Data Sheet

750-325
CC-Link Fieldbus Coupler; 156 kBaud ... 10 Mbaud;
digital and analog signals
01 02
Fieldbus
connection
231 Series (MCS)
L RUN
A
L ERR
B
SD
24V 0V
RD
I/O
ON
+
+
—
—
750-325
1 2 3 4 5 6 7 8
Operation mode,
cyclic setting,
occupied stations,
baud rate
78
456
78
901
456
The buscoupler automatically configures, creating a local process
image which may include analog, digital or specialty modules. Analog
and specialty module data is sent via words and/or bytes, digital data
is sent bit by bit.
CC‐Link allows the storing of the process image in the corresponding
Master control (PLC, PC or NC).
Description
Item No.
CC-Link Fieldbus Coupler
750-325
Pack.
Unit
1
Power jumper
contacts
The local process image is divided into two data zones containing the
data received and the data to be sent. The process data can be sent
via the CC-Link to a control system for further processing.
The process output data can be sent via the CC-Link.
The data of the analog modules is stored in the process image, which
is created automatically according to the order in which the modules
are connected to the buscoupler.
The bits of the digital modules are sent byte by byte and added to the
analog data. If the amount of digital information exceeds eight bits, the
buscoupler automatically starts with a new byte.
Technical Data
Number of fieldbus nodes on
master max.
Transmission medium
Bus segment length max.
Baud rate
Connection technology:
Fieldbus input/output
ACCESSORIES
Item No.
Mini-WSB quick marking system
Plain
Pack.
Unit
248-501
50
Supply via
power jumper
contacts
24 V
23
x10
Conguration
interface
This fieldbus coupler connects the WAGO‐I/O-SYSTEM as a slave
to the CC-Link fieldbus. The fieldbus coupler supports the CC-Link
protocol versions V1.1. and V2.0.
Supply
24 V
0V
23
x1
Adress
Data contacts
0V
901
Adress
Status
voltage supply
-System
-Power jumper
contacts
64
Shielded Cu cable 2 / 3 x 0.5 mm²
100 … 1200 m (depends on baud
rate/cable)
156 kBaud … 10 Mbaud
MCS connector included
Approvals
Conformity marking
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes
1
06.04.2017
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Tel.: +49(0)571/887-0
Fax: +49(0)571/887-169
E-Mail: [email protected]
www.wago.com
750-325
FIELDBUS
INTERFACE
I/O
modules
24 V
1
5
24 V /0 V
47 nF
6
24 V
ELEKTRONICS
3
ELEKTRONICS
24 V
FIELDBUS
INTERFACE
7
0V
4
5V
5V
0V
2
24 V
0V
10 nF
47 nF
8
750-325
Technical Data
Number of I/O modules per node
max.
Operation mode
Occupied Stations
Extended cyclic setting
Input process image (internal) max.
Output process image (internal)
max.
General specifications
64
CC-Link V2.0 (default setting)/V1.1
1 … 4 / 4 (default setting)
1, 2, 4 (default setting), 8 cycles
RX (digital inputs):
V1.1: 16, 48, 80, 112 bits
V2.0: 16, 48, 80, 112 bits (1 cycle)
V2.0: 16, 80, 144, 208 bits (2 cycles)
V2.0: 48, 176, 304, 432 bits (4 cycles)
V2.0: 112, 368, 624, 880 bits (8
cycles)
and per 16-bit system area
RWr (analog inputs):
V1.1: 4, 8, 12, 16 words (16 bit)
V2.0: 4, 8, 12, 16 words (1 cycle)
V2.0: 8, 16, 24, 32 words (2 cycles)
V2.0: 16, 32, 48, 64 words (4 cycles)
V2.0: 32, 64, 96, 128 words (8 cycles)
RY (digital outputs):
V1.1: 16, 48, 80, 112 bits
V2.0: 16, 48, 80, 112 bits (1 cycle)
V2.0: 16, 80, 144, 208 bits (2 cycles)
V2.0: 48, 176, 304, 432 bits (4 cycles)
V2.0: 112, 368, 624, 880 bits (8
cycles)
and per 16-bit system area
RWw (analog outputs):
V1.1: 4, 8, 12, 16 words (16 bit)
V2.0: 4, 8, 12, 16 words (1 cycle)
V2.0: 8, 16, 24, 32 words (2 cycles)
V2.0: 16, 32, 48, 64 words (4 cycles)
V2.0: 32, 64, 96, 128 words (8 cycles)
System supply voltage
Input current (typ.) at rated load
(24 V)
Power supply efficiency typ.
at nominal load (24 V)
Current consumption, system
supply
Total current for system supply
Isolation
Field supply voltage
Current carrying capacity of the
power jumper contacts
Ambient operating temperature
(operation)
Connection technology
Conductor size
Strip lengths
Dimensions W x H x D
Weight
Ambient operating temperature
(storage)
Relative humidity
Vibration resistance
Shock resistance
Protection type
EMC immunity to interference
EMC emission of interference
24 VDC (−25 … +30 %)
500 mA
90 %
200 mA
1800 mA
500 V system/supply
24 VDC (−25 … +30 %),
via power jumper contacts
10 A
0 … +55 °C
CAGE CLAMP®
0.08 … 2.5 mm² / 28 … 14 AWG
8 … 9 mm / 0.33 inch
61.5 x 71.9 x 100 mm
149 g
−25 … +85 °C
95 % non condensing
Per IEC 60068-2-6
per IEC 60068-2-27
IP20
Per EN 61000-6-2
per EN 61000-6-4