DIGITAL POWER MULTI METER XCM-110

DIGITAL POWER MULTI METER
XCM-110-X31 Series
“COLOR MULTI”
Backlight Color Changing
*LCD backlight color from GREEN to RED
by being in conjunction with alarm
activation
Reader- Friendly LCD
1. 3 levels of digits and bargraph display
2. Blinking alarm announcing
3. Large digits and bargraph
Variety of Display Patterns
☆Size 110 x 110 mm
☆3P4W/3P3W
☆Aux.Power AC85~264V
1. Variety of display patterns
2. By selecting [P-00] as display pattern,
an optional display pattern chosen
Max. 9 pages of display patterns
available
Output Option
1. Alarm
2. Pulse
3. RS-485 (Modbus)
TAKEMOTO Various Power Meters
* XM/XCM-110-X55: Open Phase Detection
* XM/XCM-110-X75: Harmonic Detection
LCD Panel
6
4
7
1
9
8
2
13
12
5
10
14
3
11
1. LEAD/LAG
Illuminates when var or PF is shown
2. Over Scale
Illuminates when measuring value
exceeds the max. value
3. Scale factor
Shows the scale factor of watt hour
or var hour
4. Alarm
AL1 and AL2 blinks when alarm
occurs. (This is available when alarm
output is selected as an option.)
5.Reactive Power Lead/Lag
Shows the integral direction of
reactive power
6. Contact input status
Shows CH when contact input is on
7. Bargraph
Bargraph display with 31 dots
8. Bargraph Display Unit
Shows measuring unit
9. Upper Digital
Digital display with phase type on the
upper left and unit on the right of the
digits
10. Middle Digital
Digital display with phase type on the
upper left and unit on the right of the
digits
11. Lower Digital
Digital display with phase type on the
upper left and unit on the right of the
digits
12. Under Scale
Illuminates when measuring value
exceeds the min. value
13. Max. and Min
Illuminates while max. or min. value
is displayed
14. Incoming / Outgoing
Displays when watt, var, watt hour, or
var hour is displayed
Key Operation
To switch the phase of voltage and current
2. SET
To display the primary value of the digital displays by holding
down of [SET]
3. MAX/MIN To switch Max, Min, and instantaneous values
4. +
To switch detail display mode (reset of each max. and min. value,
the phase type of the bargraph, and switching mode of harmonic
measurement order by holding down
5. To show status mode of contact inputs, if the option is chosen,
and 3-phase status by holding down
6. SET + + To switch setting mode to configure display, VT and CT primary
rating and each output by holding down
7. SET + - To switch the extended setting mode (Refer to extended manual
1. DISPLAY
http://www.takemotodenki.com/detail_product.php?at=131
8. MAX/MIN + RESET To reset max. and min. value by holding down
Setting Mode
To switch and move to the setting mode, hold down of SET + + .
The number of steps indicates on LCD such as S01 for the fist step at the
setting mode
- By pressing + / - , switch setting steps between S02, S03, S04, S05,
and S06.
By pressing SET , the setting mode switches to the setting item display
such as S01-01
- With + / - , switch from S01-01, S01-2, S01-3… to S01-40
Table 1
0
1
2
3
4
5
K
L
M N O P
6
Digital Display
7
8
9
A
B
Q R S
T
U V
C D E
F
G H
W X
Z
# $ / SP
Y
I
J
Table 2 Button operation at setting
Button
Display (Illuminating)
Modify setting (Flashing)
SET
+
-
Start
To next screen
To previous screen
Set up the change
Setting value +
Setting value -
RESET
To upper screen
Cancel setting and to upper screen
MAX/MIN
-
-
DISPLAY To measuring screen
Cancel setting and to measuring screen
Terminals
Measurement
No. 3P3W
P
1
N
2
E
3
SW1
4
SW2
5
NC
6
NC
7
V1
8
NC
9
V3
10
V2
11
1S
12
1L
13
3S
14
3L
15
3P4W
P
N
E
SW1
SW2
2S
2L
V1
V2
V3
VN
1S
1L
3S
3L
Modbus Output
Option Type
No.
8
9
10
11
12
13
14
15
16
18
20
22
24
26
28
30
17
19
21
23
25
27
29
31
1
2
3
4
5
6
7
M10
M20
17 16
RS-
RS+
RS
RS+
19 18
SL
Ter
SL
Ter
21 20
DI2
DI1
DI2
DI1
DI3
COM
DI3
23 22 COM
25 24
PLS
ALM1
27 26
ALM
ALM2
29 28
NC
NC
*Do not connect to NC
Connection Diagram
3 Phase 3 Wire
(1)
Source
R
S
Aux. Power
+(P) -(N)
T
8
9
10
11
12
13
14
15
V1
V2
V3
1S
1L
3S
3L
1
2
3
4
5
6
7
1. VT unnecessary at
direct voltage input
2. Earth connection of
VT/CT unnecessary when
low voltage circuit on the
primary side
3. Recommend to add
input between V1-VN (No.
8-9) for proper measuring
+(P)
-(N)
E
SW1
SW2
Load
(2)
3 Phase 4 Wire
Aux. Power
Source
R
S
T
+(P) -(N)
N
V1
V2
V3
VN
1S
1L
3S
3L
2S
2L
Load
8
9
10
11
12
13
14
15
1
2
3
4
5
6
7
+(P)
-(N)
E
SW1
SW2
2S
2L
Dimensions and Panel Cutout
(1)
Dimensions
110±1
18
16
88±1
100Φ±1
110±1
M5 screws
SET
M3
screws
(2)
17
19
21
23
25
27
29
31
+
-
DISPLAY
RESET MAX/MIN
16
18
20
22
24
26
28
30
8
9
10
11
12
13
14
15
Panel Cutout
Weight 600g.
1
2
3
4
5
6
7
Attention: Inner dimensions of screws
M4 screws (8.6±0.5mm)
M3 screws (6.4±0.5mm)
M4
screws
90±0.5
102Φ
90±0.5
2-6Φ
Display Settings
[DISPLAY]
A
[SET]+[+]
[SET]
[+][-]
Blinking
[SET]
S01-01: Display Pattern
Pattern types are from
P-01 to P-15
[SET]
When P-00 is
chosen, move to
optional display
pattern
[
+] ]
[[+
[-]
[SET]
A
[DISPLAY]
[+][-]
Blinking
S01-02: Optional
Display Pattern
“Bargraph”
(P-00)
[SET]
+]
[[ +
]
[
[- ]
[SET]
A
[DISPLAY]
[+][-]
Blinking
S01-03: Optional
Display Pattern
“Upper Digits”
(P-00)
[SET]
[[+
+] ]
[-]
[SET]
A
[DISPLAY]
[+][-]
Blinking
S01-04: Optional
Display Pattern
“Middle Digits”
(P-00)
[SET]
+]
[[ +
]
[- ]
[SET]
A
[DISPLAY]
[+][-]
Blinkng
S01-05: Optional
Display Pattern
“Lower Digits”
(P-00)
[SET]
+]
[[ +
]
…
[- ]
[- ]
+]
[[ +
]
There are 2nd to 9th pages as optional display patterns
after the 1st page. The operation for the settings is the
same as above, from bargraph to lower digits settings.
[SET]
A
[DISPLAY]
[+][-]
S01-38: Backlight Mode
ON/AUTO/OFF
Blinking
[SET]
[- ]
+]
[[ +
]
[SET]
A
[DISPLAY]
[+][-]
Blinking
[SET]
S01-40:
Backlight Brightness
S01-01: Display Pattern
There are 15 kinds of patterns for display. The default is P-01. Refer to Table 3.
Table 3
Pattern No.
P-01
P-02
P-03
P-04
P-05
P-06
P-07
P-08
P-09
P-10
P-11
P-12
P-13
P-14
P-15
P-00
Display Patterns
Bar
Upper
Middle
Lower
PF
PF
PF
PF
A
DA
DA
DA
DA
A
PF
PF
A
A(R)
V(RY)
Optional
V
V
A
V
V
MDA
MDA
MDA
MDA
V
Hz
Hz
V
A(R)
V(RY)
Optional
A
A
W
W
W
A
A
V
W
W
W
var
A
A(Y)
V(YT)
Optional
W
Wh
Wh
Wh
Wh
V
Wh
Wh
Wh
var
Wh
varh
1. Bargraph scales of watt, var,
Power Factor and frequency
are configurable. Refer to the
extended manual on Takemot’s
website:
http://www.takemotodenki.co
m/detail_product.php?at=131
2. However, if [P-00], optional
display patterns, is chosen,
changing the settings is not
available.
A(B)
V(BR)
Optional
S01-02 to S01-37:
:Optional Display Patterns
Max. 9 pages, 1 page consists of bargraph, upper, middle and lower digits, of optional
display patterns are available in this meter. Display changes by pressing [DISPLAY].
Example of optional display pattern settings
1
2
3
4
5
6
7
Bargraph
Upper Digital
Middle Digital
Lower Digital
AR
AR
AS
AT
VRS
VRS
VST
VTR
[DISPLAY]
W(+)
SP
SP
W(+/-)
END
END
END
END
END
END
END
END
END
END
END
END
END
END
END
END
8
9
END
END
END
END
END
END
END
END
1. [END](code: 999) means the end
code for the display table. If this
code is selected, return to the 1st
page with [DISPLAY].
2. [SP] (code: 000) means no display.
3. Batch (code: 010, 020, 030,
080,090130,140,150,160). If this
code is selected, switch phase for
display with [DISPLAY].
4. Code list is on page 15 and 16.
[DISPLAY]
[DISPLAY]
S01-38:
:Backlight Mode
There are 3 options of backlight illuminating patterns
by setting
Setting Value
Details
ON
AUTO
OFF
Always on
Turns on by pressing a button or SW1 or 2 input, and turns off after 5 mins of any
other operation
Always off
S01-40:
:Backlight Brightness
5 levels of brightness are available.
Setting Value
1
2
Brightness
Bright
3
4
5
Dark
Settings for Measuring
[DISPLAY]
A
[SET]+[+]
+] ]
[[+
Display
3P3W
3P4W
[[-
-] ]
[SET]
[SET]
Setting Value
3 Phase 3 Wire
3 Phase 4 Wire
S02-01: Phase Type
[+][-]
Blinking
[SET]
[-]
+] ]
[[+
[SET]
[+][-]
[SET]
[-]
+] ]
[[+
[SET]
[+][-]
[SET]
[-]
With
MAX/MIN
Switching
Digit No.
S02-02: VT Primary
Side Rating
+] ]
[[+
[SET]
[+][-]
[SET]
[-]
With
MAX/MIN
Switching
Digit No.
S02-07: Voltage
Input Rating
(110V,220V,440V)
With
MAX/MIN
Switching
Digit No.
S02-03: CT Primary
Side Rating
+] ]
[[+
[SET]
[+][-]
S02-04:Frequency
(50Hz/ 60Hz)
Blinking
[SET]
[-]
+] ]
[[+
[SET]
[+][-]
Blinking
S02-05: Demand
Current Time Setting
(Continuously
caluculates with 0 sec
setting )
[SET]
[-]
+] ]
[[+
[SET]
[+][-]
Blinking
[SET]
S02-06: Demand
Watt Time Setting
S02-01: Phase Type
When you start setting up,
・ each measuring max. and min. value is reset.
・ Watt hour value, collected before change
settings, integrates to data collected after
setting up
・ demand current (DA) and demand watt (DW)
start from zero 0.
・ all the setting values turn to default value.
S02-07: Voltage Input Rating
・ Be sure to configure rated voltage
・ When 110V is selected, the range of
input voltage is 0 to 150V.
・ When 220V is selected, the range of
input voltage is 0 to 300V.
・ When 440V is selected, the range of
input voltage is 0 to 500V.
S02-02: VT Primary Side Rating
Setting up for voltage primary side rating (VT)
・ Voltage, Watt, and watt hour culcurate with
VT primary value and display.
・ Watt hour value, collected before change
settings, integrates to data collected after
setting up.
・ Demand Watt (DW) starts from 0.
・ Each measuring max. and min. value is reset.
S02-03: CT Primary Side Rating
Setting up for current primary side rating (CT)
・ Current, watt, var, watt hour and var hour
culcurate with VT primary value and display.
・ Watt hour and var hour values, collected before
change settings, integrates to data collected
after setting up
・ Demand Current (DA) and Demand Watt (DW)
start from0.
・ Each measuring max. and min. value is reset.
S02-04: Frequency
・ Setting up for frequency
VT Primary Side Rating
Setting
Value
110V
220V
220V
440V
3300V
6600V
11kV
22kV
33kV
66kV
77kV
3 Digits
4 Digits
110V
220V
220V
440V
3.30kV
6.60kV
11.0kV
22.0kV
33.0kV
66.0kV
77.0kV
110.0V
220.0V
220.0V
440.0V
3300V
6600V
11.00kV
22.00kV
33.00kV
66.00kV
77.00kV
CT Primary Side Rating
Setting
Value
5A
10A
15A
20A
25A
30A
40A
50A
60A
75A
80A
100A
120A
150A
200A
250A
300A
400A
500A
600A
750A
800A
1000A
1200A
1500A
2000A
2500A
3000A
4000A
4500A
5000A
6000A
7500A
8000A
・ When measuring frequency is affected by
harmonics and the value deviates from the range
of 45Hz-65Hz, continue measuring at set frequency value.
3 digits
4 digits
5.00A
10.0A
15.0A
20.0A
25.0A
30.0A
40.0A
50.0A
60.0A
75.0A
80.0A
100A
120A
150A
200A
250A
300A
400A
500A
600A
750A
800A
1.00kA
1.20kA
1.50kA
2.00kA
2.50kA
3.00kA
4.00kA
4.50kA
5.00kA
6.00kA
7.50kA
8.00kA
5.000A
10.00A
15.00A
20.00A
25.00A
30.00A
40.00A
50.00A
60.00A
75.00A
80.00A
100.0A
120.0A
150.0A
200.0A
250.0A
300.0A
400.0A
500.0A
600.0A
750.0A
800.0A
1000A
1200A
1500A
2000A
2500A
3000A
4000A
4500A
5000A
6000A
7500A
8000A
RS-485 Communication Settings
[DISPLAY]
A
S04-01: RS-485 Address Setting (0- 255 at Decimal Digit)
[SET]+[+]
①
[SET]
[SET]
[+][-]
②
①
[SET]
[SET]
[SET]
[+]
[+]
…
[-]
[-]
[DISPLAY]
+] ]
[[+
[-]
[+][-]
+] ]
[[+
S04-02: Communication Speed
A
Comm. Speed setting value
Display
Speed
[SET]
[SET]
Parity/Stop bit
Display
N-1
E-1
O-1
N-2
E-2
O-2
[- ]
Parity/Stop bit
NON・1
EVEN・1
ODD・1
NON・2
EVEN・2
ODD・2
[+]
②
[+][-]
+]
[[ +
]
12
24
48
96
192
1200BPS
2400BPS
4800BPS
9600BPS
19200BPS
S04-03: Parity/Stop bit
Setting method is the same as the
“Communication Speed” setting
Connection Diagram
+
SL
Ter
S04-01: RS-485 Address Setting
・ Each meter necessarily needs each different
address setting due to polling system.
・ Setting “0” zero as an address means
exclusion from communication (no response
from the master).
S04-02: RS-485 Communication Speed
・ Communication speed needs to match with the spec of the master.
DO NOT CONNECT SUCH AS THE FOLLOWING WAYS
Pulse Output Settings
[DISPLAY]
A
S05-01 : Pulse Output 1
[SET]+[+]
[SET]
[SET]
Pulse Output
[+][-]
Blinking
[SET]
[+]
[+]
[-]
[DISPLAY]
[-]
A
…
[-]
+] ]
[[+
S05-02 : Pulse Output 1 Scale Factor
[[+
+] ]
[SET]
[+][-]
Blinking
[SET]
[DISPLAY]
[-]
A
Scale Factor
Display
0.01k
0.1k
+] ]
[[+
1k
S05-03 : Pulse Output 2
ATTENTION
10k
1. Set pulse output
value under 12000
pulse/hour.
2. When variable of
watt hour at 0.5
second exceeds 1
pulse, the pulse
might output in
clusters by setting
of CT/VT ratio.
Setting
Item
value
000
None
171
+Wh
172
-Wh
181
+varh LAG
182 +varh LEAD
183
-varh LAG
184
-varh LEAD
[SET]
[+][-]
100k
Blinking
[SET]
[DISPLAY]
[-]
A
1M
10M
+] ]
[[+
Scale Factor
0.01kWh(kvarh)
/Pulse
0.1kWh(kvarh)
/ Pulse
1kWh(kvarh)
/ Pulse
10kWh(kvarh)
/ Pulse
100kWh(kvarh)
/ Pulse
1MWh(Mvarh)
/ Pulse
10MWh(Mvarh)
/ Pulse
S05-04 : Pulse Output 2 Scale Factor
[SET]
[+][-]
Brinking
A
[DISPLAY]
[SET]
Connection Diagram
pulse output + alarm output
pulse output x2
Pulse 1
Pulse
Pulse 2
Alarm
Settings of Alarm Output
[DISPLAY]
A
S06-01 : Alarm Output 1
[SET]+[+]
[SET]
[SET]
[+][-]
Blinking
+] ]
[[+
[SET]
[DISPLAY]
[-]
[-]
A
…
[-]
+] ]
[[+
S06-02 : Alarm Output 1 Setting Value (Configurable
between 0-100% of primary side rating value)
+] ]
[[+
①
[SET]
[+][-]
②
[+][-]
[SET]
①
[SET]
[DISPLAY]
Please refer to
extended manual
for setting of
alarm upper and
lower limits,
relay time, and
recovery options.
[-]
A
[+][-]
②
[SET]
[SET]
+] ]
[[+
S06-03 : Alarm Output 2 (Refer to page 15 and 16)
[SET]
[+][-]
Blinking
[SET]
[DISPLAY]
[-]
A
+] ]
[[+
S06-04 : Alarm Output 2 Setting Value (Configurable
between 0-100% of primary side rating value)
A
[DISPLAY]
[SET]
Setting method is the same as the
“Communication Speed” setting
S06-02,04: Alarm Output 1 and 2 Setting
S06-01,03: Alarm Output 1 and 2
Setting of each alarm output measuring
Value
・Setting value of alrarm outputs
items
・Output measuring value≧setting value
Connection Diagram
alarm output x2
pulse+ alarm outputs
Pulse
Alarm 1
Alarm
Alarm 2
Advanced Display
Viewing hidden measuring values, extended current measurement and value at each order
and phase of harmonics measurement
Operation steps for
Switches
SET
+,RESET
[+]
[+]
MAX/MIN
Current
Switch
DISPLAY
[- ]
[+ ]
DISPLAY
for 3 sec
Operation
Switch of
bargraph phase
[-]
Voltage
[- ]
Switch
Operation
Switch
Operation
DISPLAY
Switch of
bargraph phase
DISPLAY
Switch of degree
[- ]
[+ ]
[+ ]
Voltage Harmonics RS(RN) Line
[+ ]
[- ]
[- ]
[+ ]
[- ]
Switch
Opration
Switch of
bargraph phase
[+ ]
Var hour
[- ]
[+ ]
Demand Watt
[-]
[+]
Operation
Switch of degree
[+ ]
Demand Current
DISPLAY
Switch
DISPLAY
Extended Current
[- ]
[+ ]
Operation
Switch of degree
Current Harmonics R Phase
[- ]
[+ ]
Switch
DISPLAY
[+ ]
Frequency
[- ]
Operation
Switch of degree
Current Harmonics T Phase
Power Factor cosɸ
[- ]
Switch
DISPLAY
[+ ]
var
[- ]
To measuring screen
Voltage Harmonics ST(TN) Line
Watt
[- ]
Operation
Displaying primary rating
Swtching screens
Reset max. &min. values
Switching max.&min.
values
[+ ]
Watt hour
Status
Phase Display
1. Shows voltages phase’s status at bargraph.
(The bar’s move to the right is positive phase.)
2. Shows watt status at each phase with digits.
3. Returns to the measuring screen by pressing [DISPLAY]
[-]
[-
[-]]
[[[+
+
+] ]]
Contact Input Display
1. Shows the status of contact signal: on/off
2. Shows the status of DI 1, DI 2, DI 3 from the left
3. Status ON when the bar is on the upper
(Example on the left explains Ch2 is on.)
4. Displays when communication output is selected.
5. Returns to the measuring screen by pressing [DISPLAY]
Backlight Color Changing Function
Backlight changes color from green to red
when alarm turns “ON”.
Backlight changes color from green to red
when DI turns “ON” from “OFF.
[-]
-
Switch display
Switch setting item
[RESET]
-
Max/Min reset
Return to the previous
screen
Setting
Deciding setting
value
Increase setting value
Decrease setting
value
Return to the previous
screen
-
-
Return to measuring
display screen
-
-
Return to measuring
display screen
-
-
[SET]
[+]
Measuring Display
Detail Display
While pressing primary rating value/ integral
lower digit display
Switch display
-
[MAX/MIN]
Switch display of instantaneous, max. and min.
values
[DISPLAY]
Switch display
[+] for 3 sec
[-] for 3 sec
To detail display
To status
[RESET]
for 3 sec
Reset alarm (when
alarm reset by manual)
[SET]+[+]
for 3 sec
[SET]+[-]
for 3 sec
[MAX/MIN]+
[RESET] for
3 sec
-
-
Reset max. and min.
(only the displayin
items)
Setting Mode
To setting value
changing mode
Switch setting item
To setting mode
-
-
-
To setting mode
(extended)
-
-
-
Reset max. and min.
-
-
-
(Attention) Please refer to extended manual for the settings of the communication output
range, alarm relay, alarm recovery options, alarm upper and lower limits, a blinking
announcing when a value exceeds a limit and uni/bi direction of bargraph.
Communication, Pulse, and Alarm Output Code
No.
000
010
011
012
013
014
020
021
022
023
030
031
032
033
040
041
042
050
051
052
060
061
062
063
064
070
071
072
080
081
082
083
084
090
091
092
093
094
100
Items
None
Current Max. Phase
R Phase Current
S Phase Current
T Phase Current
N Phase Current
(3P4W)
Voltage line to line
R-S Line Voltage
S-T Line Voltage
T-R Line Voltage
Phase Voltage Max. Phase
(3P4W)
R-N Phase Voltage
(3P4W)
S-N Phase Voltage
(3P4W)
T-N Phase Voltage
(3P4W)
Watt (+)
Watt (±)
Watt (-)
var
(Lag)
var
(Lead/Lag)
var (var Correction)
Power Factor
(Lead50%~100~Lag50%)
Power Factor
(Lead0%~100~Lag0%)
Power Factor
(Tide Correction)
Power Factor
(Lead0.5~1~Lag0.5)
Power Factor
(Lead0~1~Lag0)
Frequency (45~65Hz)
Frequency (45~55Hz)
Frequency (55~65Hz)
Demand Current
Max. Phase
R Phase Demand Current
S Phase Demand Current
T Phase Demand Current
N Phase Demand Current
(3P4W)
Max. Demand Current
Max. Phase
R Phase Max. Demand
Current
S Phase Max. Demand
Current
T Phase Max. Demand
Current
N Phase Max. Demand
Current (3P4W)
Demand Watt
Bar
○
○
○
○
○
Upper
○
○
○
○
○
Mid
○
○
○
○
○
Lower
○
○
○
○
○
Comm
Pulse
○
○
○
○
Alarm
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
No.
110
120
130
131
132
133
140
141
142
143
150
151
152
153
160
161
162
163
171
172
181
182
183
184
999
Items
Max. Demand Watt
Extended Current
th
(5 extension)
Current Harmonics
Effective Value Max. Phase
R Phase Current Harmonics
Effective Value
S Phase Current Harmonics
Effective Value (3P4W)
T Phase Current Harmonics
Effective Value
Current Harmonics
Distortion Rate
R Phase Current Harmonics
Distortion Rate
S Phase Current Harmonics
Distortion Rate (3P4W)
T Phase Current Harmonics
Distortion Rate
Line Voltage Harmonics
Effective Value Max. Phase
RS (RN) Line
Voltage Harmonics
Effective Value
ST (SN) Line
Voltage Harmonics
Effective Value
TR(TN) Line
Voltage Harmonics
Effective Value (3P4W)
Line Voltage Harmonics
Distortion Rate
RS (RN) Line
Voltage Harmonics
Distortion Rate
ST (SN) Line
Voltage Harmonics
Distortion Rate
TR(TN) Line
Voltage Harmonics
Distortion Rate (3P4W)
Watt hour (+)
Watt hour (-)
var hour (+) LAG
var hour (+) LEAD
var hour (-) LAG
var hour (-) LEAD
Exit Code (END code)
Bar
Upper
○
Mid
○
Lower
○
Comm
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
Pulse
Alarm
○
○
○
○
○
Head Office-Factory
3-5-11 TAGAWA YODOGAWA-KU OSAKA
532-0027 JAPAN
URL: http://www.takemotodenki.com
TEL: +81-6-6300-2195 FAX: +81-6-6308-7766
○
○
○
○
○
○