licensed boiler and steam engineers

INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE
REFERENCE NO.: LAMC 97.0201
DOCUMENT NO.:
P/MC 2014-004
Previously Issued As: P/MC 2011-004
Effective:
Revised:
01-01-2014
LICENSED BOILER AND STEAM ENGINEERS
Section 97.0201 of the Los Angeles Municipal Code specifies that a boiler or steam engineer's license
is required to operate any boiler* or steam generating apparatus of over five horsepower carrying over
15 pounds of steam. The Code does not differentiate between the conditions: 5 HP and 15 psi or 5 HP
or 15 psi.
Section 97.0201 shall be interpreted to mean that a licensed operator is not required to use the following
equipment:
1.
Heating boilers and hot water supply boilers, as covered in Section IV of the ASME Boiler and
Pressure Vessel Code (Heating Boilers), which is adopted by reference in Section 97.0303(a).
2.
Steam boilers for operation at pressures not exceeding 15 psi and equipped with safety or relief
valves set at not more than 15 psi.
3.
Lined potable water heaters for operation at pressures not exceeding 160 psi or temperatures not
exceeding 210 degrees F.
Footnotes
*
Boiler - means any High Pressure Boiler**, Low Pressure Boiler or Hot Water Boiler.
**
High Pressure Boiler - means any boiler furnishing steam in excess of 15 pounds per
square inch or hot water at temperatures in excess of 250 degrees F or at pressure in
excess of 160 pounds per square inch.
A s a c o ve red entity under T itle II of the A m ericans with D isabilities A ct, the C ity of Los A ngeles does not discrim inate on the basis of disability and, upon request, will pro v id e
reasonable accom m odation to ensure equal access to its program s, services and activities. For efficient handling of inform ation internally and in the internet, conversion to this new
form at of code related and adm inistrative inform ation bulletins including M G D and R G A that w ere previously issued w ill also allow flexibility and tim ely distribution of inform ation to
the public.