Siemens Energy & Automation, Inc. Installation and Service Instruction SD39MODULNET-1 Rev: 4 February 2003 MODULNET Carrierband Network !Notes SD39MODULNET-1 Contents Table of Contents Section Title 1.0 1.1 1.2 1.2.1 1.2.2 1.2.3 1.3 1.4 1.5 Introduction....................................................................................................................1-1 Product Description ......................................................................................................1-2 Specifications................................................................................................................1-7 Communications ....................................................................................................1-7 MODULNET Hardware ........................................................................................1-7 Environmental........................................................................................................1-9 Glossary ......................................................................................................................1-10 Product Support ..........................................................................................................1-10 Related Literature .......................................................................................................1-12 2.0 2.1 2.1.1 2.1.2 2.2 2.2.1 2.2.2 2.2.3 2.2.4 2.2.4.1 2.3 2.3.1 2.3.2 2.3.3 2.3.3.1 2.3.3.2 2.3.3.3 2.3.4 2.3.4.1 2.3.4.2 2.3.4.3 2.3.5 2.3.5.1 2.3.5.2 2.3.5.3 2.3.5.4 2.3.5.5 2.3.5.6 Installation......................................................................................................................2-1 Installation Considerations ...........................................................................................2-1 Trunk Cable............................................................................................................2-1 Trunk Tap...............................................................................................................2-2 MODULNET Design ...................................................................................................2-3 MODULNET Documentation................................................................................2-3 Safety Considerations ............................................................................................2-4 Procedure ...............................................................................................................2-4 MODULNET Length.............................................................................................2-7 Graphical Method.........................................................................................2-8 Tap and Cable Installation ..........................................................................................2-11 Tools and Test Equipment ...................................................................................2-11 Tap Installation ....................................................................................................2-12 Trunk Cable Installation.......................................................................................2-14 Trunk Cable Installation Procedure............................................................2-15 Trunk Cable Fabrication Procedure ...........................................................2-18 M-NET Cable Recommendations ..............................................................2-23 Drop Cable Installation ........................................................................................2-24 Drop Cable Installation Procedure .............................................................2-24 Drop Cable Fabrication Procedure .............................................................2-25 M-NET Cable Recommendations ..............................................................2-30 MODULNET Testing ..........................................................................................2-31 Trunk Return Loss Measurement ...............................................................2-31 Trunk Noise Level Measurement ...............................................................2-32 Drop Cable-to-Tap Return Loss Measurement ..........................................2-33 Drop Cable Noise Level Measurement ......................................................2-33 Signal Level Measurement.........................................................................2-33 Cable Sealing and Boots ............................................................................2-36 3.0 Circuit Description ........................................................................................................3-1 4.0 4.1 4.2 4.3 Maintenance ...................................................................................................................4-1 Tool and Equipment Requirements ..............................................................................4-1 Visual Inspection ..........................................................................................................4-1 MODULNET Troubleshooting ....................................................................................4-2 February 2003 Page i Contents SD39MODULNET-1 4.3.1 4.4 4.5 4.6 4.7 Advance Diagnostics Techniques Beyond this checklist.......................................4-5 MODULNET Testing...................................................................................................4-6 Tap or Cable Segment Replacement.............................................................................4-7 Spare and Replacement Parts........................................................................................4-7 Return of Shipment.......................................................................................................4-7 List of Tables Table Title Page Table 1–1 MODULNET Hardware ..........................................................................................................1-1 Table 1–2 MODULNET Accessories .......................................................................................................1-1 Table 1–3 TIC Contact Information........................................................................................................1-11 List of Illustrations Figure Title Page Figure 1–1 MODULNET Local Area Network ........................................................................................1-3 Figure 1–2 MODULBUS Expander Module and Transition Board .........................................................1-5 Figure 1–3 MODULNET Redundancy.....................................................................................................1-6 Figure 2–1 Figure 2–2 Figure 2–3 Figure 2–4 Figure 2–5 Figure 2–6 MODULNET Taps .................................................................................................................2-5 MODULNET Length vs. Number of 2-Port Taps..................................................................2-9 MODULNET Length vs. Number of 4-Port Taps................................................................2-10 Tap Mounting within MODULPAC.....................................................................................2-13 F-Male Connectors for RG-6 and RG-11 Cables .................................................................2-17 Network Signal Level Analysis Example.............................................................................2-35 Significant Changes for Revision 4 2.3 ii Tap and Cable Installation—Addition of trunk cable and drop cable fabrication procedures. February 2003 SD39MODULNET-1 1.0 Introduction Introduction This manual provides installation and service information for MODULNET hardware and accessories as listed in Table 1-1 and Table 1-2 below. Table 1–1 MODULNET Hardware Part Number Description 14753-1 Trunk Cable Tap, 2 Port 14753-3 Trunk Cable Tap, 4 Port 14753-2 F-Type 75 Ohm Terminator W2077 RG-6 Drop Cable (length specified by user) 16056-440 RG-11 Trunk Cable (200 meter reel) 16056-441 RG-11 Trunk Cable (400 meter reel) 16056-442 RG-11 Trunk Cable (800 meter reel) Table 1–2 MODULNET Accessories February 2003 Part Number Description 14784-501 F-Type Connector, RG-11 (one connector) 14784-500 F-Type Connector, RG-6 (one connector) 15753-2 F-Type Precision Terminator, 75 Ohms (one terminator) 16137-68 MNET A Drop Cable with Dropsaver, 19.7 Ft (6 M) 16137-69 MNET B Drop Cable with Dropsaver, 19.7 Ft (6 M) 16056-411 Dropsaver F Connector Protector 16056-371 MNET 2-Port Tap Kit (with mounting brackets and terminators) 16056-372 MNET 4-Port Tap Kit (with mounting brackets and terminators) 16056-438 MNET RG-6 Drop Cable Kit (with connector sealing boots, dropsavers, 163 Ft/50 Meter RG-6 cable, and Instructions) 16056-374 MNET RG-11 Connector Kit (with connector sealing boots, dropsavers, cable markers, and Instructions) 16056-378 MNET Cable Preparation Tool Kit (with RG-6 and RG-11 connector crimping tools) 16056-377 Tap Support Bar (mounting base for tap mounting bracket) 16056-318 Tap Mounting Bracket (for mounting taps in a cabinet) 16056-660 25 in-lb Torque Wrench 1-1 Introduction SD39MODULNET-1 This Instruction is divided into four major sections: Section 1, IntroductionProvides a list of hardware, cables, and accessories, a brief product description, specifications, and a glossary of terms. Section 2, InstallationFurnishes hardware selection considerations, MODULNET design parameters, cable installation and test procedures, hardware identification and installation procedures. Section 3, Circuit DescriptionContains a brief description of the MODULNET. Section 4, MaintenanceConsists of preventive maintenance and troubleshooting procedures, hardware removal and replacement references, and recommendations for spare and replacement parts. 1.1 Product Description A MODULNET is a carrierband network that permits plant-wide expansion of the APACS+ redundant MODULBUS, interconnecting Local Area Systems* (LAS) over short or long distances. A MODULBUS Expander Module (MBX) and an MBX transition board must be installed in a MODULRAC at each Local Area System. A MODULNET is installed when the local MODULBUS in a Local Area System is to be interconnected with the local MODULBUS in another Local Area System. This permits the exchange of process data and process control commands. Figure 1-1 is an illustration of a redundant MODULNET interconnecting three Local Area Systems in three separate plant areas. Each Local Area System is represented by an MBX and an MBX Extended Transition Board. MNET A is at the top of the figure, MNET B at the bottom. Each MNET (A or B) is independent and bi-directional. It consists of coaxial trunk and drop cables, taps, port terminations, end-of-trunk terminations, and the MODULBUS (A and B) in each LAS. The trunk cable connects to drop cables through nondirectional, passive, impedance-matching taps. A drop cable connects to an MBX transition board. 1-2 February 2003 SD39MODULNET-1 Introduction Figure 1–1 MODULNET Local Area Network February 2003 1-3 Introduction SD39MODULNET-1 Figure 1–2 shows an MBX and the MBX transition board. An MBX communicates with other MBXs on a MODULNET by sending and receiving MODULBUS communications across the redundant MNET. When an MBX and its transition board are installed in a MODULRAC, the transition board's Module Connector and the MBX's bottom connector (on its rear panel) are mated. Communication signals flow to and from the MODULNET through this mated pair. The MBX's top connector (also on its rear panel) mates with a connector on the MODULRAC backplane for access to the MODULBUS. The MBX has two independent channels to transfer information between the MODULBUS and the MODULNET. A System Node Address (SNA) must be assigned to each MBX so that communications can be addressed to it. Rotary switches in the MBX bezel compartment are set to assign an SNA. As shown in Figure 1–3, rack-to-rack and module-to-module redundancy are available. • Rack-To-Rack Redundancy - Two MODULRACs are involved, each with an MBX. The racks must be identical with respect to module selection and slot location. Different System Node Addresses are assigned to the two MBXs. MNET A and MNET B are connected to both MBXs. • Module-To-Module Redundancy - One MODULRAC is involved with two MBXs installed in adjacent slots. They are assigned the same System Node Address. One MBX will service MODULNET A and the other MODULNET B. The unused side of each MBX will not be connected to the MODULNET. *In this Instruction, the term Local Area System includes Unit Controllers. 1-4 February 2003 SD39MODULNET-1 Introduction Figure 1–2 MODULBUS Expander Module and Transition Board February 2003 1-5 Introduction SD39MODULNET-1 Figure 1–3 MODULNET Redundancy 1-6 February 2003 SD39MODULNET-1 1.2 Introduction Specifications 1.2.1 Communications Local Area Network (MODULNET) IEEE 802.4 (Carrierband) Network Capacity 64 nodes (0 through 63) Signal Direct Encoded Data Signal Modulation Phase Coherent FSK Signal Protocol Deterministic Token Passing Data Rate 5 Mbps MBX to MODULNET Connection Non-Directional Tap 1.2.2 MODULNET Hardware W2077 Drop Cable Type RG-6 Carrierband Network Cable IEEE 802.4 Impedance 75 Ohms +/-2 Ohms Signal Attenuation (5 Mhz) 2.16 dB/100 meters 0.66 dB/100 feet Signal Attenuation (10 Mhz) 2.52 dB/100 meters 0.77 dB/100 feet Transfer Impedance 10 milliohm/meter Max. Conductor Size 18 AWG solid Shielding Quad (4) Shields Maximum Pulling Tension 45 lbs. (20.4 kg.) Bend Radii 3.0 inches Pulling Limit 45 lbs. (20.4 Kg) W2078 Standard Trunk Cable Type RG-11 Carrierband Network Cable IEEE 802.4 Impedance 75 Ohms +\-2 Ohms Signal Attenuation (5 Mhz) 0.89 dB/100 meters 0.27 dB/100 feet Signal Attenuation (10 Mhz) 1.21 dB/100 meters 0.37 dB/100 feet Transfer Impedance 10 milli-ohm/meter Max. February 2003 1-7 Introduction SD39MODULNET-1 Conductor Size 14 AWG solid Shielding Quad (4) Shields Structural Return Loss 26 dB (5 to 450 Mhz) Cable Jacket Band Marks Every 2.6 meters (8.5 ft.) Maximum Pulling Tension 150 lbs. (68.1 kg) Bend Radii 7.0 inches Minimum Length 2.6 meters (8ft 6 in) Pulling Limit 150 lbs. (68.1 Kg) Armored Trunk Cable Type Armored RG-11 Carrierband Network Cable IEEE 802.4 Impedance 75 Ohms +\-2 Ohms Signal Attenuation (5 Mhz) 1.14 dB/100 meters 0.35 dB/100 feet Signal Attenuation (10 Mhz) 1.48 dB/100 meters 0.45 dB/100 feet Transfer Impedance 0.8 milliohm/meter Max. Conductor Size 14 AWG solid Shielding Quad (4) Shields Armor 1 (Steel or Aluminum) Structural Return Loss 26 dB (5 to 450 Mhz) Cable Jacket Band Marks Every 2.6 meters (8.5 ft.) Bend Radii 10 times od (outside diameter) NOTE Avoid runs of multiple of 45 to 55 feet (1/4 wave = 49.2 ft.) Carrierband Tap 1-8 Type (Hi-Rel) Hi-Rel Industrial Grade IEEE 802.4 Standard & MAP Carrier- band Tap Drop Ports 2 or 4 Ports Drop-to-Trunk Port Attenuation 20 dB +\-0.5 dB Trunk-to-Drop Port Attenuation 20 dB +\-0.5 dB Drop-to-Drop Isolation 30 dB Min. Trunk Insertion Loss (2-port tap) 0.3 dB Max. February 2003 SD39MODULNET-1 Introduction Trunk Insertion Loss (4-port tap) 0.45 dB Max. Impedance, all ports 75 Ohms Surge Protection, each port Gas Discharge Surge Protector Pin Connector Finish Gold Plated Trunk Cable Isolation Trunk cable segments MUST be connected between the non-isolated (grounded) trunk port (T2) and the isolated port (T1) of 2 taps (e.g., T1 connect to T2). Operating Temperature -40°C to +84°C (-58°F to +183°F) Connectors Type F-Series Industrial Grade, EIA FD Standard 550 Cable-end male Contact Finish Gold Plated Terminator Type Precision F Type Return Loss 40 dB min. @ 10 Mhz. Nominal Impedance 75 Ohms Contact Finish Gold Plated 1.2.3 Environmental Operating Temperature 0° to 60°C (32° to 140°F) Storage Temperature 0° to 85°C (32° to 185°F) Humidity Range 5 to 95% Non-Condensing IMPORTANT The MODULNET is a high performance digital data link for which the cables and hardware listed in section 1 and described above are highly recommended. Any substitutes MUST BE ELECTRICALLY EQUIVALENT and meet the IEEE 802.4 specifications for carrierband service. Failure to use proper cables and hardware can result in erratic MODULNET performance. February 2003 1-9 Introduction 1.3 SD39MODULNET-1 Glossary The following are definitions of terms used in this Instruction: Attenuation - The reduction of a signal's level as it travels along a cable. (Expressed as a relative value in dB.) Baseband - A type of cable network that supports only one signal at a time. Carrierband - A type of baseband network used in the factory. The MODULNET is a carrierband network. Drop Cable - The cable connecting the tap to the MODULBUS Expander Module. Frequency Shift Keying (FSK) - The carrierband signaling method. Binary ones are one cycle of 5 Mhz; binary zeros are two cycles of 10 Mhz. Insertion Loss - The amount of loss of the signal passing through a tap on the trunk cable. (Expressed as a relative value in dB.) Nondirectional - Signal from the drop cable splits equally in both directions from a tap onto the trunk cable. Return Loss - The amount of signal reflected from a cable impedance discontinuity. Tap - A passive non-directional impedance matching device for connecting the MBX to the MODULNET (trunk cable). Termination - A device which absorbs signals at the end of a trunk cable. 1.4 Product Support Product support can be obtained from a Technical Support Center (TSC). Each regional TSC is a customer service center that provides direct telephone support on technical issues related to the functionality, application, and integration of all products supplied by Siemens. Regional TSC contact information is provided in Table 1–3. Your regional TSC is the first place you should call when seeking product support information. When calling, it is helpful to have the following information ready: • Caller name and company name • Product part number or model number and version • If there is a problem with product operation: - 1-10 Whether the problem is intermittent The steps performed before the problem occurred Any error messages or LED indications displayed February 2003 SD39MODULNET-1 - Introduction Installation environment Customers that have a service agreement (ServiceSuite or Field Service Agreement) are granted access to the secure area of our Web site (http://www.smpa.siemens.com/TechServices/TechLibrary.asp). This area contains a variety of product support information. To log on, you will be prompted to enter your username and password. Table 1–3 TSC Contact Information TSC NORTH AMERICA Tel: +1 215 646 7400, extension 4842 Fax: +1 215 283 6343 E-mail: Hours of Operation: Secure Web Site: TSC ASIA www.sea.siemens.com/process/product/papao.html +011 65 740 7818 Fax: +011 65 740 7817 E-mail: Secure Web Site: [email protected] 8:30 a.m. to 5:30 p.m. Singapore time Monday – Friday (except holidays) www.siemens.com Tel: +44 (0) 1905 450930 Fax: +44 (0) 1905 450931 E-mail: Hours of Operation: Secure Web Site: February 2003 8 a.m. to 5 p.m. eastern time Monday – Friday (except holidays) Tel: Hours of Operation: TSC EUROPE [email protected] [email protected] 8:30 a.m. to 4:30 p.m. GMT/BST Monday – Friday (except holidays) www.siemens.com 1-11 Introduction 1.5 SD39MODULNET-1 Related Literature The following Instructions should be available for reference during a MODULNET installation. • MODULBUS Expander Module Installation and Service Instruction (document number SD39MBX-1) • MODULPAC Installation and Service Instruction (document number SD39MODULPAC-1) • MODULRAC Installation and Service Instruction (document SD39MODULRAC-1) • ANSI/IEEE 802.4, 1990, Token Passing Bus Access Method and Physical Layer Specifications; a copy can be obtained from the following addresses: U.S.A.: American National Standards Institute Attn: Customer Service 11 West 42nd Street New York, NY 10036 Phone Orders: 212-642-4900 Europe: ISO 1,Rue, De Varembe CH-1211 Geneva 20 Switzerland/Swiss Phone: 4122749011 " 1-12 February 2003 SD39MODULNET-1 2.0 Installation Installation This section describes design and installation of a redundant MODULNET including taps, terminations, and trunk and drop coaxial cables. Read this entire section before beginning an installation. Refer to the MODULBUS Expander Module's Installation and Service Instruction (document number SD39MBX-1) as necessary during the installation. 2.1 Installation Considerations Before beginning to install MODULNET hardware, complete the following: 1. System Layout Design the MODULNET cable-system (see section 2.2) and select MODULNET hardware (refer to section 1.0 , section 1.3, and section 2.1.1 in this Instruction and the MODULBUS Expander Module Instruction). Avoid areas containing environmental contaminants that could damage cables. If this is not possible, use installation techniques to control contamination. 2. Install taps (see sections 2.1.2 and 2.3.2). 3. Prepare and install trunk cables (see section 2.3.3). 4. Prepare and install drop cables (see section 2.3.4). 5. Test installed MODULNET (see section 2.3.5) 6. Refer to MODULBUS Expander Module Installation and Service Instruction to connect drop cables and set MNET A and B switches. 2.1.1 Trunk Cable Trunk cable specifications are listed in section 1.2. Cable is available in flexible and armored versions. Flexible cable is used in most installations, however, armored cable has advantages and disadvantages, as discussed later in this section. For a Superior Installation: • Use a high quality cable designed for IEEE 802.4 carrier band service from one manufacturer for the entire trunk to maintain constant impedance between cable segments. Prior to shipment, have the manufacturer test the cable to ensure that it meets attenuation specifications and that concealed (internal) discontinuities that can cause reflections do not exist. - Structural Return Loss from both cable ends: Loss should be -26 dB or better. February 2003 2-1 Installation - SD39MODULNET-1 Cable attenuation: Refer to the manufacturer's specification for the length of cable on the reel. The attenuation is measured at 10 Mhz. The cable manufacturer should provide a test document with each reel of cable listing the following: - Manufacturer's Lot Number Cable Attenuation @ 5 and 10 MHz. Structural Return Loss Tilt per Distance Cable Impedance Group Delay Distortion Maximum Cable Length The maximum cable length is an important cable parameter. It specifies the maximum length the cable can be and remain within the IEEE Standard 802.4 specification. Pretested RG-11 trunk cable can be ordered from Siemens. See Table 1–1. • All segments of trunk cable for MNET A, or for MNET B, should come from one reel. If more than one reel is required to fabricate the entire A or B trunk, use a reel from the same lot (same extruder at the same time of manufacture). It is the extruder-to-extruder differences that create slightly different characteristic impedances which cause unwanted signal reflections. • Splicing a trunk cable segment is not recommended for a new installation. Armored Cable Advantages and Disadvantages: • Superior protection from factory electrical noise. Its higher transfer impedance is indicative of its ability to reject unwanted shield currents. • Can be buried without installation in conduit. • Can be hung between poles separated by up to 150 feet (46 meters) without the need for messenger wire support. • Protected against moisture and physical damage. • More complex installation. For example, it must be formed to make bends and turns. • Requires grounding of the armor for lightning protection and additional noise immunity. 2.1.2 Trunk Tap This section discusses tap mounting locations and methods. Figure 2–1 shows 2-port and 4-port taps. 2-2 February 2003 SD39MODULNET-1 Installation NOTE Taps are known as 2-port and 4-port taps. This refers to the number of drop ports. Both taps also have two trunk ports. Each tap will have connected to it one or two trunk cables and one to four drop cables. The taps at each end of an MNET must have a 75 ohm termination installed in the trunk port that is not connected to a trunk cable. Unused drop ports must also be terminated. NOTE All Taps must be grounded by connecting the tap’s ground lug to a ground point. Do not float tap. Two taps are needed for a Local Area System to connect to a redundant MODULNET. They can be mounted either inside a cabinet housing an MBX or external to the cabinet. External Tap: At each Local Area System (LAS), mount the taps as close as possible to the cabinet housing the MBX to minimize drop cable length. Mount the taps with user supplied hardware. When the trunk cable is aerially suspended and a tap is suspended in mid-air, provide a messenger cable for support and cable strain relief to prevent axial cable loads at the tap connections. Internal Tap: MNET 2-Port and 4-Port Tap Kits (seeTable 1–2) include a tap mounting bracket for the rail mounting of taps in a MODULPAC cabinet. A mounting instruction is included in each kit. Mounting a tap internally yields the shortest drop cable which can permit additional taps or a longer trunk. This may be offset by the additional trunk cable often needed to reach the internally mounted tap. 2.2 MODULNET Design The design of the MODULNET (MNET) requires consideration of a number of parameters, including safety, environment, number of taps, and trunk and drop cable lengths. The following sections discuss these and other topics. 2.2.1 MODULNET Documentation Network documentation should be created during the design phase. The documentation can be used by cable system installers to route the cable, install and mark taps, and compare calculated signal values with measured values. It will also assist in visualizing the installation during the design phase and provide a reference for servicing the network and for future additions to the network. A permanent record of the network's physical structure and performance characteristic should include the following: February 2003 2-3 Installation - SD39MODULNET-1 Trunk and drop cable routes Length of each trunk and drop cable segment Trunk cable segment identifier (ID) and drop cable ID (including cabinet ID and MODULRAC slot number of the MBX to which it connects) Each tap type and ID Calculated trunk port SIGNAL IN/OUT level at each tap Calculated drop port SIGNAL IN (to MBX) level at each tap Measured return loss value of finished trunk 2.2.2 Safety Considerations The installation should include the following safety considerations: IMPORTANT The installation must comply with the National Electrical Code and all other applicable construction and electrical codes. 1. Physically isolate MODULNET components from all power or lighting circuits. 2. Properly ground all MODULNET taps to provide for: • The dissipation of static charges in MODULNET cables. • The shunting to ground of high-energy transients (surge protection) 3. Ensure that safety grounds to which various MODULNET components are connected are at the same electrical potential. 2.2.3 Procedure This section contains a series of steps for designing a MODULNET that will meet IEEE 802.4 specifications. IMPORTANT MNET A and B must have the same number of taps and MBXs, although trunk lengths can be different if they are within the limits of the IEEE 802.4 specifications 2-4 February 2003 SD39MODULNET-1 Installation Figure 2–1 MODULNET Taps 1. Refer to the user documentation listed in section 1.5, Related Literature, for information regarding proposed MODULNET requirements. • Note the location of each Local Area System (LAS) and the location of each cabinet that will house an MBX. February 2003 2-5 Installation SD39MODULNET-1 An MBX and transition board (or redundant MBXs and transition boards) must be installed at each LAS. • Note module-to-module and rack-to-rack redundancy requirements. See Figure 1–3. Module-to-Module Redundancy - One MBX will service MNET A and the other MNET B. The unused A or B side of each MBX is turned off. Rack-to-Rack Redundancy - Completely duplicates the MBX, control, and I/O module subsystem for maximum availability. Both MBXs are connected to MNET A and B. 2. Determine the location of each 2-port and 4-port tap and record the number of taps required and the estimated length of each drop cable. • If the plant already exists, determine the tap locations and estimate and record the length of the associated drop cables. • If the plant is being designed, tap locations and estimated drop cable lengths should be specified as an installation drawing. • Include extra taps for future Local Area Systems additions. • Provide ports for test points at critical locations on the network, for example, at each end of the trunk cable, where the trunk cable enters an inaccessible area, and where a trunk cable enters or leaves a building. • Select a cable routing medium (e.g., conduit, raceway, trough) for trunk and drop cables. 3. Determine the maximum allowable end-to-end trunk length. Refer to section 2.2.4 for a the graphical and calculation methods. Then return to step 4 below. 4. Estimate the length of each between-taps trunk cable segment. • Estimate as accurately as possible the length of each trunk cable segment. Refer to plant drawings. The sum of all cable segments must be equal to or less than the total allowable end-to-end trunk cable length. • Each trunk cable segment must be installed in increments of 8 ft. 6 in. (2.6 meters) which are clearly marked by bands on the cable's outer sheath. Note the following: - Minimum trunk cable segment: 8 ft. 6 in. (2.6 meters) - Maximum trunk cable segment: The maximum trunk cable segment length is a function of the end-to-end trunk length and number of taps between cable segments. 5. Determine secure routes for MNET A and MNET B cables from tap to tap. 2-6 February 2003 SD39MODULNET-1 Installation • To improve system reliability, MNET A and MNET B should follow separate routes between taps so that a single accident will be unlikely to damage both cables. A secure route is one that also eliminates or minimizes induced noise which can degrade system reliability. • Use a direct route whenever possible to minimize trunk cable length. Estimate and record the length of each segment (i.e., each length between two taps). • Select a suitable passage medium (conduit, flexible armor, cable trays, aerial post-to-post, etc.) to accommodate the trunk cables. 6. Compare the estimated sum of trunk cable segment lengths from step 4 with the maximum allowable end-to-end trunk length determined from step 3. The estimated end-to-end trunk lengths of MNET A and MNET B must be less than or equal to the maximum allowable trunk length. IMPORTANT If the estimated trunk length exceeds the maximum allowable trunk length, consult a Siemens engineer for options to extend trunk length. 2.2.4 MODULNET Length The MODULNET must be within the length determined in this section to ensure reliable communications. MODULNET maximum length is affected by: • Trunk and drop cable signal attenuation • The number of 2-port and 4-port taps and the signal attenuation caused by these taps The MODULNET maximum length for the needed number of taps can be determined by either of two methods: • Graphical Method: Estimated from the graphs in Figure 2–2 and Figure 2–3. • Calculation Method: Calculated by a formula provided in Appendix A. The formula describes the relationship between trunk cable length, the number and type of taps, and the length of drop cables. The formula must be used when the MODULNET consists of a mixture of 2-port and 4-port taps excluding the end-of-trunk taps. Section 2.2.4.1 describes the use of the graphs to determine the number of allowable taps versus a given MODULNET length or vice versa. February 2003 2-7 Installation SD39MODULNET-1 2.2.4.1 Graphical Method The graphs in Figure 2–2 and Figure 2–3 are applicable to MODULNETs consisting of only 2-port or 4port taps. The graphs were generated using the formula in Appendix A and the cable and tap specifications in section 1.2. The number of allowable taps per MODULNET length shown in the graphs EXCLUDES both end-oftrunk taps and represents the number of taps allowed between the end-of-trunk taps. IMPORTANT End-of-trunk taps can be of the same type or one of each type. The type of end-of-trunk taps used is independent of the composition of the intervening taps. Several examples show use of the graphs. While the examples refer to Figure 2–2, the 4-port graph in Figure 2–3 is used identically. Read the graphs carefully to avoid errors which could result in a poorly performing MODULNET. Example 1: Find the maximum allowable MODULNET trunk length. Known: Longest (estimated) Drop Cable = 120 Ft. Total Taps = 14 Tap Type = 2-port 1. Figure 2–2 (2-port tap graph) is applicable to this example. 2. Since the graph excludes the two end of trunk taps, subtract 2 from the total number of taps (14). 3. Find curve E for the 130 ft. drop cable. 4. Locate on the horizontal NUMBER OF 2-PORT TAPS scale the point for 12 taps. Follow the vertical line to curve E. 5. From the above point on curve E, move horizontally to the MODULNET LENGTH scale to read the allowable MODULNET length. For this example, the MODULNET length is an estimated 1725 feet. 2-8 February 2003 SD39MODULNET-1 Installation Figure 2–2 MODULNET Length vs. Number of 2-Port Taps February 2003 2-9 Installation SD39MODULNET-1 Figure 2–3 MODULNET Length vs. Number of 4-Port Taps 2-10 February 2003 SD39MODULNET-1 Installation Example 2: Find the maximum allowable number of 2-port taps. Known: MODULNET length (estimated) = 1900 Ft. Longest (estimated) drop cable = 60 Ft. 1. Figure 2–2 (2-port tap graph) is applicable to this example. 2. Locate on the graph the intersection of the horizontal 1900 ft. line and curve C. 3. Move down vertically and read the number of allowable taps from the horizontal tap scale. Note that the value of the tap number falls between 13 and 14 taps. Fractional numbers are rounded down to the lowest whole number, which is in this case, 13 taps. Adding the two end-of-trunk taps (any type) gives a total of 15 taps across the MODULNET. Example 3: Find the allowable drop cable length. Known: MODULNET length = 1300 ft. Number of taps (excluding end-of-trunk taps) = 20, 2-port taps 1. Figure 2-2 (2-port tap graph) is applicable to this example. 2. Locate on the graph the intersection of the 1300 ft. horizontal line and 20 tap vertical line - between the C and D curves. 3. Note that the span between the C and D curves is 40 ft. 4. Estimate from the intersection of the 1300 ft. and 20 tap lines that the allowable longest drop cable length is 75 ft. 2.3 Tap and Cable Installation The procedures in the following subsections are for installing taps, trunk cables and drop cables. It may be necessary to modify these procedure to accommodate the installation site, available tools and test equipment, or local ordinances. 2.3.1 Tools and Test Equipment Typical tools and test equipment are listed below. They are supplied by the installer. • Cable preparation and installation tools for RG-6 and RG-11 cable; see accessory list in Table 1–2 • 25 lb-in Torque Wrench (PN 16056-660) • Carrierband Network Tester Some manufacturers of carrierband hardware offer a network tester and signal generator for field testing to the IEEE 802.4 standard. February 2003 2-11 Installation SD39MODULNET-1 Frequently, a carrierband network tester can be used by cable installation personnel having no specific electronics training. An auxiliary signal generator is used as a signal source at one end of the trunk cable and the tester measures the signal strength and return loss along the trunk cable. This equipment is used for the following network activities: - Component qualification Installation verification Servicing The manufacturer of the CB Tester and Auxiliary Signal Generator (standard accessory) is: RELCOM Inc. Rt. 1, 244H Forrest Grove, OR 97116, USA • Cable pulling grips • Conduit cutting and bending tools • Heat gun for heat-shrink tubing • Standard hand tools 2.3.2 Tap Installation Mount each tap either within the cabinet housing the MBX or external to the cabinet. 1. Refer to system documentation for the quantity of each type of tap (2-port or 4-port) to be installed and for mounting locations. Taps, Installation Instructions, and mounting hardware are provided in each Tap Mounting Kit. External Mounting - Refer to Figure 2–1 for tap mounting dimensions and fabricate mounting brackets. Internal Mounting - Refer to Figure 2–4 and the Tap Mounting Kit Instructions to mount the taps. 2. Install taps in pairs at their selected locations, one each for MNET A and B. Typically, begin at an end-of-trunk tap and proceed along the trunk to the opposite end-of-trunk tap. Tag every tap with its number and MNET A or B ID. 2-12 February 2003 SD39MODULNET-1 Installation Figure 2–4 Tap Mounting within MODULPAC 3. External Mounting - Install a 14 gauge (AWG) wire between the tap's ground stud and building safety ground. Do not rely on building structure, conduit, or messenger cable to complete the ground path. 4. At each tap, install a 75 ohm Terminator on each port that will not receive either a trunk or tap cable, to maintain proper network impedance. 5. At each tap's trunk ports, provide cable strain relief so the trunk cable does not put a stress on the tap trunk port. February 2003 2-13 Installation 2.3.3 SD39MODULNET-1 Trunk Cable Installation Trunk cable installation consists of routing and installing cable segments between successive taps until all cable segments comprising the cable-system are installed. Pull each cable through conduit or lay it in cable trays at an appropriate point in the installation procedure provided below. The following is applicable to both MNET A and B trunks: • Refer to user's MODULNET documentation and the results of the MODULNET design in section 2.2 for trunk and tap cable routing, cable lengths, tap locations, MBX slot locations and other needed information. • Do not exceed the manufacturer's trunk cable pulling force during installation, especially when pulling cable through conduit. W2078 cable has a pulling limit of 150 lbs (68.1 kg). • Do not bend a cable around sharp corners. A trunk cable has a minimum bend radius of 17.75 cm (7.0 inches). • For aerial suspension, the maximum unsupported cable length for standard RG-11 cable is 100 feet (30.5 m) and for armored RG-11 cable 150 feet (45.7 m). If longer distances are required, use messenger wires. • Trunk cable can be laid in a cable tray or trough, or secured to polls, walls, or building structural members. Do not crush the trunk cable with attachment devices. • Route trunk and drop cables away from plant areas with electromagnetic/electrical fields that might interfere with MODULNET communications. Such areas may contain electric arcs, high current electrical equipment which emit strong electromagnetic fields and switching transients, welding operations, or electrical motors turning on and off. • Armored RG-11 trunk cable requires grounding of the armor for lightning protection and additional noise immunity. Ground the armor in as many places (two places minimum) between taps as possible with a 14 AWG conductor to safety ground. Do not ground the armor to the taps or to the cable's inner shields. Use ground clamps designed for armor cable to make these connections. • Make sure that all MNET taps are cabled from T1 on the first tap to T2 on the next tap (not T1 to T1 or T2 to T2). Mnet uses a segmented ground for the coaxial cable. The trunk port labeled ‘T2’ is grounded. The ‘T1’ port is isolated from ground. Connecting both ends of a cable segment to T! ports fails to ground the cable. Connecting both ends to T2 ports creates a ground loop. • Strain-relieve all MNET/MBUS cables. Replace any cables with signs of connector damage. (See MNET Kit Instructions 15900-553 and -554). Excess force on the cables can result in cable or connector failure • Verify that the entire APACS+ system is properly grounded (See Installation and Service Instruction SD39GND-1). Improper grounding can cause ground loops, which can cause noise. • Avoid runs in multiple of 45 to 55 ft. (1/4 wave = 49.2 ft.) 2-14 February 2003 SD39MODULNET-1 Installation 2.3.3.1 Trunk Cable Installation Procedure 1. Refer to MODULNET documentation and the results of the MODULNET design in section 2.2 for cable length between the first and second taps on MNET A. Include some extra cable for connector installation and future servicing. 2. Route the trunk cable between selected taps. 3. Cut cable to desired length. 4. Refer to Figure 2–5 and the section, Trunk Cable Fabrication Procedure, to attach F-male connectors to both ends of the cut trunk cable. Use a crimping tool recommended by the connector manufacturer. Tag each end of the trunk cable segment with its segment number and its MNET A or B ID. 5. Remove the rubber gasket from all MNET terminators (Service Note SN39MNET-1). 6. Completely remove any MNET terminator and chain from the T1 side of the taps before installing the cable. If the dangling terminator touches any grounded object, it can cause a ground loop by grounding the isolated tap trunk port, T1. NOTE Lubricate all MBUS/MNET connections of all connectors (Kit Instruction 15900-394, included with the lubricant kit, P/N 14850-121). Lubrication protects the contacts from harsh environments and fretting corrosion. 7. Use a proper torque wrench to tighten coaxial connectors (cables and terminators) Use P/N 16056660, 25 in.-lb. torque wrench for cables, included in Tool Kits 16056-652 and 16056-653) If a proper torque wrench is not immediately available, approximate 25 in.-lb. by finger tightening, plus 1/8 turn for connectors and terminator without gaskets. Be sure to relieve any strain the cable may exert on the connector while tightening. Insufficient torque can result in a poor connection; excessive force can result in damage to hardware. IMPORTANT Each trunk cable MUST connect to an isolated trunk port (T1) on one tap and a grounded, non-isolated trunk port (T2) on a second tap. See Figure 2-1 to identify the ports. A white dot often marks the isolated port. Be careful not to cross-connect MNET A and MNET B. 8. Install the next MNET A trunk cable segment. Repeat the preceding steps for each cable segment until all MNET A segments are installed, then proceed to step 9. 9. Install each MNET B trunk cable segment by repeating the above steps. February 2003 2-15 Installation SD39MODULNET-1 IMPORTANT Terminate the ends of the MODULNET with 75 ohm terminators. See Figure 1–1. Do not connect the network ends together. 2-16 February 2003 SD39MODULNET-1 Installation Figure 2–5 F-Male Connectors for RG-6 and RG-11 Cables February 2003 2-17 Installation SD39MODULNET-1 2.3.3.2 Trunk Cable Fabrication Procedure Follow steps 1 through 9 to fabricate the cables. Detailed procedures for each step are provided. 1. Initial Cable Preparation: Slip heat shrink over cable end. For M-NET A, use white; for M-NET B, use black. HEAT SHRINK RG-11 QUAD SHIELD TRUNK CABLE CommScope P/N 5950 COPPER-COATED STEEL CENTER CONDUCTOR F-CONNECTOR END Figure 1 - Initial Cable Preparation 2. Preparing the Cable End a. Remove 1/2 inch of the cable jacket (see Figure 2). Be careful not to cut the braid. 1 2" Figure 2 - Remove Cable Jacket b. Carefully fold back the outer braid over the jacket (see Figure 3). Figure 3 - Folding Back the Outer Braid 2-18 February 2003 SD39MODULNET-1 Installation c. Carefully peel off the outer foil after first making a small cut at the base of the foil at the end of the foil wrap (see Figure 4). PEEL OUTER FOIL SMALL CUT Figure 4 - Removing the Outer Foil d. Carefully fold back the inner braid over the outer braid (see Figure 5). Do not remove the inner foil. Figure 5 - Folding Back the Inner Braid e. Trim the dielectric so that there is 1/8 inch protruding from the jacket (see Figure 6). Use a wirestripping tool that is notched or can be adjusted so that the center conductor does not get nicked. Adjust the stripping tool to match the center conductor’s dimension of 14 AWG. 1 8" Figure 6 - Trimming the Dielectric f. Trim the center conductor, which is 14 AWG copper-coated steel wire, so that there is only 1/8 inch protruding from the dielectric (see Figure 7). 1 8" Figure 7 - Trimming the Center Conductor February 2003 2-19 Installation SD39MODULNET-1 3. Crimping the Pin to the Center Conductor: a. Insert the pin over the center connector so that the end of the pin is flush with the end of the dielectric (see Figure 8). PIN Figure 8 - Inserting the Pin over the Center Conductor b. Using the 0.100 hex of the Siemens Crimping Tool P/N 16056-414 (reference also Gilbert P/N GCRT-211), crimp pin to center conductor (see Figure 9). CROSS-SECTION OF CRIMPER JAW Figure 9 - Crimping the Pin to the Center Conductor 4. Inserting Cable into Connector: Perform the following procedure to insert the cable into the connector: a. Insert the cable into the F-connector (Siemens F-connector, P/N 14784-501 (reference also Gilbert P/N 44344) (see Figure 10). 3 32 " GILBERT F-STYLE CONNECTOR P/N 44344 Siemens P/N 14784-501 Figure 10 - Inserting the Cable into the Connector 2-20 February 2003 SD39MODULNET-1 Installation b. Check to see that cable insertion is complete by determining that the pin protrudes a minimum of 3/32 in. past the end of the connector (see Figure 11). Use the F-connector pin gauge provided. CHECK WITH 32" F-CONNECTOR PIN GAUGE Siemens P/N 16056-648 3 Figure 11 - Checking Cable Insertion 5. Crimping the Connector onto the Cable: Crimp the connector onto the cable using the 0.475 hex on the Siemens Crimping Tool, P/N 16056414 (reference also Gilbert P/N G-CRT-211) (see Figure 12). CRIMP WITH 0.475 HEX Figure 12 - Crimping the Connector onto the Cable NOTE The jaws of the crimping tool must close fully to effect a good crimp. As the jaws close, the handles can be felt to toggle over center. Make sure that you use the entire width of the crimping tool. February 2003 2-21 Installation SD39MODULNET-1 6. Sliding the Heat Shrink over the Connector a. Slide heat shrink tubing over back of connector (see Figure 13). b. Using heat gun, shrink tubing on connector. HEAT SHRINK Figure 13 - Sliding the Heat Shrink over the Connector 7. Applying the Cable Label Apply the cable label to the approximate position shown in Figure 14. LABEL A OR B Figure 14 - Applying the Cable Label 8. Installing the Protective Cap Install the protective caps onto cable ends to protect the pin during storage and handling. 2-22 February 2003 SD39MODULNET-1 Installation 2.3.3.3 M-NET Cable Recommendations • Cable Strain Relief It is recommended that all M-NET cables be strain-relieved to minimize the stress on the F connector. This can be accomplished by ensuring that a short length of cable extending from the connector is straight. Figure 15 illustrates acceptable and unacceptable cable stress conditions. • Cable Bend Radius Excessive cable bending or kinks in cables have an effect on dielectric strength, possibly causing communication problems. The bend radius on the RG-11 cable should be equal to or greater than 7 inches. If it is impossible to meet the minimum cable bend radius because of limited space, it is recommended that a right-angle, F-style adapter be employed. For maximum reliability, the adapter should have a gold-plated pin. Adapters are available from Siemens (P/N 16056-663) or Gilbert Engineering Co., Inc (P/N 46288). 16056-663 STRAIGHT GOOD GOOD BAD Figure 15 - Sample Cable Stress Conditions • Connector Tightening Torque The proper tightening torque for an F-style connector is 20 to 30 in.-lbs. A 25in.-lb. torque wrench (P/N 16056-660) is available in Siemens Kit P/N 16056-653. If a torque wrench is not available, first make the connector finger-tight; then turn the connector an additional 1/8 turn clockwise with a wrench to approximate the torque. February 2003 2-23 Installation 2.3.4 SD39MODULNET-1 Drop Cable Installation 2.3.4.1 Drop Cable Installation Procedure Install MNET A and B drop cables as follows. Drop cable does not have the band marks that appear on trunk cable and may be cut to the needed length. 1. Refer to MODULNET documentation and the results of the MODULNET design in section 2.2 for the length of each drop cable. Each cable connects to a tap drop port on MNET A or MNET B and to a connector on an MBX transition board. Also note or confirm the following: • Tap ID and location (external or internal) • Number of MBXs to be connected to the taps including: • - The ID of all cabinets housing the MBXs and their locations. - The MODULRAC slot location of each MBX and its associated transition board that is assigned to the tap's drop port "number" Route of each drop cable and needed length 2. Route the first drop cable between the assigned tap and MBX transition board. Allow extra cable for connector installation and future servicing. Do not exceed the manufacturer's drop cable pulling force (45 lbs./20.4 kg.) during installation, especially when pulling cable through conduit. IMPORTANT Do not bend a cable around sharp corners. A drop cable has a minimum bend radius of 3 inches (8 cm). 3. Attach F-male connectors to both ends of each cut drop cable as shown in Figure 2–5 and in the section, Drop Cable Fabrication Procedure. Use the crimping tool recommended by the connector manufacturer. Tag each drop cable connector with the following: • Tap end of cable: Tap ID, drop port number, and MNET A or B ID. • Transition Board end of cable: Tap ID, MBX MODULRAC slot number, and MNET A or B ID. Connector kits listed in Table 1–2 contain connector and cable preparation instructions which are duplicated in section, Drop Cable Fabrication Procedure. 2-24 February 2003 SD39MODULNET-1 Installation 4. At the tap, thread the connector onto the drop port and hand tighten. Stress relieve the cable at the drop port and use a proper torque wrench to tighten coaxial connectors (cables and terminators). Use P/N 16056-660, 25 in.-lb. torque wrench for cables, included in Tool Kits 16056-652 and 16056653). If a proper torque wrench is not immediately available, approximate 25 in.-lb. by finger tightening, plus 1/8 turn for connectors and terminator without gaskets. 5. Terminate the free end of the drop cable as follows: If an MBX transition board is installed, refer to the MBX Installation and Service Instruction (see section 1.5 for Instruction identifier) to connect the drop cable to the MBX transition board connector. If an MBX transition board is not installed, terminate the drop cable in a 75 ohm terminator. 6. Repeat the preceding steps for each MNET A and B drop cable. IMPORTANT Be careful to connect the MBX transition board's MNET A connector to MNET A and the board's MNET B connector to MNET B. 2.3.4.2 Drop Cable Fabrication Procedure Follow steps 1 through 9 to fabricate the cables. Detailed procedures for each step are provided. 1. Initial Cable Preparation a. Slip ferrite bead over cable end (see Figure 1). b. Slip heat shrink tubing (gray) over ferrite bead. c. Use heat gun to shrink tubing over bead. d. Slip smaller heat shrink over cable end. For M-NET A, use white; for M-NET B, use black. HEAT SHRINK RG-6 QUAD SHIELD DROP CABLE CommScope P/N 5750 FERRITE BEAD WITH HEAT SHRINK COPPER-COATED STEEL CENTER CONDUCTOR F-CONNECTOR END Figure 1 - Initial Cable Preparation February 2003 2-25 Installation SD39MODULNET-1 2. Preparing the Cable End: a. Remove 5/16 inch of the cable jacket (see Figure 2). Be careful not to cut the braid. 5 16" Figure 2 - Removing the Cable Jacket b. Carefully fold back the outer braid over the jacket (see Figure 3). Figure 3 - Folding Back the Outer Braid c. Carefully peel off the outer foil after first making a small cut at the base of the foil at the end of the foil wrap (see Figure 4). PEEL OUTER FOIL SMALL CUT Figure 4 - Removing the Outer Foil d. Carefully fold back the inner braid over the outer braid (see Figure 5). Do not remove the inner foil. Figure 5 - Folding Back the Inner Braid e. Trim the dielectric and inner foil so that there is 3/32 inch protruding from the jacket (see Figure 6). Use a wire-stripping tool that is notched or can be adjusted so that the center conductor does not get nicked. The center conductor is 18 AWG; adjust the stripping tool to suit. 2-26 February 2003 SD39MODULNET-1 Installation 3 32" Figure 6 - Trimming the Dielectric f. Trim the center conductor (18 AWG copper-coated steel wire) so that there is only 1/16 inch protruding from the dielectric (see Figure 7). 1 16" Figure 7 - Trimming the Center Conductor 3. Crimping the Pin to the Center Conductor a. Insert the pin over the center connector so that the end of the pin is flush with the end of the dielectric (see Figure 8). PIN Figure 8 - Inserting the Pin over the Center Conductor b. Using the 0.054 hex of the Siemens Crimping Tool P/N 16056-413 (also reference: Gilbert P/N G-CRT-188), crimp the pin to the center conductor (see Figure 9). CROSS-SECTION OF CRIMPER JAW Figure 9 - Crimping the Pin to the Center Conductor February 2003 2-27 Installation SD39MODULNET-1 4. Inserting Cable into Connector: a. Insert the cable into the Siemens F-connector, P/N 14784-500 (also reference Gilbert F-Style Connector P/N 70070) (see Figure 10). G IL B E R T F -S T Y L E C O N N E C T O R P /N 7 0 0 7 0 S ie m e n s P /N 1 4 7 8 4 -5 0 0 3 3 2" M IN Figure 10 - Inserting Cable into Connector b. Check to see that cable insertion is complete by determining that the pin protrudes a minimum of 3/32 in. past the end of the connector (see Figure 11). Use the F-connector pin gauge provided. CHECK WITH 32" F-CONNECTOR PIN GAUGE Siemens P/N 16056-648 3 Figure 11 - Checking Cable Insertion 5. Crimping the Connector onto the Cable: Crimp the connector onto the cable using the 0.324 hex on the Siemens Crimping Tool P/N 16056413 (reference also Gilbert P/N G-CRT-188) (see Figure 12). CRIMP WITH 0.324 HEX Figure 12 - Crimping the Connector onto the Cable NOTE The jaws of the crimping tool must close fully to effect a good crimp. As the jaws close, the handles can be felt to toggle over center. 2-28 February 2003 SD39MODULNET-1 Installation 6. Sliding Heat Shrink over Connector: a. Slide heat shrink tubing over back of connector (see Figure 13). b. Using heat gun, shrink tubing on connector. HEAT SHRINK Figure 13 - Sliding the Heat Shrink Tubing over the Connector 7. Applying the Cable Label: Apply the cable label to the approximate position shown in Figure 14. LABEL A OR B Figure 14 - Applying the Cable Label 8. Positioning the Ferrite Bead: Slide the ferrite bead along the cable so that it is as close to the cable end as possible (see Figure 14). 9. Installing the Protective Cap: Install the protective caps onto cable ends to protect the pin during storage and handling. February 2003 2-29 Installation SD39MODULNET-1 2.3.4.3 M-NET Cable Recommendations • Cable Strain Relief It is recommended that all M-NET cables be strain-relieved to minimize the stress on the F connector. This can be accomplished by ensuring that a short length of cable extending from the connector is straight. A good “rule of thumb” is: make sure that the section of cable between the connector and the ferrite bead, which are on each end of most cables, is straight. Figure 15 illustrates acceptable and unacceptable cable stress conditions. • Cable Bend Radius Excessive cable bending or kinks in cables have an effect on dielectric strength, possibly causing communications problems. The bend radius on the RG-6 cable should be equal to or greater than 3 inches. If it is impossible to meet the minimum cable bend radius because of limited space, it is recommended that a right-angle, F-style adapter be employed. For maximum reliability, the adapter should have a gold-plated pin. Adapters are available from Siemens (P/N 16056-663) or Gilbert Engineering Co., Inc (P/N 46288). 16056-663 STRAIGHT FERRITE BEAD FERRITE BEAD FERRITE BEAD GOOD GOOD BAD Figure 15 - Sample Cable Stress Conditions • Connector Tightening Torque The proper tightening torque for an F-style connector is 20 to 30 in.-lbs. A 25 in.-lb. torque wrench (P/N 16056-660) is available in Siemens Kit P/N 16056-652. If a torque wrench is not available, first make the connector finger-tight; then turn the connector an additional 1/8 turn clockwise with a wrench to approximate the torque. 2-30 February 2003 SD39MODULNET-1 2.3.5 Installation MODULNET Testing A carrierband tester and an auxiliary signal generator are used to perform these tests. Appendix B contains a MODULNET Signal Log to record calculated and measured signal levels. Make as many copies of the Log as necessary to document MNET A and B. An MBX connected to the MODULNET must be in the powered-down state to eliminate signals on the network during test measurements. NOTE As tests are performed, record all conditions and performance data for future use when servicing the MODULNET. These specifications apply to the test procedures in this section. • Test signal and data rate = 10 MHz at 5 Mb/s (megabits/second) • Signal sweep bandwidth = 1 to 30 MHz. • Return loss measurement units = dB (decibels) • Noise and signal level measurement units = dBmV (0 dB = 1 mV) 2.3.5.1 Trunk Return Loss Measurement Repeat the following procedure for trunk A and trunk B. Refer to the carrierband tester's operating instructions as necessary. 1. In preparation for testing the MODULNET: Check all taps to be sure that every port has either a cable or a 75 ohm termination installed. Check that every drop cable is either connected to an MBX termination board (MBX must be installed) or to a 75 ohm terminator. 2. Fabricate an extension cable. Cut a 2.6 meter length of cable from the reel of cable used for the trunk and install two F connectors. 3. At one end of MNET A, remove the 75 ohm termination from the tap's trunk port. Connect the extension cable between the carrierband tester's Transmit-Port and the trunk port. 4. Measure the return loss. Specification: -22 dB or greater at 5 Mb/s. Disconnect the cable and install the termination. 5. Repeat the test from the other end of the trunk. February 2003 2-31 Installation SD39MODULNET-1 If the return loss is within specification, leave the carrierband tester connected and proceed to section 2.3.5.2. If the specification is not met, either a tap or cable segment is defective. Isolate the defect as follows: • Remove the extension cable from the near end-of-trunk tap and terminate the tap's trunk port. • Disconnect the trunk cable from one of the trunk ports on a tap located in the middle of the network. • Test both halves of the trunk to determine the defective half. If a trunk half consists of three taps or less, the return loss should be -24 dB or greater. • Repeatedly divide and test the defective trunk until the defective tap or cable segment is located. • Repair as necessary. • Inspect network to ensure that all cables and terminators have been installed. 2.3.5.2 Trunk Noise Level Measurement Repeat the following procedure for trunk A and trunk B: 1. Ensure the far end-of-trunk tap's trunk port is terminated. 2. If not already connected, connect the carrierband tester to the near end-of-trunk tap. Connect the 2.6 meter extension cable to the tester's Receive-Port. 3. Wait for approximately one minute and read the noise level. Specification: +10 dBmV or less. 4. Disconnect the tester and install the terminator. 5. Repeat the test from the other end of the trunk. If the noise level is within specification, disconnect the tester and terminate the tap trunk port. Proceed to section 2.3.5.3. If the noise level does not meet specification, a cable routing or grounding problem probably exists. 2-32 • Inspect the cable routing for noise sources that may have been overlooked when the original site drawings where approved. Rerouting may be necessary. • Check for a ground problem by disconnecting, one tap at a time, a tap's safety ground wire. When the wire is floating, the noise level should increase indicating the safety ground is of good quality. Little or no increase of noise can indicate a poor quality ground. In this case, search for a better safety ground. February 2003 SD39MODULNET-1 Installation 2.3.5.3 Drop Cable-to-Tap Return Loss Measurement Repeat the procedure for each drop cable. 1. At each MBX transition board, either disconnect the 75 ohm terminator from MNET A drop cable or disconnect the MNET A drop cable from the MBX transition board. Connect the drop cable to the carrierband tester's Transmit-Port. 2. Measure the return loss. Specification: -14 dB or greater at 5 Mb/s. Record each measurement for future use as a service reference. Terminate the tested cable before proceeding to the next cable. If measurements are within specification, proceed to section 2.3.5.4. If a return loss measurement is not acceptable, disconnect the drop cable from the tap and terminate the cable using a coupler/splice. Test the cable for a minimum return loss of -26 dB. If the return loss is acceptable, the drop cable is good and the tap is defective. 3. Reconnect or terminate the drop cable. 2.3.5.4 Drop Cable Noise Level Measurement This measurement should be made on each drop cable that is routed through a noisy area. 1. At the MBX transition board, either disconnect the 75 ohm terminator from MNET A drop cable or disconnect the MNET A drop cable from the MBX transition board. Connect the drop cable to the carrierband tester's Transmit-Port. 2. Connect a jumper wire from the cable's F connector on the carrierband tester to the F connector's threaded barrel on the MBX Transition Board to preserve the cable shield ground. 3. Wait for approximately one minute and read the noise level. Specification: -10 dBmV minimum. If the noise level is acceptable, reconnect or terminate the drop cable and proceed to section 2.3.5.5. If the noise level is not acceptable, a new drop cable route may be required. 2.3.5.5 Signal Level Measurement A signal level measurement is the final confirmation that the connected MODULNET hardware will perform as expected. Figure 2–6 shows a sample MNET with typical signal levels. The test procedure will use an auxiliary signal generator, a standard accessory for a carrierband tester, to simulate an MBX. Reference Measurement: 1. Using the signal attenuation numbers given in section 1.2 Specifications for cables and taps, calculate the expected signal level (-dB) at the MBX transition board end of each drop cable. February 2003 2-33 Installation SD39MODULNET-1 Assume that the signal reference is the MBX transition board end of the drop cable that is connected to the tap drop port closest to one end of the network. For example, in Figure 2–6, the signal reference (i.e., signal generator) would substitute for MBX 1. 2. With the tester, measure the generator's non-adjustable output signal level (10 MHz at 5 Mb/sec = +66 +/-2 dBmV). Use this measured signal level when performing the MODULNET signal analysis. 2-34 February 2003 SD39MODULNET-1 Installation Figure 2–6 Network Signal Level Analysis Example February 2003 2-35 Installation SD39MODULNET-1 Network Measurement: Repeat the following test procedure for trunk A and trunk B. 1. At the signal reference point (MBX transition board) selected above, either disconnect the 75 ohm terminator from MNET A drop cable or disconnect the MNET A drop cable from the MBX transition board. 2. Connect the drop cable to the auxiliary signal generator. Select a 10 MHz/5 Mb/s signal. 3. Connect a ground jumper wire from the drop cable's F connector on the generator to the F connector's threaded barrel on the MBX Transition Board to preserve cable shield ground. 4. At the next down-the-line MBX Transition Board, either disconnect the 75 ohm terminator from MNET A drop cable or disconnect the MNET A drop cable from the MBX transition board. 5. Connect the drop cable to the carrierband tester's Receive-Port. 6. Connect a ground jumper wire from the drop cable's F connector on the tester to the F connector's threaded barrel on the MBX Transition Board to preserve the cable shield ground. 7. Measure the received signal level and compare it with the calculated signal. If the measured signal level is acceptable, reconnect the drop cable or install the terminator. If a unacceptable measurement is encountered, determine the cause before proceeding. To locate a fault: • Backtrack through the network toward the signal source (signal generator) by moving the carrierband tester and making signal level measurements. • Compare the calculated (expected) signal levels for each tap's trunk and drop ports to the measured signal levels. 8. Continue the test at the remaining MBX locations along trunk A. Repeat steps 4 through 7 until all MNET A MBX locations are tested. 9. When the trunk A test is completed, remove all test equipment. Repeat the test on trunk B. After verification of MODULNET A and B, remove all test equipment and terminators from all drop cables. Proceed to section 2.3.5.6. 2.3.5.6 Cable Sealing and Boots Perform the following steps at each end of each drop cable. 1. Disconnect the drop cable from the tap or MBX transition board. 2-36 February 2003 SD39MODULNET-1 Installation 2. Seal the trunk and drop cable connectors with gel tape if the environment is hostile. Otherwise, use heat shrinkable boots or sleeves to seal the drop cable connectors. Heat shrinkable boots are packaged in connector kits. White boots ..... MNET A Black boots ..... MNET B 3. At each tap and MBX transition board, thread the drop cable connector onto its assigned MNET A or B connector. Stress relieve the cable and firmly tighten the connector with a 1/2" open end wrench. If an MBX transition board is not installed, thread a Dropsaver into the unconnected end of the drop cable to protect the connector. Connect the cable after its associated MBX transition board is installed. " February 2003 2-37 Installation SD39MODULNET-1 !Notes 2-38 February 2003 SD39MODULNET-1 3.0 Circuit Description Circuit Description The MODULNET is a local area network (see Figure 1–1). It has two independent, redundant cable systems (MNET A and B). The IEEE 802.4 Token Bus standard is the MODULNET protocol. As such, it uses a deterministic access method to control which node (i.e., APACS+ MODULBUS Expander Module or other controller or computer) has the right to transmit. Every node is assured the right to transmit within a specified period of time. MODULNET uses a single-channel carrierband technology. The type of carrierband signaling used is based on a phase-coherent modulation technique that is a form of frequency-shift keying (FSK). The signal consists of a two frequency data stream with a one-zero pattern. The lower frequency is 5 MHz and is equal to 1 cycle per bit time (logic 1); the higher frequency is 10 MHz and is equal to 2 cycles per bit time (logic 0). System data rate is 5-Mbit/s. Signals originate in and are received by MODULBUS Expander Modules (MBXs). A MODULNET carries MODULBUS communications between autonomous clusters of controllers and I/O modules known as Local Area Systems (LASs) that are distributed throughout the factory. MODULNET traffic is primarily short messages pertaining to status and control that must occur on a realtime basis. " February 2003 3-1 Circuit Description SD39MODULNET-1 !Notes 3-2 February 2003 SD39MODULNET-1 4.0 Maintenance Maintenance The MODULNET trunk and drop cables and taps require minimal maintenance. Some routine maintenance is recommended in the form of a visual inspection. 4.1 Tool and Equipment Requirements The following tools and equipment are necessary for servicing: • Common electronic servicing hand tools • Carrierband Network Tester (see section 2.3.1). 4.2 Visual Inspection The MODULNET should be subjected to a periodic visual inspection. The frequency of inspection is dependent upon the severity of the environment. Inspect the MODULNET in accordance with the following check list. Refer to section 4.4 if inspection reveals a damaged tap or cable segment. MNET A/B Taps 1. Check each tap's mounting for secure mounting and proper grounding. 2. Check each tap for cracks or other signs of damage. Replace tap if necessary. 3. Check the tap ground wire connection for tightness. Ensure the opposite end of the ground wire connection is tight. 4. Ensure all unused tap ports are terminated and all terminations are tight. 5. Check all cable connectors for proper tightness. Check connector tightness with a 25 lb-in torque wrench. 6. Ensure that the environmental protection of all cable connectors (connector boots or gel tape) are intact and are effective. Replace any defective protective component. MNET A/B Trunk Cable 1. Check each cable segment for any signs of visible damage such as abrasion, cracks, or tears in the cable jacket. Check for an "out-of-round" cable section. An "out-of-round" section is an indication the cable was crushed. Replace a cable segment with any such defects. 2. At points where a trunk cable enters a building, check the cable jacket for cracks or signs of deterioration. Replace a cable segment with any such defects. February 2003 4-1 Maintenance SD39MODULNET-1 3. Trunk cables routed above the ground, especially in out-of-doors cable runs, should be checked for cable jacket defects (cracks and tears) and installation security. Replace a cable with jacket defects. If a messenger wire is used, check its condition. MNET A/B Drop Cable 1. Check each drop cable between its tap and MBX transition board for any signs of visible damage such as cracks or tears in the cable jacket or an "out-of-round" section of the cable. An "out-ofround" section is an indication the cable was crushed. Replace a drop cable with any such defects. 2. Check each drop cable connector for proper tightness. Check connector tightness with a 25 lb-in torque wrench. 4.3 MODULNET Troubleshooting Review the following troubleshooting suggestions if a MODULNET appears to be malfunctioning. The first step in troubleshooting MBUS/MNET communications is to specify the symptoms that indicate a communications problem. Identify these symptoms using the checklist provided below. Each symptom is identified with an alphabetic letter so that it may be associated with the specific faults discussed. Space is provided to list specific details for the symptoms seen (station numbers; error codes; frequency of occurrence; etc. Symptoms: Details: A. Poor, or slow communication performance B. Some station(s) unreachable C. Intermittent connection to station(s) D. Communication errors E. Other The specific faults discussed below are grouped (High, Medium, and Low) according to the likelihood of finding them in any given system, based on troubleshooting experience. HIGH 1. (A, B) Cable lengths exceed maximum allowed Check cable length. (Use calculation technique in: Installation and Service Instruction, SD39MODULNET-1) Measured Length: Calculated Length: 2. (C, D) Loose MNET drop cable crimps Check connector assembly on cable is secure. Cables labeled with date codes between 9847 and 0009 (without a second label, reading “OK-date” indicating that they have been checked), have a higher probability of problems. Re-crimp or replace all cables with date codes and/or those that appear loose. (See: Service Memo SM39MNET-1, Kit Instructions 4-2 February 2003 SD39MODULNET-1 Maintenance 15900-553 and –554. Use connector installation tool kits: RG6, P/N 16056-652; RG-11, P/N 16056-653). 3. (C, D) Tight bends in MBUS and MNET cables. Replace cables that are bent too tightly – minimum bend radii: 3 inches for MBUS and RG-6 drop cable, 7 inches for RG-11 trunk cable. For tight MNET installations, use a right-angle adapter, P/N 16056-663 (see Instructions 15900-553 and -554). Tight bend radii can cause permanent damage to the MNET cable dielectric. 4. (C, D) Un-terminated trunk or drop port Make sure that there are 75-ohm terminators (Siemens P/N 14753-2, Gilbert P/N 43933 (remove gasket), or Gilbert P/N 26560) on all MNET tap ports that do not connect to a cable. An unused trunk port indicates one end of MNET and must be terminated. Failing to terminate the trunk will cause serious degradation of the MNET signal. Unused drop ports should also be terminated although the effect of an un-terminated port is not as severe. 5. (C, D) Loose coaxial connectors Use a proper torque wrench to tighten all coaxial connectors (cables and terminators). Use P/N 16056-660, 25 in.-lb. torque wrench for cables, included in Tool Kits 16056-652 and 16056653. If a proper torque wrench is not immediately available, approximate 25 in.-lb. by finger tightening, plus 1/8 turn for connectors and terminator without gaskets. Be sure to relieve any strain the cable may exert on the connector while tightening. Insufficient torque can result in a poor connection; excessive force can result in damage to hardware. 6. (C, D) Insecure MNET tap connection to mounting plate/cabinet. Verify that all MNET taps are firmly secured to a mounting plate which is firmly attached to the cabinet thus providing a good ground. The taps use a mounting stud for connection to the mounting plate and an index hole to prevent rotation. (See Kit Instruction 15900-256). The mounting stud is the ground connection for the tap. Failure to ground the tap also leaves the coaxial cable ungrounded. A tap that is loose and can rotate does not have a good ground connection! 7. (C, D) Both ends of a cable segment connected to T1 ports Make sure that all MNET taps are cabled from T1 on the first tap to T2 on the next tap (not T1 to T1 or T2 to T2). MNET uses a segmented ground for the coaxial cable. The trunk port labeled ‘T2’ is grounded. The ‘T1’ port is isolated from ground. Connecting both ends of a cable segment to T1 ports fails to ground the cable. Connecting both ends to T2 ports creates a ground loop. 8. (B, C, D) Mismatched connectors Make sure that all MBUS and IOBUS cable connectors and associated backplane connector use the same method of securing the cable. That is: spring-lock to spring-lock or screwlock to screw-lock. (See Kit Instruction 15900-558). Mismatched connectors can cause intermittent operation. February 2003 4-3 Maintenance SD39MODULNET-1 MEDIUM 9. (B) Distortion/damage of MBUS extension cables at connector ends Replace all MBUS Extension cables showing signs of distortion or damage at the connector ends. 10. (C, D) Cables with damaged connectors Strain-relieve all MNET/MBUS cables. Replace any cables with signs of connector damage. (See MNET Kit Instructions 15900553 and -554). Excess force on the cables may result in cable or connector failure. 11. (C, D) Low grade computer cable Replace all MNET cables that are not made from high grade computer data cable. Suitable cable will be stamped “802.4” (for IEEE Specification 802.4) and use data-grade connectors. (See: Installation and Service Instruction, SD39MODULNET-1 for information on appropriate cable and connector parts.) One indication of a data grade connector is a smoothly tapered gold pin crimped to the copper center conductor. A bare, cut copper wire used as a center pin can damage other components and must not be used. Cables and connectors designed for cable TV or other analog applications should never be used for MNET! 12. (C, D) Improperly grounded APACS+ system Verify that the entire APACS+ system is properly grounded (See Installation and Service Instruction, SD39GND-1). Improper grounding can cause ground loops, which can cause noise. 13. (B, C, D) Modules not tightly attached to the MODULRAC Make sure that all modules are screwed down tight to the MODULRAC and sit evenly in the rack. Check that it is flat across the bezel of all modules. Misalignment of the bezels indicates some form of assembly problem and can result in intermittent backplane connections. 14. (B, C, D) Damaged MNI card Replace all older MNI cards with the new mounting design. (Service Memo SM39MNI-1; Kit Instruction 15900-544). On older units, the MNI card could be damaged if excess stress is applied to the connector by over-tightening or by cables not properly strain-relieved. 15. (B, C, D) Bent pins in upper / lower backplane connectors. Verify that no modules (controller and IO modules) have bent pins in the upper and lower backplane connectors. A bent pin in the upper connector, P1 (even for IO Modules), can cause MBUS faults. Bent pins in the lower connector, P2, can result in MBUS faults by causing misalignment of the module. 4-4 February 2003 SD39MODULNET-1 Maintenance LOW 16. (C, D) Poorly lubricated MBUS / MNET connections Lubricate all MBUS/MNET connections or confirm recent lubrication of all connectors(Kit Instruction 15900-394, included with the lubricant kit, P/N 14850-121). Lubrication protects the contacts from harsh environments and fretting corrosion. 17. (C, D) Unreliable connection of MNET tap to the terminator caused by rubber gasket Remove the rubber gasket from all MNET terminators (See Service Note SN39MNET-1). 18. (C, D) Dangling terminator contacting a grounded object When adding a trunk cable to a previously terminated T1 port on a tap, completely remove the MNET terminator and chain from the T1 side of the taps before installing the cable. (See Installation and Service Instruction, SD39MODULNET-1). If the dangling terminator touches any grounded object, it can cause a ground loop by grounding the isolated tap trunk port, T1. 19. (C, D) A bowed MODULRAC backplane Check for bowed backplates on ten-slot MODULRACs using Inspection Tool P/N 16114-171-T1. (See Service Memo SM39MODULRAC-4). A bowed MODULRAC backplane can cause intermittent connections with modules in the center of the MODULRAC. 20. (A, B, D) Improperly crimped coaxial cables Replace all “noisy” MBX modules (See Service Memo SM39MODULNET-3). Some coaxial cables within older MBXs are not crimped properly resulting in an intermittent connection. 21. (C, D) Loose mounting screws on MBX transition boards Make sure that both mounting screws for MBX transition boards are snug (See Installation and Service Instruction, SD39MBX-1). Each screw acts as a ground for one side of the MNET. 22. (C, D) Insufficient reinforcement for the cable connector Replace all older MBX Transition boards with the new design. (See Service Memo SM39MBX-3). The new design provides additional reinforcement for the cable connector. 23. After making any physical change to the communications network, re-check the system to assure that these guidelines are met. 4.3.1 Advance Diagnostics Techniques Beyond this checklist In nearly all cases, the detailed inspection techniques reviewed in this checklist can quickly identify the source of performance problems with MBUS/MNET communication. Many times, additional deficiencies are uncovered during the inspection that are not yet causing problems but can reduce system reliability in the future. For these reasons, we strongly encourage all APACS+ system users to follow these checklists both when attempting to resolve performance problems and as a preventative step to assure trouble-free operation. February 2003 4-5 Maintenance SD39MODULNET-1 For a variety of reasons, users may wish to have Siemens field support engineers participate in the investigation of performance issues as well as preventive maintenance activities. The field support engineers follow a procedure that includes all of the inspection steps listed in this checklist. In addition, all field support engineers are trained in the low level operation of the MBUS/MNET communication system. At times they may use advanced diagnostic tools to view information on the low level operation. These tools include: • A protocol level event logger developed exclusively for MBUS/MNET (“Mbus Analyzer”); • An MNET signal analyzer for operating systems (Carrier Band Monitor); • An MNET cable tester designed for IEEE 802.4 communication systems (Carrier Band Tester) and; • General purpose cable testing instruments (Time Domain Reflectometer); In the hands of trained and experience field support engineers, these tools can often pinpoint faults quicker and with more assurance than less sophisticated techniques. However, due to the level of training and knowledge required, Siemens supports the use to these advanced tools only by members of the Siemens technical support groups. Use of advanced diagnostic tools will be at the discretion of Siemens technical support agents involved in specific investigations. Completing the inspections reviewed in this checklist is an essential part of every investigation and should be completed before any other measures are considered. 4.4 MODULNET Testing The validation procedure in section 2.3.5 can also be used to locate a damaged cable section, a failed tap, or a failed termination. Troubleshooting involves comparing previously calculated and measured signal levels with a new set of measurements to be recorded. The first recorded signal levels should reflect the initial installation. Appendix B contains a MODULNET Signal Log. Copy the Log as many times as necessary to document MNET A and B. IMPORTANT A new set of calculated and measured signal levels should be recorded each time a MODULNET is revised or repaired (e.g., cables rerouted, MBXs added, cable section replaced). Perform the procedures under section 4.3 to troubleshoot the MODULNET. See section 2.3.5 for a carrierband tester. A time domain reflectometer can be substituted for the carrierband tester, however, it is more complex to operate. 4-6 February 2003 SD39MODULNET-1 4.5 Maintenance Tap or Cable Segment Replacement If inspection or troubleshooting reveals a damaged tap or cable segment, refer to section 2.3 Tap and Cable Installation and the following. • When replacing a trunk or drop cable segment, be sure to perform all cable installation assembly. • When replacing a tap, refer to the tap installation procedure. • Completely test the repaired MODULNET and record the results of all tests. Compare them to previously recorded (e.g., original installation) values. Save all test records for comparison with future tests. 4.6 Spare and Replacement Parts One spare Tap of each type used and one spare 75 Ohm F-Type Termination should be stocked for every 1 to 5 in service. Spare and replacement parts can be ordered from one of the addresses in the Warranty statement or through a local Moore Products Co. representative. Part numbers are stated in section 1. 4.7 Return of Shipment Within North America To return a shipment, call the Siemens Repair Order Group at +1 215 646 7400, ext. 4RMA (4762) weekdays between 8:00 a.m. and 4:45 p.m. eastern time to obtain a Return Materials Authorization (RMA) number. Mark the RMA number prominently on the outside of the return shipment. When calling for an RMA number, provide the reason for the return. If returning equipment for repair, failure information (e.g. error code, failure symptom, operating environment) will be requested. You will need to supply a purchase order number for repairs. A Material Safety Data Sheet (MSDS) must be included with each item being returned that was stored or used where hazardous materials were present. The equipment must be thoroughly cleaned (decontaminated) to remove any hazardous material prior to return for inspection or repair. The MSDS must be placed in the container so that it can be read before handling the equipment Package the assembly in original shipping materials; otherwise, package it for safe shipment or contact the Repair Order Group for shipping recommendations. A module must be placed in a static shielding bag to protect it from electrostatic discharge. Outside North America Contact the appropriate Siemens subsidiary. Provide the reason for the return. For repairs, supply a purchase order number. Request equipment packaging and shipping instructions. " February 2003 4-7 Maintenance SD39MODULNET-1 !Notes 4-8 February 2003 WARRANTY The Company warrants all equipment manufactured by it and bearing its nameplate, and all repairs made by it, to be free from defects in material and workmanship under normal use and service. If any part of the equipment herein described, and sold by the Company, proves to be defective in material or workmanship and if such part is within twelve months from date of shipment from the Company’s factory, returned to such factory, transportation charges prepaid, and if the same is found by the Company to be defective in material or workmanship, it will be replaced or repaired, free of charge, f.o.b. Company’s factory. The Company assumes no liability for the consequence of its use or misuse by Purchaser, his employees or others. A defect in the meaning of this warranty in any part of said equipment shall not, when such part is capable of being renewed, repaired or replaced, operate to condemn such equipment. This warranty is expressly in lieu of all other warranties, guaranties, obligations, or liabilities, expressed or implied by the Company or its representatives. All statutory or implied warranties other than title are hereby expressly negated and excluded. Warranty repair or replacement requires the equipment to be returned to one of the following addresses: Siemens Energy & Automation, Inc. 1201 Sumneytown Pike, P.O. Box 900 Spring House, PA 19477-0900 U.S.A. Tel: +1 215 646 7400 Fax: +1 215 283 6340 Siemens Moore Process Automation (Canada) Inc. P.O. Box 370 2719 Highway 7 West Brampton Ontario L6V 2L3 Canada Tel. (905) 457 9638 Fax (905) 457-4182 Fax (905) 457-6499 Siemens Moore Process Automation Copse Road Lufton Yeovil, Somerset BA22 8RN England, UK Tel. (44 1935) 706262 Fax (44 1935) 706969 Moore Process Automation Solutions (Italia) S.r.l.Via S. Aleramo 2 20063 Cernusco sul Naviglio Milano, Italy Tel. (39) 02 9290541 Fax (39) 02 92905454 SIEMENS Nederland NV Siemens Advanced Engineering Pte Ltd A & D AS PAS CoC/A&D PI1/PI5 CoC 2 Kallang Sector 5th Floor Singapore 349277 Tel. +65 740 7700 Fax +65 740 7817 TIC Singapore Tel: (65) 7407842 Prinses Beatrixlaan 26 NL-2595 AL Den Haag P.O. Box 16068 NL-2500 BB Den Haag Tel. +31 (0)70 333 1201 Fax +31 (0)70 333 3885 The warranty will be null and void if repair is attempted without authorization by a member of the Siemens Energy & Automation, Inc., Service Department. " Siemens Energy & Automation INSTALLATION AND SERVICE INSTRUCTION ADDENDUM CSA HAZARDOUS LOCATIONS PRECAUTIONS SDA-CSA-1 Issue: 1 Date: 11/88 INTRODUCTION This addendum provides CSA hazardous location precautions that should be observed by the user when installing or servicing the equipment described in the accompanying Instruction. These statements supplement those given in the accompanying Instruction. WARNING Failure to observe the following precautions could result in an explosion hazard. PRECAUTIONS For Class I, Division 1 and Class I, Division 2 hazardous locations: – Use only factory authorized replacement parts. Substitution of components can impair the suitability of this equipment for hazardous locations. For Division 2 hazardous locations: When the equipment described in the accompanying Instruction is installed without safety barriers, the following precautions should be observed. Switch off electrical power at its source (in non-hazardous location) before: – Connecting or disconnecting power, signal, or other wiring – Replacing a fuse, circuit board, or any other component connected to the electrical circuit. This completes the precautions. Service Publications Group Siemens Energy & Automation Addendum a la notice d’installation et de depannage. Précautions relatives aux emplacements dangereux définis par la CSA INTRODUCTION Cet addendum indique les précautions relatives aux emplacements dangereux définis par la CSA que doit prendre l’utilisateur lors de l’installation ou du dépannage de l’appareil décrit dans la notice ci-jointe. Ces directives completent celles qui sont données dans la notice ci-jointe. AVERTISSEMENT Si les précautions suivantes ne sont pas prises il pourrait résulter un danger d’explosion. PRÉCAUTIONS Emplacements dangereux de classe I, division 1 et classe I, division 2: Les pièces de rechange doivent être autorisées par l’usine. Les substitutions peuvent rendre cet appareil impropre à l’utilisation dans les emplacements dangereux. Emplacements dangereux de division 2: Lorsque l’appareil décrit dans la notice ci-jointe est installé sans barrieres de securité, on doit couper l’alimentation électrique à la source (hors de l’emplacement dangereux) avant d’effectuer les opérations suivantes: – branchement ou débranchement d’un circuit de puissance, de signalisation ou autre. – Remplacement d’un fusible, d’une carte de circuit imprimé ou de tout autre élément connecté au circuit électrique. Ceci termine la section Précautions.
© Copyright 2026 Paperzz