperature.
•
•
HIGH
PRESSURE
•
•
COOLING
HEATING
LOW
PRESSURE
4
4
CHECK AIRFLOW
•
5
5
CHECK WATER FLOW-LOW FLOW
The system was in hydronic heating. No other parameters have
generated an error, hydronic (load) water flow is a potential
problem.
•
6
7
CHECK WIRING-AIRFLOW OK
The system was in forced air heating. No other parameters have
generated an error, wiring is a potential problem.
•
•
•
1
11
CHECK REVERSING-VALVE NO
POWER
Geo (source) water in temperature is greater than geo (source)
water out, and supply air temperature is greater than return air
temperature.
•
•
•
2
10
CHECK GEOFIELD-LOW WATER
FLOW
Geo (source) side temperature difference is greater than 12°F.
•
•
•
3
13
CHECK R410A PRESS-CHECK
WIRING
•
•
•
1
14
CHECK R410A - POTENTIAL GAS
LOSS
Runtime below 30 seconds.
•
•
•
2
15
CHECK FLC PUMP - LOW WATER
FLOW
Runtime between 30 and 120 seconds.
•
•
•
3
6
CHECK GEOFIELD TEMP - COLD
GEOFIELD
Runtime above 120 seconds.
•
•
1A
11
CHECK REVERSING-VALVE NO
POWER
•
•
2
4
CHECK AIRFLOW
The cfm value is greater than zero, but less than 20% of the
nominal value for stage 1, and less than 50 % of the nominal value
for stage 2.
•
•
3
7
CHECK WIRING-AIRFLOW OK
No other parameters have generated an error, wiring is a potential
problem.
1B
5
CHECK WATER FLOW-LOW FLOW
The system was in hydronic cooling. No other parameters have
generated an error, hydronic (load) water flow is a potential
problem.
•
CONDENSATE
ALARM
No other parameters have generated an error. High pressure
switch or wiring is a potential problem.
Geo (source) water in temperature is greater than Geo (source)
water out, and supply air temperature is greater than return air
temperature.
•
•
•
1
10
CHECK GEOFIELD-LOW WATER
FLOW
Geo (source) side temperature difference is greater than 12°F.
•
•
•
2
6
CHECK GEOFIELD TEMP-COLD
GEOFIELD
No other parameters have generated an error, loop field flow is a
potential problem.
COOLING
•
•
•
1
9
CHECK FREEZE PROT-INCORRECT
SETTING
Freeze protection alarm should not occur during Cooling Mode
HEATING
•
•
1
3
FAULTY CONDENSATE-OVERFLOW
SWITCH
Alarm should not occur during Heating Mode, the drain switch is
most likely stuck
COOLING
•
•
1
2
BLOCKED DRAIN
HEATING
•
•
•
1
1
CHECK WIRING
More than 1 Alarm has occured, check wiring.
COOLING
•
•
•
1
1
CHECK WIRING
More than 1 Alarm has occured, check wiring.
SE
FREEZE
PROTECTION
HEATING
• Parameter is applicable to unit type.
16
The cfm value is greater than zero, but less than 20% of the
nominal value for stage 1, and less than 50 % of the nominal value
for stage 2.
•
COOLING
MULTIPLE
ALARMS
Alarm occurs when runtime is less than 1 second.
O
RV BS
IC O
E LE
US TE
E
ON
L
HEATING
REASON FOR ALARM
Y
MODE
WATER TO
WATER
ALARM
FORCED
AIR/ SPLIT
Table 16.1 - Alarm Message Descriptions
GEO16-531.6
The condensate drain is most likely blocked
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Menus (See Figure 17.1)
The menus to the system provide access to all the various
settings available on the system. Each menu either displays or
allows access to edit that value.
To navigate through the menus, use the “NEXT” button to cycle
the blue highlighted option. This will then highlight the next
menu option. To access the menu option that is highlighted
press the “ACCEPT” button.
To exit any menu highlight “>>RETURN”, then press the
“ACCEPT” button. If a menu has no options to cycle through
and no “>>RETURN”, press either the “NEXT” or “ACCEPT”
button to return to the previous menu.
The menus available for editing are based on the type of
equipment. These menus are designed for a specific sequence
of operations or specific conditioning modes for each type of
equipment. Other types of equipment operations or modes will
not be available. A forced air model will not have the ability to
edit hydronic settings.
SE
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 17.1 - Menu Navigation
GEO16-531.6
17
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Internal Setup (See Figure 18.1)
The “INTERNAL SETUP” menu displays the current software
version loaded onto the board and allows the user to update the
clock.
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 18.1 - Internal Setup
Mechanical Setup (See Figure 18.2)
The “MECHANICAL SETUP” menu allows for some of the
parameters set on startup to be viewed or changed. To first
enter the “MECHANICAL SETUP” menu, the installer must enter
the correct password. If the incorrect password is used, the user
is re-directed to the main operational screen for the equipment.
The password is a 3 digit number that cannot be changed.
Mechanical Setup Password: 724
When entering the password, the current password digit that
is being edited is highlighted blue. When that value has been
selected, the next value will be highlighted blue, and the
previous value is highlighted red.
To enter the password:
• Change the first value with the Next button.
• When the value reads the correct number, select the
“ACCEPT” button, the number will go red and the next value
will show blue.
Once entered, the user can go in and out of the Mechanical
Setup without re-entering the password until the screen times
out.
NOTE: When a change has occurred in the Mechanical Setup
menu, the user must return to the system status screen for the
change to take effect.
SE
Figure 18.2 - Mechanical Setup
18
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Thermostat Signals (See Figure 19.1)
The Thermostat Signals Menu will show the values for all the
thermostat inputs (Main Zone) that are being monitored by
the control panel. This menu is for display only. This is used
to troubleshoot or verify the thermostat is sending the correct
signals.
System Monitoring (See Figure 19.2)
The system monitoring menu saves data from the previous
operating period for troubleshooting purposes. The electrical
energy that is being consumed by the unit is estimated in kWh.
This value is estimated by the amp draw from the system during
operation (through a current sensor) and the voltage value
entered by the installer during the commissioning process.
The Delta T Geo Water and Delta T Air values display the
change in temperature of the fluid or air across the respective
heat exchanger.
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 19.1 - Thermostat Signals Menu
SE
Figure 19.2 - System Monitoring Menu
GEO16-531.6
19
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Alarms (See Figure 20.1)
The Alarms Menu will show the values for all the alarms
associated with the control panel. The status of the alarm is
displayed along with the total time the alarm has been on.
The History menu will display the previous 10 alarms that have
occurred.
SE
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 20.1 - Alarms Menu
20
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Run Timers (See Figure 21.1)
The RUNTIMERS menu will show the amount of time each
mechanical component has been on. These values are updated
and recorded continuously by the control panel. It displays the
time in the format of HH:MM:SS. These timers can be reset
back to zero.
The timers will reset to zero after 1,500,000 seconds.
Tracking component usage over a known time frame can help
troubleshoot incorrect settings or issues with the system.
To reset the timers:
• Highlight “RESET RUNTIMERS” blue with the Next button.
• When highlighted, select the Accept button.
• A second question confirms that the timers will be reset
“RESET SETTINGS”.
• If it is right, “RESET RUNTIMERS” is still highlighted blue,
select the Accept button.
• Run timers are set to 00:00:00.
• “SETTINGS CHANGED” will appear.
• Press any button to return to the main menu.
SE
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 21.1 - Run Timers Menu Navigation
GEO16-531.6
21
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Forced Air (Forced Air and Split units only)
(See Figure 22.1)
The “FORCED AIR” menu shows and allows for changing of
forced air unit specific startup parameters. See Startup on
page 8 for detailed descriptions of each parameter.
The status of all zone inputs, dehumidification and fan speed
settings are shown.
The zone timers menu shows the runtime for each individual
zone if configured.
(See Figure 22.2)
The “TANK SETTINGS” menu shows and allows for changing
of all the hydronic specific startup parameters. See Startup on
page 8 for detailed descriptions of each parameter.
All buffer tank set points, dead bands, and modes of operation
are shown.
When changing the operational mode or the type of buffer tank
sensor, the user will have to press “>>RETURN” twice to get
back to the system status screen. This is to prevent inadvertent
editing of critical parameters that could affect the operation of
the equipment during a menu change.
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 22.1 - Forced Air Menu Navigation
Tank Settings (Water to Water units only)
SE
Figure 22.2 - Tank Settings Menu Navigation
22
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Combined (Combination units only)
(See Figure 23.1)
The “COMBINED” menu shows and allows for change for forced
air and hydronic startup parameters. See Startup on page 8 for
detailed descriptions of each parameter.
All buffer tank set points, dead bands, modes of operation, and
fan settings are shown.
When changing the operational mode or the type of buffer tank
sensor, the user will have to press “>>RETURN” twice to get
back to the system status screen. This is to prevent inadvertent
editing of critical parameters that could affect the operation of
the equipment during a menu change.
SE
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 23.1 - Combination Menu Navigation
GEO16-531.6
23
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
System Design
O
RV BS
IC O
E LE
US TE
E
ON
L
The Orb controller is capable of controlling up to 4 forced air
zones. Unit airflow and static pressure capabilities vary by unit
type and size, refer to the Installation and Service (I&S) Manual
for more information. Ductwork should be designed to allow
each zone to handle at least 60% of the maximum unit airflow.
If the smallest zone’s ductwork is not able to be sized to handle
60% of the unit airflow, a dump zone must be designed into the
system. Modine recommends one of the following approaches
to a dump zone in a residential application:
1. Use Attic or Crawl Space: If a well-insulated attic or crawl
space is available, it must be included in the overall building
load calculation. Return grilles must be located in the attic or
crawlspace if this approach is used.
2. Use Minimum Position: If a well-insulated attic or crawl
space is not available, the larger zone dampers must be
set to stay open at a minimum position to compensate for
the smaller zones. Bypass dampers are not recommended
(barometric or powered) as they shorten the lifespan of the
unit and can cause premature compressor failure.
Components Required
1. Modine Controls System Orb Controller – Standard on Heat
Pump
2. 24 Volt Zone Dampers (By Others)
a. 4 Zone Dampers Maximum
b. 40 VA Maximum Load for All Dampers
3. 24 Volt Heat Pump Zone Thermostats (By Others)
a. Main Zone must be 4 Heat / 2 Cool
b. Zone Stats must be 1 Heat / 1 Cool
c. 3 Zone Thermostats Maximum, Plus Main Zone Thermostat
d. All thermostats must be configured for Heat Pump
Operation, per the manufacturer’s instructions
A terminal block located in the control panel is included on
forced air and combination units for easy field wiring of the zone
connections. To make a connection in the terminal block, insert
a small flat head screw driver into the square hole. Once the
screw driver is inserted far enough a stripped wire can then be
inserted in the round hole above it. Hold the wire in position
while removing the screwdriver. Gently tug the wire to make
sure the connection is tight. The Orb provides 2 damper outputs
for each zone. For Zone 1 they are labeled “D1O” (damper 1
open), and “D1C” (Damper 1 closed). The Orb provides 24VAC
to the “D1O” terminal to power the damper open, and 24VAC to
the “D1C” terminal to power the damper closed. With the open
and closed terminals, the dampers can be setup in 3 different ways:
• Power Close / Spring Open (Recommended)
• Power Open / Spring Close
• Power Open / Power Close
Y
Forced Air Zoning
Figure 24.1 - Zone Wiring Terminal Strip
Table 24.1 - Zone Wiring Terminal Descriptions
R
LABEL
DESCRIPTION
24VAC
Z3O
Zone 3: off heating, on cooling
24VAC
Z4O
Zone 4: off heating, on cooling
Common
D1O
Damper 1 open
Common
D1C
Damper 1 close
Z2Y
Zone 2 call for conditioning input
D2O
Damper 2 open
Z3Y
Zone 3 call for conditioning input
D2C
Damper 2 close
R
C
C
24
DESCRIPTION
SE
LABEL
Z4Y
Zone 4 call for conditioning input
D3O
Damper 3 open
Z2G
Zone 2 call for fan only input
D3C
Damper 3 close
Z3G
Zone 3 call for fan only input
D4O
Damper 4 open
Z4G
Zone 4 call for fan only input
D4C
Damper 4 close
Z2O
Zone 2: off heating, on cooling
GND
Ground
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Sequence of Operation
During commissioning, the installer enters the number of zones
and the size of the zone, which is represented by a percentage
of total unit airflow in CFM. (See startup items 16 through 20
for how to enter the zoning information to the Orb). These zone
percentages do not control the speed of the fan. The speed of
the fan is controlled by the compressor operating speed.
Conditioning of zones operates on a first come first serve basis.
If the unit is heating Zone 1 while Zone 2 calls for cooling, the
unit will run in heating until the Zone 1 call is satisfied. Then the
unit will delay for 5 minutes before starting in cooling mode to
handle the Zone 2 call.
Emergency Heat
If the system is in Emergency Heat mode, only the Zone 1
thermostat can call for emergency heat. If the emergency heat
is on, the zone dampers will open as needed. This will cause
uneven heating of the zones to alert the homeowner as soon as
possible that there is a problem.
NOTE: The supply air temperature sensor is mounted below
the electric heating element. The air temperature rise provided
by the electric heat will not be captured on the system status
display.
Heating or Cooling
O
RV BS
IC O
E LE
US TE
E
ON
L
Fan Only
Y
The compressor operating speed and airflow is based on
the zones calling for heating or cooling and the percentage
of airflow entered by the installer during the commissioning
process.
< 67% of total airflow called
• 1st stage compressor operation
• Low speed fan, 67% of full rated airflow delivered to
zone(s) calling
> 67% of total airflow called
• 2nd stage compressor operation
• High speed fan, 90% of full rated airflow delivered to
zone(s) calling
The Orb uses a common G terminal for all zone thermostats, if
one zone calls for constant fan, all dampers will open and the
fan will come on to 25% of total unit airflow.
Zoning Example:
SE
A system with 4 zones is in standby (Zone 1 = 25%, Zone 2
= 25%, Zone 3 = 25%, Zone 4 = 25%). Zone 1 calls for heat.
The compressor goes into 1st stage operation and 67% of the
nominal airflow is delivered to Zone 1. While Zone 1 is being
heated, Zone 2 calls for heat. The total percentage of the two
zones is still less than 67%. Zone 2 damper opens while the
compressor stays in 1st stage operation and 67% of the nominal
airflow is delivered to both zones. Zone 3 calls for heat, so now
the total percentage of airflow is above 67%. The unit goes into
second stage operation, opens Zone 3 damper, and 90% of
the nominal airflow is delivered to the 3 zones. Zone 4 calls for
cooling. After all heating calls are satisfied, the compressor will
go into a 5 minute delay then restart in cooling mode.
GEO16-531.6
25
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 26.1 - Zone Screen Display
Table 26.1 - Zone Screen Parameter Descriptions
NAME
1
STATUS
VALUE
STAND BY, HEATING, COOLING, EMRG-HEAT, ALARM ON, LOCKOUT
2
STAGING MODE
3
1
Zone 1 status, black: STANDBY, red: HEATING, blue: COOLING, green: Fan Only, yellow:
EMRG-HEAT
2
Zone 2 status, black: STANDBY, red: HEATING, blue: COOLING, green: Fan Only
3
Zone 3 status, black: STANDBY, red: HEATING, blue: COOLING, green: Fan Only
4
Zone 4 status, black: STANDBY, red: HEATING, blue: COOLING, green: Fan Only
4
5
SE
6
STAGE:1, STAGE:2, STAGE:3, STAGE:4,
26
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Orb Control Board Hardware
For all thermostat and buffer tank connections the Orb is
outfitted with Wieland screw down connectors (see Figure 27.1).
These connectors can be removed from the board for easier field
wiring.
Communication Ports (See Figure 27.2)
USB Port
Ethernet Port
The RJ45 Ethernet jack is not used.
Figure 27.3 - Real Time Clock Location On Display
O
RV BS
IC O
E LE
US TE
E
ON
L
Figure 27.1 - Main Zone (Zone 1) Thermostat
Connections
(See Figures 27.3 & 27.4)
The control panel uses a real time clock that can keep track of
the current time. The clock is displayed at the top of the screen
and also provides the day and month. To program the time for
the control panel, connect a computer directly to the controller
with an Ethernet cable and use a web browser to navigate to the
IP address of the unit. The real time clock is used to determine
conditioning cycles, run times and when alarms occurred.
To ensure that the time is being kept, the control panel has a 3
volt lithium battery (CR2032) that provides power in the event of
a power outage. To replace the battery, ensure all power is shut
off to the unit and gently pry the battery out by hand.
Y
The USB mini port type B is used to connect a laptop computer
to the Orb board. This port is used for field service programing.
Time & Date – Real Time Clock
Figure 27.4 - Battery for Real Time Clock on Orb Board
SE
Figure 27.2 - Communication Ports
GEO16-531.6
27
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Fuses (See Figure 28.1)
The control panel has 3 replaceable fuses on the board. Fuse
kit 3H0387950000 includes 4 of each fuse and ships loose with
each unit.
The low voltage fuse is a 315mA replaceable fuse (Modine Part
# 5H0836540000). This fuse is designed to protect the low level
circuitry from damage. When this fuse blows, the board and the
display will not power up (no green LEDs). When replacing a
fuse, ensure all power is shut off to the equipment.
The high voltage fuses are two 240V/10A slow blow fuses
(Modine Part # 5H0836530000). These fuses are designed to
protect the high voltage components that are connected to the
control panel, which includes the flow center, blower motor,
domestic hot water pump, and hydronic pump. These two fuses
are housed in a black tower case. When replacing a fuse,
ensure all power is shut off to the equipment.
SE
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 28.1 - Fuses on Orb Boards
28
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Table 29.1 - Troubleshooting
SYMPTOM
POSSIBLE CAUSE
CORRECTIVE ACTION
Reset power.
2. Jumper in the “PROGRAM” position
Move jumper to the “OPERATION” position.
3. Ribbon cable not connected properly or
damaged
Ensure ribbon cable connections are fully seated.
Inspect ribbon cable for damage and replace if
necessary.
1. Low voltage fuse blown
Replace fuse. Assure correct power is connected to
unit and secondary transformer voltage is not greater
than 28 VAC.
2. Trace burnt between blue and silver cylinder
Contact factory.
3. Transformer trip
Reset transformer switch (White Rodgers
transformer only).
1. Display not plugged in
Connect control board to the display with the ribbon
cable.
2. Bad ribbon cable
Inspect cable for damage and replace.
3. Bad display
Contact factory.
1. Screws holding LCD to plastic bezel too tight
Loosen screws.
2. Display bad
Contact factory.
1. Screws holding LCD to plastic bezel too tight
Loosen screws.
2. Display bad
Contact factory.
Combined unit won’t stop
calling for hydronic heat
1. Normally closed aquastats are to be used
Replace aquastat for normally closed action or wire
in a relay.
Values changed in menus
don’t change the system
1. Orb display has timed out due to inactivity
Must select “>>RETURN” twice to get to the system
status screen before changes are saved.
Fan does not run when
zones 2, 3, or 4 make a call
1. “G” terminal not connected
Connect each zone “G” terminal to the zone 1 “G”
terminal according to the wiring diagram.
1. Antifreeze type and percent set incorrectly
Verify alcohol type in “MECHANICAL SETUP” menu.
2. Temperature sensor bad/ not connected
Verify all temperature sensors are installed and
accurate according to the resistance charts.
3. Low flow through source coil
Verify correct flow through the coil.
1. Improper thermostat
Install thermostat that supports 4 stages of heat.
2. Improper thermostat wiring
Verify thermostat connections to the control board.
3. AUX heat control harness not connected
Connect Aux heat control harness according to
wiring diagram.
Display screen is all white
O
RV BS
IC O
E LE
US TE
E
ON
L
No power to board, green
light on board not on
Y
1. Power needs to be reset
No power to display, green
light on display not on
Display Buttons are too
sensitive
Display Buttons don’t
respond
Freeze protect alarm
SE
Aux heat won’t come on
GEO16-531.6
29
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
°F
RESISTANCE Ω
°F
RESISTANCE Ω
-11.2
97490
57.2
15790
-9.4
92430
59
15130
-7.6
87660
60.8
14500
-5.8
83160
62.6
13900
-4
78910
64.4
13330
-2.2
74910
66.2
12790
-0.4
71130
68
12260
1.4
67570
69.8
11770
3.2
64200
71.6
11290
10.4
12.2
14
15.8
17.6
19.4
21.2
23
24.8
26.6
28.4
30.2
32
33.8
35.6
37.4
39.2
41
42.8
44.6
10840
10410
55170
77
10000
52480
78.8
9605
49940
80.6
9227
47540
82.4
8867
45270
84.2
8523
43110
86
8194
41070
87.8
7880
39140
89.6
7579
37310
91.4
7291
35570
93.2
7016
33930
95
6752
32370
96.8
6500
30890
98.6
6258
29490
100.4
6026
28150
102.2
5805
26890
104
5592
25690
105.8
5389
24550
107.6
5193
23460
109.4
5006
22430
111.2
4827
21450
113
4655
20520
114.8
4489
19630
116.6
4331
18790
118.4
4179
51.8
17980
120.2
4033
53.6
17220
122
3893
46.4
48.2
50
30
73.4
75.2
O
RV BS
IC O
E LE
US TE
E
ON
L
8.6
61020
58012
SE
5
6.8
Y
Table 30.1 - Type III 10k Thermistor Resistance vs.
Temperature
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Table 31.1 - Service Parts
MODINE PART#
5H0835950001
Orb Display
5H0835950002
Orb Ribbon Cable 5’
5H0833070060
Orb Ribbon Cable 20’
5H0833070240
Fuse Kit
3H0387950000
Low Voltage Fuse 315mA
5H0836540000
High Voltage Fuse 10A
5H0836530000
5H0835930000
3H0388160000
10K Outside Air Temperature Sensor
5H0835240000
SE
O
RV BS
IC O
E LE
US TE
E
ON
L
Orb Backup Battery
10K Buffer Tank Temperature Sensor
Y
SERVICE PART
Orb Control Board
GEO16-531.6
31
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Appendix A: Orb Display Mounting Kit Instructions
General
Remove the front and right side access panels from the unit.
The installer must determine where the Orb Display will be
located. If the display will be mounted on top of the unit, remove
the knock-out located in the top panel (see Figure 32.1 below).
If the display will be mounted remotely, the installer has the
choice of using either the knock-out located in the top panel or
in the back panel. On GFH/EFH units, the only option is to exit
the top panel.
NOTE: The ribbon cable is 6 feet long. If the display is to be
mounted remotely, the installer must ensure that the length of
the ribbon cable will be adequate to reach the desired mounting
location. If a longer cable is needed, see Table 33.1 for an
accessory part number.
SE
O
RV BS
IC O
E LE
US TE
E
ON
L
Figure 32.1 - Knockout Locations
Unit Location
Y
Modine Water to Water (GH/EH), Split Condensing Units (GS/
ES) and Horizontal Forced Air Units (GFH/EFH) are supplied
with a mounting bracket assembly that allows the installer to
mount the ORB LCD Display on top of the unit or remotely, such
as, on a wall near the unit. All mounting hardware is provided.
The units are built with knockouts that provide a location for the
display ribbon cable to penetrate the casing.
32
GEO16-531.6
MODINE CONTROL SYSTEM MANUAL
ORB CONTROLLER
Bracket Orientation / Mounting Display
If the bracket is to be mounted on a horizontal surface, the
bracket orientation is shown in Figure 33.1. If the bracket is
to be mounted on a vertical surface, the bracket orientation is
shown in Figure 33.2. Secure the Orb display to the mounting
bracket using the nylon screws provided in the kit. Do not over
tighten the screws.
Figure 33.1 - Horizontal Mounting
Mount Bracket & Display
If mounting remotely, secure to surface using hardware
provided.
If mounting to top of unit, position the mounting bracket over
the top of the grommet. Rotate bracket to desired position and
secure to top panel using self-tapping screws provided in kit.
Connecting Ribbon Cable
Remove control panel cover. Plug one end of ribbon cable into
main PCB plug (see Figure 33.4).
O
RV BS
IC O
E LE
US TE
E
ON
L
Y
Figure 33.4 - Ribbon Cable Connection
Figure 33.2 - Vertical Mounting
Ribbon Cable Socket on PCB
“LCD/TOUCHSCREEN”, P17
Take care not to cut, tear, crease or otherwise damage the
ribbon cable. Route the ribbon cable through a bushing in the
control panel.
Install Ribbon Cable Grommet
Install the grommet (provided in the kit) in the hole where the
knockout was removed. Using a razor knife or similar tool, cut a
single slit through the grommet per Figure 33.3.
Figure 33.3 - Grommet
If display is mounted on top of unit, route ribbon cable through
grommet in top panel and plug ribbon cable into socket on back
of display. Secure remaining ribbon cable inside of unit away
from any discharge lines or sharp edges.
For remote mounted displays, the ribbon cable may be routed
through the top panel or back panel of the unit, depending on
which knockout was chosen by the installer. Run ribbon cable
to display and plug ribbon cable into socket on back of display.
Secure ribbon cable ensuring it is protected from damage inside
and outside of the unit.
SE
Table 33.1 - Orb Mounting Kit Replacement Parts
GEO16-531.6
Item
Modine Part Number
Mounting Bracket
5H0832870000
Grommet, 1-½”
5H0836190003
Ribbon Cable, 20’
5H0833070240
33
Y
O
RV BS
IC O
E LE
US TE
E
ON
L
SE
THIS PAGE INTENTIONALLY LEFT BLANK
34
GEO16-531.6
Y
O
RV BS
IC O
E LE
US TE
E
ON
L
SE
THIS PAGE INTENTIONALLY LEFT BLANK
GEO16-531.6
35
(For Residential Warranty, see GEO16-510)
Seller warrants its products to be free from defects in material and
workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use
of materials substituted under emergency conditions for materials normally
employed. This warranty covers replacement of any parts furnished from the
factory of Seller, but does not cover labor of any kind and materials not
furnished by Seller, or any charges for any such labor or materials, whether
such labor, materials or charges thereon are due to replacement of parts,
adjustments, repairs, or any other work done. This warranty does not apply to
any equipment which shall have been repaired or altered outside the factory of
Seller in any way so as, in the judgment of Seller, to affect its stability, nor
which has been subjected to misuse, negligence, or operating conditions in
excess of those for which such equipment was designed. This warranty does
not cover the effects of physical or chemical properties of water or steam or
other liquids or gases used in the equipment.
BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO BE
FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP, AS LIMITED
HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER
WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING
FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE,
THERE ARE NO OTHER WARRANTIES, INCLUDING WARRANTY OF
MERCHANTABILITY OR FITNESS FOR PURPOSE, WHICH EXTEND
BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND
SELLER AS OF THE DATE OF FINAL AGREEMENT.
BUYER AGREES THAT IN NO EVENT WILL SELLER BE LIABLE FOR
COSTS OF PROCESSING, LOST PROFITS, INJURY TO GOODWILL, OR
ANY OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY KIND
RESULTING FROM THE ORDER OR USE OF ITS PRODUCT, WHETHER
ARISING FROM BREACH OF WARRANTY, NONCONFORMITY TO
ORDERED SPECIFICATIONS, DELAY IN DELIVERY, OR ANY LOSS
SUSTAINED BY THE BUYER.
Component
Applicable Models
Heat Exchangers
Gas-Fired Units
These warranties are issued only to the original owner-user and cannot be
transferred or assigned. No provision is made in these warranties for any
labor allowance or field labor participation. Seller will not honor any expenses
incurred in its behalf with regard to repairs to any of Seller’s products. No
credit shall be issued for any defective part returned without proper written
authorization (including, but not limited to, model number, serial number,
date of failure, etc.) and freight prepaid.
OPTIONAL SUPPLEMENTAL WARRANTY
Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years on certain compressors.
Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years or nine (9) years on certain
heat exchangers.
EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND SELLER’S
CONTROL
This warranty shall not be applicable to any of the following items: refrigerant
gas, belts, filters, fuses and other items consumed or worn out by normal wear
and tear or conditions beyond Seller’s control, including (without limitation as
to generality) polluted or contaminated or foreign matter contained in the air or
water utilized for heat exchanger (condenser) cooling or if the failure of the part
is caused by improper air or water supply, or improper or incorrect sizing of
power supply.
O
RV BS
IC O
E LE
US TE
E
ON
L
This warranty is void if the input to the product exceeds the rated input as
indicated on the product serial plate by more than 5% on gas-fired and oil-fired
units, or if the product in the judgment of SELLER has been installed in a
corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected
to misuse, negligence, accident, excessive thermal shock, excessive humidity,
physical damage, impact, abrasion, unauthorized alterations, or operation
contrary to SELLER’S printed instructions, or if the serial number has been
altered, defaced or removed.
BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL
OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR
REPLACEMENT AT THE FACTORY OF SELLER, ANY COMPONENT WHICH
SHALL, WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN
AND UPON PRIOR WRITTEN APPROVAL, BE RETURNED TO SELLER
WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE
EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE;
EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A
COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER,
BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE
LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR
GAS-FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS
AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS, BUYER’S
REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO
TEN YEARS FROM DATE OF SHIPMENT FROM SELLER.
Y
commercial Warranty
Heat Exchangers
Low Intensity Infrared Units
Compressors
Condensing Units for Cassettes
Burners
Low Intensity Infrared Units
Other
Components excluding Heat Exchangers,
Coils, Condensers, Burners, Sheet Metal
SE
Heat Exchangers/Coils
Indoor and Outdoor Duct Furnaces and
System Units, Steam/Hot Water Units,
Oil-Fired Units, Electric Units, Cassettes,
Vertical Unit Ventilators, Geothermal Units
Compressors
Vertical Unit Ventilators, Geothermal Units
“APPLICABLE WARRANTY PERIOD”
TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE
HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER
OCCURS FIRST
FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX
MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
Burners
High Intensity Infrared Units
Sheet Metal Parts
All Products
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.
© Modine Manufacturing Company 2015
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, WI 53403
Phone: 1.877.679.4436 (4GEO)
www.modinehvac.com