CPA Wall Furnace Page 1 of 2 FURNACE (WALL) City of Palo Alto (CPA) Building Inspection Division 285 Hamilton Ave. Inspection Request: 650 329-2496 Building Division Revision Date: 03/04/11 General Requirements/Checklist for: Residential Codes Enforced: 2010 CRC, CBC, CMC,CEC,CPC Palo Alto Municipal Code (PAMC) IVR# 609 The information provided in this document is general and intended as a guide only. Each project is unique and additional requirements may be enforced as deemed appropriate. WARNING Failure to complete items below, prior to inspection, may result in a re-inspection fee. GREEN BUILDING TIPS *Rebate www.cityofpaloalto.org/smartenergy *Energy Star gas furnace saves as much as 20% annually on your total energy cost. Replacement of vented wall furnaces of the same or less BTU input may be installed in the same location if it doesn’t create an unsafe condition. Recommendation: do not install wall furnace on exterior wall. Install on interior wall for maximum efficiency. All wall furnaces must be installed in accordance with manufacturer’s instructions and local requirements. CPA INSPECTION provide inspector with manufacturer’s instruction manual & access to attic during inspection. CMC 108.4 Clearances minimum 12” inches from door swing minimum 4” inches from wall minimum 6” inches from inside corner (unless listed for less) minimum 18” inches below any structural projection ( including doors and windows that would project over the furnace.) See figure 805 (a)-1 and 805 (a)-2 Combustion Air Vented wall furnaces shall be provided with combustion air per CMC chapter 7. (exception: combustion air openings may be omitted to an area in which a vented wall furnace is installed, provided there is a permanent case opening into other rooms having a combustion volume of 50 cubic feet per 1000 BTU. limitations: ducts shall not be attached to wall furnace. CBC 701.0 See Figure 805 c-1 CPA Wall Furnace Page 2 of 2 Venting Gas appliance Vents shall be installed per Chapter 8 of the 2007 California Mechanical Code. Vents that pass through unconditioned areas such as attic, roofs, underfloor, and unconditioned basements shall be listed Type B or Type L double wall vents and shall have a minimum 1” inch clearance to combustibles. Single wall vents are not allowed. CMC 802.10.2 One story or top story of multistory installation: install 26 gage metal sleeve open and extending into attic 12” inches or 2” from roof sheathing. Ceiling plate spacer (not firestop spacer) to ventilate stud above base plate at first header only. See figure 907-1 Listed BW gas vent outlet shall terminate a minimum of 12’ feet in vertical height above bottom of wall furnace. CMC 802.6.2.2 Vents shall be attached to a solid header plate designed for the vented wall furnace. Note: 1 strap per plate with a minimum of 14 nails each side shall be installed to any bearing wall. CMC 928.1 by listing Stud spaces in which type BW vent are installed shall be free of any obstructions and be cut flush with the adjacent stud walls. Clearances of type BW vents shall be maintained by the base & ceiling plates spacers strap of fire stop space. See figure 9-2, 928.1 c Type BW gas vents listed for only single story buildings are allowed only in single story buildings or the top floor of multi story buildings. note: BW vents listed for multi-story use may be installed in single or multi story buildings. Stud space that contains a type BW gas vent in a single story and the top story of multi story building shall be open to the attic and supplied with a storm collar. fire stop spacers are required at the ceiling plate. CMC 928.1 c Stud spaces shall be vented at the first ceiling plate above the furnace. CMC 928.1 c A suitable metal guard (16 gage) shall be installed at each floor level. BW vent installed in an existing building shall be completely open for installation and inspection. Vents shall extend from the header plate through the roof with out offsets or crossover. See figure 907-1, 903 (a)-3, 903(a)-4 and 907-2 Gas line air test required when any modifications are made to gas line piping, excluding gas connector. If applicable see “Whole House Gas Test” for testing guidelines. CPC 1214.5 Gas connector shall be rated/sized for load/demand of the furnace; shall not pass through any walls, partitions, ceilings, floors or concealed space; connector shall not exceed 3’ feet in length; and the existing old connector shall not be reused when replacing the furnace. DO NOT REMOVE SIZING LABLE FROM CONNECTOR, INSPECTOR MUST VERIFY. CMC 1312.1 (d) NOTE: Wall furnace located in structural walls may require PA heavy gauge metal straps to maintain load transfer capacity @ double top plates.
© Copyright 2026 Paperzz