3002038-2008-03-01.fm GB EON-ZONE module Original instructions EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov Tel. +45 65 66 12 34 Fax +45 65 66 11 10 [email protected] www.exhausto.dk 3002038-2008-03-01.fm 1. Product information 1.1 Usage .........................................................................................................3 1.2 Positioning and fitting the ZONE module...............................................3 2. Installation 2.1 Connection ................................................................................................3 2.2 Connection of EON bus............................................................................4 2.3 Connection and use of analogue input...................................................5 2.4 Connection and use of analogue output ................................................6 2.5 Connection and use of digital input........................................................7 2.6 Optional simultaneous connection of EON-TOUCH Panel ...................7 2.7 Connection and use of digital relay output ............................................8 3. Commissioning 3.1 Setting the address...................................................................................9 3.2 Controlling the connection ......................................................................9 2/12 Product information 3002038-2008-03-01.fm 1. Product information 1.1 Usage The ZONE module is used for the activation of the zone damper, modulating or on/off control of the zone damper, and automatic override of the VEX to Comfort level when the module’s inputs are activated. 1.2 Positioning and fitting the ZONE module Use the screw holes in the corners of the module’s fitting box to fix the ZONE module in position. Position the module in the most appropriate place, for example close to the zone damper or close to the VEX unit. When positioning the module, please note that the maximum cable length of the EON bus is 50 m. The length of the other cables between the ZONE module and connected units should not exceed 50 m. 2. Installation 2.1 Connection Signal Chapter Usage 1 EON bus 2.2 Communication with the VEX control unit Always used 2 Analogue input 2.3 Control signal from the CO2 sensor, for example 0…10V, RL=50 kΩ 3 Analogue output 2.4 Control signal for regulating damper 0…10V, Imax.=10mA 4 Digital input 2.5 Control signal from PIR sensor or pushbutton, for example 24V, RL=5 kΩ 5 Relay output 2.7 Voltage-free signal to On/Off damper, for example 250V, 2A Supply voltage for sensors and actuators 24 VDC +10%/-20% max. 400 mA Power Output Permitted power consumption Comments The supply voltage for the ZONE module is supplied via the EON bus. The maximum permitted combined power supply for all modules is 400 mA. The ZONE module also features terminals to provide a power supply for the sensors (e.g. CO2 sensors, humidity sensors and PIR sensors) and for supplying power to actuators (such as damper and valve motors). 3/12 Installation 3002038-2008-03-01.fm External power supply If the total power consumption required by the actuators and sensors is higher than 400 mA, an external power supply must be used for one or more of the units connected. The external power supply used must be a safety transformer (cf. EN60 742). This power supply must not be separately grounded if it is connected to a 0V terminal on the ZONE module. Registration of power consumption This form can be used for registering the power consumed by connected actuators and sensors. Sensors/Actuators Power No. consumption of mA units Total power consumption, mA Total power consumption (must not exceed 400 mA) 2.2 Connection of EON bus Connect the EON bus as shown in the diagram below To see how to connect a shielded cable, please refer to section “4.3.5 Connection of shielded cable to EON-BUS” in the instructions for the VEX unit. NB. All EON modules must be connected in series – like a “Daisy-chain” – from the connection box. The total length of the EON connection must not exceed 50 m (see chapter 4, section: “Wiring diagram” in the instructions for the VEX unit). 4/12 Installation 3002038-2008-03-01.fm 2.3 Connection and use of analogue input The analogue input is used to start and override the VEX unit to Comfort Operation when the pre-programmed change limit (4.0 V) is exceeded, irrespective of whether the clock setting of the unit is Economy/Standby or Comfort. The input is equipped with a timer function that sets the minimum operating time for the unit to 30 min. – regardless of whether the change limit is only briefly exceeded. Connection Use the following terminals to connect the sensor to the analogue input. Connection on ZONE module NB Example: Use of analogue input Terminal Description Used for … 5 0VDC Common ground (0V) for signal and supply 6 +24VDC Electrical supply for sensor, used as required 7 0–10V Signal input The maximum permitted power consumption for the EON bus is 400 mA, see section “2.1 Connection”. The example shows a CO2 sensor connected to the ZONE module. The output signal of the CO2 sensor is: 0…2000 ppm = 0…10 V. The VEX unit will switch to Comfort Operation when the CO2 measurement exceeds 4V = 2000 ppm x 4V = 800 ppm 10V 5/12 Installation 3002038-2008-03-01.fm 2.4 Connection and use of analogue output The analogue output is used to transfer the analogue signal from the ZONE-module’s analogue input. The output signal can, for example, be used for the regulation damper or other actuators. Connection Use the following terminals to connect the actuator to the analogue output. Connection on ZONE module NB Terminal Description: 8 0VDC 9 +24VDC 10 0–10V Used for … Common ground (0V) for signal and supply. Electrical supply for sensor, used as required. Signal output. The maximum permitted power consumption for the EON bus is 400 mA, see section “2.1 Connection”. The example shows a regulation damper (0…10V= 0…100% opening) connected to the Example: ZONE module’s analogue output. Use of analogue output with external A CO2 sensor is connected to the analogue input of the ZONE module. power supply The output signal of the CO2 sensor is: 0…2000 ppm = 0…10 V. The regulation damper will follow the CO2 signal, which will thus be fully open when the CO2 value is 2000 ppm. 6/12 Installation 3002038-2008-03-01.fm 2.5 Connection and use of digital input The digital input is used to start and override the VEX unit to Comfort Operation when the input is activated – irrespective of whether the clock setting of the unit is Economy/ Standby or Comfort. Connection Use the following terminals to connect the sensor to the digital input. Connection on ZONE module NB Terminal Description: 11 0VDC Common ground (0V) for supply. 12 +24VDC Electrical supply to input and sensors, if any. 13 24VDC Signal input Used for … The maximum permitted power consumption for the EON bus is 400 mA, see section “2.1 Connection”. Example: The example shows a PIR sensor connected to the ZONE module’s digital input, which Use of digital input is used to start the VEX unit and/or override it to Comfort Operation. If more than one PIR sensor is to be connected to the same ZONE module, the relay contacts in the PIR sensors are to be connected in parallel (max. 4 sensors). 2.6 Optional simultaneous connection of EON-TOUCH Panel If the same address is used for the ZONE module and the EON-TOUCH module with timer function (FUNCTION 1), activation of the digital input will activate the timer function. NB. • • The TOUCH panel cannot be deactivated if the ZONE module input is activated. TOUCH panels set to a master function are not suitable for ZONE control (see chapter 4, section: “Setting the address and function of the TOUCH panel” in the instructions for the VEX100) 7/12 Installation 3002038-2008-03-01.fm 2.7 Connection and use of digital relay output The digital output is used to open an On/Off Zone damper. The damper opens when … • the ZONE module’s inputs are activated, resulting in a switch to Comfort Operation. • a TOUCH panel with the same address is activated. • night-time cooling is activated. NB. The relay will not be activated until the unit is operating. The relay output is a voltage-free switch. The ZONE module cannot normally provide the power supply for connected dampers. An external power supply should be used. Connection Use the following terminals to connect an adapter to the digital relay output. Connection on ZONE module NB Terminal Description: 14 C Common contact 15 NC Breaker function 16 NO Closing function Used for … The maximum permitted power consumption for the EON bus is 400 mA, see section “2.1 Connection”. Example: The example shows an On/Off damper with external electrical supply connected to Use of the relay output. digital relay output If the digital input of the ZONE module is activated, or if the electrical supply in the analogue input is greater than 4V DC, the damper will open when the extractor fan motor starts or is operating. 8/12 Commissioning 3002038-2008-03-01.fm 3. Commissioning 3.1 Setting the address If more than one ZONE module is connected, each module must have its own address. No more than 8 modules can be connected. NB. After the required settings have been entered, disconnect the power supply at the main switch and then restart the unit. In addition, fill out the label on top of the module. The EON-ZONE module and the address number are detected automatically when electrical supply is connected to the VEX unit. 3.2 Controlling the connection NB. The DISPLAY panel must be set at specialist or technician level before the control procedure can be carried out (see chapter 5, section: “ Switch between user modes” in the VEX100 instructions). To find out how to switch between user levels, please refer to the instructions for the VEX. Step Go to menu … 1 - 2 921 Action • Disconnect main power supply and restart the unit. • Check that there is an EON-ZONE module with the address selected, and that the number of “devices” has increased by 1. (requires reading prior to installation). 9/12 3002038-2008-03-01.fm 10/12 3002038-2008-03-01.fm 11/12 3002038-2008-03-01.fm EXHAUSTO A/S SCAN-PRO AG Odensevej 76 DK-5550 Langeskov Tel.: +45 6566 1234 Fax: +45 6566 1110 [email protected] www.exhausto.dk Postfach 74 CH-8117 Fällanden Tel.: +41 43 355 34 00 Fax: +41 43 355 34 09 [email protected] www.scanpro.ch EXHAUSTO GmbH Tempcold Oy Am Ockenheimer Graben 40 D-55411 Bingen-Kempten Tel.: +49 6721 9178-0 Fax: +49 6721 9178-99 [email protected] www.exhausto.de Sähkötie 8 PL 233 SF-01511 Vantaa Tel.: +358 201334130 Fax: +358 201334140 [email protected] www.tempcold.fi EXHAUSTO NORGE A/S Lilleakerveien 4 N-0283 Oslo Tel.: +47 2412 4200 Fax: +47 2412 4201 [email protected] www.exhausto.no Carl Steiner HWI GmbH & Co KG Bäckerfeldstrasse 15-17 A-4050 Traun Tel.: +43 7229 51021 0 Fax: +43 7229 51021 1333 [email protected] www.steiner-hwi.at EXHAUSTO Ventilation Ltd. Unit 1, Pelham Court Pelham Place Broadfield - Crawley West Sussex - RH11 9SH Tel. +44 (0) 1293 511555 Fax +44 (0) 1293 533888 [email protected] www.exhausto-ventilation.co.uk INATHERM B.V. Vijzelweg 10 NL-5145 NK Waalwijk Tel.: +31 416 317 830 Fax: +31 416 342 755 [email protected] www.inatherm.nl Limtre Virnet ehf EXHAUSTO AB Verkstadsgatan 13 S-542 33 Mariestad Tel.: +46 501 39 33 40 Fax: +46 501 39 33 41 [email protected] www.exhausto.se Vesturhrauni 3 IS-210 Gardabæ Tel.: +354 530 3400 Fax: +354 530 3401 [email protected] www.limtrevirnet.is
© Copyright 2026 Paperzz