PAW GmbH & Co. KG Böcklerstr. 11, D-31789 Hameln, Germany Tel.: +49-5151-9856-0, Fax: +49-5151-9856-98 Email: [email protected], Web: www.paw.eu Installation and Commissioning Instructions Low Temperature Zone Module F33 - 1" (DN 25) 1 General information item no. 994736071xNA – version V01 – issued 2008/02 PAW GmbH & Co. KG We reserve the right to make technical changes without notice! Böcklerstr. 11 Printed in Germany – Copyright by PAW GmbH & Co. KG 31789 Hameln, Germany 994736071xNA – V01 2008/02 1 General information Contents 1 General information............................................................................................................. 4 1.1 Scope of these instructions .......................................................................................... 4 1.2 Designated use............................................................................................................. 4 2 Safety instructions ............................................................................................................... 5 3 Product description.............................................................................................................. 6 3.1 Equipment .................................................................................................................... 7 3.2 Function...................................................................................................................... 10 3.2.1 Mixing valve [specialist] .......................................................................................... 11 3.2.2 Check valve [specialist] .......................................................................................... 14 3.3 4 Accessories: Actuator (not included in delivery) ......................................................... 15 Assembly and installation [specialist] ................................................................................ 16 4.1 Option 1: Installation of the manifold .......................................................................... 16 4.2 Option 2: Installation of the wall brackets with mounting plate ................................... 17 4.3 Installation of the zone module and commissioning ................................................... 18 4.4 Accessories: Compression-ring coupling (not included in delivery)............................ 21 5 Scope of delivery [specialist] ............................................................................................. 22 6 Technical data................................................................................................................... 23 6.1 Pressure drop ............................................................................................................. 24 1 General information 1 General information 1.1 Scope of these instructions These instructions describe the function, installation, commissioning and operation of the F33 low temperature zone module. For other components of the installation, such as pumps, controllers and manifolds, see the manufacturers' instructions. The chapters called [specialist] are directed to specialists only. 1.2 Designated use The zone module may only be used in hydronic heating closed-loop systems taking into consideration the technical limit values indicated in these instructions. The zone module must not be used in any applications for fuel or oil and domestic water applications such as jacuzzis. The wrapping materials are made of recyclable materials and can be disposed of with recyclable materials. 994736071xNA – V01 2008/02 2 Safety instructions 2 Safety instructions The installation and commissioning of the zone module as well as the connection of electrical components require technical knowledge commensurate with a recognised vocational qualification as a fitter for plumbing, heating and air conditioning technology, or a profession requiring a comparable level of knowledge [specialist]. The following must be observed during installation and commissioning: • Relevant local and national prescriptions • Accident prevention regulations of the professional association • Instructions and safety instructions mentioned in these instructions All field wiring made during installation must comply with: • National Electrical Code NFPA 70 and any other national, state, provincial or local codes or requirements • In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any other local codes Attention The F33 PAW zone module may only be used in hydronic heating closedloop systems taking into consideration the technical limit values indicated in these instructions. The zone module must not be used in any applications for fuel or oil and domestic water applications such as jacuzzis. Attention: Material damage due to mineral oils! It is imperative to avoid that the EPDM sealing elements of the station get in contact with substances containing mineral oils. Mineral oil products cause lasting damage to the material, whereby its sealant properties are lost. If necessary, ask the manufacturer whether the solar fluid, fats or installation aids contain mineral oils. We do not assume liability nor provide warranty for damage to property resulting from sealants damaged in this way. 3 Product description Attention: overheating The in-line aquastat has to be installed to the supply pipe in any case! Only in this way it is possible to securely avoid overheating of the circuit and damage of the floor covering. 3 Product description The F33 zone module is a preassembled fitting group for hydronic heating closed loop systems. It is equipped with isolation valves, so that the pump can be easily maintained or changed. It is designed such that it can be directly mounted onto a PAW distribution manifold or a mounting plate with thread connections. Only use PAW accessories in combination with the zone module. 994736071xNA – V01 2008/02 3 Product description 3.1 Equipment F-1 A-1 A-1 Supply (zone) A-2 Ball valve in the supply with integrated temperature gauge F-2 handle A-2 B-1 E B D D-1 C C-5 C-2 C-1 B-1 Swivel flanges B 3-speed pump C 3-way mixing valve with adjustable bypass 0-50% C-1 Supply (boiler loop) C-2 Return (boiler loop) C-5 Flow check valves D-1 D Return pipe E Design insulation with optimized function F-2 Ball valve in the return with integrated temperature gauge handle F-1 Return (zone) 3 Product description The F33 is equipped with swivel flanges for the integration of flanged and 90° rotated flanged pumps. 994736071xNA – V01 2008/02 3 Product description The insulation consists of three parts: • the front shell (E-1) • the back shell (E-2) • and the return pipe insulation (E-3) If the pump is too large, you can use an appropriate knife and cut a hole into the front insulation shell along the pre-cut lines. E-1 E-2 E-3 3 Product description 3.2 Function F33 - Low temperature zone module with 3-way mixing valve The supply temperature of the zone module is controlled by the integrated mixing valve. Hot supply water and cold return water are mixed to obtain the desired supply temperature of the zone module. The supply temperature is adjusted with a thermostatic head and an aquastat. The three-way actuator is continuously adjustable (closed… completely open) The rate of pre-mixing can be adjusted at the mixing valve bypass and up to 50% of cold return water are mixed to the hot supply water. Example: Radiant heating systems require a low temperature level with small temperature differences and high flow rates. It is therefore sufficient to mix the return water that is still quite warm with only a small amount of hot water. Applications • Zones with supply temperature that are considerably lower than the boiler supply temperature • Small zones with low power outputs and few requirements regarding the control 994736071xNA – V01 2008/02 3 Product description 3.2.1 Mixing valve [specialist] The supply temperature of the zone module is controlled by the mixing valve. Hot water from the boiler and cold return water are mixed to obtain the desired supply temperature. The mixing valve is suitable for low temperature heating zones which are operated with a constant supply temperature. In case of maintenance of the mixing valve, please order the special gasket set which is available as spare part. zone return supply C-4 bypass screw C-3 C-5 adjustment check valve knob return supply boiler loop 3 Product description F33 is designed to provide constant C-6 supply temperatures to the radiant system. Depending on the geographic location of the installation, periodic adjustments to the temperature may or may not be necessary. The thermostatic head (C-6) serves to adjust the desired supply temperature. Rotating the dial of the thermostatic head to a higher number will provide for hotter temperatures. The designer of the radiant system must ensure that the range of temperatures provided by the control is suitable for the installation. The mixing valve is equipped with an additional flow channel serving as adjustable bypass. Through the bypass water from the return is being mixed to the outgoing supply. Like this, the flow temperature sinks, but the flow inside the system rises. The following diagram shows the relationship between the warm-up time and the position of the bypass.The bigger the volume flow and the more open the bypass, the longer it takes to reach adjusted temperature. 994736071xNA – V01 2008/02 3 Product description 1. During the start-up of the system, determine the correct bypass position in a trial and error process. • When the bypass screw (C-4) is turned by 90° so that the slot is in a vertical position, the bypass is closed. Usually, this is the operation position for smaller floor zones. The temperature might be a bit higher than adjusted on the thermostatic head. C-4 • When the slot of the bypass screw (C-4) is in horizontal position, the bypass is completely open. This means that the biggest possible flow volume flows from the return to the supply. The supply temperature is reduced and might even be lower than adjusted on the thermostatic head. 2. Check the bypass adjustment during operation. Take care that there is a sufficient flow volume to the radiant floor and that the desired temperature is reached 3 Product description 3.2.2 Check valve [specialist] The zone module F33 is equipped with a check valve in the return pipe (D-1) and in the return of the mixing valve (C-5). The check valve is spring-operated. The opening pressure is 2 kPa. Operation During operation the mark must be directed to "Z". Æ The check valve is operating. Æ Flow only in one direction For filling, emptying and bleeding Filling, emptying, bleeding the mark must be directed to "A". Æ The check valve is lifted (not operating) Æ Flow in both directions 994736071xNA – V01 2008/02 3 Product description 3.3 Accessories: Actuator (not included in delivery) The PAW actuator type SR10 - 24/3P is available as an accessory (item # 7054). It is for weathercompensated control and includes a cable and a mounting set for halting assembly onto the PAW mixing valves. It operates the mixing valve. 4 Assembly and installation [specialist] 4 Assembly and installation [specialist] The F33 zone module must be mounted either on a PAW distribution manifold or on a set of wall bracket and mounting plate. The distribution manifold, the wall brackets and the mounting plate are not included in delivery. Attention The location of installation must be dry, load-carrying and frost-proof to prevent material damage to the installation. 4.1 Option 1: Installation of the manifold 4 13/32" (112 mm) 1 3/8" (35 mm) 2 5/32" 1 (55 mm) Install the distribution manifold to the wall either with wall brackets (1) or onto a mounting plate (2) as described in the instructions. 2 If possible, choose the largest distance to the wall, so that the insulation of the manifold can be easily mounted and changed. 994736071xNA – V01 2008/02 4 Assembly and installation [specialist] 4.2 Option 2: Installation of the wall brackets with mounting plate 3. Choose the position for installation. 4. Copy the mounting holes for the wall bracket onto the mounting surface. 5. Drill the holes and insert the wall anchors. 6. Fix the wall bracket to the wall with the screws and washers. 7. Screw the mounting plate onto the wall bracket. 4 Assembly and installation [specialist] 4.3 Installation of the zone module and commissioning The zone module can be installed • Option 1: on a PAW distribution • manifold Option 2: on a PAW mounting plate with thread connections zone zone return supply return supply return return supply supply boiler loop boiler loop 994736071xNA – V01 2008/02 4 Assembly and installation [specialist] 1. Take off the temperature gauge flange handles (A-2, F-2) and remove the (top view) 1 front insulation shell (E-1) of the zone nut 2 module. Remove the return pipe insulation (E-3). 2. Screw off the union nuts (C-1, C-2) 3 and take off the sealing rings of the zone module. 3. Flip the two nuts over the two flanges flange (side view) as shown in the figure. 4 Assembly and installation [specialist] 3. Insert the sealing rings into the nuts. sealing ring 4. Put the zone module onto the two nuts. 5. Tighten the nuts. Take care that the nuts do not get jammed and that the sealing rings do not slip. 6. Connect the upper connections (A-1, F-1) of the zone module to the installation. The connection must be stress-free. 7. Connect the distribution manifold or the lower connections of the mounting plate to the boiler (do not forget the F-1 sealing rings). The connection must be A-1 stress-free. 8. Connect the pump (B) to the controller. A-2 F-2 9. Connect the aquastat to the upper supply pipe. B-1 E 10. Check and tighten all the thread connections and union nuts, then carry D B out the pressure test. 11. Mount the return pipe insulation (E-3) and the front insulation shell (E-1) of D-1 C C-5 the zone module and attach the temperature gauge handles (A-2, F-2). Mount the insulation of the distribution C-2 manifold. C-1 994736071xNA – V01 2008/02 4 Assembly and installation [specialist] 4.4 Accessories: Compression-ring coupling (not included in delivery) The connection to the heating installation can be carried out fast, pressure-proof and without soldering when you use the optionally available compression-ring couplings. 1. Push the union nut ② and the ring ③ onto the copper pipe ①. To guarantee secure load transmission and sealing, the pipe must extend at least 3/8" (3 mm) out of the ring. 2. Insert the support sleeve ④ into the copper pipe. 3. Insert the copper pipe with the plugged-on individual parts (②, ③ and ④) all the way into the housing of the compression-ring coupling ⑤. 4. First screw the union nut ② manually. 5. Tighten the union nut ② by rotating one full turn. Secure the housing of the compression-ring coupling ⑤ against distort in order to avoid damaging the sealing ring. Not included in delivery! 5 Scope of delivery [specialist] 5 Scope of delivery [specialist] 994736071xNA – V01 2008/02 6 Technical data 6 Technical data F33 1" DN 25 Dimensions " mm Center distance (1) 4 21/32 125 Total width (2) 9 27/32 250 Total height (3) 15 1/32 382 Installation length (4) 18 3/16 462 Connections Zone module outlet (A-1, F-1) 1" female thread Zone module inlet (C-1, C-2) 1½" male thread Technical data Opening pressure check valve (C-5, D-1) 2 kPa can be opened Materials Fittings Brass Gaskets EPDM/NBR Insulation (E) EPP 3 4 F-1 A-1 C-2 C-1 E D-1 C-5 1 2 6 Technical data F33 1" DN 25 Pressure, maximum 116 psi 8 bars Temperature, maximum 230 °F 110 °C CV value 4.4 Hydraulics 6.1 Pressure drop Flow rate [USgpm] 0,5 1 1,5 2 2,5 3 3,5 4 21,0 18,0 Wilo-Star-S21 U25 15,0 12,0 9,0 6,0 Pressure [ft head] Pressure [mmwc] 0 7,0 6,5 6,0 5,5 5,0 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0,0 K33 - DN 25 3,0 0 100 200 300 400 500 600 700 800 900 0,0 1000 Flow rate [l/h] 994736071xNA – V01 2008/02
© Copyright 2026 Paperzz