Augusta State Med. 1.5 ton Revised 3-28-17

Submittal
Prepared For:
Georgia Dept. Corrections
Date: March 28, 2017
Job Name:
Augusta State Med. 1.5 ton
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty
Product
8
1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A
The attached information describes the equipment we propose to
furnish for this project, and is submitted for your approval.
Brian Cullinan
Trane
3609 Ogeechee Blvd., Suite A
Savannah, GA 31405
Phone: (912) 965-0313
Cell: (912) 704-9358
Fax: (912) 965-0314
Product performance and submittal data is valid for a period of 6 months
from the date of submittal generation. If six months or more has elapsed
between submittal generation and equipment release, the product
performance and submittal data will need to be verified. It is the
customer’s responsibility to obtain such verification.
J:\JOBS\1135\28352\5\Augusta State Med. 1.5 ton Revised 3-28-17.doc
Table Of Contents
Product Summary ..................................................................................................................... 1
1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A (Item A1) ........................................................... 3
Tag Data .................................................................................................................................................. 3
Product Data ............................................................................................................................................ 3
Mechanical Specifications ........................................................................................................................ 4
Unit Dimensions ....................................................................................................................................... 6
Weight, Clearance & Rigging Diagram..................................................................................................... 8
Accessory .............................................................................................................................................. 10
Field Installed Options - Part/Order Number Summary ........................................................ 12
1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A ........................................................................................ 12
Augusta State Med. 1.5 ton
March 28, 2017
Tag Data - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A (Qty: 8)
Item Qty Description
Model Number
A1
8
1.5 Ton Pkgd. Heat Pump R-410A 4WCC4024-1000
Product Data - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A
Item: A1 Qty: 8
R-410A convertible heat pump 14 SEER
2 Tons, 14 SEER
208-230/1/60
3.76/5.0kw 208/240/1 (Fld)
1-2" Filter frame (Fld)
Manual fresh air damper (Fld)
Prog, 7 Day, 3 Htg/2 Clg w/dehumid (Fld)
2-5th yr Parts warr.
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal
Page 3 of 12
Augusta State Med. 1.5 ton
March 28, 2017
Mechanical Specifications - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A
Item: A1 Qty: 8
Programmable Electronic Night Setback Thermostat
Programmable electronic thermostat shall provide heating setback and cooling setup with 7-day, programming
capability. 1H/1C or 2H/2C models available.
Manual Outside Air Dampers
Rain hood and screen shall be field installed. Suitable for up to 25% outside air.
Electric Heaters
Each heater assembly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat
limiter for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage
wiring. Electric heat modules shall be UL listed.
4WCC4 - General
The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped,
internally wired and fully charged with refrigerant. Units shall be certified to UL Standard 1995. All units shall be factory
run tested to check cooling operation, fan and blower rotation and control or TXV sequence. Units shall be designed to
operate at ambient temperatures between 115°F and 55°F in cooling as manufactured. Cooling performance shall be
rated in accordance with AHRI standards.
4WCC4 - Unit Casing
All components shall be mounted in a weather-resistant steel cabinet with an enamel finish. Access panels shall be
provided for unit controls and indoor coil and fans. Indoor air section compartment shall be completely insulated with
fireproof, permanent, odorless fiber material. Knockouts shall be provided for utility and control connections. Drain
connections shall be provided to accommodate indoor water runoff.
4WCC4 - Compressor
The compressor shall be hermetically sealed, high efficiency scroll compressors. Internal over current and over
temperature protection, internal pressure relief shall be standard. Other features include centrifugal oil pump, low
vibration and noise.
4WCC4 - Refrigeration System
All units shall have refrigerant control. Service pressure tap ports and a refrigerant line filter shall be standard.
4WCC4 - Evaporator Coil
Internally enhanced 3/8"OD seamless copper tubing mechanically bonded to aluminum fins, factory pressure and leak
tested at 480 - 650 psig. All units have TXV to control refrigerant flow.
4WCC4 - Condenser Coil
The Spine Fin condenser coil shall be continuously wrapped, corrosion resistant all aluminum with minimum brazed
joints. This coil is 3/8¿ OD seamless aluminum tubing glued to a continuous aluminum fin. Coils are lab tested to
withstand 2.000 pounds of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat
transfer. The coil is protected on all four sides by louvered panels.
4WCC4 - Indoor Air Fan
Constant Torgue, forward-curved, centrifugal wheel in a Composite Vortica ® Blower housing. Motor shall have thermal
overload protection and permanently lubricated motor bearings. Motor/blower assembly isolated from unit with rubber
mounts.
4WCC4 - Outdoor Fan
One direct-drive, statically and dynamically balanced propeller fan shall be used in a draw through vertical discharge
configuration. Permanently lubricated weather proof motor shall have built-in thermal overload protection.
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal
Page 4 of 12
Augusta State Med. 1.5 ton
March 28, 2017
4WCC4 - System Controls
System controls include condenser fan, evaporator fan and compressor contactors.
4WCC4 - Electric Heaters
Each heater assembly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat
limiters for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage
wiring. Electric heat modules shall be UL listed.
4WCC4 - Manual Outside Air Dampers
Rain hood and screen shall be field installed. Suitable for up to 25% outside air.
4WCC4 - Programmable Electronic Night Setting Thermostat
Programmable electronic thermostat shall provide heating setback
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal
Page 5 of 12
Augusta State Med. 1.5 ton
March 28, 2017
Unit Dimensions - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A
Item: A1 Qty: 8
FAN GRILLE
41 5/16"
Y Y
SUPPLY
RETURN
12"
46"
3 3/16"
16"
3 3/16"
6 5/8"
16"
7"
48 13/16"
UNIT - TOP VIEW
71"
UNIT - BOTTOM PENETRATION VIEW
70"
72"
SECTION X-X
TYPICAL (8) SIDES OF
SIDEFLOW DUCT OPENINGS
56"
20 7/8"
SECTION Y-Y
TYPICAL (8) SIDES OF
DOWNFLOW DUCT OPENINGS
11 11/16"
SUPPLY
RETURN
X
2 5/16"
6 15/16"
3 5/16"
X
15 11/16"
7 3/16"
15 11/16"
UNIT - BACK AND PENETRATION VIEW
24V ENTRY
37 3/8"
14 3/16"
11 3/8"
8 7/8"
POWER ENTRY 7/8" DIA. HOLE 1 3/8" DIA. KNOCKOUT
1 5/8" DIA. KNOCKOUT
4 5/8"
1"
18 11/16"
CONDENSATE DRAIN FOR
<0.75~ln>> FEMALE NPT
3 3/8"
5 1/16"
POWER ENTRY 7/8" DIA. KNOCKOUT
1 3/8" DIA. KNOCKOUT 1 5/8" DIA. KNOCKOUT
SINGLE POINT ENTRY 1 3/8" DIA. KNOCKOUT
1 5/8" DIA. KNOCKOUT 2 7/16" DIA. KNOCKOUT
UNIT - LEFT SIDE VIEW
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
UNIT - RIGHT SIDE VIEW
Equipment Submittal
Page 6 of 12
Augusta State Med. 1.5 ton
March 28, 2017
Unit Dimensions - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A
Item: A1 Qty: 8
ELECTRICAL / GENERAL DATA
POWER CONNECTION
Model:
Voltage Range:
Min. Circuit Ampacity:
Max. Circuit Breaker:
Prot. Rtg. Recmd:
EER/SEER
Noise Rating # :
COMPRESSOR
4WCC4024A1
208-230/1/60
19.4
30.0
30.0
12.0/14.0
66.4
OUTDOOR MOTOR
Number:
Horsepower:
Phase
Full Load Amps:
Locked Rotor Amps:
INDOOR MOTOR
1
0.08
1
0.54
0.82
HEATER
Model:
Voltage:
Phase:
Heater Capacity (Kw):
Heater (Btu):
# of Stages:
Stage # 1:
Stage # 2:
MCA:
MBS:
Number:
Phase:
Rated Load Amps:
Locked Rotor Amps:
Number:
Horsepower:
Motor Speed (RPM):
Phase
Full Load Amps:
Locked Rotor Amps:
1
1
12.8
58.3
REFRIGERANT
1
0.33
1050
1
2.8
-
Type:
Factory Charge
Circuit #1:
R-410
5.7 lb
SINGLE CIRCUIT POWER AMPACITY AND OVER CURRENT PROTECTION
BAYHTRV105
208/240
1
3.76/5.0
12800/17100
1
3.76/5.0
N/A
23.0/26.0
25.0/30.0
Single Power Entry Kit
Minimum Circuit Ampacity
Maximum Over-Current Device
1. Single Circuit Power fuses are supplied if required for unit and / or heater.
2. Wiring requirements if unit and electric heaters are operated from a single circuit
using a single power entry kit.
NOTES:
UNIT ONLY
1. Rated in accordance with A.H.R.I. Standard 210/240.
2. Rated in accordance with D.O.E. test procedure.
3. Rated in accordance with A.H.R.I. Standard 270.
ELECTRIC HEATER ACCESSORY ONLY
4. Any power supply and circuits must be wired and protected in accordance with local electrical codes.
5. The MCA values listed are for electric heater only.
6. The MCA values listed are for electric heater only.
7. Field wire must be rated at least 75 C.
8. The HACR circuit breaker is for U.S.A. installations only.
9. For Canada installations reference only.
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal
Page 7 of 12
Augusta State Med. 1.5 ton
March 28, 2017
Weight, Clearance & Rigging Diagram - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A
Item: A1 Qty: 8
A
W3
W6
W1
W2
W4
W5
B
CENTER OF GRAVITY
UNIT WEIGHT
SHIPPING
CORNER WEIGHT
NET
W1
W2
W3
W4
CLEARANCE TO COMBUSTIBLE MATERIAL
BOTTOM
CENTER OF GRAVITY
W5
W6
A
B
RECOMMENDED SERVICE CLEARANCE
0
UNIT
BACK SIDE
1"
BACK SIDE
12"
LEFT SIDE
6"
LEFT SIDE
36"
RIGHT SIDE
6"
RIGHT SIDE
24"
FRONT SIDE
12"
FRONT SIDE
42"
TOP
36"
WITH O.A. DAMPER/ECON.
WITH 2 POS. DAMPER
30"
42"
LIFTING LUG KITS
FOUR REUSABLE LUGS IN EACH KIT ALLOW UNITS TO BE EASILY LIFTED TO ROOFTOP INSTALLATIONS.
THESE LUGS SNAP (NO SCREWS REQUIRED) INTO SLOTS IN THE UNIT DRIP LIP CHANNEL.
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal
Page 8 of 12
Augusta State Med. 1.5 ton
March 28, 2017
Weight, Clearance & Rigging Diagram - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A
Item: A1 Qty: 8
A
W3
W6
W1
W2
W4
W5
B
CENTER OF GRAVITY
UNIT WEIGHT
SHIPPING
402.0 lb
CORNER WEIGHT
NET
W1
328.0 lb
117"
W2
73"
W3
W4
53.0 lb
84.0 lb
CLEARANCE TO COMBUSTIBLE MATERIAL
BOTTOM
CENTER OF GRAVITY
A
B
22 5/16"
16 7/8"
RECOMMENDED SERVICE CLEARANCE
0
UNIT
BACK SIDE
1"
BACK SIDE
12"
LEFT SIDE
6"
LEFT SIDE
36"
RIGHT SIDE
6"
RIGHT SIDE
24"
FRONT SIDE
12"
FRONT SIDE
42"
TOP
36"
WITH O.A. DAMPER/ECON.
WITH 2 POS. DAMPER
30"
42"
LIFTING LUG KITS
FOUR REUSABLE LUGS IN EACH KIT ALLOW UNITS TO BE EASILY LIFTED TO ROOFTOP INSTALLATIONS.
THESE LUGS SNAP (NO SCREWS REQUIRED) INTO SLOTS IN THE UNIT DRIP LIP CHANNEL.
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal
Page 9 of 12
Augusta State Med. 1.5 ton
March 28, 2017
Accessory - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A
Item: A1 Qty: 8
6"
1 3/8"
4 5/8"
THERMOSTAT - TCONT800A/802A/803A
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal
Page 10 of 12
Augusta State Med. 1.5 ton
March 28, 2017
Accessory - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A
Item: A1 Qty: 8
OUTSIE AIR
DAMPER HOOD
9 9/16"
12 3/8"
MANUAL OUTSIDE AIR- HOOD
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal
Page 11 of 12
Augusta State Med. 1.5 ton
March 28, 2017
Field Installed Options - Part/Order Number Summary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order
numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of
material for the job.
Product Family - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A
Item Tag(s)
Qty Description
A1
No Tag
8
1.5 Ton Pkgd. Heat Pump R-410A
Field Installed Option Description
Prog, 7 Day, 3 Htg/2 Clg w/dehumid
3.76/5.0kw 208/240/1
Manual fresh air damper
1-2" Filter frame
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Model Number
4WCC4024-1000
Part/Ordering Number
TCONT803AS32DA
BAYHTRV105F
BAYOSAH001A
BAYFLTR101C
Equipment Submittal