IDP-FIRE-CO - Campus Safety Magazine

Advanced Multi-Criteria Fire/CO Detector
IDP-FIRE-CO
Agency Listings
The IDP-FIRE-CO is a plug-in, addressable device that
provides both fire and carbon monoxide (CO) detection. For
fire, the detector combines four separate sensing elements in
one unit (smoke, CO, light/flame, and heat) to sense multiple
components of a fire. This approach enables enhanced
sensitivity to real fire with heightened immunity to nuisance
particulate. For CO, the detector’s electrochemical sensing
cell creates a separate signal for life safety CO detection.
Released through the incomplete burning of various fuels,
CO is a colorless, odorless and deadly gas that is virtually
impossible to detect with the human senses. Because the
potential exists for dangerous levels of CO to accumulate in
almost any building, legislation mandating the use of CO
detection in commercial spaces continues to increase across
the U.S. and Canada. The IDP-FIRE-CO is listed to the UL
2075 standard for system-connected life safety carbon
monoxide monitoring.
The IDP-FIRE-CO should be used in conjunction with the
B200S intelligent sounder base (sold separately), which can
generate either a Temp 3 pattern for fire or a Temp 4 pattern
for CO alarm indication. With each sounder base carrying a
unique address, the FACP can then command an individual
sounder, or a group of sounders, to activate. The command
set from the panel can be tailored to the specific event,
allowing selection of tone, and group. For more information
on the B200S refer to Data Sheet P/N 351182.
IDP-FIRE-CO can also be used with the B210LP 6” standard
base, the B200SR sounder base or the B224RB relay base.
Features
• Unique ability to detect all four major elements of a fire:
- Smoke
- Carbon Monoxide (CO)
- Light/flame
- Heat
• Separate CO detection signal
• Highest nuisance alarm immunity
• Automatic drift compensation of smoke sensor and CO cell
• Uses only one address on the SLC
• RealTest® CO testing capability
• UL 268 and UL 2075 listed
• Separates audible signal for fire or CO alarm when used
with B200S base
• CO cell end-of-life warning and fault
IDP-FIRE-CO installed in a B200S Sounder Base
(sold separately)
Compatibility
The IDP-FIRE-CO is compatible with the
following FACPs programmed for System
Sensor protocol: (Firmware version 13.0 or
higher for IFP-100 & IFP-1000. Firmware
version 4.0 or higher for IFP-2000).
• IFP-2000/RPS-2000 Intelligent Fire Panel
• IFP-2000ECS Emergency Communication
System with Fire Alarm Control Pane
• IFP-1000 Intelligent Fire Panel
• IFP-1000ECS Emergency Communication
System with Fire Alarm Control Panel
• IFP-100 Intelligent Fire Panel
• IFP-100ECS Emergency Communication
System with Fire Alarm Control Panel
• IFP-50 Intelligent Fire Panel
P/N 351180 Rev D
Copyright © 2014 Honeywell International Inc.
Specifications
Physical
Diameter:
Shipping Weight:
Color:
6.875” (17.46 cm) installed in a
B200S base
3.46” (8.79 cm) installed in
B200S base
4.6 oz
Ivory
Air Velocity:
32° F to 100° F (0° C to 38° C)
15 to 90% relative humidity
(non-condensing)
0 to 4,000 ft/min (0 to 20 m/sec)
Height:
Operating
Temperature Range:
Humidity:
Electrical
Operating Voltage:
Maximum Standby:
Maximum Alarm
Current (LED on):
15 to 32 VDC
300µA at 24 VDC (no
communication every 5 seconds
with LED blink enabled)
7.2 mA at 24 VDC
Sensitivity Settings
Sensitivity settings are programmable through zone
programming.
Low:
Medium:
High:
4% per foot (30.48 cm) of
smoke. Used in equipment
rooms, kitchens, paint shop.
3% per foot (30.48 cm) of
smoke. Moderately clean
environments: Used in hotel
rooms, dorm rooms.
2% per foot (30.48 cm) of
smoke. Clean environments:
Used in offices.
Warning: After the CO cell has reached the end-of-life,
the CO sensor no longer provides life safety protection.
However, when the fire detector enters Photo, Thermal,
Infrared (PTIR) mode, the following sensitivities apply:
Level 1:
1% per foot (30.48 cm) of smoke.
Very clean environments- Used in
laboratories.
Level 2:
2% per foot (30.48 cm) of smoke.
Clean environments - offices.
Level 5:
3% per foot (30.48 cm) of smoke.
Moderately clean environmentsUsed in hotel rooms, dorm rooms.
Level 6:
Thermal alarm at 135° F (57° C).
CO Monitoring UL Standard Reference - Alarm
Parts Per Million
70 ± 5 ppm
Detector Response Time
150 ± 5 ppm
400 ± 10 ppm
60-240 min.
10-50 min.
4-15 min.
Thresholds are as follows:
Note: Per UL Standard 2075, the IDP-FIRE-CO has
been tested to the sensitivity limits defined in UL
Standard 2034.
Ordering Information
IDP-FIRE-CO
included)
Multi-Criteria CO Detector (base not
Note: Due to the unique nature of this detector, please consult
your Fire Alarm Control Panel Manufacturer for the specific
model and compatibility.
Optional Accessories
B200S
Intelligent sounder base
B210LP
6” mounting base
B200SR
Sounder base
B224RB
Relay base
M02-04-01
Detector test magnet
M02-09-01
Telescoping test magnet
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610
Phone: (800) 328-0103, Fax: (203) 484-7118. For Techincal Support, Please call
800-446-6444. www.farenhyt.com
Made in the U.S.A.