Submittal Prepared For: Georgia Dept. Corrections Date: March 28, 2017 Job Name: Augusta State Med. 1.5 ton Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 8 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval. Brian Cullinan Trane 3609 Ogeechee Blvd., Suite A Savannah, GA 31405 Phone: (912) 965-0313 Cell: (912) 704-9358 Fax: (912) 965-0314 Product performance and submittal data is valid for a period of 6 months from the date of submittal generation. If six months or more has elapsed between submittal generation and equipment release, the product performance and submittal data will need to be verified. It is the customer’s responsibility to obtain such verification. J:\JOBS\1135\28352\5\Augusta State Med. 1.5 ton Revised 3-28-17.doc Table Of Contents Product Summary ..................................................................................................................... 1 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A (Item A1) ........................................................... 3 Tag Data .................................................................................................................................................. 3 Product Data ............................................................................................................................................ 3 Mechanical Specifications ........................................................................................................................ 4 Unit Dimensions ....................................................................................................................................... 6 Weight, Clearance & Rigging Diagram..................................................................................................... 8 Accessory .............................................................................................................................................. 10 Field Installed Options - Part/Order Number Summary ........................................................ 12 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A ........................................................................................ 12 Augusta State Med. 1.5 ton March 28, 2017 Tag Data - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A (Qty: 8) Item Qty Description Model Number A1 8 1.5 Ton Pkgd. Heat Pump R-410A 4WCC4024-1000 Product Data - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A Item: A1 Qty: 8 R-410A convertible heat pump 14 SEER 2 Tons, 14 SEER 208-230/1/60 3.76/5.0kw 208/240/1 (Fld) 1-2" Filter frame (Fld) Manual fresh air damper (Fld) Prog, 7 Day, 3 Htg/2 Clg w/dehumid (Fld) 2-5th yr Parts warr. FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment Submittal Page 3 of 12 Augusta State Med. 1.5 ton March 28, 2017 Mechanical Specifications - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A Item: A1 Qty: 8 Programmable Electronic Night Setback Thermostat Programmable electronic thermostat shall provide heating setback and cooling setup with 7-day, programming capability. 1H/1C or 2H/2C models available. Manual Outside Air Dampers Rain hood and screen shall be field installed. Suitable for up to 25% outside air. Electric Heaters Each heater assembly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat limiter for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage wiring. Electric heat modules shall be UL listed. 4WCC4 - General The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped, internally wired and fully charged with refrigerant. Units shall be certified to UL Standard 1995. All units shall be factory run tested to check cooling operation, fan and blower rotation and control or TXV sequence. Units shall be designed to operate at ambient temperatures between 115°F and 55°F in cooling as manufactured. Cooling performance shall be rated in accordance with AHRI standards. 4WCC4 - Unit Casing All components shall be mounted in a weather-resistant steel cabinet with an enamel finish. Access panels shall be provided for unit controls and indoor coil and fans. Indoor air section compartment shall be completely insulated with fireproof, permanent, odorless fiber material. Knockouts shall be provided for utility and control connections. Drain connections shall be provided to accommodate indoor water runoff. 4WCC4 - Compressor The compressor shall be hermetically sealed, high efficiency scroll compressors. Internal over current and over temperature protection, internal pressure relief shall be standard. Other features include centrifugal oil pump, low vibration and noise. 4WCC4 - Refrigeration System All units shall have refrigerant control. Service pressure tap ports and a refrigerant line filter shall be standard. 4WCC4 - Evaporator Coil Internally enhanced 3/8"OD seamless copper tubing mechanically bonded to aluminum fins, factory pressure and leak tested at 480 - 650 psig. All units have TXV to control refrigerant flow. 4WCC4 - Condenser Coil The Spine Fin condenser coil shall be continuously wrapped, corrosion resistant all aluminum with minimum brazed joints. This coil is 3/8¿ OD seamless aluminum tubing glued to a continuous aluminum fin. Coils are lab tested to withstand 2.000 pounds of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. 4WCC4 - Indoor Air Fan Constant Torgue, forward-curved, centrifugal wheel in a Composite Vortica ® Blower housing. Motor shall have thermal overload protection and permanently lubricated motor bearings. Motor/blower assembly isolated from unit with rubber mounts. 4WCC4 - Outdoor Fan One direct-drive, statically and dynamically balanced propeller fan shall be used in a draw through vertical discharge configuration. Permanently lubricated weather proof motor shall have built-in thermal overload protection. FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment Submittal Page 4 of 12 Augusta State Med. 1.5 ton March 28, 2017 4WCC4 - System Controls System controls include condenser fan, evaporator fan and compressor contactors. 4WCC4 - Electric Heaters Each heater assembly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat limiters for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage wiring. Electric heat modules shall be UL listed. 4WCC4 - Manual Outside Air Dampers Rain hood and screen shall be field installed. Suitable for up to 25% outside air. 4WCC4 - Programmable Electronic Night Setting Thermostat Programmable electronic thermostat shall provide heating setback FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment Submittal Page 5 of 12 Augusta State Med. 1.5 ton March 28, 2017 Unit Dimensions - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A Item: A1 Qty: 8 FAN GRILLE 41 5/16" Y Y SUPPLY RETURN 12" 46" 3 3/16" 16" 3 3/16" 6 5/8" 16" 7" 48 13/16" UNIT - TOP VIEW 71" UNIT - BOTTOM PENETRATION VIEW 70" 72" SECTION X-X TYPICAL (8) SIDES OF SIDEFLOW DUCT OPENINGS 56" 20 7/8" SECTION Y-Y TYPICAL (8) SIDES OF DOWNFLOW DUCT OPENINGS 11 11/16" SUPPLY RETURN X 2 5/16" 6 15/16" 3 5/16" X 15 11/16" 7 3/16" 15 11/16" UNIT - BACK AND PENETRATION VIEW 24V ENTRY 37 3/8" 14 3/16" 11 3/8" 8 7/8" POWER ENTRY 7/8" DIA. HOLE 1 3/8" DIA. KNOCKOUT 1 5/8" DIA. KNOCKOUT 4 5/8" 1" 18 11/16" CONDENSATE DRAIN FOR <0.75~ln>> FEMALE NPT 3 3/8" 5 1/16" POWER ENTRY 7/8" DIA. KNOCKOUT 1 3/8" DIA. KNOCKOUT 1 5/8" DIA. KNOCKOUT SINGLE POINT ENTRY 1 3/8" DIA. KNOCKOUT 1 5/8" DIA. KNOCKOUT 2 7/16" DIA. KNOCKOUT UNIT - LEFT SIDE VIEW FLD = Furnished by Trane U.S. Inc. / Installed by Others UNIT - RIGHT SIDE VIEW Equipment Submittal Page 6 of 12 Augusta State Med. 1.5 ton March 28, 2017 Unit Dimensions - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A Item: A1 Qty: 8 ELECTRICAL / GENERAL DATA POWER CONNECTION Model: Voltage Range: Min. Circuit Ampacity: Max. Circuit Breaker: Prot. Rtg. Recmd: EER/SEER Noise Rating # : COMPRESSOR 4WCC4024A1 208-230/1/60 19.4 30.0 30.0 12.0/14.0 66.4 OUTDOOR MOTOR Number: Horsepower: Phase Full Load Amps: Locked Rotor Amps: INDOOR MOTOR 1 0.08 1 0.54 0.82 HEATER Model: Voltage: Phase: Heater Capacity (Kw): Heater (Btu): # of Stages: Stage # 1: Stage # 2: MCA: MBS: Number: Phase: Rated Load Amps: Locked Rotor Amps: Number: Horsepower: Motor Speed (RPM): Phase Full Load Amps: Locked Rotor Amps: 1 1 12.8 58.3 REFRIGERANT 1 0.33 1050 1 2.8 - Type: Factory Charge Circuit #1: R-410 5.7 lb SINGLE CIRCUIT POWER AMPACITY AND OVER CURRENT PROTECTION BAYHTRV105 208/240 1 3.76/5.0 12800/17100 1 3.76/5.0 N/A 23.0/26.0 25.0/30.0 Single Power Entry Kit Minimum Circuit Ampacity Maximum Over-Current Device 1. Single Circuit Power fuses are supplied if required for unit and / or heater. 2. Wiring requirements if unit and electric heaters are operated from a single circuit using a single power entry kit. NOTES: UNIT ONLY 1. Rated in accordance with A.H.R.I. Standard 210/240. 2. Rated in accordance with D.O.E. test procedure. 3. Rated in accordance with A.H.R.I. Standard 270. ELECTRIC HEATER ACCESSORY ONLY 4. Any power supply and circuits must be wired and protected in accordance with local electrical codes. 5. The MCA values listed are for electric heater only. 6. The MCA values listed are for electric heater only. 7. Field wire must be rated at least 75 C. 8. The HACR circuit breaker is for U.S.A. installations only. 9. For Canada installations reference only. FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment Submittal Page 7 of 12 Augusta State Med. 1.5 ton March 28, 2017 Weight, Clearance & Rigging Diagram - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A Item: A1 Qty: 8 A W3 W6 W1 W2 W4 W5 B CENTER OF GRAVITY UNIT WEIGHT SHIPPING CORNER WEIGHT NET W1 W2 W3 W4 CLEARANCE TO COMBUSTIBLE MATERIAL BOTTOM CENTER OF GRAVITY W5 W6 A B RECOMMENDED SERVICE CLEARANCE 0 UNIT BACK SIDE 1" BACK SIDE 12" LEFT SIDE 6" LEFT SIDE 36" RIGHT SIDE 6" RIGHT SIDE 24" FRONT SIDE 12" FRONT SIDE 42" TOP 36" WITH O.A. DAMPER/ECON. WITH 2 POS. DAMPER 30" 42" LIFTING LUG KITS FOUR REUSABLE LUGS IN EACH KIT ALLOW UNITS TO BE EASILY LIFTED TO ROOFTOP INSTALLATIONS. THESE LUGS SNAP (NO SCREWS REQUIRED) INTO SLOTS IN THE UNIT DRIP LIP CHANNEL. FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment Submittal Page 8 of 12 Augusta State Med. 1.5 ton March 28, 2017 Weight, Clearance & Rigging Diagram - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A Item: A1 Qty: 8 A W3 W6 W1 W2 W4 W5 B CENTER OF GRAVITY UNIT WEIGHT SHIPPING 402.0 lb CORNER WEIGHT NET W1 328.0 lb 117" W2 73" W3 W4 53.0 lb 84.0 lb CLEARANCE TO COMBUSTIBLE MATERIAL BOTTOM CENTER OF GRAVITY A B 22 5/16" 16 7/8" RECOMMENDED SERVICE CLEARANCE 0 UNIT BACK SIDE 1" BACK SIDE 12" LEFT SIDE 6" LEFT SIDE 36" RIGHT SIDE 6" RIGHT SIDE 24" FRONT SIDE 12" FRONT SIDE 42" TOP 36" WITH O.A. DAMPER/ECON. WITH 2 POS. DAMPER 30" 42" LIFTING LUG KITS FOUR REUSABLE LUGS IN EACH KIT ALLOW UNITS TO BE EASILY LIFTED TO ROOFTOP INSTALLATIONS. THESE LUGS SNAP (NO SCREWS REQUIRED) INTO SLOTS IN THE UNIT DRIP LIP CHANNEL. FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment Submittal Page 9 of 12 Augusta State Med. 1.5 ton March 28, 2017 Accessory - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A Item: A1 Qty: 8 6" 1 3/8" 4 5/8" THERMOSTAT - TCONT800A/802A/803A FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment Submittal Page 10 of 12 Augusta State Med. 1.5 ton March 28, 2017 Accessory - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A Item: A1 Qty: 8 OUTSIE AIR DAMPER HOOD 9 9/16" 12 3/8" MANUAL OUTSIDE AIR- HOOD FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment Submittal Page 11 of 12 Augusta State Med. 1.5 ton March 28, 2017 Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family - 1.5-5 Ton Pkgd. Heat Pump Rooftop R-410A Item Tag(s) Qty Description A1 No Tag 8 1.5 Ton Pkgd. Heat Pump R-410A Field Installed Option Description Prog, 7 Day, 3 Htg/2 Clg w/dehumid 3.76/5.0kw 208/240/1 Manual fresh air damper 1-2" Filter frame FLD = Furnished by Trane U.S. Inc. / Installed by Others Model Number 4WCC4024-1000 Part/Ordering Number TCONT803AS32DA BAYHTRV105F BAYOSAH001A BAYFLTR101C Equipment Submittal Page 12 of 12
© Copyright 2026 Paperzz