2011 National Energy Code of Canada for Buildings (NECB) Errata Package Selected replacement pages have been produced for the NECB. Please print and insert in your copy of the Code. Errata Issued by the Canadian Commission on Building and Fire Codes The Change History table that follows describes errata and editorial updates that apply to the National Energy Code of Canada for Buildings 2011: • Errata are corrections to existing text. • Editorial updates are provided for information purposes only. Code pages containing errata are identified with the words “Amended Page” in the footer; pages with editorial updates and index pages with changes are not flagged. Contact your local authority having jurisdiction to find out if these errata apply in your province or territory. National Energy Code of Canada for Buildings 2011 xv Preface Change History — National Energy Code of Canada for Buildings 2011 Division Code Reference Change Date (Y-M-D) Description of Change B Table 1.3.1.2. erratum 2012-12-21 Entry was added for standard “DOE 10 CFR, Part 430-2011” B Table 1.3.1.2. erratum 2012-12-21 Entry for NRCan standard was corrected to read “SOR/94-651-2008” B 1.3.2.1.(1) editorial update 2012-12-21 Entry was added for DOE B 3.2.1.4.(1) erratum 2012-12-21 Equations for FDWR values were modified for clarity B Table 3.5.1.1. erratum 2012-12-21 Attributions for Sentences 3.2.4.4.(2) and (3) were deleted B 4.2.3.1.(3) erratum 2012-12-21 Sentence was corrected to read “... shall not be greater than the individual allowance for that application taken from Table 4.2.3.1.C. ...” B 5.2.5.3.(5) erratum 2012-12-21 Ratio was corrected to read “u2/u1” B 5.2.5.3.(6) erratum 2012-12-21 Ratio was corrected to read “u2/u1” B 5.2.10.2.(2) erratum 2012-12-21 Sentence was corrected to read “... that provides at least 80% of the dehumidification ...” B Table 5.2.12.1. erratum 2012-12-21 Table Note (5) was added to entries for furnaces B Table 5.5.1.1. erratum 2012-12-21 Attribution for Sentence 5.2.5.3.(2) was deleted B Table 6.2.2.1. erratum and editorial update 2012-12-21 Under entry for gas-fired service water heaters, input value “22–117 kW” was deleted Table Note (5) was deleted B 6.2.3.1.(2) erratum 2012-12-21 Ratio was corrected to read “u2/u1” B 6.2.3.1.(3) erratum 2012-12-21 Ratio was corrected to read “u2/u1” B Table 6.2.3.1. erratum 2012-12-21 Second value under column entitled “Mean Rating Temperature, °C” was corrected to read “38” B Table 6.5.1.1. erratum 2012-12-21 Attribution was added for Sentence 6.2.1.1.(1) B 7.2.4.1.(1) erratum 2012-12-21 Reference in Sentence was corrected to read “... Tables 3 and 5 of CSA C390, ...” B Table 8.4.4.22.A. erratum 2012-12-21 In entry for Furnace Part-Load Performance Curve(s), values listed for variable c under Condensing Furnace and Atmospheric Furnace were interchanged B Table 8.5.1.1. erratum 2012-12-21 Functional Statement F99 was deleted from attribution for Clauses 8.4.4.20.(3)(b) and (c) Index Letter H erratum 2012-12-21 Reference under Heaters/heating systems, recessed, was corrected to read “3.2.1.2.” Reference under Heating, ventilating and air-conditioning (HVAC) systems, baseboard heaters, was corrected to read “3.2.1.2.” xvi National Energy Code of Canada for Buildings 2011 Division B 1.3.1.2. Table 1.3.1.2. (Continued) Issuing Agency AHRI ANSI/AHRI 390-2003 Performance Rating of Single Package Vertical Air-Conditioners and Heat Pumps Table 5.2.12.1. AHRI ANSI/AHRI 1060-2005 Performance Rating of Air-to-Air Exchangers for Energy Recovery Ventilation 5.2.10.1.(5) AMCA 500-89 Louvers, Dampers and Shutters 5.2.4.2.(2) ANSI/CSA Gas Water Heaters – Volume III, Storage Water Heaters With Input Ratings Above Table 6.2.2.1. 75,000 Btu Per Hour, Circulating and Instantaneous Table 5.2.12.1. Gas-Fired Low Pressure Steam and Hot Water Boilers ASHRAE ANSI Z21.10.3-2004/ CSA 4.3-04 ANSI Z21.13-2004/ CSA 4.9-04 ANSI Z21.47-2006/ CSA 2.3-2006 ANSI Z21.56-2006/ CSA 4.7-2006 ANSI Z83.8-2006/ CSA 2.6-2006 2009 ASHRAE ANSI/CSA Document Number (1) Document Title (2) Code Reference Gas-Fired Central Furnaces Table 5.2.12.1. Gas-Fired Pool Heaters Table 6.2.2.1. Gas Unit Heaters, Gas Packaged Heaters, Gas Utility Heaters and Gas-Fired Duct Furnaces ASHRAE Handbook – Fundamentals Table 5.2.12.1. ANSI/ASHRAE 127-2007 Rating Computer and Data Processing Room Unitary Air-Conditioners Table 5.2.12.1. ASHRAE ANSI/ASHRAE 140-2007 Evaluation of Building Energy Analysis Computer Programs ASME PTC 4-2008 Fired Steam Generators - Performance Test Codes 3.3.4.4.(4) 8.4.2.2.(5) Table 5.2.12.1. ASME/CSA Plumbing Supply Fittings ASTM ASME A112.18.1-05/ CAN/CSA-B125.1-05 C 177-10 ASTM C 335/C 335M-05 ASTM C 518-10 ASTM C 1363-05 ASTM E 283-04 CCBFC NRCC 53301 National Building Code of Canada 2010 CCBFC NRCC 53302 National Plumbing Code of Canada 2010 CSA CSA AAMA/WDMA/CSA 101/I.S.2/A440-08 A440.2-09/A440.3-09 CSA CAN/CSA-B125.3-05 NAFS – North American Fenestration Standard/Specification for Windows, Doors, and Skylights Fenestration Energy Performance/User Guide to CSA A440.2-09, Fenestration Energy Performance Plumbing Fittings CSA CAN/CSA-B140.4-04 Oil-Fired Warm Air Furnaces 6.2.6.1.(1) 6.2.6.2.(1) Table 5.2.12.1. CSA CAN/CSA-B211-00 Energy Efficiency of Oil-Fired Storage Tank Water Heaters Table 6.2.2.1. CSA B212-00 Energy Utilization Efficiencies of Oil-Fired Furnaces and Boilers Table 5.2.12.1. ANSI/CSA ANSI/CSA ANSI/CSA Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Guarded-Hot-Plate Apparatus Steady-State Heat Transfer Properties of Pipe Insulation Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen National Energy Code of Canada for Buildings 2011 3.1.1.5.(4) 6.2.6.1.(1) 6.2.6.2.(1) 3.1.1.5.(1) 5.2.5.3.(7) 6.2.3.1.(4) 3.1.1.5.(1) 3.1.1.5.(4) 3.1.1.5.(5) 3.2.4.3.(2) 3.2.4.4.(1) to (3) 1.1.1.1.(1) (3) 1.1.1.3.(1) (3) 1.1.1.3.(2) (3) 1.1.4.1.(1) 1.4.1.2.(1) (3) 3.1.1.5.(1) 3.2.2.1.(3) 5.2.1.1.(1) 5.2.2.1.(1) 5.2.2.8.(2) 5.2.5.1.(1) 5.2.10.4.(2) 6.2.1.1.(1) 3.2.4.3.(3) 3.2.4.3.(4) 3.1.1.5.(3) Division B 1-3 1.3.1.2. Division B Table 1.3.1.2. (Continued) Issuing Agency CSA CAN/CSA-C191-04 Electric Storage Tank Water Heaters for Domestic Hot Water Service Table 6.2.2.1. CSA CAN/CSA-C368.1-M90 Room Air Conditioners Table 5.2.12.1. CSA C390-10 7.2.4.1.(1) CSA CAN/CSA-C439-09 Test Methods, Marking Requirements, and Energy Efficiency Levels for Three-Phase Induction Motors Rating the Performance of Heat/Energy-Recovery Ventilators CSA C654-M91 Fluorescent Lamp Ballast Efficacy Measurements 4.2.1.2.(1) and (2) CSA CAN/CSA-C656-05 Split-System and Single-Package Central Air Conditioners and Heat Pumps Table 5.2.12.1. CSA CAN/CSA-C743-09 Rating Packaged Water Chillers Table 5.2.12.1. CSA CSA CAN/CSA-C746-06 Packaged Terminal Air Conditioners and Heat Pumps (Bi-National Standard, with ARI 310/380-2004) Energy Efficiency of Electric Storage Tank Water Heaters and Heat Pump Water Heaters Rating Large and Single Packaged Vertical Air Conditioners and Heat Pumps Table 5.2.12.1. CSA ARI 310/380-2004/ CAN/CSA-C744-04 CAN/CSA-C745-03 CSA C748-94 Direct-Expansion (DX) Ground-Source Heat Pumps Table 5.2.12.1. CSA CAN/CSA-C802.1-00 Minimum Efficiency Values for Liquid-Filled Distribution Transformers 7.2.3.1.(1) CSA CAN/CSA-C802.2-06 Minimum Efficiency Values for Dry-Type Transformers 7.2.3.1.(1) CSA CAN/CSA-C802.3-01 Maximum Losses for Power Transformers 7.2.3.1.(1) Document Number (1) Document Title (2) Code Reference 5.2.10.4.(2) Table 6.2.2.1. Table 5.2.12.1. CSA CAN/CSA-C828-06 Thermostats Used with Individual Room Electric Space Heating Devices 5.2.8.5.(4) CSA CAN/CSA-C860-07 Internally Lighted Exit Signs 4.2.1.1.(1) CSA CAN/CSA-C13256-1-01 Table 5.2.12.1. CSA CAN/CSA-C13256-2-01 CSA CSA CAN/CSA-F379 SERIES-09 CAN/CSA-P.3-04 Water-Source Heat Pumps - Testing and Rating for Performance - Part 1: Water-to-Air and Brine-to-Air Heat Pumps (Adopted ISO 13256-1:1998, with Canadian Deviations) Water-Source Heat Pumps - Testing and Rating for Performance - Part 2: Water-to-Water and Brine-to-Water Heat Pumps (Adopted ISO 13256-2:1998, with Canadian Deviations) Packaged Solar Domestic Hot Water Systems (Liquid-to-Liquid Heat Transfer) CTI Table 5.2.12.1. 6.2.2.3.(1) Measuring Energy Consumption and Determining Efficiencies of Gas-Fired Storage Water Heaters Table 6.2.2.1. 201(04) Certification of Water-Cooling Tower Thermal Performance Table 5.2.12.1. DOE 10 CFR, Part 430-2011 Energy, Energy Conservation Program for Consumer Products Table 6.2.2.1. HRAI SAR-G1 HRAI Digest 2005 1.1.4.2.(1) ISO 13790:2008 1.1.4.2.(1) NEMA NEMA ANSI C82.11:2002 Energy performance of buildings – Calculation of energy use for space heating and cooling High-Frequency Fluorescent Lamp Ballasts NFRC 100-2010 Determining Fenestration Product U-factors 3.1.1.5.(3) NRCan SOR/94-651-2008 Energy Efficiency Act and its Regulations SMACNA ANSI/SMACNA 006-2006 HVAC Duct Construction Standards – Metal and Flexible SMACNA 1985 HVAC Air Duct Leakage Test Manual 5.2.12.3.(1) 6.2.2.4.(1) 6.2.2.5.(1) 5.2.2.3.(1) Table 5.2.2.3. 5.2.2.4.(1) 4.2.1.2.(2) Notes to Table 1.3.1.2.: (1) (2) (3) Some documents may have been reaffirmed or reapproved. Check with the applicable issuing agency for up-to-date information. Some titles have been abridged to omit superfluous wording. Code reference is in Division A. 1-4 Division B Amended Page National Energy Code of Canada for Buildings 2011 Division B 1.3.2.1. 1.3.2. Organizations 1.3.2.1. Abbreviations of Proper Names 1) The abbreviations of proper names in this Code shall have the meanings assigned to them in this Article (the appropriate addresses of the organizations are shown in brackets). AAMA ......... American Architectural Manufacturers Association (1827 Walden Office Square, Suite 550, Schaumburg, Illinois 60173-4268 U.S.A.; www.aamanet.org) AHAM ......... Association of Home Appliance Manufacturers (111 19th Street, NW, Suite 402, Washington, D.C. 20036 U.S.A.; www.aham.org) AHRI ........... Air-Conditioning, Heating and Refrigeration Institute (2111 Wilson Boulevard, Suite 500, Arlington, Virginia 22201 U.S.A.; www.ahrinet.org) AMCA ......... Air Movement and Control Association (30 West University Drive, Arlington Heights, Illinois 60004 U.S.A.; www.amca.org) ANSI ............ American National Standards Institute (25 West 43rd Street, 4th Floor, New York, New York 10036 U.S.A.; www.ansi.org) ASHRAE ..... American Society of Heating, Refrigerating and Air-Conditioning Engineers (1791 Tullie Circle, NE, Atlanta, Georgia 30329 U.S.A.; www.ashrae.org) ASME .......... American Society of Mechanical Engineers (Three Park Avenue, New York, New York 10016-5990 U.S.A.; www.asme.org) ASTM .......... American Society for Testing and Materials International (100 Barr Harbor Drive, West Conshohoken, Pennsylvania 19428-2959 U.S.A.; www.astm.org) CAN ............. National Standard of Canada designation CCBFC ......... Canadian Commission on Building and Fire Codes (National Research Council of Canada, Ottawa, Ontario K1A 0R6; www.nationalcodes.ca) CSA .............. Canadian Standards Association (5060 Spectrum Way, Suite 100, Mississauga, Ontario L4W 5N6; www.csa.ca) CTI ............... Cooling Technology Institute (P.O. Box 73383, Houston, Texas 77273-3383 U.S.A.; www.cti.org) DOE ............. Department of Energy (1000 Independence Avenue, SW, Washington, D.C. 20585 U.S.A.; http://energy.gov) HRAI ........... Heating, Refrigeration and Air Conditioning Institute of Canada (2800 Skymark Avenue, Building 1, Suite 201, Mississauga, Ontario L4W 5A6; www.hrai.ca) HVI .............. Home Ventilating Institute (1000 N. Rand Road, Suite 214, Wauconda, Illinois 60084 U.S.A.; www.hvi.org) IESNA .......... Illuminating Engineering Society of North America (120 Wall Street, Floor 17, New York, New York 10005-4001 U.S.A.; www.iesna.org) ISO ............... International Organization for Standardization (Standards Council of Canada, 270 Albert Street, Suite 200, Ottawa, Ontario K1P 6N7; www.iso.org) NBC ............. National Building Code of Canada 2010 (see CCBFC) NECB ........... National Energy Code of Canada for Buildings 2011 NEMA ......... National Electrical Manufacturers Association (1300 North 17th Street, Suite 1752, Rosslyn, Virginia 22209 U.S.A.; www.nema.org) NFRC ........... National Fenestration Rating Council (6305 Ivy Lane, Suite 140, Greenbelt, Maryland 20770 U.S.A.; www.nfrc.org) NPC ............. National Plumbing Code of Canada 2010 (see CCBFC) National Energy Code of Canada for Buildings 2011 Division B 1-5 1.3.2.1. Division B NRC ............. National Research Council of Canada (Ottawa, Ontario K1A 0R6; www.nrc-cnrc.gc.ca) NRCan ......... Natural Resources Canada (www.nrcan.gc.ca) SMACNA .... Sheet Metal and Air Conditioning Contractors’ National Association (4201 Lafayette Center Drive, Chantilly, Virginia 20151-1219 U.S.A.; www.smacna.org) TIAC ............ Thermal Insulation Association of Canada (1485 Laperrière Avenue, Ottawa, Ontario K1Z 7S8; www.tiac.ca) U.S. Gov’t .... U.S. Government Printing Office (732 North Capitol Street, NW, Washington, D.C. 20401-0001 U.S.A.; www.gpo.gov) WDMA ........ Window & Door Manufacturers Association (401 N. Michigan Avenue, Suite 2200, Chicago, Illinois 60611 U.S.A.; www.wdma.com) 1-6 Division B National Energy Code of Canada for Buildings 2011 Division B 3.2.1.2. balcony slabs, beams, girders, columns, and ornamentation or appendages that must completely penetrate the building envelope to perform their intended function need not be taken into account, provided that the sum of the cross-sectional areas at such major structural penetrations is limited to a maximum of 2% of the above-ground building envelope area. (See Appendix A.) 5) Where a component of the building envelope is protected by an enclosed unconditioned space, such as a sun porch, enclosed veranda or vestibule, the unconditioned enclosure may be considered to have an overall thermal transmittance of 6.25 W/(m2·K), which is equivalent to that of one layer of glass. (See Appendix A.) 6) For the purposes of this Article, roof assemblies shall be considered to include all related structural framing. 7) For the purposes of this Article, wall assemblies inclined less than 60° from the horizontal shall be considered as roof assemblies, and roof assemblies inclined 60° or more from the horizontal shall be considered as wall assemblies. 8) For the purposes of this Article, wall assemblies shall be considered to include all related structural framing and perimeter areas of intersecting interior walls but shall not include the perimeter areas where floor or roof slabs interrupt the wall’s construction. (See Appendix A.) 9) For the purposes of this Article, floor assemblies shall be considered to include all related structural framing. Section 3.2. Prescriptive Path 3.2.1. General 3.2.1.1. Protection of Insulation Materials 1) Except as provided in Sentence (2), the building envelope shall be designed to avoid increasing the overall thermal transmittance of the insulation material due to a) air leakage or convection, b) wetting, or c) moisture bypassing the plane of thermal resistance. (See Appendix A.) 2) Where any of the conditions described in Clauses (1)(a) to (c) occur as a result of the designed building envelope system, their effect on the overall thermal transmittance of the insulation material shall be calculated in accordance with Article 3.1.1.5. 3.2.1.2. Continuity of Insulation 1) Except as provided in Sentences (2) to (6), interior building components that intersect with components of the building envelope and major structural members that partly penetrate the building envelope shall not break the continuity of the insulation and shall not increase the overall thermal transmittance at their projected area to more than that permitted in Section 3.2. (See Appendix A.) 2) Where an interior wall penetrates an exterior wall or insulated roof or ceiling and breaks the continuity of the building envelope, it shall be insulated a) on both of its sides inward or outward from the building envelope for a distance equal to 4 times the uninsulated thickness of the penetrating wall, and b) to an overall thermal transmittance no more than that required for the exterior wall. National Energy Code of Canada for Buildings 2011 Division B 3-3 3.2.1.3. Division B 3) Where an ornamentation or appendage other than a balcony slab or canopy slab penetrates an exterior wall and breaks the continuity of the building envelope, it shall be insulated a) on both of its sides inward or outward from the building envelope for a distance equal to 4 times the thickness of the penetrated wall, and b) to an overall thermal transmittance no more than that required for the exterior wall. 4) Where building envelope assemblies in the same plane intersect but their respective expanses of insulation do not, one of the two expanses of insulation shall be extended beyond the intersecting assembly for a distance equal to at least 4 times the distance separating the two expanses of insulation. (See Appendix A.) 5) Where mechanical ducts and chases or electrical system components, such as pipes, ducts, conduits, cabinets, panels, or recessed heaters, are placed within and parallel to the building envelope, the overall thermal transmittance of the building envelope at the projected area of the mechanical or electrical system components shall not be increased. 6) Except as provided in Sentence (4), joints between components of the building envelope, such as expansion or construction joints or joints between walls and doors or fenestration, shall be insulated in a manner that provides continuity across such joints. (See Appendix A.) 3.2.1.3. Spaces Heated to Different Temperatures 1) The overall thermal transmittance, U1, of building assemblies separating conditioned spaces that are intended to be heated to temperatures that differ by more than 10°C shall not be greater than that obtained with the following equation: where t1 = indoor heating design temperature of the colder conditioned space, in °C, t2 = indoor heating design temperature of the warmer conditioned space, in °C, t0 = outdoor 2.5% January design temperature as specified in Article 1.1.4.1., in °C, and U = overall thermal transmittance required in Sentences 3.2.2.2.(1), 3.2.2.3.(2) and 3.2.2.4.(1), in W/(m2·K). (See Appendix A.) 3.2.1.4. Allowable Fenestration and Door Area 1) The maximum allowable total vertical fenestration and door area to gross wall area ratio (FDWR), determined in accordance with Article 3.1.1.6., shall be as follows: where HDD = the heating degree-days of the location of the building determined according to Sentence 1.1.4.1.(1). (See Appendix A.) 2) The total skylight area shall be less than 5% of the gross roof area as determined in Article 3.1.1.6. 3-4 Division B Amended Page National Energy Code of Canada for Buildings 2011 Division B 4.2.3.1. illuminated shall not be greater than the individual allowance for that application taken from Table 4.2.3.1.C. for the applicable lighting zone plus any unused power applied from the basic site allowance listed in Table 4.2.3.1.B. (See Appendix A.) Table 4.2.3.1.B. Basic Site Allowances for Exterior Lighting Forming Part of Sentences 4.2.3.1.(2) and (3) Basic Site Allowance According to Lighting Zone Zone 0 Zone 1 Zone 2 Zone 3 Zone 4 No allowance 500 W 600 W 750 W 1300 W 4) Except as provided in Sentence (5), the connected exterior lighting power for all general building exterior applications not listed in Table 4.2.3.1.C. that are to be illuminated shall not be greater than the sum of the individual allowances for these applications provided in Table 4.2.3.1.D. for the applicable lighting zone plus any remaining basic site allowance not used in compliance with Sentence (3). (See Appendix A.) Table 4.2.3.1.C. Lighting Power Allowances for Specific Building Exterior Applications Forming Part of Sentences 4.2.3.1.(3) and (4) Exterior Application Lighting Power Allowances According to Lighting Zone Zone 0 Zone 1 Zone 2 Zone 3 Zone 4 No allowance for each 1.1 illuminated wall or surface, or 8.2 W/m for each illuminated wall or surface length for each 1.6 illuminated wall or surface, or 12.3 W/m for each illuminated wall or surface length 2.2 W/m2 for each illuminated wall or surface, or 16.4 W/m for each illuminated wall or surface length W/m2 Building facades (facade lighting) Automated teller machines (ATM) and night depositories Entrances and gatehouse inspection stations at guarded facilities Loading areas for law enforcement, fire, ambulance and other emergency service vehicles A single luminaire of 60 W or less may be installed for each roadway or parking entry, trail head, and toilet facility, or other locations approved by the authority having jurisdiction W/m2 270 W per location plus 90 W per additional ATM per location 8.1 W/m2 of covered and uncovered area 5.4 W/m2 of covered and uncovered area Drive-up windows and doors 400 W per drive-through Parking near 24-hour retail entrances 800 W per main entry 5) The following exterior lighting applications need not comply with Sentences (1) to (4) where the lighting is equipped with an independent control device that complies with the requirements of Subsection 4.2.4.: a) specialized signal, directional, and marker lighting associated with transportation, b) lighting for advertising and directional signage, c) lighting integral to equipment or instrumentation and installed by its manufacturer, d) lighting for theatrical purposes, including performance, stage, film and video production, National Energy Code of Canada for Buildings 2011 Amended Page Division B 4-13 4.2.4.1. Division B e) lighting for athletic activity areas, f) temporary lighting, g) lighting for industrial production, material handling, transportation sites, and associated storage areas for industrial sites, h) lighting for theme elements in theme/amusement parks, and i) lighting used to highlight features of art objects, public monuments and designated national or provincial historic sites. Table 4.2.3.1.D. Lighting Power Allowances for General Building Exterior Applications Forming Part of Sentence 4.2.3.1.(4) Exterior Application Lighting Power Allowances According to Lighting Zone Zone 0 Zone 1 Zone 2 Zone 3 Zone 4 No allowances 0.4 W/m2 0.7 W/m2 1.1 W/m2 1.4 W/m2 Walkways less than 3 m wide 2.3 W/m 2.3 W/m 2.6 W/m 3.3 W/m Walkways 3 m wide or greater, plaza areas, special feature areas 1.5 W/m2 1.5 W/m2 1.7 W/m2 2.2 W/m2 8.1 W/m2 11.0 W/m2 11.0 W/m2 11.0 W/m2 W/m2 W/m2 W/m2 3.2 W/m2 Uncovered Parking Areas Parking areas and drives Building Grounds Stairways No allowances Pedestrian tunnels 1.6 Landscape lighting 0.4 W/m2 0.5 W/m2 0.5 W/m2 0.5 W/m2 66 W/m of door width 66 W/m of door width 98 W/m of door width 98 W/m of door width 66 W/m of door width 66 W/m of door width 66 W/m of door width 66 W/m of door width 2.7 W/m2 2.7 W/m2 4.3 W/m2 4.3 W/m2 6.5 W/m2 6.5 W/m2 8.6 W/m2 11.0 W/m2 2.7 W/m2 2.7 W/m2 5.4 W/m2 7.5 W/m2 No allowance 33 W/m 33 W/m 98 W/m 1.6 2.2 Exterior Entrances and Exterior Exits Main entries No allowances Other doors Entry canopies Sales Canopies Free-standing and attached No allowances Outdoor Sales Open areas (including vehicle sales lots) Street frontage for vehicle sales lots in addition to “open area” allowance No allowances 4.2.4. Exterior Lighting Controls 4.2.4.1. Requirements 1) Except as provided in Sentences (2) and (3), exterior lighting shall be controlled by a) b) c) d) 4-14 Division B astronomical time controls, photosensors, a combination of photosensors and timer shut-off switch, or other types of controls that perform the same function as those referred to in Clauses (a) to (c). National Energy Code of Canada for Buildings 2011 Division B 5.2.3.2. 5.2.4.2. Constant-Volume Fan Systems 1) Where fans produce a constant airflow rate whenever the system is operating, the power demand required by the motors for the combined supply and return fan system at design conditions shall not exceed 1.6 W per L/s of supply air delivered to the conditioned space, calculated using the following equation: where W = power demand, in watts, F = design flow rate, in L/s, SP = design static pressure across the fan, in Pa, and η = combined fan-drive-motor efficiency, expressed as a decimal fraction. (See Appendix A.) 5.2.3.3. Variable-Air-Volume Fan Systems 1) For fan systems through which airflow varies automatically as a function of load, the power demand required by the motors for the combined supply and return fan system, as calculated using the equation in Sentence 5.2.3.2.(1), shall not exceed 2.65 W per L/s of supply air delivered to the conditioned space at design conditions. (See Appendix A.) 2) In variable-air-volume systems, any individual supply, relief or return fan with a power demand greater than 7.5 kW and less than 25 kW, as calculated using the equation in Sentence 5.2.3.2.(1), shall incorporate controls and devices such that, if air delivery volume is reduced to 50% of design air volume, the corresponding fan power demand will be no more than 55% of design wattage, based on the manufacturer‘s test data. 3) In variable-air-volume systems, any individual supply, relief or return fan with a power demand equal to or greater than 25 kW, as calculated using the equation in Sentence 5.2.3.2.(1), shall incorporate controls and devices necessary to prevent the fan motor from demanding more than 30% of design wattage at 50% of design air volume, based on the manufacturer’s test data. 5.2.4. Air Intake and Outlet Dampers 5.2.4.1. Required Dampers 1) Except as provided in Sentences (2) to (4), every duct or opening intended to discharge air from a conditioned space to the outdoors or to unconditioned space, and every outdoor air intake duct or opening shall be equipped with a motorized damper. 2) Where dampers are not permitted by other regulations, air intakes and outlets need not comply with Sentence (1). 3) Air intakes and outlets serving HVAC systems required to operate continuously need not comply with Sentence (1). 4) Where the duct or opening does not exceed 0.08 m2 in cross-sectional area, air intake dampers required by Sentence (1) are permitted to be manually operated and air outlet dampers required by Sentence (1) are permitted to consist of gravity or spring-operated backflow dampers. 5.2.4.2. Type and Location of Dampers 1) Except as provided in Sentences (3) and (4), dampers required by Article 5.2.4.1. shall be a) located as near as possible to the plane of the building envelope, and b) designed to close automatically when the HVAC system is not in operation. 2) Motorized dampers required in Sentence 5.2.4.1.(1) shall be designed so that, when the damper is in the closed position, airflow does not exceed 15 L/s per m2 of National Energy Code of Canada for Buildings 2011 Division B 5-5 5.2.5.1. Division B cross-sectional area at a pressure differential of 250 Pa, when tested in accordance with AMCA 500, “Louvers, Dampers and Shutters.” 3) Dampers required in Article 5.2.4.1. are permitted to be located inboard of the building envelope, provided the portion of the duct between the damper and the building envelope is insulated in conformance with Sentence 5.2.2.5.(4) for ducts located outdoors. 4) Dampers in air intakes and outlets serving air-heating or -cooling equipment located outside of the building envelope are permitted to be located within the equipment. 5.2.5. Piping for Heating, Ventilating and Air-conditioning Systems 5.2.5.1. Design and Installation of Piping 1) HVAC piping shall be designed and installed in accordance with the NBC. 5.2.5.2. Provision for Balancing 1) All hydronic systems shall be designed so that they can be balanced. (See Appendix A.) 5.2.5.3. Piping Insulation 1) Except as provided in Sentences (2) to (5), piping forming part of an HVAC system shall be thermally insulated in accordance with Table 5.2.5.3. 2) Except for suction-line piping of direct expansion systems, piping located within conditioned space in a dwelling unit and serving only that dwelling unit need not comply with Sentence (1). 3) HVAC piping located outside the building envelope shall be insulated to the level specified in Table 5.2.5.3. for heating system piping conveying fluid with design operating temperatures above 177°C. 4) HVAC piping that conveys fluids with design operating temperatures greater than 13°C and less than 41°C need not comply with Table 5.2.5.3. 5) Where piping insulation has a thermal conductivity that is greater than the ranges given in Table 5.2.5.3., the insulation thickness given in the Table shall be increased by the ratio u2/u1, where u1 is the value at the higher end of the conductivity range for the operating temperature and u2 is the measured thermal conductivity of the insulation at the mean rating temperature. 6) Where piping insulation has a thermal conductivity that is lower than the ranges given in Table 5.2.5.3., the insulation thickness given in the Table may be decreased by the ratio u2/u1, where u1 is the value at lower end of the conductivity range for the operating temperature and u2 is the measured thermal conductivity of the insulation at the mean rating temperature. 7) The thermal conductivity of piping insulation at a mean rating temperature shall be determined in conformance with ASTM C 335/C 335M, “Steady-State Heat Transfer Properties of Pipe Insulation.” 8) Insulation material required in Sentence (1) shall be installed in accordance with good practice. (See A-5.2.2.5.(6) and 5.2.5.3.(8) in Appendix A.) 5-6 Division B Amended Page National Energy Code of Canada for Buildings 2011 Division B 5.2.10.1. 5) Vestibules between conditioned spaces and the outdoors shall have a temperature-control device that limits the maximum heating temperature in the vestibule to 15°C. 5.2.8.6. Ice- and Snow-Melting Heater Controls 1) Ice- and snow-melting heaters shall be provided with automatic controls or readily accessible manual controls that allow them to be shut down when not required. 5.2.8.7. Control of Temperature of Air Leaving the Supply Air Handler 1) Except as provided in Sentences (2) and (3), a supply air handler shall be designed and equipped with controls to achieve the design supply air temperature without a) heating previously cooled air, b) cooling previously heated air, or c) heating outdoor air, separately from the return air or mixed with it, in excess of the minimum required for ventilation. 2) Reheating supply air for humidity control is permitted where specified humidity levels are required. (See Appendix A.) 3) Reheating supply air is permitted where such reheating will not cause an increase in energy consumption. 5.2.8.8. Control of Space Temperature by Reheating or Recooling 1) Except as provided in Sentence (4), HVAC systems that control the temperature of a space by reheating previously cooled air shall be equipped with controls that automatically adjust the temperature of the cool air supply to the highest temperature that will satisfy the temperature-control zone requiring the coolest air. 2) Except as provided in Sentence (4), HVAC systems that control the temperature of a space by recooling previously heated air shall be equipped with controls that automatically adjust the temperature of the warm air supply to the lowest temperature that will satisfy the temperature-control zone requiring the warmest air. 3) Except as provided in Sentence (4), HVAC systems that control the temperature of a space by mixing heated supply air and cooled supply air shall be equipped with controls that a) automatically adjust the temperature of the warm supply air to the lowest temperature that will satisfy the temperature-control zone requiring the warmest air, and b) automatically adjust the temperature of the cool supply air to the highest temperature that will satisfy the temperature-control zone requiring the coolest air. 4) HVAC systems that are designed to reduce the air supplied to each temperature-control zone to no more than 2 L/s per m2 of floor surface area of the temperature-control zone before reheating, recooling or mixing of supply air takes place need not comply with Sentences (1) to (3). 5.2.9. Humidification 5.2.9.1. Humidification Controls 1) If an HVAC system is equipped with a means for adding or removing moisture to maintain specific humidity levels in a space, an automatic humidity control device shall be provided. 5.2.10. Heat Recovery 5.2.10.1. Heat-Recovery Systems 1) Except as provided in Sentence (3), when the sensible heat content of an exhaust air system as calculated in accordance with Sentence (4) exceeds 150 kW, the system National Energy Code of Canada for Buildings 2011 Division B 5-9 5.2.10.2. Division B shall be equipped with a heat-recovery apparatus capable of recovering sensible heat with a minimum 50% efficiency. (See Appendix A.) 2) Heat recovered in accordance with Sentence (1) shall be used in building systems. 3) Specialized exhaust systems, such as those used to exhaust smoke, grease-laden vapours, or toxic, flammable, paint, or corrosive fumes or dust, need not comply with Sentence (1). 4) The sensible heat, in kW, referred to in Sentence (1), which is the sensible heat content of the total quantity of exhaust, shall be calculated as follows: where Q = rated capacity of exhaust system at normal exhaust air temperature, in L/s, Te = temperature of exhaust air before heat recovery, in °C, and To = outdoor 2.5% January design temperature, in °C (see Appendix A). 5) At airflow rates not less than the system design capacity, the sensible-heat-recovery efficiency of a heat-recovery apparatus referred to in Sentence (1) shall be determined in conformance with a) the test method described in ANSI/AHRI 1060, “Performance Rating of Air-to-Air Exchangers for Energy Recovery Ventilation,” or b) another acceptable test method. 5.2.10.2. Heat Recovery from Dehumidification in Swimming Pools 1) Except for pools with a water surface area of less than 10 m2 and except as provided in Sentence (2), systems that exhaust air from swimming pools within conditioned spaces shall be capable of recovering at least 40% of the sensible heat from exhaust air at design conditions, as calculated in accordance with Sentence 5.2.10.1.(4). (See Appendix A.) 2) Indoor swimming pools need not comply with Sentence (1), provided a stationary mechanical or desiccant dehumidification system is installed that provides at least 80% of the dehumidification that would result from compliance with Sentence (1). 5.2.10.3. Heat Recovery from Ice-making Machines in Ice Arenas and Curling Rinks 1) Where an ice arena or a curling rink has a heating requirement, the refrigeration system shall incorporate a means of recovering the heat rejected by the system to satisfy some or all of the building’s space-heating or service water heating requirements. (See Appendix A.) 5.2.10.4. Heat Recovery in Dwelling Units 1) Except for climate zones 4, 5 and 6, where a self-contained mechanical ventilation system serves a single dwelling unit, the principal exhaust component of the ventilation system shall be equipped with heat-recovery capability. (See Appendix A.) 2) Heat-recovery ventilators used to meet the requirements of Sentence (1) shall have a sensible-heat-recovery efficiency, when tested in conformance with the low-temperature thermal and ventilation test methods described in CAN/CSA-C439, “Rating the Performance of Heat/Energy-Recovery Ventilators,” of a) at least 65% at an outside air test temperature of 0°C, and b) not less than that required by Table 5.2.10.4. for the 2.5% January design temperature for the building’s location, as listed in Appendix C of Division B of the NBC. (See Appendix A.) 5-10 Division B Amended Page National Energy Code of Canada for Buildings 2011 Division B 5.2.12.1. Table 5.2.12.1. (Continued) Computer Room Air Conditioners Component or Equipment Air conditioners, air-cooled Air conditioners, water-cooled Air conditioners, water-cooled with fluid economizer Cooling or Heating Capacity, kW (Btu/h) Rating Conditions (1) Minimum Performance (2) < 19 (65 000) SCOP = 2.20 / 2.09 ≥ 19 (65 000) and < 70 (240 000) SCOP = 2.10 / 1.99 ≥ 70 (240 000) SCOP = 1.90 / 1.79 < 19 (65 000) SCOP = 2.60 / 2.49 ≥ 19 (65 000) and < 70 (240 000) — SCOP = 2.50 / 2.39 ≥ 70 (240 000) SCOP = 2.40 / 2.29 < 19 (65 000) SCOP = 2.55 / 2.44 ≥ 19 (65 000) and < 70 (240 000) SCOP = 2.45 / 2.34 ≥ 70 (240 000) < 19 (65 000) Air conditioners, glycol-cooled Standard SCOP = 2.35 / 2.24 ANSI/ASHRAE 127 SCOP = 2.50 / 2.39 ≥ 19 (65 000) and < 70 (240 000) SCOP = 2.15 / 2.04 ≥ 70 (240 000) rated at 40% propylene glycol < 19 (65 000) SCOP = 2.10 / 1.99 SCOP = 2.45 / 2.34 Air conditioners, glycol-cooled with fluid economizer ≥ 19 (65 000) and < 70 (240 000) SCOP = 2.10 / 1.99 ≥ 70 (240 000) SCOP = 2.05 / 1.94 < 19 (65 000) SCOP = 8.00 / 6.06 Chilled water air handler ≥ 19 (65 000) and < 70 (240 000) — ≥ 70 (240 000) SCOP = 9.00 / 7.06 SCOP = 11.00 / 9.06 Packaged Water Chillers Component or Equipment Vapour compression, airor water-cooled, electrically operated Absorption, single- or double-effect, indirector direct-fired Cooling or Heating Capacity, kW (Btu/h) Standard Rating Conditions (1) Minimum Performance (2) < 5 600 (19 000 000) CAN/CSA-C743 — See standard National Energy Code of Canada for Buildings 2011 Division B 5-17 5.2.12.1. Division B Table 5.2.12.1. (Continued) Boilers Component or Equipment Electric boilers Cooling or Heating Capacity, kW (Btu/h) — < 88 (300 000) ≥ 88 (300 000) and < 733 (2 500 000) Gas-fired boilers (4) ≥ 733 (2 500 000) Standard Rating Conditions (1) Minimum Performance (2) — — (3) ANSI Z21.13/CSA 4.9 — AFUE = 85% ANSI Z21.13/CSA 4.9 or ASME PTC 4 — Ec ≥ 82.5% Et ≥ 83.0% — Ec ≥ 83.3% AFUE ≥ 84.7% < 88 (300 000) ≥ 88 (300 000) and < 733 (2 500 000) Oil-fired boilers CSA B212 or ASME PTC 4 — Ec ≥ 85.8% ≥ 733 (2 500 000) Oil-fired boilers, residual (No. 5 or No. 6 oil) and other Et ≥ 83.4% < 88 (300 000) CSA B212 ≥ 88 (300 000) and < 733 (2 500 000) ASME PTC 4 AFUE ≥ 84.7% — Et ≥ 83.4% Ec ≥ 85.8% ≥ 733 (2 500 000) Warm-Air Furnaces, Combination Warm-Air Furnace/Air-conditioning Units, Duct Furnaces and Unit Heaters Component or Equipment Cooling or Heating Capacity, kW (Btu/h) Standard ≤ 117.23 (400 000) Gas-fired warm-air furnaces (4)(5) > 117.23 (400 000) Gas-fired duct furnaces (4)(5) Gas-fired unit heaters (4) Oil-fired warm-air furnaces (5) Oil-fired duct unit heaters furnaces (5) and ANSI Z21.47/CSA 2.3 ≤ 117.23 (400 000) ANSI Z83.8/CSA 2.6 ≤ 66 (225 000) CSA B212 Minimum Performance (2) — AFUE ≥ 92.4% Maximum rated capacity, steady-state Et ≥ 81% Minimum rated capacity, steady-state Et ≥ 81% Et ≥ 81% Et ≥ 82% — Et ≥ 84.5% Et ≥ 81.3% > 66 (225 000) — Rating Conditions (1) CAN/CSA-B140.4 Et ≥ 81% Notes to Table 5.2.12.1.: (1) (2) (3) (4) (5) The abbreviations that appear in this column have the following meanings: db = dry bulb outdoor air temperature wb = wet bulb outdoor air temperature The symbols and abbreviations that appear in this column have the following meanings: AFUE = annual fuel utilization efficiency, in % Capc = rated cooling capacity, in W(Btu/h) COP = coefficient of performance, in W/W Ec = combustion efficiency, in % EER = energy efficiency ratio, in (Btu/h)/W Et = thermal efficiency, in % ICOP = integrated coefficient of performance, in W/W IPLV = integrated part-load value (no units) SCOP = sensible coefficient of performance, in downflow units/upflow units (first value is downflow; second value is upflow). The SCOP is a ratio that is calculated by dividing the net sensible cooling capacity, in W, by the total power input, in W (excluding re-heaters and humidifiers). SEER = seasonal energy efficiency ratio, in (Btu/h)/W (no metric equivalent) No standards address the performance efficiency of electric boilers; however, their efficiency typically approaches 100%. Includes propane. Excludes packaged rooftop units. 5-18 Division B Amended Page National Energy Code of Canada for Buildings 2011 Division B Part 6 Service Water Heating Systems Section 6.1. General 6.1.1. General 6.1.1.1. Scope 1) This Part is concerned with the systems used to heat service water. 6.1.1.2. Application 1) This Part applies to service water heating systems. 6.1.1.3. Compliance 1) Except as provided in Sentence (2), compliance with this Part shall be achieved by following a) the prescriptive path described in Section 6.2., b) the trade-off path described in Section 6.3., or c) the performance path described in Section 6.4. (see A-3.1.1.3.(1)(c) in Appendix A). (See Appendix A.) 2) Back-up systems shall comply with the prescriptive requirements stated in Section 6.2. 6.1.1.4. Definitions 1) Words that appear in italics are defined in Article 1.4.1.2. of Division A. Section 6.2. Prescriptive Path 6.2.1. System Design 6.2.1.1. Regulations 1) Service water heating systems shall be designed in accordance with the relevant provincial, territorial or municipal building regulations or, in the absence of such regulations, or where service water heating systems are not covered by such regulations, with the National Plumbing Code of Canada 2010. 6.2.2. Water Heating Equipment and Storage Vessels 6.2.2.1. Equipment Efficiency 1) Storage-type and non-storage-type service water heaters and pool heaters shall comply with the performance requirements stated in Table 6.2.2.1. (See Appendix A.) National Energy Code of Canada for Buildings 2011 Division B 6-1 6.2.2.1. Division B Table 6.2.2.1. Service Water Heating Equipment Performance Standards Forming Part of Sentences 5.2.12.3.(1), 6.2.2.1.(1), 6.2.2.4.(2), 6.2.2.5.(1), 6.3.2.5.(1) and 6.3.2.6.(1) Component Input ≤ 12 kW Storage-Type and Non-Storage-Type (Instantaneous) Service Water Heaters Rating Input/Vt, W/L Standard Capacity, L Vt, L (US gal.) Conditions (Btu/h/US gal.) 50 – 270 CAN/CSA-C191 Electric Heat pump water heaters — > 270 and ≤ 454 > 12 kW > 454 ≤ 24 A and ≤ 250 V — — ANSI Z21.10.3/CSA 4.3 (2) < 22 kW — Gas-fired > 117 kW — — CAN/CSA-C745 — EF ≥ 2.1 — — CAN/CSA-P.3 — EF ≥ 0.67 – 0.0005V — < 310 (4000) Oil-fired, instantaneous Others — — ≤ 30.5 kW — — < 310 (4000) ≥ 310 (4000) ≤ 190 — t = 50°C (90°F) — t = 50°C (90°F) Et ≥ 77% (3) EF ≥ 0.59 – 0.0019 V Et ≥ 78% (3) SL ≤ 1.3 + 95/Vt (2) Et ≥ 80% (3) Et ≥ 77% SL ≤ 2.3 + 67/Vt (2) CAN/CSA-B211 > 190 > 190 DOE 10 CFR, Part 430, Subpart B, Appendix E Et ≥ 80% Et ≥ 80% (3) t = 50°C (90°F) ANSI Z21.10.3/CSA 4.3 < 37.8 (10) Oil-fired, storage-type > 30.5 kW ≥ 310 (4000) — ≥ 37.8 (10) t = 50°C (90°F) ANSI Z21.10.3/CSA 4.3 < 37.8 (10) ≥ 37.8 (10) ≤ 61.5 kW (4) — Performance Requirement (1) SL ≤ 35 + 0.20V (top inlet) SL ≤ 40 + 0.20V (bottom inlet) See standard SL ≤ (0.472V) – 38.5 (top inlet) SL ≤ (0.472V) – 33.5 (bottom inlet) Et ≥ 98% t = 44.4°C EF ≥ 0.98 (80°F) — — — < 310 (4000) < 37.8 (10) ≥ 37.8 (10) DOE 10 CFR, Part 430, Subpart B, Appendix E ANSI Z21.10.3/CSA 4.3 ≥ 310 (4000) — EF ≥ 0.55 t = 50°C (90°F) — EF ≥ 0.55 t = 50°C (90°F) EF ≥ 0.55 SL ≤ 2.3 + 67/Vt (2) EF ≥ 0.55 Pool Heaters Component Gas-fired (2) Oil-fired Input < 117.2 kW — Capacity, L Vt, L (US gal.) Input/Vt, W/L (Btu/h/US gal.) Standard Rating Conditions — — — ANSI Z21.56/CSA 4.7 — Performance Requirement (1) Et ≥ 78% Et ≥ 78% (3) Notes to Table 6.2.2.1.: (1) The symbols and abbreviations used in this column have the following meanings: Vt = tank storage volume, in L, as measured according to the referenced standard SL = standby losses, in %/h or in W, depending on standard Et = thermal efficiency with 38.9°C (70°F) water temperature difference EF = energy factor, in %/h V = storage volume, in L, as specified by the manufacturer 6-2 Division B Amended Page National Energy Code of Canada for Buildings 2011 Division B 6.2.3.1. Table 6.2.2.1. (Continued) (2) (3) (4) When testing an electric storage-type service water heater for standby losses using the test procedure described in Section 2.9. of the referenced standard, the electrical supply voltage shall be maintained within ±1% of the centre of the voltage range specified on the water heater nameplate. Also, when needed for calculations, the thermal efficiency (Et) shall be 98%. Includes propane. Consistent with the US National Appliance Energy Conservation Act of 1987. 6.2.2.2. Equipment Insulation 1) Except for tanks covered by Article 6.2.2.1., hot service water storage tanks shall be covered with insulation having a maximum U-value of 0.45 W/(m2·K). 2) Tank insulation referred to in Sentence (1) that is installed in areas where it may be subject to mechanical damage shall be protected. 6.2.2.3. Solar Thermal Service Water Heating Equipment 1) Service water heating equipment using solar thermal technology shall be designed and installed in accordance with a) the manufacturer’s procedures, or b) CAN/CSA-F379 SERIES, “Packaged Solar Domestic Hot Water Systems (Liquid-to-Liquid Heat Transfer).” 6.2.2.4. Combination Service Water Heating and Space-Heating Equipment 1) Combination service water heating and space-heating equipment is only permitted to be used where input to the combination equipment is a) less than 22 kW, or b) less than twice the design service water heating load. 2) Where combination equipment referred to in Sentence (1) is used, its performance shall meet the greater of the minimum energy efficiency ratings for service water heating equipment and space-heating equipment required in the applicable standards listed in Table 5.2.12.1. or 6.2.2.1. or, where such equipment is not covered in these Tables, with the Energy Efficiency Act and its Regulations. 6.2.2.5. Space-Heating Equipment Used for Indirect Service Water Heating 1) Space-heating equipment used solely to provide indirect service water heating or used to provide a combination of space heating and indirect service water heating shall meet the greater of the minimum energy efficiency ratings for service water heating equipment and space-heating equipment required in the applicable standards listed in Table 5.2.12.1. or 6.2.2.1. or, where such equipment is not covered in these Tables, with the Energy Efficiency Act and its Regulations. 6.2.3. Piping 6.2.3.1. Insulation 1) All piping conveying hot service water in circulating systems, non-circulating systems without heat traps and non-circulating systems with electric heating elements along the pipes to maintain temperature shall be insulated in accordance with Table 6.2.3.1. and Sentences (2) to (4). (See Appendix A.) 2) Where piping insulation has a thermal conductivity, as determined in accordance with Sentence (4), that is greater than the range given in Table 6.2.3.1., the thickness given in the Table shall be increased by the ratio u2/u1, where u1 is the value at the higher end of the conductivity range for the operating temperature and u2 is the measured thermal conductivity of the insulation at the mean rating temperature. 3) Where piping insulation has a thermal conductivity, as determined in accordance with Sentence (4), that is lower than the range given in Table 6.2.3.1., the thickness given in the Table may be decreased by the ratio u2/u1, where u1 is the value National Energy Code of Canada for Buildings 2011 Amended Page Division B 6-3 6.2.4.1. Division B at the lower end of the conductivity range for the operating temperature and u2 is the measured thermal conductivity of the insulation at the mean rating temperature. 4) The thermal conductivity of piping insulation at the mean rating temperature shall be determined in conformance with ASTM C 335/C 335M, “Steady-State Heat Transfer Properties of Pipe Insulation.” 5) On non-circulating systems with heat traps, the inlet and outlet piping between the storage or heating vessel and the heat traps as well as the first 2.4 m of outlet piping downstream of the heat trap, shall be insulated in accordance with Table 6.2.3.1. and Sentences 5.2.5.3.(5) to (7). Table 6.2.3.1. Minimum Thickness of Piping Insulation for Service Water Heating Systems Forming Part of Sentences 6.2.3.1.(1), (2), (3) and (5) Thermal Conductivity of Insulation Location of Piping Conductivity Range, W/m·°C Mean Rating Temperature, °C Nominal Pipe Diameter, in. (mm) Minimum Thickness of Piping Insulation, (1) mm Runouts (1) ≤ 2 (51) ≤ 1 (25.4) 0.035-0.040 Conditioned space 38 1¼ to 2 (32 to 51) 2½ to 4 (64 to 102) ≥ 5 (127) Runouts (1) ≤ 2 (51) Unconditioned space or outside ≤ 1 (25.4) 0.046-0.049 38 25.4 1¼ to 2 (32 to 51) 38.1 38.1 63.5 2½ to 4 (64 to 102) 76.2 ≥ 5 (127) 88.9 Notes to Table 6.2.3.1.: (1) Applies to recirculating sections of service water heating systems and to the first 2.4 m from storage tanks for non-recirculating systems. 6.2.4. Controls 6.2.4.1. Temperature Controls 1) Service water heating systems with storage tanks shall be equipped with automatic temperature controls capable of adjustment between the lowest and the highest acceptable temperature settings for the intended use. (See Appendix A.) 6.2.4.2. Shutdown 1) Except for systems whose storage capacity is less than 100 L, each service water heating system shall be equipped with a readily accessible and clearly labeled shut-off device that allows the system, including any heating elements installed along the pipes to maintain temperature, to be shut-off. (See Appendix A.) 6-4 Division B Amended Page National Energy Code of Canada for Buildings 2011 Division B 6.5.1.1. Section 6.4. Performance Path (See A-1.1.2.1. in Appendix A.) 6.4.1. General 6.4.1.1. Scope 1) Subject to the limitations stated in Article 6.4.1.2., where the service water heating system does not comply with the requirements of Section 6.2. or 6.3., it shall comply with Part 8. 6.4.1.2. Limitations 1) Notwithstanding use of the performance path, all service water heating appliances and equipment shall comply with the applicable appliance or equipment energy efficiency act or, in the absence of such an act or where the appliance or equipment is not covered by such an act, with the applicable performance standard. 2) This Section does not apply to back-up SWH systems, which shall comply with Sentence 6.1.1.3.(2). Section 6.5. Objective and Functional Statements 6.5.1. Objective and Functional Statements 6.5.1.1. Attributions to Acceptable Solutions 1) For the purpose of compliance with this Code as required in Clause 1.2.1.1.(1)(b) of Division A, the objective and functional statements attributed to the acceptable solutions in this Part shall be the objective and functional statements listed in Table 6.5.1.1. (See A-1.1.3.1.(1) in Appendix A.) Table 6.5.1.1. Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 Forming Part of Sentence 6.5.1.1.(1) Table 6.5.1.1. (Continued) Functional Statements and Objectives (1) 6.2.3.1. Insulation (1) [F92,F93-OE1.1] 6.2.1.1. Regulations (2) [F92,F93-OE1.1] (1) [F96,F98-OE1.1] (4) [F92,F93-OE1.1] 6.2.2.1. Equipment Efficiency (5) [F92,F93-OE1.1] (1) 6.2.4.1. Temperature Controls Functional Statements and Objectives (1) [F96,F98-OE1.1] 6.2.2.2. Equipment Insulation (1) (1) [F93,F96-OE1.1] 6.2.4.2. Shutdown (2) [F93,F96-OE1.1] (1) [F96-OE1.1] [F96-OE1.1] 6.2.2.3. Solar Thermal Service Water Heating Equipment 6.2.4.3. Maintaining Temperature of Hot Service Water (1) (1) [F96,F98,F99-OE1.1] [F96-OE1.1] 6.2.2.4. Combination Service Water Heating and Space-Heating Equipment 6.2.5.1. Remote or Booster Heaters (1) [F95,F96,F98,F99-OE1.1] 6.2.6.1. Showers (2) [F95,F96,F98,F99-OE1.1] (1) [F96-OE1.1] (2) [F96-OE1.1] 6.2.2.5. Space-Heating Equipment Used for Indirect Service Water Heating (1) [F95,F96,F98,F99-OE1.1] National Energy Code of Canada for Buildings 2011 (1) [F96-OE1.1] 6.2.6.2. Lavatories (1) [F96-OE1.1] Amended Page Division B 6-9 6.5.1.1. Division B Table 6.5.1.1. (Continued) Functional Statements and Objectives (1) (2) [F96-OE1.1] 6.2.7.1. Controls (1) [F95,F96,F99-OE1.1] (2) [F95,F96,F99-OE1.1] 6.2.7.2. Pool and Hot Tub Covers (1) [F95-OE1.1] (2) [F95-OE1.1] 6.3.1.1. Application (1) [F96,F99-OE1.1] 6.3.1.3. Compliance (1) [F96,F99-OE1.1] 6.3.2.1. SWH Trade-off Index (1) [F96,F99-OE1.1] (2) [F96,F99-OE1.1] (3) [F96,F99-OE1.1] 6.3.2.2. Determination of Peak Daily Flow Ratio (1) [F96,F99-OE1.1] 6.3.2.3. Determination of Normalized Tank Area (1) [F96,F99-OE1.1] 6.3.2.4. Determination of Normalized Tank Diameter (1) [F96,F99-OE1.1] 6.3.2.5. Determination of Trade-off Values of Components, ToVi (1) [F96,F99-OE1.1] 6.3.2.6. Determination of Reference Heat Generator Efficiency, ηref (1) [F96,F99-OE1.1] 6.4.1.2. Limitations (1) [F98,F99-OE1.1] Notes to Table 6.5.1.1.: (1) See Parts 2 and 3 of Division A. 6-10 Division B National Energy Code of Canada for Buildings 2011 Division B Part 7 Electrical Power Systems and Motors Section 7.1. General 7.1.1. General 7.1.1.1. Scope 1) This Part is concerned with electrical power systems and motors for the application listed in Article 7.1.1.2. 7.1.1.2. Application 1) This Part applies to the electrical power systems and motors that are connected to the building’s electrical service. (See Appendix A.) 7.1.1.3. Compliance 1) Compliance with this Part shall be achieved by following a) the prescriptive path described in Section 7.2., or b) the performance path described in Section 7.4. (see A-3.1.1.3.(1)(c) in Appendix A). (See Appendix A.) 7.1.1.4. Definitions 1) Words that appear in italics are defined in Article 1.4.1.2. of Division A. Section 7.2. Prescriptive Path 7.2.1. Electrical Distribution System 7.2.1.1. Monitoring (See Appendix A.) 1) Electrical distribution systems whose load-carrying capacity is greater than 250 kVA shall be designed to facilitate the installation of a means to monitor the electrical energy consumption of a) HVAC systems, b) interior lighting, and c) exterior lighting. 2) The electrical distribution systems of buildings with tenants or dwelling units shall have a means to separately monitor the electrical energy consumption of the total building and of each individual tenant or dwelling unit, excluding shared systems. 7.2.2. Voltage Drop 7.2.2.1. Feeders 1) Feeder conductors shall be sized for a maximum voltage drop of 2% at design load. National Energy Code of Canada for Buildings 2011 Division B 7-1 7.2.2.2. 7.2.2.2. Division B Branch Circuits 1) Branch circuit conductors shall be sized for a maximum voltage drop of 3% at design load. 7.2.3. Transformers 7.2.3.1. Transformer Selection 1) Transformers shall conform to a) CAN/CSA-C802.1, “Minimum Efficiency Values for Liquid-Filled Distribution Transformers,” b) CAN/CSA-C802.2, “Minimum Efficiency Values for Dry-Type Transformers,”or c) CAN/CSA-C802.3, “Maximum Losses for Power Transformers.” 7.2.4. Electrical Motors 7.2.4.1. Efficiency 1) Except for elevator motors and motors that are components of rated equipment, permanently wired polyphase motors serving the building shall have a nominal full-load motor efficiency not less than the minimum specified in Tables 3 and 5 of CSA C390, “Test Methods, Marking Requirements, and Energy Efficiency Levels for Three-Phase Induction Motors.” Section 7.3. Trade-off Path (Reserved) Section 7.4. Performance Path (See A-1.1.2.1. in Appendix A.) 7.4.1. General 7.4.1.1. Scope 1) Where electrical power systems and motors do not comply with the requirements of Section 7.2., they shall comply with Part 8. Section 7.5. Objective and Functional Statements 7.5.1. Objective and Functional Statements 7.5.1.1. Attributions to Acceptable Solutions 1) For the purpose of compliance with this Code as required in Clause 1.2.1.1.(1)(b) of Division A, the objective and functional statements attributed to the acceptable solutions in this Part shall be the objective and functional statements listed in Table 7.5.1.1. (See A-1.1.3.1.(1) in Appendix A.) Table 7.5.1.1. Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 7 Forming Part of Sentence 7.5.1.1.(1) Functional Statements and Objectives (1) 7.2.2.1. Feeders (1) [F99-OE1.1] 7-2 Division B Amended Page National Energy Code of Canada for Buildings 2011 Division B 8.4.4.22. 4) Where more than one energy type is used by the proposed building's service water heating system, a) the heating capacities of the reference building's service water heating equipment shall match the ratio of the proposed building's service water heating equipment capacity allocation, and b) the operating schedule, priority of use and other operational characteristics of the proposed building's use of energy types shall apply. 5) Service water heating equipment performance characteristics as a function of part-load shall be modeled in accordance with the part-load performance curves found in Table 8.4.4.22.G. 6) The service water heating system’s supply temperature shall be modeled as being identical to that of the proposed building. (See Appendix A.) 7) Where a storage tank is to be modeled, the service water heating system's storage temperature shall be modeled as being identical to that of the proposed building. (See Appendix A.) 8) Where the proposed building's service water heating system comprises multiple water heaters, the reference building’s service water heating system shall be modeled with the same number of water heaters. 9) Where the proposed building's service water heating system is a recirculation system, the circulation pumps shall be modeled as a) constant speed operation, and b) having a flow rate that is identical to that of the proposed building's circulation pumps. 8.4.4.22. Part-Load Performance Curves 1) Part-load performance curves for the reference building's systems shall be calculated in accordance with Tables 8.4.4.22.A. to 8.4.4.22.G., as applicable. Table 8.4.4.22.A. Heating Equipment Part-Load Performance Characteristics Forming Part of Sentences 8.4.4.10.(8) and 8.4.4.22.(1) Boiler Part-Load Performance Curve(s) The fuel consumption at part-load conditions, derived by applying an adjustment factor to the fuel consumption at design conditions, shall be calculated using the following equation. Condensing and non-condensing boiler curves fit the quadratic equation of FHeatPLC defined therein. For modulating boilers, values for Qpartload/Qdesign and corresponding values for FHeatPLC shall be those listed in the last row of this Table. (1) where Fuelpartload = fuel consumption at part-load conditions, in Btu/h, Fueldesign = fuel consumption at design conditions, in Btu/h, and FHeatPLC = fuel heating part-load efficiency curve determined using Equation (2) or values from the last row of this Table, as applicable. (2) where Qpartload = boiler capacity at part-load conditions, in Btu/h, or values from the last row of this Table, as applicable, Qdesign = boiler capacity at design conditions, in Btu/h, or values from the last row of this Table, as applicable, and a, b, c = applicable values as follows: Variable a b c National Energy Code of Canada for Buildings 2011 Condensing Boiler 0.00533 0.904 0.09066 Non-condensing Boiler 0.082597 0.996764 –0.079361 Division B 8-19 8.4.4.22. Division B Table 8.4.4.22.A. (Continued) Furnace Part-Load Performance Curve(s) The fuel consumption at part-load conditions, derived by applying an adjustment factor to the fuel consumption at rated conditions, shall be calculated using the following equation. Condensing and atmospheric furnace curves fit the quadratic equation of FHeatPLC defined therein. For modulating furnaces, values for Qpartload/Qrated and corresponding values for FHeatPLC shall be those listed in the last row of this Table. (3) where Fuelpartload = fuel consumption at part-load conditions, in Btu/h, Fuelrated = fuel consumption at rated conditions, in Btu/h, and FHeatPLC = fuel heating part-load efficiency curve determined using Equation (4) or values from the last row of this Table, as applicable. (4) where Qpartload = furnace capacity at part-load conditions, in Btu/h, or values from the last row of this Table, as applicable, Qrated = furnace capacity at rated conditions, in Btu/h, or values from the last row of this Table, as applicable, and a, b, c = applicable values as follows: Variable a b c Modulating Boilers and Furnaces 8-20 Division B Amended Page Condensing Furnace 0.00533 0.904 0.09066 Qpartload, Qrated and Qdesign (Part-Load Ratio) 0.1 FHeatPLC 0.2 0.209 0.3 0.308 0.4 0.407 0.5 0.506 0.6 0.605 0.7 0.704 0.8 0.802 0.9 0.901 1 1 Atmospheric Furnace 0.0186100 1.0942090 –0.1128190 0.118 National Energy Code of Canada for Buildings 2011
© Copyright 2026 Paperzz