TEST REPORT REPORT NUMBER: 3171430COQ-001 ORIGINAL ISSUE DATE: March 24, 2009 REVISED DATE: April 7, 2009 EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Adex Systems Inc. 5575 rue des Tenailles Ville De Québec, QC G2J 1R6 PRODUCT EVALUATED: Wall Exterior Insulation and Finish System EVALUATION PROPERTY: Fire Resistance Report of testing wall exterior insulation and finish system for compliance with the applicable requirements of the following criteria: CAN/ULC S101-04, Standard Test Methods for Fire Tests of Building Construction and Materials This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. 1 Adex Systems Inc. Report No. 3171430COQ-001 March 24, 2009 Page 2 of 13 1 Table of Contents PAGE 1 Table of Contents.............................................................................................................. 2 2 Introduction ....................................................................................................................... 3 3 Test Samples .................................................................................................................... 3 3.1 SAMPLE SELECTION ................................................................................................ 3 3.2 SAMPLE AND ASSEMBLY DESCRIPTION ............................................................... 3 4 Testing and Evaluation Methods ....................................................................................... 4 4.1 CONDITIONS OF ACCEPTANCE .............................................................................. 4 4.2 TEST WALL CONSTRUCTION .................................................................................. 4 4.3 THE FIRE TEST.......................................................................................................... 5 5 6 Testing and Evaluation Results......................................................................................... 6 5.1 FIRE TEST OBSERVATIONS..................................................................................... 6 5.2 POST-TEST OBSERVATIONS................................................................................... 6 Conclusion ........................................................................................................................ 7 APPENDIX A – Photographs .............................................................................................3 Pages APPENDIX B – Temperature Data ......................................................................................1 Page REVISION SUMMARY Adex Systems Inc. Report No. 3171430COQ-001 2 March 24, 2009 Page 3 of 13 Introduction Intertek Testing Services NA Ltd. (Intertek) has conducted testing for Adex Systems Inc. to evaluate their Wall ADEX – ICI - RS. wall system Testing was conducted in accordance with CAN/ULC S101-04, Standard Test Methods for Fire Tests of Building Construction and Materials, to determine that the wall system would remain in place for 15 minutes as per National Building Code of Canada (1995), Sentence 3.2.3.7, National Building Code of Canada (2005), Sentence 3.2.3.8, the Ontario Building Code (1997), Sentence 3.2.3.7, Clause 7b and 8, the Ontario Building Code (2006), Sentence 3.2.3.8, and the City of Vancouver Building By-Law (1999), Sentence 3.2.3.7, Clause 7b and 8 requirements. This evaluation began March 12, 2009 and was completed March 12, 2009. Testing was witnessed by Bill Emde, Brian Barry and Ken Yohnke of Akrilon Industries, representing Adex Systems Inc. 3 Test Samples 3.1. SAMPLE SELECTION Sample components were submitted to Intertek directly from the client. Samples were not independently selected for testing and require further analysis for certification. The materials used in the construction of the test sample were retained for analysis. Samples were received at the Evaluation Center on February 17, 2009. 3.2. SAMPLE AND ASSEMBLY DESCRIPTION Wall Panel: 10 ft. by10 ft. steel stud framed with 1/2 in. conventional gypsum wallboard substrate EPS Thickness: Adex 5 in. type 1 expanded polystyrene (EPS) Mesh: Adex 4.5 oz. fibreglass Mesh Vapour Block: Adex Hydroflex VP – Air/Vapour and Moisture Barrier, applied to gypsum Base Coat/Adhesive: Adex Base Coat Finish Coat: Adex Sanded Finish Coat Adex Systems Inc. Report No. 3171430COQ-001 4 Testing and Evaluation Methods 4.1. CONDITIONS OF ACCEPTANCE March 24, 2009 Page 4 of 13 The term "remain in place" was defined as the ability for the panel system to resist the separation of its joints and consequent development of openings greater than 1/2 in. in width into the insulation of the panel, when viewed normal to the panel. 4.2. TEST WALL CONSTRUCTION The wall dimensions were 10 ft. wide by 10 ft. high and constructed using nominal 2 in. by 4 in. steel studs, located 16 in. on centre, with standard 1/2 in. thick gypsum sheathing installed with the long dimension in the horizontal orientation and fastened with Type S 1-5/8 in. long buglehead drywall screws 12 in. on centre. The finished wall system contained a single horizontal and vertical joint approximately 12 in. from the bottom and 12 in. from the right-hand side. The E.I.F.S. system components were applied to the substrate wall by Bill Emde representing Adex Systems Inc. The horizontal and verticals joints on the gypsum were sealed by embedding a 4” wide, 4.5 ounce mesh into Adex Hydroflex moisture barrier, once set the Adex Hydroflex moisture barrier was applied to the rest of the substrate. At 12” from the bottom of the wall panel a through wall flashing detail was created by priming, then attaching A-Flex tape horizontally at this location. 22 jauge flashing was then mechanically fastened and lapped onto substrate with the HydroFlex moisture barrier. The 5” EPS boards edges were encapsulated with Adex basecoat mixed with Target GU cement. Detail mesh was embedded a minimum of 4” on the back side of the EPS board, across the end and returned 4” onto the face of the board in accordance with manufacturer’s instructions to apply the back wrap prior to installation. The 5” thick EPS board was secured to the wall using a 3/8’x1/2”x 11/2” notched trowel, the ribbons of adhesive were applied in a vertical orientation to insure the presence of a drainage plane. Once all EPS panels were in place Adex basecoat mixed with Target GU cement is trowel applied to the complete surface, while wet, Adex standard (4.5 oz.) 36” wide mesh is embedded into the basecoat. A 2 1/2” minimum overlap is maintained at mesh overlaps. The thickness of the basecoat is maintained at 1.5mm thickness. The basecoat was cured for seven days prior to the application of the Adex finish coat. The finish coat was mixed and trowel applied in accordance with the manufacturer’s instructions. A polyethylene backer rod and manufacturer specified caulking was installed into the vertical joint Adex Systems Inc. Report No. 3171430COQ-001 4.3. March 24, 2009 Page 5 of 13 THE FIRE TEST The test wall assembly was mounted in the full-scale vertical furnace mounting frame. Additional gypsum wallboard and steel studs were used to complete the test frame width of 12 ft., and the assembly was clamped to the front of the test furnace. See Appendix A – Photographs. The moveable frame containing the test wall assembly was secured to the furnace. The pilot burners were ignited and burned until the temperature inside the furnace reached 20 ± 2°C (70 ± 3°F). All burners were fired and timing was begun immediately upon achieving maximum high fire. The temperatures inside the furnace are monitored by nine equally spaced thermocouples. These readings were recorded by a calibrated Fluke "Hydra Data Bucket" automatic data recorder every 5 seconds and automatically displayed every 15 seconds. See Appendix B – Temperature Data. The wall assembly was subjected to the standard time/temperature curve of CAN/ULC S101-04 and the exposed surface was observed. The test was continued for 15 minutes. Adex Systems Inc. Report No. 3171430COQ-001 March 24, 2009 Page 6 of 13 5 Testing and Evaluation Results 5.1. FIRE TEST OBSERVATIONS Time (min.) 2:30 Exposed Side Surface has ignited 10:00 15:00 Surface is intact Test discontinued, membrane is intact 16:00 5.2. Unexposed Side Removed the assembly POST-TEST OBSERVATIONS After the test the membrane was intact as seen through viewing ports in the back of the furnace. As the assembly and test frame was lifted and moved away from the furnace the membrane began to break apart. Although the membrane stayed intact for the full duration of the test, the post test pictures do not show the membrane intact. (See Appendix A – Photographs) Adex Systems Inc. Report No. 3171430COQ-001 6 March 24, 2009 Page 7 of 13 Conclusion The ADEX – ICI - RS. wall system remained in place throughout the 15 minute fire exposure in accordance with CAN/ULC S101-04, Standard Test Methods for Fire Tests of Building Construction and Materials. Consequently, when constructed as described in this report, the system met the requirements of the National Building Code of Canada (1995), Sentence 3.2.3.7, National Building Code of Canada (2005), Sentence 3.2.3.8, the Ontario Building Code (1997), Sentence 3.2.3.7, Clause 7b and 8, the Ontario Building Code (2006), Sentence 3.2.3.8, and the City of Vancouver Building By-Law (1999), Sentence 3.2.3.7, Clause 7b and 8. The conclusions of this test report may be used as part of the requirements for Intertek product certification. Authority to Mark must be issued for a product to become certified. INTERTEK TESTING SERVICES NA LTD. Tested and Reported by: _____________________ Scott Leduc, EIT Technician – Construction Products Testing Reviewed by: _____________________ Greg Philp Reviewer – Fire Testing SL G:\Building\Fire Testing\Fire Test Reports\Systemes Adex 3171430\Systemes Adex S101 RPT 3171430 Mar 23 09.doc Adex Systems Inc. Report No. 3171430COQ-001 March 24, 2009 Page 8 of 13 APPENDIX A Photographs Adex Systems Inc. Report No. 3171430COQ-001 March 24, 2009 Page 9 of 13 Unexposed Side Prior to the Fire Test Exposed Side Prior to the Fire Test Adex Systems Inc. Report No. 3171430COQ-001 March 24, 2009 Page 10 of 13 Exposed Side After the Fire Test Adex Systems Inc. Report No. 3171430COQ-001 March 24, 2009 Page 11 of 13 APPENDIX B Temperature Data Adex Systems Inc. Report No. 3171430COQ-001 March 24, 2009 Page 12 of 13 TIME TEMPERATURE CURVE AVERAGE TEMPERATURE OF FURNACE DURING THE FIRE TEST 1800 1600 Temperature (°F) 1400 1200 1000 800 600 400 200 0 0 5 10 15 Time (min) Actual Frunace Temperatures Required Furnace Temperatures Adex Systems Inc. Report No. 3171430COQ-001 March 24, 2009 Page 13 of 13 REVISION SUMMARY DATE March 24, 2009 April 7, 2009 PAGE -3, 4 ,7 SUMMARY Original Issue Date Name correction, assembly identification, detail in wall construction
© Copyright 2025 Paperzz