EON-ZONE module

3002038-2008-03-01.fm
GB
EON-ZONE module
Original instructions
EXHAUSTO A/S
Odensevej 76
DK-5550 Langeskov
Tel. +45 65 66 12 34
Fax +45 65 66 11 10
[email protected]
www.exhausto.dk
3002038-2008-03-01.fm
1. Product information
1.1 Usage .........................................................................................................3
1.2 Positioning and fitting the ZONE module...............................................3
2. Installation
2.1 Connection ................................................................................................3
2.2 Connection of EON bus............................................................................4
2.3 Connection and use of analogue input...................................................5
2.4 Connection and use of analogue output ................................................6
2.5 Connection and use of digital input........................................................7
2.6 Optional simultaneous connection of EON-TOUCH Panel ...................7
2.7 Connection and use of digital relay output ............................................8
3. Commissioning
3.1 Setting the address...................................................................................9
3.2 Controlling the connection ......................................................................9
2/12
Product information
3002038-2008-03-01.fm
1.
Product information
1.1 Usage
The ZONE module is used for the activation of the zone damper, modulating or on/off
control of the zone damper, and automatic override of the VEX to Comfort level when
the module’s inputs are activated.
1.2 Positioning and fitting the ZONE module
Use the screw holes in the corners of the module’s fitting box to fix the ZONE module in
position.
Position the module in the most appropriate place, for example close to the zone damper
or close to the VEX unit.
When positioning the module, please note that the maximum cable length of the EON
bus is 50 m. The length of the other cables between the ZONE module and connected
units should not exceed 50 m.
2.
Installation
2.1 Connection
Signal
Chapter
Usage
1
EON bus
2.2
Communication with the VEX
control unit
Always used
2
Analogue input
2.3
Control signal from the CO2 sensor,
for example
0…10V, RL=50 kΩ
3
Analogue
output
2.4
Control signal for regulating damper 0…10V, Imax.=10mA
4
Digital input
2.5
Control signal from PIR sensor or
pushbutton, for example
24V, RL=5 kΩ
5
Relay output
2.7
Voltage-free signal to On/Off
damper, for example
250V, 2A
Supply voltage for sensors and
actuators
24 VDC +10%/-20%
max. 400 mA
Power Output
Permitted power
consumption
Comments
The supply voltage for the ZONE module is supplied via the EON bus. The maximum
permitted combined power supply for all modules is 400 mA.
The ZONE module also features terminals to provide a power supply for the sensors
(e.g. CO2 sensors, humidity sensors and PIR sensors) and for supplying power to
actuators (such as damper and valve motors).
3/12
Installation
3002038-2008-03-01.fm
External power
supply
If the total power consumption required by the actuators and sensors is higher than 400
mA, an external power supply must be used for one or more of the units connected.
The external power supply used must be a safety transformer (cf. EN60 742). This
power supply must not be separately grounded if it is connected to a 0V terminal on the
ZONE module.
Registration of
power
consumption
This form can be used for registering the power consumed by connected actuators and
sensors.
Sensors/Actuators
Power
No.
consumption
of
mA
units
Total power
consumption,
mA
Total power consumption
(must not exceed 400 mA)
2.2 Connection of EON bus
Connect the EON bus as shown in the diagram below
To see how to connect a shielded cable, please refer to section “4.3.5 Connection of
shielded cable to EON-BUS” in the instructions for the VEX unit.
NB.
All EON modules must be connected in series – like a “Daisy-chain” – from the
connection box.
The total length of the EON connection must not exceed 50 m (see chapter 4, section:
“Wiring diagram” in the instructions for the VEX unit).
4/12
Installation
3002038-2008-03-01.fm
2.3 Connection and use of analogue input
The analogue input is used to start and override the VEX unit to Comfort Operation when
the pre-programmed change limit (4.0 V) is exceeded, irrespective of whether the clock
setting of the unit is Economy/Standby or Comfort.
The input is equipped with a timer function that sets the minimum operating time for the
unit to 30 min. – regardless of whether the change limit is only briefly exceeded.
Connection
Use the following terminals to connect the sensor to the analogue input.
Connection on ZONE module
NB
Example:
Use of
analogue input
Terminal
Description
Used for …
5
0VDC
Common ground (0V) for
signal and supply
6
+24VDC
Electrical supply for
sensor, used as required
7
0–10V
Signal input
The maximum permitted power consumption for the EON bus is 400 mA, see section
“2.1 Connection”.
The example shows a CO2 sensor connected to the ZONE module.
The output signal of the CO2 sensor is: 0…2000 ppm = 0…10 V.
The VEX unit will switch to Comfort Operation when the CO2 measurement exceeds
4V = 2000 ppm x 4V = 800 ppm
10V
5/12
Installation
3002038-2008-03-01.fm
2.4 Connection and use of analogue output
The analogue output is used to transfer the analogue signal from the ZONE-module’s
analogue input.
The output signal can, for example, be used for the regulation damper or other actuators.
Connection
Use the following terminals to connect the actuator to the analogue output.
Connection on ZONE
module
NB
Terminal
Description:
8
0VDC
9
+24VDC
10
0–10V
Used for …
Common ground (0V) for
signal and supply.
Electrical supply for
sensor, used as
required.
Signal output.
The maximum permitted power consumption for the EON bus is 400 mA, see section
“2.1 Connection”.
The example shows a regulation damper (0…10V= 0…100% opening) connected to the
Example:
ZONE module’s analogue output.
Use of analogue
output with external
A CO2 sensor is connected to the analogue input of the ZONE module.
power supply
The output signal of the CO2 sensor is: 0…2000 ppm = 0…10 V.
The regulation damper will follow the CO2 signal, which will thus be fully open when the
CO2 value is 2000 ppm.
6/12
Installation
3002038-2008-03-01.fm
2.5 Connection and use of digital input
The digital input is used to start and override the VEX unit to Comfort Operation when
the input is activated – irrespective of whether the clock setting of the unit is Economy/
Standby or Comfort.
Connection
Use the following terminals to connect the sensor to the digital input.
Connection on ZONE
module
NB
Terminal
Description:
11
0VDC
Common ground (0V) for
supply.
12
+24VDC
Electrical supply to input
and sensors, if any.
13
24VDC
Signal input
Used for …
The maximum permitted power consumption for the EON bus is 400 mA, see section
“2.1 Connection”.
Example:
The example shows a PIR sensor connected to the ZONE module’s digital input, which
Use of digital input is used to start the VEX unit and/or override it to Comfort Operation.
If more than one PIR sensor is to be connected to the same ZONE module, the relay
contacts in the PIR sensors are to be connected in parallel (max. 4 sensors).
2.6 Optional simultaneous connection of EON-TOUCH Panel
If the same address is used for the ZONE module and the EON-TOUCH module with
timer function (FUNCTION 1), activation of the digital input will activate the timer
function.
NB.
•
•
The TOUCH panel cannot be deactivated if the ZONE module input is activated.
TOUCH panels set to a master function are not suitable for ZONE control
(see chapter 4, section: “Setting the address and function of the TOUCH panel”
in the instructions for the VEX100)
7/12
Installation
3002038-2008-03-01.fm
2.7 Connection and use of digital relay output
The digital output is used to open an On/Off Zone damper.
The damper opens when …
• the ZONE module’s inputs are activated, resulting in a switch to Comfort
Operation.
• a TOUCH panel with the same address is activated.
• night-time cooling is activated.
NB.
The relay will not be activated until the unit is operating.
The relay output is a voltage-free switch. The ZONE module cannot normally provide
the power supply for connected dampers. An external power supply should be used.
Connection
Use the following terminals to connect an adapter to the digital relay output.
Connection on ZONE
module
NB
Terminal
Description:
14
C
Common contact
15
NC
Breaker function
16
NO
Closing function
Used for …
The maximum permitted power consumption for the EON bus is 400 mA, see section
“2.1 Connection”.
Example:
The example shows an On/Off damper with external electrical supply connected to
Use of
the relay output.
digital relay output
If the digital input of the ZONE module is activated, or if the electrical supply in the
analogue input is greater than 4V DC, the damper will open when the extractor fan motor
starts or is operating.
8/12
Commissioning
3002038-2008-03-01.fm
3.
Commissioning
3.1 Setting the address
If more than one ZONE module is connected, each module must have its own
address. No more than 8 modules can be connected.
NB.
After the required settings have been entered, disconnect the power supply at the main
switch and then restart the unit. In addition, fill out the label on top of the module.
The EON-ZONE module and the address number are detected automatically when
electrical supply is connected to the VEX unit.
3.2 Controlling the connection
NB.
The DISPLAY panel must be set at specialist or technician level before the control
procedure can be carried out (see chapter 5, section: “ Switch between user modes” in
the VEX100 instructions). To find out how to switch between user levels, please refer to
the instructions for the VEX.
Step
Go to menu
…
1
-
2
921
Action
• Disconnect main power supply and restart the
unit.
• Check that there is an EON-ZONE module with
the address selected, and that the number of
“devices” has increased by 1.
(requires reading prior to installation).
9/12
3002038-2008-03-01.fm
10/12
3002038-2008-03-01.fm
11/12
3002038-2008-03-01.fm
EXHAUSTO A/S
SCAN-PRO AG
Odensevej 76
DK-5550 Langeskov
Tel.: +45 6566 1234
Fax: +45 6566 1110
[email protected]
www.exhausto.dk
Postfach 74
CH-8117 Fällanden
Tel.: +41 43 355 34 00
Fax: +41 43 355 34 09
[email protected]
www.scanpro.ch
EXHAUSTO GmbH
Tempcold Oy
Am Ockenheimer Graben 40
D-55411 Bingen-Kempten
Tel.: +49 6721 9178-0
Fax: +49 6721 9178-99
[email protected]
www.exhausto.de
Sähkötie 8
PL 233
SF-01511 Vantaa
Tel.: +358 201334130
Fax: +358 201334140
[email protected]
www.tempcold.fi
EXHAUSTO NORGE A/S
Lilleakerveien 4
N-0283 Oslo
Tel.: +47 2412 4200
Fax: +47 2412 4201
[email protected]
www.exhausto.no
Carl Steiner HWI GmbH & Co KG
Bäckerfeldstrasse 15-17
A-4050 Traun
Tel.: +43 7229 51021 0
Fax: +43 7229 51021 1333
[email protected]
www.steiner-hwi.at
EXHAUSTO Ventilation Ltd.
Unit 1, Pelham Court
Pelham Place
Broadfield - Crawley
West Sussex - RH11 9SH
Tel. +44 (0) 1293 511555
Fax +44 (0) 1293 533888
[email protected]
www.exhausto-ventilation.co.uk
INATHERM B.V.
Vijzelweg 10
NL-5145 NK Waalwijk
Tel.: +31 416 317 830
Fax: +31 416 342 755
[email protected]
www.inatherm.nl
Limtre Virnet ehf
EXHAUSTO AB
Verkstadsgatan 13
S-542 33 Mariestad
Tel.: +46 501 39 33 40
Fax: +46 501 39 33 41
[email protected]
www.exhausto.se
Vesturhrauni 3
IS-210 Gardabæ
Tel.: +354 530 3400
Fax: +354 530 3401
[email protected]
www.limtrevirnet.is