J . v e R , 5 1 6 3 3 1 4 1 VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Part No. 14-1336-15, Rev. J Installation Instructions Issued March 2016 Refer to the QuickLIT website for the most up-to-date version of this document. Applications Installation The VA9104 Series Actuators are direct-mount, non-spring return electric valve actuators that operate on AC 24 V power. These synchronous, motor-driven actuators are used to provide accurate positioning on Johnson Controls® VG1000 Series DN15, DN20, and DN25 (1/2, 3/4, and 1 in.) ball valves in HVAC applications. Install the ball valve with the actuator at or above the centerline of the horizontal piping (Figure 1). The VA9104 Series Electric Non-Spring Return Actuators provide a running torque of 35 lbin (4 Nm). The nominal travel time is 60 seconds at 60 Hz (72 seconds at 50 Hz) for 90° of rotation IMPORTANT: Do not install or use this VA9104 Series Electric Non-Spring Return Valve Actuator in or near environments where corrosive substances or vapors could be present. Exposure of the electric actuator to corrosive environments may damage the internal components of the device, and will void the warranty. IMPORTANT : Utiliser ce VA9104 Series Actuator uniquement pour commander des équipements dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du VA9104 Series Actuator risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du VA9104 Series Actuator. FIG:mntpos_H2O_app IMPORTANT: Use this VA9104 Series Actuator only to control equipment under normal operating conditions. Where failure or malfunction of the VA9104 Series Actuator could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the VA9104 Series Actuator. Figure 1: Mounting Positions for Chilled Water and Condensing Atmosphere Applications Special Tool Needed To install the actuator, use a digital voltmeter or a M9000-200 Commissioning Tool. Dimensions See Figure 2 for dimensions of the Non-Spring Return VA9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with M9000-551 Linkage. See Table 1 for specific model linkage dimensions. See Table 2 for specific model dimensions for the VA9104 Actuated VG1275 and VG1875 Series Sweat End and the VA9104 Actuated VG1295 and VG1895 Series Press End Connection Ball Valves. VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions 1 See Figure 3 and Table 3 for VA9104 Valve Actuator dimensions with optional M9000-561 Thermal Barrier installed. Minimum Clearance Required 3-1/2 (89) 2-13/16 (71) 6-1/16 (154) F A Port Marking Locations A B C C C B B G E D Two-Way Valve Three-Way Valve Two-Way Valve Three-Way Valve FIG:M9104dims E Figure 2: Non-Spring Return VA9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with Optional M9000-551 Linkage Dimensions, in. (mm.) Table 1: VA9104 or M9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with Optional M9000-551 Linkage Dimensions, in. (mm) Valve Size, in. (DN)1 A B C D E F G 1/2 (DN15) 3-7/8 (98) 21/32 (17) 1-7/32 (31) 5-7/64 (129) 2-33/64 (64) 11/32 (9) 1-1/4 (32) 3/4 (DN20) 3-7/8 (98) 21/32 (17) 1-7/32 (31) 5-7/32 (133) 2-51/64 (71) 11/32 (9) 1-13/32 (36) 1 (DN25) 3-11/16 (100) 3/4 (19) 1-19/64 (33) 5-9/16 (141) 3-13/32 (87) 11/32 (9) 1-11/16 (43) 1. Port A must always be connected to the coil (Figure 2). Table 2: VA9104 Actuated VG1275 and VG1875 Series Ball Valve with Sweat End Connections and VA9104 Actuated VG1295 and VG1895 Series Ball Valves with Press End Connections Dimensions, in. (mm) Valve Size, in. (DN)1 A B C D E F G 1/2 (DN15) 3-7/8 (98) 21/32 (17) 1-7/32 (31) 5-45/64 (145) 3-25/32 (96) 11/32 (9) 2-13/16 (55) 3/4 (DN20) 3-7/8 (98) 21/32 (17) 1-7/32 (31) 5-57/64(150) 4-3/32 (104) 11/32 (9) 2-15/32 (62) 1 (DN25) 3-15/16 (100) 3/4 (19) 1-19/64 (33) 6-1/8 (156) 4 21/32 (118) 11/32 (9) 2-27/32 (72) 1. Port A must always be connected to the coil (Figure 2). VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions 2 3-1/2 (89) Clearance Required 6-1/16 (154) 2-13/16 (71) A FIGVA9104X_dims Port Marking Locations D Figure 3: Field-Installed VA9104 Series Electric Actuator Dimensions with Optional M9000-561 Thermal Barrier Dimensions, in. (mm) Table 3: VA9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series NPT Ball Valves with Optional Thermal Barrier Installed Dimensions, in. (mm) Valve Size, in. (DN)1 A B C D E F G 1/2 (DN15) 5-11/32 (135) 21/32 (17) 1-7/32 (31) 5-7/64 (129) 2-33/64 (64) 11/32 (9) 1-1/4 (32) 3/4 (DN20) 5-11/32 (135) 21/32 (17) 1-7/32 (31) 5-7/32 (133) 2-51/64 (71) 11/32 (9) 1-13/32 (36) 1 (DN25) 5-27/64 (137) 3/4 (19) 1-19/64 (33) 5-9/16 (141) 3-13/32 (87) 11/32 (9) 1-11/16 (43) 1. Port A must always be connected to the coil (Figure 3). Accessories Table 4: Accessories (Order Separately) Code Number Description M9000-200 Commissioning Tool That Provides a Control Signal to Drive 24 V On/Off, Floating, Proportional, and/or Resistive Electric Actuators M9000-561 Thermal Barrier Extends M(VA)9104, M(VA)9203, and M(VA)9208 Series Electric Spring Return Actuator Applications to Include Low Pressure Steam (Quantity 1) M9000-341 Weathershield Kit for VG1000 Series Ball Valve Application of M(VA)9104, M(VA)9203, and M(VA)9208 Series Electric Spring Return Actuators (Quantity 1) VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions 3 FIG: hndl Figure 5: Installing the Handle FIG: CUPLACT Mounting Mounting the Actuator To mount the actuator: Figure 6: Coupling the Actuator to the Valve 1. Turn valve stem to position below. 2 Way 3 Way FIG:VG1000 5. Install the valve actuator over the ball valve mounting flange (Figure 6). Depending on the installation, position the assembly in any one of four 90° increments on the valve. Note: For proper operation, the actuator must drive the valve counterclockwise to open Port A when viewed from above the valve. 6. To secure the actuator to the valve, use a 1/4 in. (6 mm) flat blade screwdriver. Recommended torque is 8 to 12 lbin (0.9 to 1.4 Nm). Figure 4: Positioning the Valve Stem 2. Mount optional M9000-561 Thermal Barrier to the valve if fluid temperature exceeds 212°F (100°C). See the Mounting the Thermal Barrier section for more information. 3. Place the handle the top of the drive shaft (Figure 5). The handle is keyed on and can only be mounted in one orientation. IMPORTANT: Do not overtighten the manual handle mounting screw. Overtightening may strip the threads resulting in damage to the valve stem threads. 4. Check that the actuator coupler and handle are in the fully counterclockwise position as viewed from the top of the actuator. If not, press the actuator gear release and rotate the handle until the actuator coupler is fully counterclockwise. VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions 4 Mounting the Thermal Barrier 2. Rotate the drive shaft to align marks on the top of the thermal drive shaft with matching marks on the valve stem. Figure 7 shows the optional M9000-561 Thermal Barrier. 3. Mount the thermal barrier onto the valve using the four included M5x16 mm machine screws and four M5 flange nuts. Tighten the screws to a recommended torque of 21 to 25 lb·in. (2.4 to 2.8 N·m) (Figure 9). Machine Screws Flange Nuts Barrier Drive Shaft Figure 7: Optional M9000-561 Thermal Barrier To mount the optional thermal barrier: FIG:in_act 1. Install the thermal barrier drive shaft into the thermal barrier by aligning the tab on the drive shaft with the slot on the thermal barrier (Figure 8). Figure 9: Installing the Barrier 4. Proceed to Mounting the Actuator. Follow the same steps as mounting directly to the valve when mounting the actuator to the thermal barrier. Figure 8: Installing the Drive Shaft into the Thermal Barrier VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions 5 Wiring (3.05 m) long cable; see Figure 10 for proper wiring. DA DA BLK RED ORN 2 3 Risk of Electric Shock. Disconnect the power supply before making electrical connections to avoid electric shock. ~ AC 24 V 50/60 Hz VA9104-xGA-2S ii07.cdr 1 Figure 10: VA9104-AGA-2S and VA9104-IGA-2S Control Wiring Diagram, Floating Risque de décharge électrique. Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique. Note: When using the VA9104-AGA-1S or VA9104-IGA-1S Series actuator with a controller featuring triac output, add a 4.7k ohm resistor one half watt between the Common (COM) and Counterclockwise (CCW) terminals. Risk of Property Damage. Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment. Note: For all VA9104-AGA Series actuators, use a controller and/or software that provides a timeout function at the end of rotation (stall) to avoid excessive wear or drive time on the actuator motor. The -GGA and -IGA models have an auto shutoff feature to prevent excessive wear or drive time on the motor. VA9104-GGA-2S The VA9104-GGA Series Electric Non-Spring Return valve actuators require AC 24 V power and a DC 0(2) to 10 V or 0(4) to 20 mA controller input signal. These electric actuators include an integrated 120 in. (3.05 m) long cable; see Figure 11 for proper wiring. Risque de dégâts matériels. Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement. IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the VA9104 Series Electric Non-Spring Return Valve Actuator. VA9104-AGA-2S and VA9104-IGA-2S The VA9104-AGA and VA9104-IGA Series Electric Non-Spring Return valve actuators require an AC 24 V input signal and work with a variety of controllers. These electric actuators include an integrated 120 in. VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions 6 DC 0(2)...10 V Control BLK RED GRY ORN 3 1 2 4 AC 24 V ~ ~ 3 + + ~ B A Y AC 24 V + U DC 0(2)...10 V Y DC 0(2)...10 V + + DC 0(2)...10 V U U COM 4 C ~ Y DC 0(2)...10 V 0(4)...20 mA Control with External Resistor BLK RED GRY ORN AC 24 V BLK RED GRY ORN 3 4 1 2 AC 24 V DC 0(2)...10 V 2 Override to MAX position BLK RED GRY ORN 3 4 1 2 + DC 0(2)...10 V 1 Override to MIN position COM A Open = MIN Position A Closed = Normal Operation B Closed = MAX Position C Closed = Normal Operation + DC 0(4)...20 V Y Override to MIN, MID, MAX positions 0(4)...20 mA Control with External Resistor BLK RED GRY ORN + U Figure 11: VA-9104-GGA-2S Control Wiring Diagram 1 3 2 Override to MIN, MID, MAX positions 0(2)...10 V Control BLK RED GRY ORN 4 3 1 2 4 + A A B B AC 24 V AC 24 V ~ 0(4)...20 mA C + U C + 100% ( MAX ) NORMAL NORMAL C 100% ( MAX ) B 0% ( MIN ) 50% ( MID ) A N O I T C N U F ︶ 0% ( MIN 50% ( MID ) Y U COM C B A N O I T C N U F COM ~ DC 0(2)...10 V Y 500 Ω / 0.25 W Figure 12: VA9104-IGA-2S Wiring Diagram, On/Off + FIG:VA9104GGx2(Z)_wir DC 0(4)...10 V Figure 13: VA-9104-GGA-2S Control Wiring Diagram (Overrides) VA9104-GGA actuators are factory set for Direct Acting (DA) mode and for a DC 0 to 10 V input control signal. In DA mode, a minimum control signal drives the actuator to the full CCW position, and a maximum control signal drives the actuator to the full Clockwise (CW) position. VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions 7 Setup and Adjustments For Reverse Acting (RA) operation, a minimum control signal drives the actuator to the full CW position and a maximum signal drives the actuator to the full CCW position. To change the factory settings, remove the actuator cover and adjust the switches on the circuit board as shown in Figure 14. Commissioning After wiring is complete, apply power to the Variable Air Volume (VAV) or Variable Air Volume and Temperature (VVT) controller and provide input signals to the actuator to drive it at least one complete cycle open and closed. Troubleshooting If the VA9104 Series Electric Non-Spring Return Valve Actuator is not responding or working properly: Figure 14: VA9104-GGA Factory Switch Setting • verify that the actuator assembly is properly secured to the valve. • check that all electrical connections are complete and that power is applied. • verify that the valve fully opens and closes, using the gear release button on the actuator and the manual override handle, shown in Figure 5. Repairs If the VA9104 Series Electric Non-Spring Return Actuator fails to operate within its specifications, replace the unit. For a replacement electric actuator, contact the nearest Johnson Controls representative. Technical Specifications VA9104-xGA-2S Electric Non-Spring Return Valve Actuators (Part 1 of 2) Power Requirements Control Type AC 24 V +25%/-20% at 50/60 Hz, 2.3 VA (AGA), 2.9 VA (GGA), and 3.0 VA (IGA) Supply, Class 2 or Safety Extra-Low Voltage (SELV) VA9104-AGA-2S Floating or On/Off Control without Timeout VA9104-GGA-2S Proportional Control VA9104-IGA-2S Floating or On/Off Control with Timeout VA9104-AGA-2S AC 24 V +25%/-20% at 50/60 Hz, Class 2 or SELV without Timeout VA9104-GGA-2S DC 0 (2) to 10 V or 0 (4) to 20 mA with Field-Furnished 500 ohm Resistor VA9104-IGA-2S AC 24 V +25%/-20% at 50/60 Hz, Class 2 or SELV with Timeout Feedback Signal VA9104-GGA-2S DC 0 (2) to 10 V for 90° Corresponds to Input Signal Span Selected Motor Input Impedance VA9104-AGA-2S 200 ohms Nominal Control Input Impedance VA9104-GGA-2S Voltage Input: 200,000 ohm Current Input: 500 ohm With Field-Furnished 500 ohm Resistor Input Signal Running Torque 35 lbin (4 Nm) Travel Time 60 Seconds at 60 Hz (72 Seconds at 50 Hz) for 90° of Rotation Rotation Range 93° ±3°, CW or CCW Cycles 100,000 Full Stroke Cycles; 2,500,000 Repositions at Rated Running Torque Audible Noise Rating Electrical Connections 35 dBA Nominal at 39-13/32 in. (1 m) VA9104-xGA-2S 120 in. (3.05 m) UL 444 Type CMP Plenum Rated cable with 19 AWG (0.75 mm2) Conductors and 0.25 in. (6 mm) Ferrule Ends and Connector for 3/8 in. Flexible Metal Conduit VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions 8 VA9104-xGA-2S Electric Non-Spring Return Valve Actuators (Part 2 of 2) Enclosure Ambient Conditions Fluid Temperature Limits (Actuator and Valve Assembly) Compliance VA9104-xGA-2S NEMA 2, IP42 Operating -4 to 140°F (-20 to 60°C); 90% RH Maximum, Noncondensing Storage -20 to 150°F (-29 to 66°C); 90% RH Maximum, Noncondensing VG12x1 and VG18x1 Series 23 to 203°F (-5 to 95°C) VG12x5 and VG18x5 Series -22 to 212°F (-30 to 100°C) VG12x5 and VG18x5 Series with M9000-561 Thermal Barrier -22 to 284°F (-30 to 140°C) Water; 15 psig (103 kPa) at 250°F (121°C) Saturated Steam United States UL Listed, CCN XAPX, File 27734 Plenum rated, UL2043, suitable for use in other environmental spaces (plenums) in accordance with section 300.22.(c) of the National Electrical Code Canada cUL Listed, CCN XAPX7, File 27734 Plenum Rated Per CSA 22.2 No. 236/UL 1995, Heating and Cooling Equipment Europe Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive and the Low Voltage Directive. Australia and New Zealand RCM Mark, Australia/NZ Emissions Compliant Shipping Weight 1.25 lb (0.55 kg) European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact: JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc. VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions Published in U.S.A. 9 www.johnsoncontrols.com
© Copyright 2026 Paperzz