Fire Performance Evaluation of Nominal K=5.6 Ceiling Sprinklers For Protecting 8-Ft. High Storage of Paper Files in Compact Mobile Shelving Under a 10-Ft. Ceiling Technical Report Underwriters Laboratories Inc. Project 07CA64050, NC5756 for the Fire Protection Research Foundation April 25, 2008 Copyright © 2008, Underwriters Laboratories Inc. NC5756 07CA64050 Issued: 04/25/2008 EXECUTIVE SUMMARY A series of five (5) bench-scale and two (2) large-scale fire tests was conducted to develop data regarding the level of protection provided by nominal K-5.6 (gpm/psi ½) pendent, quick response ceiling sprinklers in protecting an arrangement of paper in standard manila paperboard folders stored in moveable compact mobile shelving units to a nominal height of 8- ft. Bench-scale testing consisted of a single 36-in x 24-in x 9.75-in sheet metal shelf loaded with varying densities of commodity. A total of five bench-scale fire tests were conducted on a load cell beneath a calorimeter where total heat release rate was measured over the course of each test. Based on the results of these bench-scale tests, the project consulting engineers determined that a 70% loading density by volume would be used as the basis for both large-scale fire tests. The tests were conducted under a 10- ft high ceiling with 155°F pendent ceiling sprinklers installed on 15 by 15-ft. spacing with the deflectors positioned 8- in. below the ceiling. The first large-scale test was conducted with the moveable compact mobile shelving units in the open position, including a 3- ft. center aisle. The second large-scale test was conducted with the moveable compact mobile shelving units in the closed position, and included full- height longitudinal sheet metal barriers in two of the four 24- in deep moveable shelving units. For both large-scale tests, the ceiling sprinkler system was supplied with water resulting in a nominal sprinkler discharge density of 0.10 gpm/ft2 . The ignition location for each of the two tests was located between four sprinklers. The large-scale fire tests utilized both moveable and fixed compact shelf units. The individual shelving fixtures in the moving units of the systems were nominally 3- ft wide, 2- ft deep, and 8- ft tall. Vertical transverse sheet metal barriers were provided between each of the five (5) storage bays at 3- ft. intervals. There were eight (8) shelf levels positioned with a nominal vertical spacing of 8, 18.5, 29, 39.5, 50, 60.5, 71, 81.5 and 95-in. from the floor. There were five (5) shelf fixtures in each row with a total length of 15- ft. For the first large-scale fire test, an open shelving arrangement was used consisting of six compact shelf units. Five of the compact shelf units were moveable. Four of the moveable units were approximately 24-in. deep and one moveable unit was approximately 12- in. deep. The sixth compact shelf unit was fixed and approximately 12- in. deep. The compact shelf configuration was open with a 36-in aisle space provided in the center of the array. No longitudinal barriers were provided. The target arrangement consisted of cardboard fixed to upright structures. The paper- faced cardboard was positioned across a 36- in. aisle space on the north, south, east and west sides of the compact shelving array. The cardboard affixed to the target assembly spanned 16- ft. long x 8- ft high. The first large-scale fire test was conducted for 90 minutes (90:00) as requested by the project consulting engineers. A total of thirteen (13) ceiling sprinklers operated during the 90-minute test period. The fire in Test 1 propagated to the east, west and south ends of the main shelving array. However, the fire was contained within the main shelving units and did not spread to the adjacent targets. 1 NC5756 07CA64050 Issued: 04/25/2008 For the second large-scale fire test, a closed shelving arrangement was used consisting of five moveable compact shelf units in the main array and one fixed compact unit as a target. Four of the moveable units were approximately 24- in. deep and one unit was approximately 12- in. deep. Full height longitudinal sheet metal barriers were installed in two of the four 24- in deep moveable units. The sixth compact shelf unit was a target which consisted of a 12- in. deep compact shelving unit positioned across a 36-in aisle on the north side, filled to the same capacity of the main shelving array. Cardboard fixed to upright structures were also placed across a 36- in. aisle space on the south, east and west sides of the compact shelving array. The cardboard target assemblies spanned 16- ft. long x 8- ft. high. The second large-scale fire test was conducted for 82 minutes (82:00) as requested by the project consulting engineers. A total of four (4) ceiling sprinklers operated during the 82-minute test period. The fire in Test 2 propagated to the east and west ends of the array, but was generally limited to the area between the full- height longitudinal sheet metal barriers. The fire was contained within the main shelving units and did not spread to the adjacent target arrays. A summary of the parameters and results is presented in Table E1. 2 NC5756 07CA64050 Issued: 04/25/2008 FIRE TEST DATE Test Code 01/11/2008 01110802 01/18/2008 01180802 Compact Mobile Shelving Compact Mobile Shelving Parameters Storage Type Shelving Array Configuration Open Closed Commodity Type Paper in manila folders with 70% loading density Paper in manila folders with 70% loading density Nominal Storage Height (ft) 8 8 Nominal Ceiling Height (ft) 10 10 Deflector Clearance to Storage (in) 18 18 Aisle Width (in.) 36 36 Shelf Type Solid Steel Solid Steel Longitudinal Barrier None Solid Steel Transverse Barrier Solid Steel Solid Steel Nominal Shelf Depth (in.) 24 24 Ignition Location Beneath Walkway Sprinklers Between 4 Sprinklers Between 4 Sprinklers Ceiling Sprinkler Temperature Rating °F 155 155 Deflector to Ceiling (in) 8 8 Nominal Ceiling Sprinkler Discharge Coefficient K (gpm/psi ½) 5.6 5.6 Nominal Ceiling Sprinkler Discharge Pressure (psi) 16.1 16.1 2 Nominal Ceiling Sprinkler Discharge Density (gpm/ft ) 0.10 0.10 Ceiling Sprinkler Spacing (ft x ft) 15 x 15 15 x 15 Ambient Outdoor Temperature (°F) 35.4 21.7 Length of Test (min:s) 90 82 First Ceiling Sprinkler Operation (min:s) 36:09 81:11 Last Ceiling Sprinkler Operation (min:s) 85:58 81:51 Number of Operated Ceiling Sprinklers 13 4 Peak Gas Temperature at Ceiling Above Ignition °F 1551 1585 Maximum 1 Minute Average Gas Temperature at Ceiling Above Ignition °F 1460 1560 Peak Steel Temperature at Ceiling Above Ignition °F 1063 928 Maximum 1 Minute Average Steel Temperature Above Ignition °F 902 846 Fire Spread Across Aisle Yes No Fire Spread To the Ends of the Array Yes Yes Fire Spread to Target No No Results Table E1 – Summary of Test Parameters and Results 3 NC5756 07CA64050 Issued: 04/25/2008 NOTE This Report was prepared as an account of a test sponsored by and under the direction of the Fire Protection Research Foundation. In no event shall UL be responsible for whatever use or nonuse is made of the information contained in this Report and in no event shall UL, its employees, or its agents incur any obligation or liability for damages arising out of or in connection with the use, or the inability to use, information contained in this Report. 4 NC5756 07CA64050 Issued: 04/25/2008 Table Of Contents INTRODUCTION......................................................................................................................... 7 1 TEST FACILITY.................................................................................................................. 7 2 EQUIPMENT AND INSTRUMENTATION ..................................................................... 8 2.1 2.2 2.3 3 8 8 9 TEST ARRANGEMENT ................................................................................................... 12 3.1 3.2 3.2.1 3.2.2 3.3 3.4 3.4.1 3.4.2 4 BENCH-SCALE INSTRUMENTATION CEILING SPRINKLER SYSTEMS (LARGE -SCALE TESTS ONLY ) LARGE -SCALE INSTRUMENTATION BENCH-SCALE TESTING AND RESULTS LARGE -SCALE TESTING Test 1 Test 2 TEST METHOD – LARGE - SCALE TESTS 1 AND 2 TEST RESULTS Test 1 Test 2 12 15 15 18 21 25 25 25 SUMMARY......................................................................................................................... 46 APPENDIX A ................................................................................................................................ 1 GRAPHICAL PRESENTATION OF HEAT RELEASE RATE DATA FOR BENCH-SCALE TESTING 1 1 1 APPENDIX B ................................................................................................................................ 1 GRAPHICAL PRESENTATION OF TEMPERATURES AND W ATERFLOW - TEST 1 1 1 APPENDIX C ................................................................................................................................ 1 GRAPHICAL PRESENTATION OF TEMPERATURES AND W ATERFLOW - TEST 2 1 1 List of Tables TABLE 1 TABLE 2 TABLE 3 SPRINKLER W ATER SUPPLY PARAMETERS ........................................................................................................ 8 BENCH-SCALE TEST PARAMETERS AND RESULTS.......................................................................................... 12 SUMMARY OF TEST PARAMETERS AND RESULTS........................................................................................... 27 Table Of Figures FIGURE 1 FIGURE 2 FIGURE 3 FIGURE 4 FIGURE 5 FIGURE 6 FIGURE 7 FIGURE 8 FIGURE 9 FIGURE 10 TEST FACILITY ....................................................................................................................................................... 7 NOMINAL K=5.6 PENDENT SPRINKLER.............................................................................................................. 9 SPRINKLER AND INSTRUMENTATION LOCATIONS........................................................................................... 11 BENCH-SCALE TEST A RRANGEMENT – ELEVATION VIEW............................................................................ 13 BENCH-SCALE TEST A RRANGEMENT – PLAN VIEW....................................................................................... 13 BENCH-SCALE TEST A RRANGEMENT ............................................................................................................... 14 PLAN VIEW – TEST 1........................................................................................................................................... 16 PLAN VIEW DETAIL – TEST 1............................................................................................................................. 17 EAST / WEST ELEVATION VIEW – TEST 1........................................................................................................ 18 PLAN VIEW – TEST 2........................................................................................................................................... 19 5 NC5756 07CA64050 FIGURE 11 FIGURE 12 FIGURE 13 FIGURE 14 FIGURE 15 FIGURE 16 FIGURE 17 FIGURE 18 FIGURE 19 FIGURE 20 FIGURE 21 FIGURE 22 FIGURE 23 FIGURE 24 FIGURE 25 FIGURE 26 FIGURE 27 FIGURE 28 FIGURE 29 FIGURE 30 FIGURE 31 FIGURE 32 FIGURE 33 FIGURE 34 FIGURE 35 FIGURE 36 FIGURE 37 FIGURE 38 FIGURE 39 FIGURE 40 FIGURE 41 FIGURE 42 FIGURE 43 Issued: 04/25/2008 PLAN VIEW DETAIL – TEST 2............................................................................................................................. 20 EAST ELEVATION VIEW – TEST 2...................................................................................................................... 21 TEST SET -UP PHOTOS - TEST 1.......................................................................................................................... 22 TEST SET -UP PHOTOS - TEST 1.......................................................................................................................... 23 TEST SET -UP PHOTOS - TEST 2.......................................................................................................................... 24 EXTENT OF FIRE SPREAD – TEST 1 PLAN VIEW .............................................................................................. 28 SPRINKLER OPERATIONS – TEST 1.................................................................................................................... 29 RACK ORIENTATION FOR DAMAGE A SSESSSMENT VIEWS – TEST 1............................................................ 30 DAMAGE – TEST 1, UNIT A................................................................................................................................ 30 DAMAGE - TEST 1, UNIT B................................................................................................................................. 31 DAMAGE - TEST 1, UNIT C................................................................................................................................. 31 DAMAGE – TEST 1, UNIT D................................................................................................................................ 32 DAMAGE - TEST 1, UNIT E................................................................................................................................. 32 DAMAGE - TEST 1, UNIT F ................................................................................................................................. 33 DAMAGE - TEST 1, UNIT G................................................................................................................................. 33 DAMAGE - TEST 1, UNIT H................................................................................................................................. 34 DAMAGE - TEST 1, UNIT I .................................................................................................................................. 34 DAMAGE - TEST 1, UNIT J.................................................................................................................................. 35 POST TEST PHOTOS – TEST 1 ............................................................................................................................. 36 EXTENT OF FIRE SPREAD – TEST 2 PLAN VIEW .............................................................................................. 37 SPRINKLER OPERATIONS – TEST 2.................................................................................................................... 38 RACK ORIENTATION FOR DAMAGE A SSESSSMENT VIEWS – TEST 2............................................................ 39 DAMAGE – TEST 2, UNIT A................................................................................................................................ 39 DAMAGE - TEST 2, UNIT B................................................................................................................................. 40 DAMAGE - TEST 2, UNIT C................................................................................................................................. 40 DAMAGE – TEST 2, UNIT D................................................................................................................................ 41 DAMAGE - TEST 2, UNIT E................................................................................................................................. 41 DAMAGE - TEST 2, UNIT F ................................................................................................................................. 42 DAMAGE - TEST 2, UNIT G................................................................................................................................. 42 DAMAGE - TEST 2, UNIT H................................................................................................................................. 43 DAMAGE - TEST 2, UNIT I .................................................................................................................................. 43 DAMAGE - TEST 2, UNIT J.................................................................................................................................. 44 POST TEST PHOTOS – TEST 2 ............................................................................................................................. 45 6 NC5756 07CA64050 Issued: 04/25/2008 INTRODUCTION This Test Report describes the Special Service Investigation conducted for the Fire Protection Research Foundation to develop fire test data relative to the level of protection provided for a fire scenario involving a compact mobile shelving arrangement of paper in manila folders. 1 TEST FACILITY The fire tests were conducted in Underwriters Laboratories Inc.’s large-scale fire test facility located in Northbrook, Illinois. The large-scale fire test building used for this investigation includes four fire test areas that are used to develop data on the fire growth and fire suppression characteristics of commodities, as well as the fire suppression characteristics of automatic water sprinkler systems. A schematic of the test facility is shown in Figure 1Figure 1. ADD Test Facility Large Scale Fire Test Facility Heat Release Calorimeter & RDD PDPA Test Facility Conditioning Room Warehouse Figure 1 Test Facility The fire tests were conducted in a 120 by 120 by 54- ft. high room fitted with an adjustable height ceiling. The ceiling was positioned 10- ft above the floor. The test room was equipped with an exhaust system including a regenerative thermal oxidizing (RTO) smoke abatement system. The test cell was heated prior to ignition to approximately 70 °F. Ambient temperature outside make-up air at approximately 60,000 cfm was provided through four inlet ducts positioned along the walls of the test facility after first sprinkler operation. Prior to first sprinkler operation, ambient temperature outside make-up air was drawn in through the ducts at approximately 30,000 cfm. The floor of the test facility was smooth, flat and surrounded with a grated drainage trench to insure adequate drainage from the test area. The water runoff from the suppression system drain was collected through a 180,000-gallon water treatment system. 7 NC5756 07CA64050 2 2.1 Issued: 04/25/2008 EQUIPMENT AND INSTRUMENTATION Bench-Scale Instrumentation The instrumentation used in the bench-scale fire testing consisted of the following devices: • • • • • • • • 2.2 Three (3) 1/16- in. diameter, Type K inconel sheathed thermocouples attached to the shelving exterior to obtain shelf temperatures Three(3) 1/16- in. diameter, Type K inconel sheathed thermocouples positioned within the shelving to obtain gas temperatures Two (2) Radiometers Moisture meter to measure the commodity moisture content of the fuel package Weigh-scale in the appropriate range Electronic data acquisition system at a two-second-scan rate to obtain the oxygen consumption, temperature, and heat flux data Video and still cameras to capture and record images of the fire test Stopwatches and timing devices located within the data acquisition system were used to monitor and record significant events during the fire tests Ceiling Sprinkler Systems (large-scale tests only) Thirty-six (36) quick-response standard spray pendent style sprinklers having a 155° F temperature rating and a nominal flow coefficient (K) of 5.6 gpm/psi1/2 were installed on 15-x 15-ft. spacing in a closed head, wet pipe, automatic sprinkler system at the ceiling level. The sprinklers were supplied through a looped piping system consisting of 2 ½- in. diameter branch lines. The sprinklers were positioned with the distance between the deflector and ceiling measured to be 8- in. The water supply to the ceiling sprinklers was controlled to achieve the parameters shown in Table 1. Close- up photos of the sprinklers used in this test are shown in Figure 2. A plan view of the sprinkler and instrumentation layout is shown in Figure 3. Table 1 Sprinkler Location Ceiling Sprinkler Water Supply Parameters Nominal flow per sprinkler (gpm) 22.5 8 Nominal pressure at sprinkler (psig) 16.1 NC5756 07CA64050 Issued: 04/25/2008 Figure 2 2.3 Nominal K=5.6 Pendent Sprinkler Large-Scale Instrumentation The instrumentation used in the testing consisted of the following devices: • Thirty-six (36) 1/16- in. diameter, Type K inconel sheathed thermocouples located below the ceiling adjacent to each sprinkler. • Thirty-two (32) 1/16- in. diameter, Type K inconel sheathed thermocouples located below the ceiling on 3 concentric rings about the center of the ceiling. • 1/16-in. diameter, Type K inconel sheathed thermocouple located 6- in. below the ceiling above the ignition location. • Five 1/16- in. diameter, Type K inconel sheathed thermocouples embedded in a 50.5- in. long steel angle attached to the bottom of the ceiling directly above the fire. • A pressure transducer in a 0-100 psi range will be used to measure the water pressure in the sprinkler system. • A 12-in. magnetic flow meter in the 0-3200 gpm range will be used to measure the water flow rate. • Stopwatches and timing devices located within the data acquisition system will be used to monitor and record significant events during the fire test. • Moisture meter to measure the commodity moisture content of the fuel package. • Video and Infrared cameras will be used to capture and record images of the fire test. • Electronic data acquisition system with a one-second-scan rate to obtain the data generated. 9 NC5756 07CA64050 • • Issued: 04/25/2008 Five 1/16- in. diameter, Type K inconel sheathed thermocouples attached to the shelving to obtain shelf temperatures. Five 1/16- in. diameter, Type K inconel sheathed thermocouples were positioned within the shelving to obtain gas temperatures. In Test 1, thermocouples were located as follows (also see Appendix B): 1. Steel shelf directly above ignition (Unit E – Figure 18) 2. Air temperature directly above ignition (Unit E – Figure 18) 3. Steel upright barrier 1-bay west of ignition (Unit E – Figure 18) 4. Air temperature opposite ignition, across aisle (Unit F – Figure 18) 5. Air temperature in 2nd shelf above ignition (Unit E – Figure 18) 6. Air temperature in top shelf above ignition (Unit E – Figure 18) 7. Air temperature in top shelf 1-bay west of ignition (Unit E – Figure 18) 8. Air temperature in top shelf 1-bay east of ignition (Unit E – Figure 18) 9. Air temperature in top shelf 1-bay south of ignition (Unit D – Figure 18) 10. Air temperature in top shelf 2-bays south of ignition (Unit C – Figure 18) In Test 2, thermocouples were located as follows (also see Appendix C): 1. Air temperature in the 8th level flue space (Unit s A-B – Figure 32) 2. Steel upright barrier at the 8th level (Unit B – Figure 32) 3. Steel upright barrier at the 8th level (Unit C – Figure 32) 4. Air temperature in the 8th level flue space (Units C-D – Figure 32) 5. Steel shelf directly above ignition (Unit E – Figure 32) 6. Steel upright barrier at the 1st level (Unit F – Figure 32) 7. Air temperature in the 8th level flue space (Units E-F – Figure 32) 8. Air temperature in the 8th level flue space (Units G-H – Figure 32) 9. Steel upright barrier at the 1st level (Unit G – Figure 32) 10. Air temperature in the 1st level flue space (Units A-B – Figure 32) 10 NC5756 07CA64050 Issued: 04/25/2008 Figure 3 Sprinkler and Instrumentation Locations 11 NC5756 07CA64050 3 Issued: 04/25/2008 TEST ARRANGEMENT 3.1 Bench-Scale Testing and Results Bench-scale testing was conducted beneath a 500-kW rated product calorimeter in a test room measuring 50- ft. x 15-ft. x 15-ft. (l x w x h) with a 12.75-ft. x 12.75-ft. square-shaped collection hood located centrally in the room approximately 7- ft. above the floor. Collected combustion products are exhausted by way of a 24- in. x 24- in. plenum into an 18- in. diameter exhaust duct for data measurement. Bench-scale testing consisted of a single 36-in x 24-in x 9.75-in sheet metal shelf loaded with varying densities of commodity. A total of six (6) vertical sheet metal dividers approximately 9in. long x 6- in. high were attached to the shelf to evenly space the folders. The shelf enclosure was insulated on the top with a single thickness of Cerawool refractory blanket. The stored commodity consisted of sheet paper in common manila paperboard folders. Stored commodity loading was based on sheet count, folder count, and weight. Ignition was accomplished using a one-quarter standard igniter constructed from a 1.5-in. diameter by 3- in. long cellulosic bundle soaked with two fluid ounces of gasoline and wrapped in a polyethylene bag. Fire tests with a loading density of 100% were conducted twice to confirm baseline weight and folder count, and the loading arrangement ignition location was similar in both tests. Fire tests with a loading density of 70% were conducted twice to gather additional heat release data. In the first 70% loading test, 110 folders were evenly spaced back to back within the 24-in. deep shelf. In the second 70% loading test, the 110 folders were not evenly spaced but were more loosely loaded in the ignition area. With the test commodity samples loaded in the shelf assembly and positioned under the products collector with video and data collection operating, ignition was accomplished and the fire was allowed to burn freely until the fuel was either consumed or no longer sustained combustion. The bench-scale test parameters and results are presented in Table 2. Test Load Density No. (%) Moisture Initial Weight Weight Loss Test Duration Folder Count Content (%) (lbs) (lbs) (min) Peak HRR (kW) 1 100 5.6 169.2 0.5 153 60 1.3 2 70 5.6 118.4 16.6 110 60 16.5 3 85 5.6 143.1 5 128 30 8.9 4 100 5.4 168.6 0.2 153 40 7.4 5 70 5.4 118.3 22.4 110 78 38.4 Note: All folders contained an average of 110 sheets of standard 8.5-in x 11- in plain white paper Table 2 Bench-Scale Test Parameters and Results 12 NC5756 07CA64050 Issued: 04/25/2008 A diagram of the bench-scale she lf mockup and photos of the fire test arrangement are shown in Figures 4, 5 and 6. Figure 4 Figure 5 Bench-Scale Test Arrangement – Elevation View Bench-Scale Test Arrangement – Plan View 13 NC5756 07CA64050 Issued: 04/25/2008 Figure 6 Bench-Scale Test Arrangement 14 NC5756 07CA64050 3.2 Issued: 04/25/2008 Large-Scale Testing The large-scale fire tests utilized both moveable and fixed units. The moveable units were assembled on a carriage rail system which was attached to the test room floor. The individual shelving fixtures in the moveable units were nominally 3- ft wide, 2- ft deep, and 8-ft tall. Vertical transverse sheet metal barriers were provided between each of the five (5) storage bays at 3-ft. intervals. There were eight (8) shelf levels positioned with a nominal vertical spacing of 8, 18.5, 29, 39.5, 50, 60.5, 71, 81.5 and 95-in. from the floor. There were five (5) shelf fixtures in each row with a total length of 15- ft. Based on the results of the bench-scale tests, the project consulting engineers determined that a loading density of 70% would be used for both large-scale tests. This loading density included 56 folders per 12- in. x 36-in. loading bay, with the folders evenly spaced by partial vertical dividers. There was a nominal 2-in. clear space between the top of the folders and the bottom of the next shelf above the folders. 3.2.1 Test 1 For the first large-scale fire test, an open shelving arrangement was used consisting of six compact shelf units. Five of the compact shelf units were moveable. Four of the moveable units were approximately 24-in. deep and one moveable unit was approximately 12- in. deep. The sixth compact shelf unit was fixed and approximately 12- in. deep. The compact shelf configuration was open with a 36- in aisle space provided in the center of the array. A nominal 1in. flue space was maintained between each shelving unit. No longitudinal barriers were provided. The target arrangement consisted of cardboard fixed to upright structures. The paperfaced cardboard was positioned across a 36- in. aisle space on the north, south, east and west sides of the compact shelving array. The cardboard affixed to the target assembly spanned 16-ft. long x 8- ft high. The individual shelving unit bays were nominally 36-in wide, 10.5- in high and 24- in deep. At the center of each 24- in deep bay, a 4.75- in tall sheet metal divider was located as a backing device and vertical divider support. A total of six (6) vertical sheet metal dividers approximately 9-in. long x 6- in. high were attached to each 36- in wide, 10.5- in high and 24-in deep shelf bay to evenly space the folders. A total of three (3) vertical sheet metal dividers approximately 9-in. long x 6- in. high were attached to each 36- in wide, 10.5- in high and 12- in deep shelf bay. The arrangement is shown in Figures 7,8 and 9. Photos of the arrangement are shown in Figures 13 and 14. 15 NC5756 07CA64050 Issued: 04/25/2008 Figure 7 Plan View – Test 1 16 NC5756 07CA64050 Issued: 04/25/2008 Figure 8 Plan View Detail – Test 1 17 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01110802 Main Array from East Project 07CA64050 File NC5756 Figure 9 3.2.2 East / West Elevation View – Test 1 Test 2 For the second large-scale fire test, a closed shelving arrangement was used consisting of five moveable compact shelf units in the main array and one fixed compact unit as a target. Four of the moveable units were approximately 24- in. deep and one unit was approximately 12- in. deep. Full height longitudinal sheet metal barriers were installed in two of the four 24- in deep moveable units. The sixth compact shelf unit was a target which consisted of a 12- in. deep compact shelving unit positioned across a 36-in aisle on the north side, filled to the same capacity of the main shelving array. A nominal 1-in. flue space was maintained between each shelving unit. Cardboard fixed to upright structures was also placed across a 36- in. aisle space on the south, east and west sides of the compact shelving array. The cardboard target assemblies spanned 16- ft. long x 8- ft. high. The individual shelving unit bays were nominally 36-in wide, 10.5- in high and 24- in deep. At the center of each 24- in deep bay, a 4.75- in tall sheet metal divider was located as a backing device and vertical divider support. A total of six (6) vertical sheet metal dividers approximately 9-in. long x 6- in. high were attached to each 36- in wide, 10.5- in high and 24-in deep shelf bay to evenly space the folders. A total of three (3) vertical sheet metal dividers approximately 9-in. long x 6- in. high were attached to each 36- in wide, 10.5- in high and 12- in deep shelf bay. The arrangement is shown in Figures 10, 11 and 12. Photos of the arrangement are shown in Figure 15. 18 NC5756 07CA64050 Issued: 04/25/2008 Figure 10 Plan View – Test 2 19 NC5756 07CA64050 Issued: 04/25/2008 Figure 11 Plan View Detail – Test 2 20 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01180802 Main Array from East Project 07CA64050 File NC5756 Figure 12 3.3 East Elevation View – Test 2 Test Method – Large-Scale Tests 1 and 2 The nominal 8-ft. high storage array was positioned under a 10-ft. ceiling. The distance from the top of the commodity to the sprinkler deflector was 18- in. Thirty-six upright, nominal K=5.6 ceiling sprinklers were installed on a 15 by 15- ft. spacing for this test. The moveable compact mobile shelving array was assembled between four sprinklers such that the ignition location for each of the two tests, at the base of storage, was located between four sprinklers. The ceiling sprinkler system was supplied with water resulting in a nominal sprinkler discharge density of 0.10 gpm/ft 2 . Ignition was accomplished using one standard igniter constructed from a 3- in. diameter by 6-in. long cellulosic bundle soaked with 8 oz. of gasoline and wrapped in a polyethylene bag. The igniter was located on the base of the south side shelf (Rack E in Figures 18 and 32), within a storage folder. The ignition location was centered between four (4) ceiling sprinklers. 21 NC5756 07CA64050 Issued: 04/25/2008 Shelf Setup Carriage Arrangement Carriage Arrangement Shelf Detail Shelf Detail Figure 13 Loading Detail Test Set-Up Photos - Test 1 22 NC5756 07CA64050 Issued: 04/25/2008 Ignitor Figure 14 Final Test Arrangement Test Set-Up Photos - Test 1 23 NC5756 07CA64050 Issued: 04/25/2008 Divider Detail Barrier Detail Shelf Detail Shelf / Carriage Detail Loading Detail Final Test Arrangement Figure 15 Test Set-Up Photos - Test 2 24 NC5756 07CA64050 3.4 3.4.1 Issued: 04/25/2008 Test Results Test 1 The test was conducted for 90 minutes (90:00). A total of eight (13) ceiling sprinklers operated during the 90- minute test period. The first sprinkler activated at thirty-six minutes nine seconds (36:09) after ignition and the last sprinkler operated at eighty-five minutes fifty-eight seconds (85:58) after ignition. A combination photoelectric / ionization type smoke detector was located at the ceiling leve l directly above ignition. The detector activated at 0 minutes 44 seconds (00:44) after ignition. Visible flaming was noted at the top level of storage at approximately ten minutes (10:00) after ignition. Flame travel was noted across the ignition aisle at approximately fifty-our minutes (54:00) after ignition. The fire in Test 1 propagated to the east, west and south ends of the main shelving array. The fire was contained within the main shelving units and did not spread to the adjacent target arrays. The maximum one- minute average steel beam temperature measured above ignition was 902 ºF and the maximum one-minute average gas temperature measured above ignition was 1460 ºF. A plan view of the extent of fire is presented in Figure 16 and sprinkler operation times in Figure 17. The test assembly orientation is shown in Figure 18. Elevation views of the extent of fire spread and damage are shown in Figures 19 through 28. Post-test photos are presented in Figure 29. Tabulated test results are presented in Table 3. Temperature data vs. time charts are presented in Appendix B. 3.4.2 Test 2 The second large-scale fire test was conducted for 82 minutes (82:00). A total of four (4) ceiling sprinklers operated during the 82- minute test period. The first sprinkler activated at eighty-one minutes eleven seconds (81:11) after ignition and the last sprinkler operated at eighty-one minutes fifty-one seconds (81:51) after ignition. A combination photoelectric / ionization type smoke detector was located at the ceiling level directly above ignition. The detector activated at 1 minute 52 seconds (01:52) after ignition. Visible flaming was noted at the top level of storage at approximately five minutes thirty seconds (05:30) after ignition. The fire in Test 2 propagated to the east and west ends of the array, but was generally limited to the area between the full- height longitudinal sheet metal barriers. The fire was contained within the main shelving units and did not spread to the adjacent target arrays. The maximum oneminute average steel beam temperature measured above ignition was 846 ºF and the maximum one- minute average gas temperature measured above ignition was 1560 ºF. 25 NC5756 07CA64050 Issued: 04/25/2008 A plan view of the extent of fire is presented in Figure 30 and sprinkler operation times in Figure 31. The test assembly orientation is shown in Figure 32. Elevation views of the extent of fire spread and damage are shown in Figures 33 through 42. Post-test photos are presented in Figure 43. Tabulated test results are presented in Table 3. Temperature data vs. time charts are presented in Appendix C. 26 NC5756 07CA64050 Issued: 04/25/2008 FIRE TEST DATE Test Code 01/11/2008 01110802 01/18/2008 01180802 Compact Mobile Shelving Compact Mobile Shelving Parameters Storage Type Shelving Array Configuration Open Closed Commodity Type Paper in manila folders with 70% loading density Paper in manila folders with 70% loading density Nominal Storage Height (ft) 8 8 Nominal Ceiling Height (ft) 10 10 Deflector Clearance to Storage (in) 18 18 Aisle Width (in.) 36 36 Shelf Type Solid Steel Solid Steel Longitudinal Barrier None Solid Steel Transverse Barrier Solid Steel Solid Steel Nominal Shelf Depth (in.) 24 24 Ignition Location Beneath Walkway Sprinklers Between 4 Sprinklers Between 4 Sprinklers Ceiling Sprinkler Temperature Rating °F 155 155 Deflector to Ceiling (in) 8 8 Nominal Ceiling Sprinkler Discharge Coefficient K (gpm/psi ½) 5.6 5.6 Nominal Ceiling Sprinkler Discharge Pressure (psi) 16.1 16.1 2 Nominal Ceiling Sprinkler Discharge Density (gpm/ft ) 0.10 0.10 Ceiling Sprinkler Spacing (ft x ft) 15 x 15 15 x 15 Ambient Outdoor Temperature (°F) 35.4 21.7 Length of Test (min:s) 90 82 First Ceiling Sprinkler Operation (min:s) 36:09 81:11 Last Ceiling Sprinkler Operation (min:s) 85:58 81:51 Number of Operated Ceiling Sprinklers 13 4 Peak Gas Temperature at Ceiling Above Ignition °F 1551 1585 Maximum 1 Minute Average Gas Temperature at Ceiling Above Ignition °F 1460 1560 Peak Steel Temperature at Ceiling Above Ignition °F 1063 928 Maximum 1 Minute Average Steel Temperature Above Ignition °F 902 846 Fire Spread Across Aisle Yes No Fire Spread To the Ends of the Array Yes Yes Fire Spread to Target No No Results Table 3 Summary of Test Parameters and Results 27 NC5756 07CA64050 Issued: 04/25/2008 Figure 16 Extent of Fire Spread – Test 1 Plan View 28 NC5756 07CA64050 Issued: 04/25/2008 Figure 17 Sprinkler Operations – Test 1 29 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01110802 Damage Assessment Orientation Project 07CA64050 File NC5756 Figure 18 Rack Orientation for Damage Assesssment Views – Test 1 TEST Code: 01110802 Damage Assessment - Unit A Project 07CA64050 File NC5756 Figure 19 Damage – Test 1, Unit A 30 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01110802 Damage Assessment - Unit B Project 07CA64050 File NC5756 Figure 20 Damage - Test 1, Unit B TEST Code: 01110802 Damage Assessment - Unit C Project 07CA64050 File NC5756 Figure 21 Damage - Test 1, Unit C 31 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01110802 Damage Assessment - Unit D Project 07CA64050 File NC5756 Figure 22 Damage – Test 1, Unit D TEST Code: 01110802 Damage Assessment - Unit E Ignition Aisle Project 07CA64050 File NC5756 Figure 23 Damage - Test 1, Unit E 32 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01110802 Damage Assessment - Unit F Project 07CA64050 File NC5756 Figure 24 Damage - Test 1, Unit F TEST Code: 01110802 Damage Assessment - Unit G Project 07CA64050 File NC5756 Figure 25 Damage - Test 1, Unit G 33 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01110802 Damage Assessment - Unit H Project 07CA64050 File NC5756 Figure 26 Damage - Test 1, Unit H TEST Code: 01110802 Damage Assessment - Unit I Project 07CA64050 File NC5756 Figure 27 Damage - Test 1, Unit I 34 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01110802 Damage Assessment - Unit J Project 07CA64050 File NC5756 Figure 28 Damage - Test 1, Unit J 35 NC5756 07CA64050 Issued: 04/25/2008 Ignition Aisle Aisle Opposite Ignition Aisle “A” Aisle “J” Overhead from NE Figure 29 Overhead from NE Post Test Photos – Test 1 36 NC5756 07CA64050 Issued: 04/25/2008 Figure 30 Extent of Fire Spread – Test 2 Plan View 37 NC5756 07CA64050 Issued: 04/25/2008 Figure 31 Sprinkler Operations – Test 2 38 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01180802 Damage Assessment Orientation Project 07CA64050 File NC5756 Figure 32 Rack Orientation for Damage Assesssment Views – Test 2 TEST Code: 01180802 Damage Assessment - Unit A Project 07CA64050 File NC5756 Figure 33 Damage – Test 2, Unit A 39 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01180802 Damage Assessment - Unit B Project 07CA64050 File NC5756 Figure 34 Damage - Test 2, Unit B TEST Code: 01180802 Damage Assessment - Unit C Project 07CA64050 File NC5756 Figure 35 Damage - Test 2, Unit C 40 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01180802 Damage Assessment - Unit D Project 07CA64050 File NC5756 Figure 36 Damage – Test 2, Unit D TEST Code: 01180802 Damage Assessment - Unit E Ignition Aisle Project 07CA64050 File NC5756 Figure 37 Damage - Test 2, Unit E 41 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01180802 Damage Assessment - Unit F Project 07CA64050 File NC5756 Figure 38 Damage - Test 2, Unit F TEST Code: 01180802 Damage Assessment - Unit G Project 07CA64050 File NC5756 Figure 39 Damage - Test 2, Unit G 42 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01180802 Damage Assessment - Unit H Project 07CA64050 File NC5756 Figure 40 Damage - Test 2, Unit H TEST Code: 01180802 Damage Assessment - Unit I Project 07CA64050 File NC5756 Figure 41 Damage - Test 2, Unit I 43 NC5756 07CA64050 Issued: 04/25/2008 TEST Code: 01180802 Damage Assessment - Unit J Project 07CA64050 File NC5756 Figure 42 Damage - Test 2, Unit J 44 NC5756 07CA64050 Issued: 04/25/2008 Ignition Aisle Aisle Opposite Ignition Aisle A* Aisle H* *Note: Vertical barriers installed between B/C and F/G Aisle C Figure 43 Aisle D Post Test Photos – Test 2 45 NC5756 07CA64050 4 Issued: 04/25/2008 SUMMARY A series of five (5) bench-scale and two (2) large-scale fire tests was conducted to develop data regarding the level of protection provided by nominal K-5.6 (gpm/psi ½) pendent, quick response ceiling sprinklers in protecting an arrangement of paper in standard manila paperboard folders stored in moveable compact mobile shelving units to a nominal height of 8- ft. Bench-scale testing consisted of a single 36-in x 24-in x 9.75-in sheet metal shelf loaded with varying densities of commodity. A total of five bench-scale fire tests were conducted on a load cell beneath a calorimeter where total heat release rate was measured over the course of each test. Based on the results of these bench-scale tests, the project consulting engineers determined that a 70% loading density by volume would be used as the basis for both large-scale fire tests. The large-scale tests were conducted under a 10-ft high ceiling with 155°F pendent ceiling sprinklers installed on 15 by 15- ft. spacing with the deflectors positioned 8- in. below the ceiling. The first large-scale test was conducted with the moveable compact mobile shelving units in the open position, including a 3- ft. center aisle. The second large-scale test was conducted with the moveable compact mobile shelving units in the closed position, and included full- height longitudinal sheet metal barriers in two of the four 24- in deep moveable shelving units. For both large-scale tests, the ceiling sprinkler system was supplied with water resulting in a nominal sprinkler discharge density of 0.10 gpm/ft2 . The ignition location for each of the two tests was located between four sprinklers. The large-scale fire tests utilized both moveable and fixed compact shelf units. The individual shelving fixtures in the moving units of the systems were nominally 3- ft wide, 2- ft deep, and 8- ft tall. Vertical transverse sheet metal barriers were provided between each of the five (5) storage bays at 3- ft. intervals. There were eight (8) shelf levels positioned with a nominal vertical spacing of 8, 18.5, 29, 39.5, 50, 60.5, 71, 81.5 and 95-in. from the floor. There were five (5) shelf fixtures in each row with a total length of 15- ft. For the first large-scale fire test, an open shelving arrangement was used consisting of six compact shelf units. Five of the compact shelf units were moveable. Four of the moveable units were approximately 24-in. deep and one moveable unit was approximately 12- in. deep. The sixth compact shelf unit was fixed and approximately 12- in. deep. The compact shelf configuration was open with a 36-in aisle space provided in the center of the array. No longitudinal barriers were provided. The target arrangement consisted of cardboard fixed to upright structures. The paper- faced cardboard was positioned across a 36- in. aisle space on the north, south, east and west sides of the compact shelving array. The cardboard affixed to the target assembly spanned 16- ft. long x 8- ft high. The first large-scale fire test was conducted for 90 minutes (90:00) as requested by the project consulting engineers. A total of thirteen (13) ceiling sprinklers operated during the 90-minute test period. The first sprinkler activated at thirty-six minutes nine seconds (36:09) after ignition and the last sprinkler operated at eighty- five minutes fifty-eight seconds (85:58) after ignition. 46 NC5756 07CA64050 Issued: 04/25/2008 The fire in Test 1 propagated to the east, west and south ends of the main shelving array. However, the fire was contained within the main shelving units and did not spread to the adjacent targets. The maximum one-minute average steel beam temperature measured above ignition was 902 ºF and the maximum one- minute average gas temperature measured above ignition was 1460 ºF. For the second large-scale fire test, a closed shelving arrangement was used consisting of five moveable compact shelf units in the main array and one fixed compact unit as a target. Four of the moveable units were approximately 24- in. deep and one unit was approximately 12- in. deep. Full height longitudinal sheet metal barriers were installed in two of the four 24- in deep moveable units. The sixth compact shelf unit was a target which consisted of a 12- in. deep compact shelving unit positioned across a 36-in aisle on the north side, filled to the same capacity of the main shelving array. Cardboard fixed to upright structures were also placed across a 36- in. aisle space on the south, east and west sides of the compact shelving array. The cardboard target assemblies spanned 16- ft. long x 8- ft. high. The second large-scale fire test was conducted for 82 minutes (82:00) as requested by the project consulting engineers. A total of four (4) ceiling sprinklers operated during the 82-minute test period. The first sprinkler activated at eighty-one minutes eleven seconds (81:11) after ignition and the last sprinkler operated at eighty-one minutes fifty-one seconds (81:51) after ignition. The fire in Test 2 propagated to the east and west ends of the array, but was generally limited to the area between the full- height longitudinal sheet metal barriers. The fire was contained within the main shelving units and did not spread to the adjacent target arrays. The maximum oneminute average steel beam temperature measured above ignition was 846 ºF and the maximum one- minute average gas temperature measured above ignition was 1560 ºF. A summary of the parameters and results is presented in Table 3. Report by: Reviewed by: Christopher Gates Project Engineer 3019INBK Tel: 847-664-2618 Fax: 847-313-2618 Michael McCormick Staff Engineering Associate 3019INBK Tel: 847-664-3303 Fax: 847-313-3303 47 NC5756 07CA64050 Appendix A – Graphs APPENDIX A Graphical Presentation of Heat Release Rate Data for Bench-Scale Testing A-1 Issued 04/25/2008 NC5756 07CA64050 Appendix A – Graphs Issued 04/25/2008 Fire Protection Research Foundation HRR Comparison Bench Scale Loading Density Data 40 35 30 Loading Density HRR (kW) 25 70% Test 1 70% Test 2 20 85% Test 1 100% Test 1 15 100% Test 2 10 5 0 0 10 20 30 40 50 60 Time (min) Fire Protection Research Foundation HRR Comparison Bench Scale Loading Density Data 40 35 30 HRR (kW) 25 Loading Density 70% - Test 1 20 70% - Test 2 15 10 5 0 0 10 20 30 40 Time (m) A-2 50 60 70 80 NC5756 07CA64050 Appendix B – Graphs Issued 04/25/2008 APPENDIX B Graphical Presentation of Temperatures and Waterflow - Test 1 B-1 NC5756 07CA64050 Appendix B – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Sprinklers 1-6 90 80 70 60 (Deg C) Spk.001 Spk.002 Spk.003 Spk.004 Spk.005 50 40 Spk.006 30 20 10 0 0 10 20 30 40 50 60 70 80 90 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Sprinklers 7-12 90 80 70 60 (Deg C) Spk.007 Spk.008 Spk.009 Spk.010 Spk.011 50 40 Spk.012 30 20 10 0 0 10 20 30 40 50 Time (Min) B-2 60 70 80 90 NC5756 07CA64050 Appendix B – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Sprinklers 13-18 90 80 70 60 (Deg C) Spk.013 Spk.014 Spk.015 Spk.016 Spk.017 50 40 Spk.018 30 20 10 0 0 10 20 30 40 50 60 70 80 90 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Sprinklers 19-24 90 80 70 60 (Deg C) Spk.019 Spk.020 Spk.021 Spk.022 Spk.023 50 40 Spk.024 30 20 10 0 0 10 20 30 40 50 Time (Min) B-3 60 70 80 90 NC5756 07CA64050 Appendix B – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Sprinklers 24-30 90 80 70 60 (Deg C) Spk.025 Spk.026 Spk.027 Spk.028 Spk.029 50 40 Spk.030 30 20 10 0 0 10 20 30 40 50 60 70 80 90 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Sprinklers 31-36 90 80 70 60 (Deg C) Spk.031 Spk.032 Spk.033 Spk.034 Spk.035 50 40 Spk.036 30 20 10 0 0 10 20 30 40 50 Time (Min) B-4 60 70 80 90 NC5756 07CA64050 Appendix B – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Sprinkler System Flow 600 500 GPM 400 Flow 300 200 100 0 30 40 50 60 70 80 90 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Ceiling Steel Temperature above Ignition Note: TC #1 malfunctioned 700 600 500 400 (Deg C) AMB02 AMB03 AMB04 AMB05 300 200 100 0 0 10 20 30 40 50 Time (Min) B-5 60 70 80 90 NC5756 07CA64050 Appendix B – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Air Temperature above Ignition 900 800 700 (Deg C) 600 6-in. TC 500 12-in. TC 18-in. TC 400 300 200 100 0 0 10 20 30 40 50 60 70 80 90 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Ignition Aisle Shelf Steel Temperature 900 800 700 Steel temp 1-bay west of Ignition 600 (Deg C) Steel temp above Ignition 500 TC1 TC3 400 300 200 100 0 0 10 20 30 40 50 Time (Min) B-6 60 70 80 90 NC5756 07CA64050 Appendix B – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 1 Ignition Aisle Air Temperature 900 Air above Ignition - 8th Level 800 Air above Ignition 700 600 (Deg C) TC2 500 TC4 Shelf 2 above Ignition TC5 400 TC6 TC8 300 200 1 Bay East of Ignition - 8th Level 100 Air temp opposite Ignition (across aisle) 0 0 10 20 30 40 50 60 70 80 90 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 1 South Aisle Air Temperature 800 700 600 8th Level Air Temp (C) (Deg C) 500 400 TC9 300 200 100 0 0 10 20 30 40 50 Time (Min) B-7 60 70 80 90 NC5756 07CA64050 Appendix C – Graphs Issued 04/25/2008 APPENDIX C Graphical Presentation of Temperatures and Waterflow - Test 2 C-1 NC5756 07CA64050 Appendix C – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Sprinklers 1-6 90 80 70 60 (Deg C) Spk.001 Spk.002 Spk.003 Spk.004 Spk.005 50 40 Spk.006 30 20 10 0 0 10 20 30 40 50 60 70 80 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Sprinklers 7-12 90 80 70 60 (Deg C) Spk.007 Spk.008 Spk.009 Spk.010 Spk.011 50 40 Spk.012 30 20 10 0 0 10 20 30 40 Time (Min) C-2 50 60 70 80 NC5756 07CA64050 Appendix C – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Sprinklers 13-18 90 80 70 60 (Deg C) Spk.013 Spk.014 Spk.015 Spk.016 Spk.017 50 40 Spk.018 30 20 10 0 0 10 20 30 40 50 60 70 80 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Sprinklers 19-24 90 80 70 60 (Deg C) Spk.019 Spk.020 Spk.021 Spk.022 Spk.023 50 40 Spk.024 30 20 10 0 0 10 20 30 40 Time (Min) C-3 50 60 70 80 NC5756 07CA64050 Appendix C – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Sprinklers 25-30 90 80 70 60 (Deg C) Spk.025 Spk.026 Spk.027 Spk.028 Spk.029 50 40 Spk.030 30 20 10 0 0 10 20 30 40 50 60 70 80 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Sprinklers 31-36 90 80 70 60 (Deg C) Spk.031 Spk.032 Spk.033 Spk.034 Spk.035 50 40 Spk.036 30 20 10 0 0 10 20 30 40 Time (Min) C-4 50 60 70 80 NC5756 07CA64050 Appendix C – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Sprinkler System Flow 250 240 230 220 GPM 210 200 6" Flow 190 180 170 160 150 0 10 20 30 40 50 60 70 80 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Ceiling Steel Temperature above Ignition Note: TC #1 malfunctioned 600 500 (Deg C) 400 AMB02 AMB03 AMB04 AMB05 300 200 100 0 0 10 20 30 40 Time (Min) C-5 50 60 70 80 NC5756 07CA64050 Appendix C – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Air Above Ignition 900 800 700 (Deg C) 600 500 6-in. TC 12-in. TC 18-in. TC 400 300 200 100 0 0 10 20 30 40 50 60 70 80 Time (Min) Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Storage Array Steel Temperatures NOTE: TC2 destroyed - 8th Level steel (B); TC6 destroyed - 1st Level steel (F) 1000 Steel above Ignition 900 800 700 (Deg C) 600 TC3 1st Level steel (G) TC5 500 TC9 400 300 200 8th Level steel (C) 100 0 0 10 20 30 40 Time (Min) C-6 50 60 70 80 NC5756 07CA64050 Appendix C – Graphs Issued 04/25/2008 Fire Protection Research Foundation Compact Mobile Shelving - Test 2 Storage Array Air Temperatures 800 1st Level (C-D) 700 600 8th Level (E-F) 8th Level (C-D) TC1 (Deg C) 500 TC4 TC7 400 TC8 TC10 300 200 8th Level (G-H) 100 8th Level (A-B) 0 0 10 20 30 40 Time (Min) C-7 50 60 70 80
© Copyright 2025 Paperzz