VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

J
.
v
e
R
,
5
1
6
3
3
1
4
1
VA9104-xGA-2S Series Electric Non-Spring Return Valve
Actuators
Part No. 14-1336-15, Rev. J
Installation Instructions
Issued March 2016
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
Installation
The VA9104 Series Actuators are direct-mount,
non-spring return electric valve actuators that operate
on AC 24 V power. These synchronous, motor-driven
actuators are used to provide accurate positioning on
Johnson Controls® VG1000 Series DN15, DN20, and
DN25 (1/2, 3/4, and 1 in.) ball valves in HVAC
applications.
Install the ball valve with the actuator at or above the
centerline of the horizontal piping (Figure 1).
The VA9104 Series Electric Non-Spring Return
Actuators provide a running torque of 35 lbin (4 Nm).
The nominal travel time is 60 seconds at 60 Hz
(72 seconds at 50 Hz) for 90° of rotation
IMPORTANT: Do not install or use this VA9104
Series Electric Non-Spring Return Valve Actuator in
or near environments where corrosive substances
or vapors could be present. Exposure of the electric
actuator to corrosive environments may damage the
internal components of the device, and will void the
warranty.
IMPORTANT : Utiliser ce VA9104 Series Actuator
uniquement pour commander des équipements
dans des conditions normales de fonctionnement.
Lorsqu'une défaillance ou un dysfonctionnement du
VA9104 Series Actuator risque de provoquer des
blessures ou d'endommager l'équipement contrôlé
ou un autre équipement, la conception du système
de contrôle doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du VA9104
Series Actuator.
FIG:mntpos_H2O_app
IMPORTANT: Use this VA9104 Series Actuator
only to control equipment under normal operating
conditions. Where failure or malfunction of the
VA9104 Series Actuator could lead to personal
injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the VA9104 Series Actuator.
Figure 1: Mounting Positions for Chilled Water
and Condensing Atmosphere Applications
Special Tool Needed
To install the actuator, use a digital voltmeter or a
M9000-200 Commissioning Tool.
Dimensions
See Figure 2 for dimensions of the Non-Spring Return
VA9104 Actuated VG1241, VG1245, VG1841, and
VG1845 Series Ball Valve with M9000-551 Linkage.
See Table 1 for specific model linkage dimensions.
See Table 2 for specific model dimensions for the
VA9104 Actuated VG1275 and VG1875 Series Sweat
End and the VA9104 Actuated VG1295 and VG1895
Series Press End Connection Ball Valves.
VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators
Installation Instructions
1
See Figure 3 and Table 3 for VA9104 Valve Actuator
dimensions with optional M9000-561 Thermal Barrier
installed.
Minimum Clearance Required
3-1/2 (89)
2-13/16
(71)
6-1/16
(154)
F
A
Port Marking
Locations
A B
C
C
C
B
B
G
E
D
Two-Way Valve
Three-Way Valve
Two-Way Valve
Three-Way Valve
FIG:M9104dims
E
Figure 2: Non-Spring Return VA9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
with Optional M9000-551 Linkage Dimensions, in. (mm.)
Table 1: VA9104 or M9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with
Optional M9000-551 Linkage Dimensions, in. (mm)
Valve Size,
in. (DN)1
A
B
C
D
E
F
G
1/2 (DN15)
3-7/8 (98)
21/32 (17)
1-7/32 (31)
5-7/64 (129)
2-33/64 (64)
11/32 (9)
1-1/4 (32)
3/4 (DN20)
3-7/8 (98)
21/32 (17)
1-7/32 (31)
5-7/32 (133)
2-51/64 (71)
11/32 (9)
1-13/32 (36)
1 (DN25)
3-11/16 (100)
3/4 (19)
1-19/64 (33)
5-9/16 (141)
3-13/32 (87)
11/32 (9)
1-11/16 (43)
1.
Port A must always be connected to the coil (Figure 2).
Table 2: VA9104 Actuated VG1275 and VG1875 Series Ball Valve with Sweat End Connections and
VA9104 Actuated VG1295 and VG1895 Series Ball Valves with Press End Connections
Dimensions, in. (mm)
Valve Size,
in. (DN)1
A
B
C
D
E
F
G
1/2 (DN15)
3-7/8 (98)
21/32 (17)
1-7/32 (31)
5-45/64 (145)
3-25/32 (96)
11/32 (9)
2-13/16 (55)
3/4 (DN20)
3-7/8 (98)
21/32 (17)
1-7/32 (31)
5-57/64(150)
4-3/32 (104)
11/32 (9)
2-15/32 (62)
1 (DN25)
3-15/16 (100)
3/4 (19)
1-19/64 (33)
6-1/8 (156)
4 21/32 (118)
11/32 (9)
2-27/32 (72)
1.
Port A must always be connected to the coil (Figure 2).
VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions
2
3-1/2 (89)
Clearance Required
6-1/16
(154)
2-13/16
(71)
A
FIGVA9104X_dims
Port Marking
Locations
D
Figure 3: Field-Installed VA9104 Series Electric Actuator Dimensions with Optional M9000-561 Thermal
Barrier Dimensions, in. (mm)
Table 3: VA9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series NPT Ball Valves with Optional
Thermal Barrier Installed Dimensions, in. (mm)
Valve Size,
in. (DN)1
A
B
C
D
E
F
G
1/2 (DN15)
5-11/32 (135)
21/32 (17)
1-7/32 (31)
5-7/64 (129)
2-33/64 (64)
11/32 (9)
1-1/4 (32)
3/4 (DN20)
5-11/32 (135)
21/32 (17)
1-7/32 (31)
5-7/32 (133)
2-51/64 (71)
11/32 (9)
1-13/32 (36)
1 (DN25)
5-27/64 (137)
3/4 (19)
1-19/64 (33)
5-9/16 (141)
3-13/32 (87)
11/32 (9)
1-11/16 (43)
1.
Port A must always be connected to the coil (Figure 3).
Accessories
Table 4: Accessories (Order Separately)
Code Number
Description
M9000-200
Commissioning Tool That Provides a Control Signal to Drive 24 V On/Off, Floating, Proportional, and/or
Resistive Electric Actuators
M9000-561
Thermal Barrier Extends M(VA)9104, M(VA)9203, and M(VA)9208 Series Electric Spring Return
Actuator Applications to Include Low Pressure Steam (Quantity 1)
M9000-341
Weathershield Kit for VG1000 Series Ball Valve Application of M(VA)9104, M(VA)9203, and M(VA)9208
Series Electric Spring Return Actuators (Quantity 1)
VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions
3
FIG: hndl
Figure 5: Installing the Handle
FIG: CUPLACT
Mounting
Mounting the Actuator
To mount the actuator:
Figure 6: Coupling the Actuator to the Valve
1. Turn valve stem to position below.
2 Way
3 Way
FIG:VG1000
5. Install the valve actuator over the ball valve
mounting flange (Figure 6). Depending on the
installation, position the assembly in any one of
four 90° increments on the valve.
Note: For proper operation, the actuator must drive
the valve counterclockwise to open Port A when
viewed from above the valve.
6.
To secure the actuator to the valve, use a 1/4 in.
(6 mm) flat blade screwdriver. Recommended
torque is 8 to 12 lbin (0.9 to 1.4 Nm).
Figure 4: Positioning the Valve Stem
2. Mount optional M9000-561 Thermal Barrier to the
valve if fluid temperature exceeds 212°F (100°C).
See the Mounting the Thermal Barrier section for
more information.
3. Place the handle the top of the drive shaft
(Figure 5). The handle is keyed on and can only be
mounted in one orientation.
IMPORTANT: Do not overtighten the manual
handle mounting screw. Overtightening may strip
the threads resulting in damage to the valve stem
threads.
4. Check that the actuator coupler and handle are in
the fully counterclockwise position as viewed from
the top of the actuator. If not, press the actuator
gear release and rotate the handle until the
actuator coupler is fully counterclockwise.
VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions
4
Mounting the Thermal Barrier
2. Rotate the drive shaft to align marks on the top of
the thermal drive shaft with matching marks on the
valve stem.
Figure 7 shows the optional M9000-561 Thermal
Barrier.
3. Mount the thermal barrier onto the valve using the
four included M5x16 mm machine screws and four
M5 flange nuts. Tighten the screws to a
recommended torque of 21 to 25 lb·in.
(2.4 to 2.8 N·m) (Figure 9).
Machine Screws
Flange
Nuts
Barrier
Drive
Shaft
Figure 7: Optional M9000-561 Thermal Barrier
To mount the optional thermal barrier:
FIG:in_act
1. Install the thermal barrier drive shaft into the
thermal barrier by aligning the tab on the drive
shaft with the slot on the thermal barrier (Figure 8).
Figure 9: Installing the Barrier
4. Proceed to Mounting the Actuator. Follow the
same steps as mounting directly to the valve when
mounting the actuator to the thermal barrier.
Figure 8: Installing the Drive
Shaft into the Thermal Barrier
VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions
5
Wiring
(3.05 m) long cable; see Figure 10 for proper wiring.
DA
DA
BLK RED ORN
2
3
Risk of Electric Shock.
Disconnect the power supply before making electrical
connections to avoid electric shock.
~ AC 24 V
50/60 Hz
VA9104-xGA-2S ii07.cdr
1
Figure 10: VA9104-AGA-2S and
VA9104-IGA-2S Control Wiring Diagram,
Floating
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.
Note: When using the VA9104-AGA-1S or
VA9104-IGA-1S Series actuator with a controller
featuring triac output, add a 4.7k ohm resistor one half
watt between the Common (COM) and
Counterclockwise (CCW) terminals.
Risk of Property Damage.
Do not apply power to the system before checking all
wiring connections. Short circuited or improperly
connected wires may result in permanent damage to
the equipment.
Note: For all VA9104-AGA Series actuators, use a
controller and/or software that provides a timeout
function at the end of rotation (stall) to avoid excessive
wear or drive time on the actuator motor. The -GGA
and -IGA models have an auto shutoff feature to
prevent excessive wear or drive time on the motor.
VA9104-GGA-2S
The VA9104-GGA Series Electric Non-Spring Return
valve actuators require AC 24 V power and a
DC 0(2) to 10 V or 0(4) to 20 mA controller input signal.
These electric actuators include an integrated 120 in.
(3.05 m) long cable; see Figure 11 for proper wiring.
Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir
vérifié tous les raccords de câblage. Des fils formant
un court-circuit ou connectés de façon incorrecte
risquent d'endommager irrémédiablement
l'équipement.
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the VA9104 Series Electric Non-Spring Return
Valve Actuator.
VA9104-AGA-2S and VA9104-IGA-2S
The VA9104-AGA and VA9104-IGA Series Electric
Non-Spring Return valve actuators require an AC 24 V
input signal and work with a variety of controllers.
These electric actuators include an integrated 120 in.
VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions
6
DC 0(2)...10 V Control
BLK RED GRY ORN
3
1
2
4
AC
24 V
~
~
3
+
+
~
B
A
Y
AC
24 V
+
U
DC 0(2)...10 V
Y
DC 0(2)...10 V
+
+
DC 0(2)...10 V
U
U
COM
4
C
~
Y
DC 0(2)...10 V
0(4)...20 mA Control with
External Resistor
BLK RED GRY ORN
AC
24 V
BLK RED GRY ORN
3
4
1
2
AC
24 V
DC 0(2)...10 V
2
Override to MAX position
BLK RED GRY ORN
3
4
1
2
+
DC 0(2)...10 V
1
Override to MIN position
COM
A Open = MIN Position
A Closed = Normal Operation
B Closed = MAX Position
C Closed = Normal Operation
+
DC 0(4)...20 V
Y
Override to
MIN, MID, MAX positions
0(4)...20 mA Control with
External Resistor
BLK RED GRY ORN
+
U
Figure 11: VA-9104-GGA-2S
Control Wiring Diagram
1
3
2
Override to
MIN, MID, MAX positions
0(2)...10 V Control
BLK RED GRY ORN
4
3
1
2
4
+
A
A
B
B
AC
24 V
AC
24 V
~
0(4)...20 mA
C
+
U
C
+
100% ( MAX )
NORMAL
NORMAL
C
100% ( MAX )
B
0% ( MIN )
50% ( MID )
A
N
O
I
T
C
N
U
F
︶
0% ( MIN
50% ( MID )
Y
U
COM
C
B
A
N
O
I
T
C
N
U
F
COM
~
DC
0(2)...10 V
Y
500 Ω / 0.25 W
Figure 12: VA9104-IGA-2S Wiring
Diagram, On/Off
+
FIG:VA9104GGx2(Z)_wir
DC 0(4)...10 V
Figure 13: VA-9104-GGA-2S Control Wiring
Diagram (Overrides)
VA9104-GGA actuators are factory set for Direct
Acting (DA) mode and for a DC 0 to 10 V input control
signal. In DA mode, a minimum control signal drives
the actuator to the full CCW position, and a maximum
control signal drives the actuator to the full Clockwise
(CW) position.
VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions
7
Setup and Adjustments
For Reverse Acting (RA) operation, a minimum control
signal drives the actuator to the full CW position and a
maximum signal drives the actuator to the full CCW
position. To change the factory settings, remove the
actuator cover and adjust the switches on the circuit
board as shown in Figure 14.
Commissioning
After wiring is complete, apply power to the Variable Air
Volume (VAV) or Variable Air Volume and Temperature
(VVT) controller and provide input signals to the
actuator to drive it at least one complete cycle open
and closed.
Troubleshooting
If the VA9104 Series Electric Non-Spring Return Valve
Actuator is not responding or working properly:
Figure 14: VA9104-GGA Factory Switch Setting
•
verify that the actuator assembly is properly
secured to the valve.
•
check that all electrical connections are complete
and that power is applied.
•
verify that the valve fully opens and closes, using
the gear release button on the actuator and the
manual override handle, shown in Figure 5.
Repairs
If the VA9104 Series Electric Non-Spring Return
Actuator fails to operate within its specifications,
replace the unit. For a replacement electric actuator,
contact the nearest Johnson Controls representative.
Technical Specifications
VA9104-xGA-2S Electric Non-Spring Return Valve Actuators (Part 1 of 2)
Power Requirements
Control Type
AC 24 V +25%/-20% at 50/60 Hz, 2.3 VA (AGA), 2.9 VA (GGA), and
3.0 VA (IGA) Supply, Class 2 or Safety Extra-Low Voltage (SELV)
VA9104-AGA-2S
Floating or On/Off Control without Timeout
VA9104-GGA-2S
Proportional Control
VA9104-IGA-2S
Floating or On/Off Control with Timeout
VA9104-AGA-2S
AC 24 V +25%/-20% at 50/60 Hz, Class 2 or SELV without Timeout
VA9104-GGA-2S
DC 0 (2) to 10 V or 0 (4) to 20 mA with Field-Furnished 500 ohm Resistor
VA9104-IGA-2S
AC 24 V +25%/-20% at 50/60 Hz, Class 2 or SELV with Timeout
Feedback Signal
VA9104-GGA-2S
DC 0 (2) to 10 V for 90° Corresponds to Input Signal Span Selected
Motor Input Impedance
VA9104-AGA-2S
200 ohms Nominal
Control Input Impedance
VA9104-GGA-2S
Voltage Input: 200,000 ohm
Current Input: 500 ohm With Field-Furnished 500 ohm Resistor
Input Signal
Running Torque
35 lbin (4 Nm)
Travel Time
60 Seconds at 60 Hz (72 Seconds at 50 Hz) for 90° of Rotation
Rotation Range
93° ±3°, CW or CCW
Cycles
100,000 Full Stroke Cycles;
2,500,000 Repositions at Rated Running Torque
Audible Noise Rating
Electrical Connections
35 dBA Nominal at 39-13/32 in. (1 m)
VA9104-xGA-2S
120 in. (3.05 m) UL 444 Type CMP Plenum Rated cable with 19 AWG
(0.75 mm2) Conductors and 0.25 in. (6 mm) Ferrule Ends and Connector
for 3/8 in. Flexible Metal Conduit
VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions
8
VA9104-xGA-2S Electric Non-Spring Return Valve Actuators (Part 2 of 2)
Enclosure
Ambient Conditions
Fluid Temperature Limits
(Actuator and Valve
Assembly)
Compliance
VA9104-xGA-2S
NEMA 2, IP42
Operating
-4 to 140°F (-20 to 60°C); 90% RH Maximum, Noncondensing
Storage
-20 to 150°F (-29 to 66°C); 90% RH Maximum, Noncondensing
VG12x1 and
VG18x1 Series
23 to 203°F (-5 to 95°C)
VG12x5 and
VG18x5 Series
-22 to 212°F (-30 to 100°C)
VG12x5 and
VG18x5 Series
with M9000-561
Thermal Barrier
-22 to 284°F (-30 to 140°C) Water; 15 psig (103 kPa) at 250°F (121°C)
Saturated Steam
United States
UL Listed, CCN XAPX, File 27734
Plenum rated, UL2043, suitable for use in other environmental spaces
(plenums) in accordance with section 300.22.(c) of the National Electrical
Code
Canada
cUL Listed, CCN XAPX7, File 27734
Plenum Rated Per CSA 22.2 No. 236/UL 1995, Heating and Cooling
Equipment
Europe
Johnson Controls, Inc. declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive
and the Low Voltage Directive.
Australia and
New Zealand
RCM Mark, Australia/NZ Emissions Compliant
Shipping Weight
1.25 lb (0.55 kg)
European Single Point of Contact:
NA/SA Single Point of Contact:
APAC Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions
Published in U.S.A.
9