Applied Acoustics 65 (2004) 441–455 www.elsevier.com/locate/apacoust Technical note Design of an acoustic enclosure with duct silencers for the heavy duty diesel engine generator set Hyeon-Don Jua,*, Shi-Bok Leeb, Weui-Bong Jeongb, Byung-Hoon Leeb a Department of Computer Industrial Application, Chinju College, Chinju, 660-759, South Korea b School of Mechanical Engineering, Pusan National University, Pusan, 609-735, South Korea Received 15 October 2002; received in revised form 1 May 2003; accepted 21 October 2003 Abstract Diesel engine generator sets in heavy industry plants and residential/official buildings can cause serious noise problems. In this paper, a low noise diesel engine generator set is developed through constructing an acoustic enclosure with ventilation duct silencers that effectively block the acoustic flow but guarantee good thermal flow. Acoustic design of the enclosure, which is initially layout by rule of thumb, is evolved systematically through numerical reanalysis procedure, based on indirect boundary element method (IBFM) with a commercial acoustic analysis code. The cooling performance of the acoustically determined enclosing structure is checked and confirmed through numerical heat flow analysis. The acoustic and cooling performances of the developed low noise diesel engine generator set are confirmed by the experiment. # 2003 Published by Elsevier Ltd. Keywords: Acoustic enclosure; Ventilation duct silencer; Indirect boundary element method (IBEM) 1. Introduction Diesel engine generator sets are widely used as main electric power supplying equipment in many industrial plants and facilities in official/residential buildings, especially in the situation of abrupt electric outage. In this case, the components of * Corresponding author. Tel.: +82-55-751-8149; fax: +82-55-761-7407. E-mail address: [email protected] (H.-D. Ju). 0003-682X/$ - see front matter # 2003 Published by Elsevier Ltd. doi:10.1016/j.apacoust.2003.10.007 442 H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 the diesel engine generator set, such as the diesel engine, generator, radiator fan, and engine exhaust, etc., would appear as main noise sources in the plants or buildings. Most conventional diesel engine generator sets have simple covers only to protect the components and guide the flow of cooling air, and would generate very high level of noise. In this paper, an acoustic enclosure system for a heavy duty diesel engine generator set is designed to reduce the noise level below A-weighted sound pressure level (SPL) of 80 dB from the high level exceeding 100 dB at a specified work position. The enclosure system adopts some ventilation duct silencers that effectively block and dissipate the noise flow but guarantee good thermal outflow. The design process consists of two phases, one of which is acoustic phase and the other is thermal one. First, the acoustic design is performed through numerical analysis procedure using an acoustic analysis code SYSNOISE, based on the indirect boundary element method (IBEM). To prepare real acoustic source conditions necessary in analyzing the acoustic system, the sound intensities of the components of the generator set, i.e. diesel engine, generator, and radiator fan are measured and used in the calculation of the sound power. Second, the acoustically determined enclosure system is inspected in terms of cooling performance given as a specified temperature difference between at inside and outside of the enclosure. A commercial program FLUENT is used in this design phase. 2. Measurement of noise characteristics and sound power Noise characteristics of the generator set should be identified to produce effective and concrete measures to control the noise. The sound powers of the noise sources need to be used in the numerical analysis. The sound powers of the main noise sources, the diesel engine [1], generator and radiator fan, are measured by sound intensity method. A sound intensity probe with two microphones (B&K 4183) of 12 mm distance is used [2]. A measuring grid wall with a grid size of 200 mm height and 200 mm width is installed at 0.75 m in front of the centerline of the generator set as shown in Fig. 1(a) and another measuring grid wall with a grid size of 290 mm height and 290 mm width at the front of the radiator. Fig. 2(a–c) present the results of 1/3 octave sound intensity spectrum analysis. The symbol ^ in any bar in Fig. 2 indicates the intensity of the sound reversing to the source. The units of sound intensity and A-weighted sound power are W/m2 and dB, respectively. Fig. 2(a) presents the sound intensity spectrum at the grid position in front of the engine exhaust manifold located around the cross point of the 4th row and 4th column grid lines on the measuring wall. The spectrum reveals that a dominant noise reaching the A-weighted sound intensity level of 99 dB arises in the 1/3 octave band centered at 1000 Hz. The overall A-weighted sound power radiated from the engine is 108 dB. In Fig. 2(b), showing the sound intensity spectrum at the grid position in front of the generator cooling fan located around the cross point of H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 443 Fig. 1. Grid wall for sound intensity measurement and a typical diesel engine generator set without any special anti-noise measures. the 6th row and 2nd column grid lines on the measuring wall for the generator, the 1/3 octave band centered at 500 Hz appears to be the most troublesome frequency band, in which A-weighted sound intensity level from the generator cooling fan reaches up to 102 dB. On considering that the blade rotation frequency of the cooling fan of the generator is 450 Hz, it is apparent that the high noise in this band is due to the blade rotation. The overall A-weighted sound power of the generator is 110 dB. Fig. 2(c), giving the sound intensity spectrum emitted from the radiator fan located around the cross point of the 5th row and 4th column grid lines on the measuring wall for the radiator, reveals that the 1/3 octave hand centered at 200 Hz, which encompasses the blade rotation frequency 217 Hz, of the radiator fan, is most problematic, generating A-weighted sound intensity of 112 dB. These experimental facts provide some important guides for us to adopt ventilation ducts with silencing capability of low frequency noise. But straight ducts are ways for the noise to pass out through and act as effective noise transmitters. In order to interrupt noise flow effectively, the ducts should be bent in some angles. 444 H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 Fig. 2. 1/3 octave-band sound intensity spectra from the three main noise components: (a) engine exhaust manifold, (b) generator cooling fan, (c) radiator fan. H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 445 2.1. Initial design of the acoustic enclosure and ventilation duct silencers Our acoustic enclosure design is performed for a heavy duty diesel engine generator set with a high electric power supplying capacity above 320 kW, the specification of which is given in Table 1. The main idea in our design, different from conventional diesel engine generator sets covered with simple enclosures, is to install the ventilation ducts and impose silencing function on them. Initial spatial configuration of the generator system with an acoustic enclosure and ventilation ducts is laid out by the rule of thumb, paying attention to the maintenance feasibility and space utility, to conform to the following requirements and specifications. 1. The acoustically designed generator set should satisfy that length is smaller than 5.0 m, width 1.5 m, and height 4.0 m. 2. The A-weighted SPL at the maintainer work position of 1 m away from the enclosure side wall, 1 m above the ground and 0.75 m behind the enclosure front wall should be lower than 80 dB. 3. Temperature difference between at the inside and outside of the acoustic enclosure should be lower than 10 C. The shape and structure of enclosure are laid out so as to block up effectively broad band noise, especially high frequency noise, and supply cooling air with an intake duct and evacuate heated air with an outtake duct sufficiently. The enclosure acoustically encompasses the internal components, i.e. a diesel engine, generator, radiator, radiator fan, electric control unit and two ventilation ducts. Table 1 Specification of a heavy duty diesel engine generator set Diesel Engine Maker, model no. Net power output Rated speed Generator Maker, Model No. Rated output Frequency/rpm Radiator Muffler Core size (mm) Cummins NTA-855-G3 Stand-by 515 HP Continuous 460 HP 1800 rpm Newage Stamford MHC 634-2G 576 kW(720 kVA) at 80 C 60 Hz/1800 rpm Radiated heat Pin pitch 12001200141 7 Row 275,000 kCal/h 3.0 mm Sound Attention Overall length Body diameter 40 dB 2187 mm 460 mm 446 H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 Fig. 1(b) shows a typical diesel engine generator set (length of 4.6 m, width of 1.5 m and height of 3.0 m) designed without paying attention to noise-reduction, having the electric power capacity the same as our design generator set. The noise level of this generator set appears to be A-weighted 102 dB at the maintainer position. The main contribution of the high level noise comes from the noise radiated directly through the ventilation outlet of the enclosure. From this observation, we judge that the conventional diesel engine generator enclosures are not effective on the control of the low frequency noises that compose the main portion of the overall level. So substantial reduction of the noise level can only be accomplished through adopting some means to control the low frequency noises. Here, we try to cope with this problem by adopting two square-type ventilation ducts, one of which is the intake one and the other is the outtake one, and assigning a silencing function to them. To obstruct the free passage of the low frequency noise, the outtake ventilation duct is bent by 90 near mid length. The vertical part of the outtake ventilation duct is put in the enclosure and the upper part outside above the enclosure, and is bent once more by 90 near the outlet. Splitting a square duct into two ducts with two separation plates makes the intake duct and the tipper part of the outtake duct. One of the plates has some inclination angle to the duct length direction, to use the space effectively. They are placed just above the enclosure. The inclination angle of the separation plate has large influence on the noise transmission characteristics of the outtake duct [3]. Now this ventilation duct acts as a duct silencer. With the same reasoning, the intake ventilation duct is bent twice by 90 . Fig. 3 shows the acoustic enclosure, ventilation duct silencers and the flow path of cooling air. The cooling air enters into the inlet of the intake duct silencer, flows into the internal space and subsequently passes Fig. 3. Acoustic enclosure with ventilation duct silencers. 447 H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 over the heat sources, such as the generator, diesel engine, and radiator fan. The heated air goes outside through the outlet of the outtake duct silencer. The cutoff frequency [4] of the outtake duct silencer is designed to be higher than the blade rotation frequency of the radiator fan. Only a small portion of the noises in the frequency range lower than the cutoff frequency is diffracted out into the air. The initial basic design is evolved by numerical reanalysis procedure to accomplish systematically the second and third requirements. 3. Design improvement by numerical acoustic analysis In our system, the noises pass through the ventilation duct silencers or radiate through the acoustic enclosure, and so form both internal acoustic scattering and external acoustic radiation problems. Here we rely on the indirect boundary element method (IBEM) that can deal with both internal and external acoustic fields simultaneously with relatively less computation effort [5]. The boundary condition for the enclosure surface is assumed to be zero double-layer potential and the engine, generator and radiator fan are considered as acoustic spherical sources. Generally, several design parameters can be adopted to select the best choice of noise reduction system. But, with our purpose to develop a low noise generator set with a SPL below 80 dB with low cost and time, we choose only one critical design parameter in our basic design, i.e. the inclination angle of the separation plate between the intake and outtake ducts. The plate was adopted to suppress the low frequency noises by prolonging the outlet duct length. In implementing the plate, the inclination angle complicatedly influences the acoustic field structure in our comlex shape duct. The noise level variations occur due to the variation of the acoustic field structure. The variation of the noise reduction performance due to the inclination angle of the plate is calculated from the numerical reanalysis and the best inclination angle is identified. From the search results given in Table 2, the inclination angle of about 30 degrees is assumed to be most favourable. Fig. 4 shows the A-weighted SPL contours at the frequencies 125 and 500 Hz in the middle cross-section of the upper outtake duct along the length direction. Also, Fig. 5 gives the results in the middle cross-section of the intake duct along the length direction. Still, some portion of the noise in the frequency range lower than the cutoff frequency, 230 Hz, of the duct silencer, is transmitted out by diffraction as shown in Fig. 4(a). The contour lines of A-weighted SPL in the frequency range greater than the cutoff frequency appear to be dense near the walls of the enclosure, which means Table 2 SPL variations according to the dividing plate angle Angle ( ) 27 28 29 30 31 32 33 34 SPL (dBA) 93.9 115.0 83.1 83.5 83.7 83.9 83.7 87.4 448 H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 Fig. 4. A-weighted SPL (dBA) contours in the middle cross-section of the upper outtake duct at two main troubled frequencies: (a) 125 Hz, (b) 500 Hz. H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 449 Fig. 5. A-weighted SPL (dBA) contours in the middle cross-section of the upper intake duct at two main troubled frequencies: (a) 125 Hz, (b) 500 Hz. 450 H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 that the noise in this frequency range is greatly reduced in the ducts. The noise through the outtake duct silencer is radiated into the sky without substantial influence on the system maintainer location. Fig. 6 shows the A-weighted SPL contour lines at 1 m in front of the wall of the enclosure at the frequency 500 Hz. The contributions of two frequency components 125 Hz and 250 Hz are little. It informs that the SPL is lower than 80 dB at the system maintainer position of 1 m distance from the control panel side wall, 1 m height front the ground and 0.75 m distance from the front wall. 4. Cooling performance check by numerical analysis Since most noise sources in the genetator set also play as heat sources, the acoustical design of the enclosure system should be examined in terms of cooling performance [6,7]. The cooling performance of the designed enclosure model is checked by numerical thermal flow analysis with a commercial code FLUENT [8]. Fig. 3 also presents the thermal boundary conditions at the inlet and outlet of cooling air. First, the velocity of cooling air at the inlet is assumed to be constant, and the flow direction at the outlet not to vary. Second, pressure conditions at the inlet and outlet are set with the total pressure, i.e. sum of ambient and dynamic pressure, and the ambient pressure, respectively. At the inlet, the flow velocity into Fig. 6. A-weighted SPL (dBA) of 500 Hz at 1 m in front of the enclosure wall. H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 451 the enclosure is 16 m/sec, the dynamic pressure 128.6 Pa and temperature 38 C. The boundary conditions of the enclosure wall and the plates consisting the internal structure are assumed such that the enclosure is adiabatic and the internal plates have the thermal conductivity of 73 W/(m C). And no-slip flow condition for all the walls and plates are forced. The surface temperatures of the diesel engine and generator are set constant as 100 and 60 C, respectively. Fig. 7. Temperature contours ( C) along: (a) the intake cooling air path, (b) the outtake cooling air path. 452 H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 Fig. 7(a) and (b) show the temperature contours along the intake and outtake cooling air path, respectively. These are the analysis results with only forced convection considered. As shown in the figures, the temperature contours concentrate densely around the heat sources, and lie sparsely in the other space. These observations show that the temperature varies rapidly only near the heat sources, but does not change much along the cooling air path and so the cooling air temperature is not varied substantially during the travel from the inlet to the outlet. From this, it can be judged that the acoustically designed enclosure with ventilation ducts satisfies the specification of temperature difference, lower than 10 C, between ambience and enclosure inside. 5. Experimental confirmation of the design The designed low noise generator set is constructed and placed in a yard fenced by a wall made of absorbing materials to make a free acoustic field. As shown in Figs. 8 Table 3 Comparison of analyzed and measured SPLs Location 1 2 3 4 5 6 7 Measuring height (m) (from ground) 1 1 2 2 3.7 3.7 3.7 SPL [dBA(A)] : analysis SPL [dBA(A)]: experiment 125 Hz 250 Hz 500 Hz Overall value 45 45 46 45 53 46 45 65 68 65 68 68 69 65 76 76 73 73 75 75 78 76.3 76.6 73.6 74.2 75.8 76.0 78.2 Fig. 8. SPL measuring points. 81 77 81 74 78 75 78 H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 453 and 9, and Table 3, the sound pressures are measured at several specified points on a measuring plane in front of the generator set. Table 3 compares the Sound Pressure Levels between numerically analyzed and measured. The small differences between the analyzed and measured values at the locations 1 and 3 seem to occur due to the neglect of the noise radiated through the Fig. 9. 1/3 octave-band sound pressure spectra at two main locations: (a) location 1, (b) location 3. 454 H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 chinks of the doors in the boundary condition and the noise above the frequency 500 Hz in the analysis. At the location 3, the A-weighted SPL from the measurement shows the highest value, 76 dB, at 1.6 kHz, the noise of which frequency may go out easily through the door chinks. Henceforth, if the frequency range extends to 2 kHz and the door chinks are considered in the numerical analysis, the analyzed values are expected to be much closer to the measured values. At locations 5 around the inlet, 6 and 7 around the outlet, the analysis anticipates relatively well the measured values. The relatively large difference at the location 5 between them seems to be due to the noise of the exhaust gas pipe located near to the position 5. The position 2 is where the control panel is installed and the system maintainer does his job and so is the most important location in the noise reduction design. At this position, the analyzed value closely predicts the experimental one, A-weighted 77 dB, which is less than the design target level 80 dB. Resistance temperature detectors are installed in the upper space just above the engine, at the inlet and outlet. Fig. 10 shows the measured temperatures. The ambient temperature of the generator set varies from 17 to 28 C. The temperature difference between in the ambience and in the enclosure inside is measured as about 2 C. 6. Conclusion An acoustic enclosure system with ventilation duct silencers for the heavy duty diesel engine generator set was designed through an acoustic analysis procedure based on the indirect boundary element method (IBEM). The noise characteristics Fig. 10. Measured temperatures of the upper space above the engine, the inlet and the outlet. H.-D. Ju et al. / Applied Acoustics 65 (2004) 441–455 455 of the system required for the analysis and design guide were identified with sound intensity measurement. The acoustically designed enclosure and duct system was confirmed to guarantee smooth circulation of the cooling air through the numerical thermal and flow analysis. First, the acoustic enclosure system with ventilation duct silencers was initially designed by rule of thumb and improved numerically to satisfy A-weighted SPL lower than 80 dB at a specified system maintainer position and temperature difference lower than 10 C between in the ambience and the enclosure inside. Finally, the developed low noise generator set was approved by the experiment. References [1] Baxa DE. Noise control in internal combustion engines. New York: Wiley; 1982. [2] Fahy FJ. Sound intensity. London: Elsevier Science LTD; 1989. [3] Schulz N, Summerson WA. Noise control for diesel engine generator sets. Sound and Vibration 1980:30–3. [4] Munjal ML. Acoustics of ducts and mufflers. New York: Wiley; 1987. [5] Ciskowski RD, Brebhia CA. Boundary element methods in acoustics. Southampton: Computational Mechanics Publications; 1991. [6] Aoki K, Hanaoka Y, Hara M. Numerical simulation of three dimensional engine compartment air flow in FWD vehicles. SAL paper 1990;900086. [7] Dugand MM, Vitali DF. Vehicle internal thermo-fluid dynamics, experimental and numerical evaluation. SAL paper 1990;905234. [8] Choi JW, Kim KE, Lee HJ. Simple design method of the engine enclosure considering cooling and noise reduction. Journal of KSNVE 1999;9(1):184–8.
© Copyright 2026 Paperzz