Heating Line Product Guide 435.0 Ignition Controls Section Product Bulletin G67 Issue Date 1098 G67 Intermittent Pilot Ignition Controls The G67 Intermittent Pilot Ignition (IPI) Control is used to automatically light a pilot burner and energize the main burner gas valve of a heating system in response to the thermostat’s call for heat. When the heating load is satisfied, the thermostat opens and the G67 de-energizes the pilot and main burner gas valves. The G67 can be used with equipment with a maximum firing rate of 117 kW (400,000 Btu/hr) Any application over 117 kW (400,000 Btu/hr) must be approved in advance by the Johnson Controls Application Engineering Department. Figure 1: G67 Intermittent Pilot Ignition Control Figure 2: EC Approved G67EG Intermittent Pilot Ignition Control Features and Benefits ❑ Energy Efficient Allows pilot gas to be on only during the run cycle ❑ High Energy Spark Promotes consistent dependable pilot lighting ❑ Compact Size Provides limited space applications ❑ Solid State Components Provides long life ❑ Quick Response to Loss of Provides rapid closure of main valve (0.8 second maximum) Pilot Flame ❑ G67EG Approved Worldwide © 1998 Johnson Controls, Inc. Code No. LIT-4350400 Broadens applications to include global markets 1 www.johnsoncontrols.com A pplication S equence of Operation The G67 ignition control may only be used for two types of applications: Figure 3 illustrates the sequence of operation for the G67. • well ventilated or outdoor applications • power vent or induced draft application On a call for heat from the system thermostat, the G67 ignition control simultaneously opens the pilot valve and supplies a continuous spark to the pilot burner’s electrode. When the pilot burner gas ignites, the pilot flame sensor detects the pilot flame and signals the G67 to energize the main gas valve and discontinue the spark. The main gas valve will not be energized until the flame sensor detects the presence of the pilot flame. The G67 is suitable for operation over a temperature range of -40 to 66°C (-40 to 150°F). Consideration must be given to the temperature of the surface on which the G67 is mounted. Use the G67B( ) only on rooftop, excess air, and power vented gas burning equipment. When using the G67, the appliance or equipment must be approved by a recognized testing agency in accordance with the applicable American National Standards. See Specifications section. No other application is permissible. The G67 solid-state ignition control lights a pilot burner by a spark. Pilot gas is ignited and burns during each run cycle (intermittent pilot). Main burner and pilot gas are extinguished during the Off cycle. All applications must use a redundant main gas valve. The main gas valve will not open until the pilot flame has been proven by the sensing circuit. Should a loss of flame occur, the main valve closes and the spark recurs within 0.8 seconds. O perating Mode Definitions The following definitions describe operating conditions: Trial for Ignition--Period during which the pilot valve and spark are activated attempting to ignite gas at the main burner. Run--Main gas valve remains energized and the spark is turned off after successful ignition. Flameout--Loss of proven flame. Should a flameout occur, the main valve closes and the spark recurs within 0.8 seconds. 2 G67 Intermittent Pilot Ignition Controls Product Bulletin If the pilot flame goes out (with the thermostat still calling for heat), the G67 will de-energize the main gas valve and provide a continuous spark at the pilot burner’s electrode. When the pilot flame is re-ignited and detected by the pilot flame sensor, the main gas valve is energized and the spark is shut off. The G67 ignition control de-energizes the pilot gas valve and main burner gas valve when the thermostat stops calling for heat. M ounting Choose a location that provides the shortest, direct cable route to the spark electrode, flame sensor assembly. Easy access to the terminals is desired for wiring and servicing. The G67 may be mounted in any position. For G67A and G67B, refer to Figures 4 through 6 for wiring schematics/diagrams and Figure 7 for mounting dimensions. For G67EG, refer to Figures 8 and 9 for wiring schematic/diagram and Figure 10 for mounting dimensions. Thermostat Call for Heat Start Yes Flame Present? No Trial for Ignition No Pilot Flame Sensed? Yes Energize Main Valve Run Flameout? Yes De-energize Main Valve No Yes Thermostat Calling for Heat? No De-energize Control Pilot and Main Valves. End Figure 3: Sequence of Operation G67 Intermittent Pilot Ignition Control Product Bulletin 3 Therm ostat R H igh Lim its in this Line O nly W Internal W iring E xte rn a l W irin g 6 2 Q1 24 V A C Input R R3 1 R2 R1 3 Q S park C ircuit GR S ensing C ircuit PV MV GR P ilot B urner G round Flam e S ensor GR GR 5 Jum per Figure 4: Wiring Schematic for G67 Self-Checking Control Th erm o stat W Y R H ig h Lim its in th is L in e O nly 24 VA C MV P o w er S u pp ly PV P ilo t B u rne r G ro un d G ro un d Term ina ls Jum pe r 5 1 6 2 4 3 Flam e S e nsor H ig h Vo lta ge C a ble P o w er is w ired directly to R (C o m m o n) on th e th erm o stat an d Te rm ina l 6 o n th e G 6 7. Figure 5: Wiring Diagram for G67A( ) 4 G67 Intermittent Pilot Ignition Controls Product Bulletin 4 Therm o stat : 5 < H igh Lim its in this L ine On ly 24 VA C MV PV P ow er S upply P ilot B urner Grou nd Grou nd Te rm inals Ju m per 5 1 2 3 4 Y 75 Flam e S ensor H igh Voltage C able P ow er is w ired directly to R (C om m on) on the therm osta t. Term inals 1 and 2 on th e G 67 are tied together intern ally. Figure 6: Wiring Diagram for G67B( ) 8 .89 0 .35 S p ark Te rm ina l fo r R a ja h C on ne ctor 2 2.6 0 .89 5 0.8 2 .00 6 7.5 6 2 .66 Tw o H o le s fo r M ou ntin g S cre w s 6 .35 Q uick C on ne ct 0 .25 Term in a ls 4 .11 0 .16 2 1 04 .9 4 .13 11 5 4 .53 2 2.3 0 .88 56 2 .21 5 .33 0 .21 5 5.6 2 .19 5 .58 0 .22 Figure 7: G67(A and B) Mounting Dimensions, mm (in.) G67 Intermittent Pilot Ignition Control Product Bulletin 5 Internal Wiring External Wiring High Limits in this Line Only 6 Thermostat R 2 W K1a 24VAC Input K2 K2c Flame Sensor 1 K2b K2a 3 K1 7 Spark Circuit MV Chassis PV Sensing Circuit 4 Spark Gap 7 Burner Ground 5 Jumper Figure 8: Wiring Schematic for G67EG Self-Checking Control Pilot Burner/ Spark Igniter Main Burner Ground Flame Sensor Pilot Gas Supply CHASSIS 5 24V 7 COM Transformer THS 2 M.V. 3 MV P.V. 1 24V 6 SENSE 4 PV Limits in Thermostat Line Only Thermostat G67EG Ignition Control Figure 9: Wiring Diagram for G67EG 6 G67 Intermittent Pilot Ignition Controls Product Bulletin Power Supply 7 .87 0 .31 5 6.3 8 2 .22 5 7.9 1 2 .28 6 .35 S p ad e Te rm in als 0 .25 7 7.7 2 3 .06 3 3.7 8 1 .33 5 .58 0 .22 1 9.5 5 0 .77 1 07 .95 4 .25 11 6 4 .57 11 9.3 8 4 .70 Tw o H ole s 4 .1 fo r N o . 8 M ach in e 0 .16 2 o r N o . 6 S h ee t M e tal M ou ntin g S cre w s 5 .58 0 .22 6 6.8 2 .63 5 0.8 2 .00 Figure 10: G67EG Mounting Dimensions, mm (in.) G67 Intermittent Pilot Ignition Control Product Bulletin 7 O rdering Information G 67 _ _ - _ _ Customer-specific Requirements 1st Letter A Trial Time Other Features Non-100% Lockout Self Checking B Non-100% Lockout Non-Self Checking E Non-100% Lockout Self Checking/EC Approval 2nd Letter G The presence of a particular construction in this information does not guarantee its availability. Consult Johnson Controls for available constructions. 8 G67 Intermittent Pilot Ignition Controls Product Bulletin Voltage 24V 60 Hz Notes G67 Intermittent Pilot Ignition Control Product Bulletin 9 Notes 10 G67 Intermittent Pilot Ignition Controls Product Bulletin Notes G67 Intermittent Pilot Ignition Control Product Bulletin 11 S pecifications Product Ignition Type Ignition Source G67 Non-100% Lockout Intermittent Pilot Ignition Control Indirect High voltage spark, capacitive discharge Maximum High Voltage Cable Length 1,220 mm (48 in.) recommended Flame Detection Means Flame rectification Flame Detection Types Remote sensing Minimum Flame Current 0.2 microampere Flame Failure Response Time 0.8 second, maximum Spark Gap Ignition Trial Time Power Requirements Control Operation Current Contact Ratings Main Valve Pilot Valve 2.5 mm (0.1 in.) nominal Infinite 24 VAC, 50/60 Hz, nominal 0.15A nominal + valves 2A continuous, 5A inrush 2A continuous, 5A inrush Ambient Operating and Storage Temperature -40 to 66°C (-40 to 150°F) Humidity 95% RH non-condensing Types of Gas Packaging Bulk Pack Quantity Bulk Pack Weight Agency Listing Specification Standards Natural, Liquefied Petroleum (LP), manufactured, mixed, or LP gas-air mixture may be used in a well-vented or outdoor application. Bulk pack supplied to original equipment manufacturer (individual pack options). 50 12 kg (27 lb) IAS (AGA, CGA) Certificate Number C2154020 EN/EC Type Examination Certificate Number 115687 (G67EG only) ANSI Standard Z21.20 CSA C22.2-No. 199 EN 298 (G67EG only) The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Refer to the G67 Series Technical Bulletins (LIT-121190 and LIT-121191) for necessary information on the installation, use, and servicing of this product. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 12 G67 Intermittent Pilot Ignition Controls Product Bulletin www.johnsoncontrols.com FAN 435.0 Heating Line Product Guide Printed in U.S.A
© Copyright 2025 Paperzz