Installation and Operating Instruction for B.E.G. - Occupancy detectors PD9-1C (-GH)-FC
A circular opening of
diameter min. 34 mm
must be produced in
the ceiling.
Having connected the cables in accordance with
the regulations, connect the power supply via the
RJ11 plug. Therefore, open the power supply with
the help of the screws and close it afterwards. After
that, put the power supply through the opening in
the ceiling and mount the sensor onto the ceiling
according to figure.
Zeit
Lux
TEST
30sec
1min
2
4 6 8
30
12
TIME
Zeit
TEST
30sec
1min
2
4 6 8
200
TIME
600
2000
1200
LUX
6. Article / Part-Nr. / Accessory
Type
Follow-up time for light control
2000
The time can be set
infinitely variably at between
200
1200
30 seconds
and
600 30 minutes.
Symbol : LUXImpulse < 1 sec.
Symbol TEST: Test mode
(Every movement switches on the light for a period of
1 second, switching it off for a period of 2 seconds after
that regardless of the level of brightness)
Lux
30
12
RAL9010
RAL9006
92902
92903
PD9-1C-GH-FC
92934
92935
Accessory:
Wire basket BSK
Coverring for PD9
white
Coverring for PD9
silver
Coverring for PD9
anthracite
Blind GH
white
92199
92238
92237
92235
33207
7. Technical data
Connection of sensor and power supply
by means of telephone plug R J11
Declaration of Conformity: The product complies with
the low voltage recommendation 2006/95/EC and the
EMV recommendation 2004/108/EC.
PD9-1C
PD9-1C-GH-FC
25
25
45
45
166 mm
24 mm
24 mm
9. Range of Coverage
1. Lamp does not light up
PD9-1C-GH-FC
Lamp may be defect:
Replace lamps
9,00 m
RJ
No mains connection/power:
Check connection and mains fuse by qualified electrician
Incorrect setting of CDS twilight threshold:
Correct setting of CDS threshold
Lens of sensor unit obstructed by dirt or other objects:
Clean lens, remove objects
360°
2. Lamp turns ON too late or detection range too small
LUXOMAT® PD9-1C-GH-FC is mounted too high:
See table of mounting heights.
Correct mounting if required.
5,40 m
3. Lamp stays ON continuously
Continuous thermal activity detected ie fan, central heating
ducts, animals within detection area:
Remove heatsource. Check proper function of
LUXOMAT® PD9-1C-GH-FC by covering the fresnel-lens.
After expiry of delay timer, has to turn OFF lighting.
PD9-1C
2.50 m
RJ
LUXOMAT® PD9-1C-GH-FC connected in parallel to a
manual override switch:
Connect switch correctly
4. Unintended switching of light
Movement of heat source within detection area:
Check on presence of animals, fans or heaters
2
3
m
10
Power supply:230 V~ ±10 %
Power consumption:
< 1W
Ambient temperature:
-25°C – +50°C
Degree of protection/class: IP20 / II / CE
Settings: Settings made manually
using potentiometer
Light values:
10 - 2000 Lux
Area of coverage:
circular 360°
Range Ø H 2.50 m / T = 18°C:
PD9-1C-FC
seated 2.50 m / tangential
10 m / radial 6 m
PD9-1C-GH-FCmax. Ø 5.40 m
Recommended height for mounting:
PD9-1C-FC
2 - 3m
PD9-1C-GH-FC
5 - 10 m
One channel to switch the lighting
Type of contact:NOC/with pretravel tungsten contact
1000 W, cos ϕ=1 /
Contact load:
500 W, cos ϕ= 0,5
Time-settings:
30 sec. - 30 min. / Test
Dimensions
PD9-1C-FC
Ø 45 x H 12 mm
PD9-1C-GH-FC
Ø 45 x H 40 mm
Power supply
L 165 x W 24 x H 24 mm
5. Dimensions
Twilight-switch for light control
The switch-on value for the light can be set at between
10 and 2000 Lux. Using the rotary control, the luminance set points can be set as desired.
Symbol :
Night-time operation
Symbol
: Daytime /Night-time operation
8. Trouble shooting
PD9-1C-FC
In case the sensing area of the
LUXOMAT® PD9-1C­(-GH)-FC
is too large or areas are being
covered that should not be monitored, the range can be reduced
or limited through use of the
enclosed masking clips.
m
4. Putting into operation / Settings
The LUXOMAT® PD9-1C
(-GH) enters an initial
60-second self-test cycle,
when the supply is first connected. The occupancy detector is ready for operation.
L L' N
5,4
0
Disconnect supply before installing!
3. E
xclude sources of
interference
16
Work on the 230 V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision of
qualified skilled electrical personnel
in accordance with electrotechnical
regulations.
The detector has
been designed and
developed specifically for installation in
suspended ceilings.
2c. Self test cycle
24
34
mm
32
22 - 30
mm
2b. Connecting
terminals
16
2a. Installation
12
1. Mounting preparations
1
1
2
3
360°
quer
zum Melder
Walking
across gehen
frontal
zumtowards
Melder gehen
Walking
Unterkriechschutz
Smaller motions
4m
6m
10 m
10. Wiring diagrams
Standard mode with 1-channel motion detector
L
N




E1





N
L
L΄΄
C1
Standard mode with 1-channel motion detector with
permanent light function

L

N


E1

S1





N
L
L΄΄

C1


optional:
S1 = switch for permanent light
RC = RC-suppression kit if required


Standard mode with 1-channel motion detector with
NC pushbutton
L
N



T1
N

T1 = NC button
 additionManual switching
ally possible
(press opener

approx. 2 sec.).

E1
L

L΄΄
C1



Parallel connection with 1-channel motion

detectors
(max. 8 parallel)
L
N
E1
N
L
L΄΄
C1
N
L














L΄΄
C1
Standard mode with 1-channel motion detector (f.ex.
stairs)

L
N

T2
L


30 sek. 
10 min.

4

3


N
L
L΄΄
C1
MAN 6132 – 270812–4
T1
E1
N