TJC ADP Submittals Slakey All 0613

June 2013
Upflow/Downflow A-Coil Specifications
ADP Model #
Width
Depth
Height
Pallet
Qty.
Coil
Weight
(lbs)
CFM
C36A142(*)126
C36A175(*)126
C36A142(*)536
C48A175(*)156
C48A210(*)156
C60A210(*)366
C60A210(*)526
14.25"
17.50"
14.25"
17.50"
21.00"
21.00"
21.00"
21"
21"
21"
21"
21"
21"
21"
16.5"
16.5"
31.5"
21.5"
21.5"
24.5"
31.5"
12
8
4
4
4
4
4
38
40
60
48
50
57
77
1200
1200
1200
1600
1600
2000
2000
(1)
Face Vel.
(fpm)
Wet Air Pressure Drop
(in WC)
386
386
180
360
360
409
300
.36
.34
.20
.29
.27
.42
.32
(*) - "C" represents a copper slab. "L" represents an aluminum slab.
(1) Face velocity in Bold above 350 ft/min. is not recommended for downflow applications due to potential water blow-off.
Product Features:
• High efficiency lanced fin design.
• “No-hassle” 5 year warranty, with an additional 5 years upon registration at www.adpwarranty.com
• R-410A TXVs installed. Threaded installation.
• All coils have durable packaging with bar coded labels on the box.
• Coils are air pressure tested at 500 psi, leak tested with helium, sealed with rubber plugs, then charged with dry air.
• Liquid line refrigerant connections are 3/8" ODF.
• Suction line refrigerant connections are 3/4" ODF (A-Coil 18-36 size models) or 7/8" ODF (A-Coil 42-60 size models).
• Copper refrigerant connections for easy brazing on both copper and aluminum slab models.
• Cased coils have heavy gauge painted cabinets fully lined with 5/8" foil faced insulation.
• Corrosion resistant coil header plates.
• All A-Coils are upflow or downflow capable.
• Cabinet insulation hold down tabs for easy drain pan removal.
Bottom Opening Width is cabinet width less 1"
• Interlocking doors reduce air leakage and allow for easy access.
Bottom opening Depth is cabinet depth less .5"
• Enhanced refrigerant pipe grommets: secure, tight, and easy to install.
Top Opening Width is cabinet Width less 1.5"
• Intertek lab tested 1% or less cabinet air leakage for better efficiency.
Top opening Depth is cabinet depth less 1.5"
• Foam drain seal for reduced air leakage.
Cabinet Height doesn't include 3/4" duct flange.
• Non-captive refrigerant lines with long stubs make for easy installation.
• Dual 3/4" FPT condensate drains on front-left and front-right side of drain pans.
• UV resistant drain pans are molded of high temperature (450 deg. F) engineered polymer.
• Microban® antimicrobial additive to inhibit the growth of mold and mildew in the drain pan.
• HydroTEC™ low water retention drain pan.
June 2013
Horizontal Coil Specifications
ADP Model #
Width
[A]
Depth
[B]
Height
[C]
Pallet Qty.
Coil
Weight
(lbs)
CFM
C36H175(*)256
C36H142(*)426
C36H142(*)446
C36H175(*)456
C48H210(*)286
C48H175(*)366
C60H210(*)166
C60H210(*)196
C60H210(*)306
C60H245(*)566
26.50"
26.50"
26.50"
26.50"
26.50"
26.50"
26.50"
26.50"
36.50"
36.50"
21"
21"
21"
21"
21"
21"
21"
21"
21"
21"
17.50"
14.25"
14.25"
17.50"
21.00"
17.50"
21.00"
21.00"
21.00"
24.50"
4
8
6
6
6
4
6
6
6
2
47
47
52
66
54
49
62
77
90
94
1200
1200
1200
1200
1600
1600
2000
2000
2000
2000
17.5"
16" x 19.5"
16.5" x 20"
21"
19.5" x 19.5"
20" x 20"
24.5"
23" x 19.5"
23.5" x 20"
(1)
Face Vel.
(fpm)
300
342
277
257
274
343
400
343
240
218
Dry Air Pressure Drop
(in WC)
.21
.28
.20
.27
.23
.33
.43
.48
.29
.27
(*) - "D" represents a copper slab. "P" represents an aluminum slab.
^For wet coil conversion at standard ARI conditions, use 1.3 multiplier.
Cabinet Height
Supply opening (Height x Depth)
Return opening (Height x Depth)
14.25"
12.75" x 19.75"
13.25"x 20"
Product Features:
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
Short cabinet with easy access.
High efficiency lanced fin design.
R-410A threaded TXV installed.
Copper refrigerant connections for easy brazing on both copper and aluminum slab models.
Dual 3/4" FPT condensate drains on front and back of coil allows flexibility of placement to accommodate left or right airflow furnaces.
Easy to remove access panel with only 4 screws.
Non-captive panels allow access to inside of cabinet without the need to cut refrigerant lines.
Refrigerant connections on top of coil.
Coils are air pressure tested at 500 psi, leak tested with helium, sealed with rubber plugs, then charged with dry air.
Copper distributor tube assembly provides brass to brass threads for trouble-free service of TXV.
Heavy gauge painted cabinets fully lined with 5/8" foil faced insulation.
All coils are foam packed and include bar coding on label.
Easy to use filler strip, for use if coil dimensions are larger than furnace.
Dedicated cutouts for condensate drains reduce air leakage.
Intertek lab tested 1% or less cabinet air leakage for better efficiency.
Microban® antimicrobial additive to inhibit the growth of mold and mildew in the drain pan.
HydroTEC™ low water retention drain pan.
UV resistant drain pans are molded of high temperature (450 deg. F) engineered polymer.
Refrigerant connections are 3/8" ODF liquid and 7/8" ODF suction.
Refrigerant connections in center of coil away from airflow path.
June 2013
Plenum Coil Specifications
Coil Model Number
PL36H142P44635
PL36H175P15635
PL48H175P14635
PL60H210P50635
PL60H210P16635
Height
Width
Length
14.25
17.50
17.50
21.00
21.00
21.25
21.25
21.25
21.25
21.00
35.00
35.00
35.00
35.00
35.00
Drain Connections - 3/4" FPT Condensate drain
connections on both the front and back sides of cabinet.
Refrigerant Connections
Liquid Line - 3/8" ODF
Suction Line - 7/8" ODF
Cabinet Height
Supply opening (Height x Depth)
14.0"
14.25"
14.5"
17.5"
21"
24.5"
12.5 x 19.75 12.75 x 19.75 13.0 x 19.75 16.0 x 19.75 19.5 x 19.75 23.0 x 19.75
25.25"
23.75 x 19.75
Return opening (Height x Depth)
13.0 x 20.25 13.25 x 20.25 13.5 x 20.25 16.5 x 20.25 20.0 x 20.25 23.5 x 20.25
24.25 x 20.25
Product Features:
Top Refrigerant connections for installation flexibility
UV light knockouts
Top panel with only four screws for fast and easy coil access
TXV with all threaded connections, no brazing required
Light weight aluminum evaporator coils with aluminum header plates
Pilot holes for fast secondary drain pan attachment
Optional patented float switch is designed to shut off the unit for drain overflow protection
Patent pending "V" pan directs water to the front of the pan and away from the furnace flue connection
Green/Red connections on each side for easy installation
Counter flow and line re-routing not required
Healthy Solutions® coils feature an available 10-year limited warranty. Simply register online at www.adpwarranty.com
Manufactured Housing Coil Specifications
June 2013
Coil Model
M36E329
M36E339
M36E349
M36E359
M36E599
M48E669
M60E379
M60E499
M60E599
Nominal
Tonnage
1.5-3
1.5 - 3
1.5 - 3.5
1.5 - 3.5
1.5 - 3
3. - 4
3.5 - 5
3.5 - 5
3.5 - 5
Pan
Width
18
18
18
18
18
18
18
18
18
Pan
Depth
19.5
19.5
19.5
19.5
19.5
19.5
19.5
19.5
19.5
Coil
Height
15
17
23
21
29
21
25
25
19
Coil
Weight
28
32
41
39
45
48
45
46
45
Pallet
Metering
Quantities Device
8
TXV
8
TXV
4
TXV
4
TXV
8
TXV
4
TXV
4
TXV
4
TXV
8
TXV
Features
· Sloped drain pan for lower water retention.
· Downflow drip shields are molded into drain pan.
· Drain pan in 18" and 19 5/8" widths to match all furnace sizes.
· Piston or TXV models available.
· Filter-friendly top plate on most models (except 22" & above).
· Down-turned headers are sized out to easily receive line set.
· Sweat connections with available quick-connect stub kit.
· Leak free product - pressure tested twice (500 psi immersion & 300 psi He).
· High performance fin design.
· Factory software for TXV failure testing.
· Includes die-cut foam sheet for sealing, drain ELL, drain hose & clamp.
· Dedicated upflow/downflow.
· Protective foam packaging.
· Dry air holding charge.
C-Series Premier Collection Nomenclature
C
24
A
210
C01
6
Metering Device
6 = Non-Bleed A/C TXV (R-410A)
6W = Non-Bleed A/C TXV (R-410A) w/Bulb Wrap
9 = Non-Bleed HP-A/C TXV (R-410A)
9W = Non-Bleed HP-A/C TXV (R-410A) w/Bulb Wrap
Premier Distributor Collection
C-Series*
Nominal MBTUH Capacity
Coil Type/Style (Painted Only)
A = Upflow/Downflow Cased A-Coil
H = Dedicated Horizontal A-Coil
Slab Number
Upflow/Downflow
Cased A-Coil
C = copper
L = aluminum
Dimension
Upflow/Downflow Cased A-Coil Widths
142 = 14.25"
175 = 17.5"
210 = 21.0"
245 = 24.5"
Dedicated Horizontal A-Coil Heights
142 = 14.25"
175 = 17.5"
210 = 21.0"
245 = 24.5"
Note: Cased A-Coil widths correspond to
Horizontal Coil heights
*Cabinet Coordinates w/Carrier Color
Plenum Coil Nomenclature
PL
24
H
145
P03
6
35
Cabinet Length
Coil Style
PL = Plenum
25"
30"
Metering Device
1 = Piston (R-410A)
2 = Piston (R-22)
3 = Bleed A/C TXV (R-22)
4 = Non-Bleed A/C TXV (R-22)
5 = Non-Bleed HP-A/C TXV (R-22)
6 = Non-Bleed A/C TXV (R-410A)
9 = Non-Bleed HP-A/C TXV (R-410A)
Nominal MBTUH Capacity
Coil Type
H = Horizontal A-Coil
Coil Height
14.00"
14.25"
14.50"
17.50"
21.00"
24.50"
25.25"
Cabinet Features
Painted cabinet for furnace color coordination.
35"
40"
Slab Number
P = aluminum
Coil Features
Non-captive refrigerant lines for easier service.
Scratch resistant cabinet for appearance and rust prevention
Patent protected lanced fin for enhanced heat transfer.
Enhanced grommets for secure, tight fit and easy
Refrigerant connections are 3/8" ODF liquid and 3/4"
installation.
ODF (18-36 MBTUH) or 7/8" ODF (42-60 MBTUH) suction.
Easy Glide™ one piece panel for full access and easy removal.
Durable packaging with a bar coded label on the box.
Foil-faced insulation for easy cleaning.
Upflow or downflow configuration capable.
ETL lab tested 1.25% A-Coil & 1% Horizontal A-Coil air leakage
Coils are air pressure tested at 500 PSI, leak tested with Helium,
for better efficiency.
sealed and then charged with dry air.
UV light knock-outs for easy installation.
Distributor "bell" joints for enhanced quality.
Perfect fit for your furnace to eliminate coil overhang.
Drain Pan Features
Patent protected HydroTECH TM drain pan with dual 3/4" FPT drains on
TX Valve Features
Wrapped TXV bulbs for improved temperature control.
both sides of cabinet (24.5" wide Cased A-Coils: drains on left side only).
(Optional)
UV resistant drain pans are molded of high temperature (450O F)
Equalizer line has threaded fitting for easy TXV
engineered polymer.
servicing.
Microban® antimicrobial additive inhibits the growth of mold
TXV location provides better airflow and serviceability.
and mildew on the drain pan.
Dedicated Horizontal
A-Coil
D = copper
P = aluminum