Fire Safety in the 2012 BC Building Code Zachary May Building and Safety Standards Branch FPOABC | Kelowna | May 2013 Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads Confederation WWII National Codes • Early codes • Current codes National Code Development Process National Code change Model national Codes adopted as regulation in each province Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads 2012 BC Building Code Old ‘Exit’ Sign ISO 7010 Designed by Yukio Ota in 1982 ISO 7010 2010 National Building Code 2012 BC Building Code Becoming global standard Hong Kong Becoming global standard Stockholm Subway 2012 BC Building Code Worth clarifying: • Internally Illuminated exit signs must have a powered light – photo luminescent does not comply • Photo luminescent signs may be used, but they must have a powered light to illuminate •Applies to renovations as well as new construction Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads Limiting Distance St Lawrence Burns Edmonton, Alberta NRC Testing Facility New changes in the 2012 BCBC •Some significant changes for buildings within 2.0m of property line • Requirement for windows and projections • New requirements for containment & egress • Clarification of terms and intent of Code Table 3.2.3.1.A. Maximum Concentrated Area of Unprotected Openings Forming Part of Sentence 3.2.3.1.(5) Limiting Distance, m Max Area of Individual Unprotected Openings, m² 1.2 0.35 1.5 0.78 2.0 1.88 3.2.3.1.(6) SPACING OF UNPROTECTED OPENINGS WITHIN 2 M The spacing between individual unprotected openings that serve a single room or space shall not be less than: a) 2 m horizontally of another unprotected opening that is on the same exposing building face and serves the single room or space, or b) 2 m vertically of another unprotected opening that serves the single room or space, or another room or space on the same storey. 3.2.3.1.(7) SINGLE ROOM OR SPACE "single room or space" shall mean a) two or more adjacent spaces having a full-height separating wall extending less than 1.5 m from the interior face of the exterior wall, or b) two or more stacked spaces that are on the same storey. 3.2.3.1.(7) SINGLE ROOM OR SPACE 7) For the purpose of Sentence (6), "single room or space" shall mean a) two or more adjacent spaces having a full-height separating wall extending less than 1.5 m from the interior face of the exterior wall, or b) two or more stacked spaces that are on the same storey. 3.2.3.6 COMBUSTIBLE PROJECTIONS •3.2.3.6.(2) L.D. < .45 M - no soffits allowed •3.2.3.6.(3) L.D. > .45 M - soffits not allowed to extend within .45 M of P/L. •3.2.3.6.(4) .45M < L.D < 1.2 M – soffits fire blocked •3.2.3.6.(5) where soffits fire blocked for (4) and building is combustible, additional finishes allowed on surface of fire block materials. Plenum Wires and Cables 3.1.4.3. , 3.1.5.18. and 3.6.4.3. •Plenum - concealed space often used for return air systems •Cables in plenums in combustible buildings must be FT4 •Cables in plenums in noncombustible buildings must be FT6 •Unless in totally enclosed noncombustible raceway These requirements do not apply to cables used for transmissions of signals for fire alarm, security, radio and television. BC Fire Code 2.4.1.1.(5) requires removal of abandoned cables. 3.1.9.3. 3) Single conductor metal sheathed cables with combustible jacketting that are more than 25 mm in overall diameter are permitted to penetrate a fire separation required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2., provided the cables are not grouped and are spaced a minimum of 300 mm apart. Fire Stops and Fire Blocks New definition for “Fire Block” and “Fire Stop” Block is to resist fire spread between concealed spaces. Fire block means a material, component or system that restricts the spread of fire within a concealed space or from a concealed space to an adjacent space. Stop is used for filling gaps around penetrations in fire separations. Fire stop means a system consisting of a material, component and means of support used to fill gaps between fire separations or between fire separations and other assemblies, or used around items that wholly or partially penetrate a fire separation. 3.1.9.1. 3) Penetrations of a fire separation in conformance with Sentence 3.6.4.2.(2) shall be sealed by a fire stop that, when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems,” has an FT rating not less than the fire-resistance rating for the fire separation of the assembly. 4) Sprinklers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fireresistance rating without having to meet the fire stop requirements of Sentences (1) to (3), provided the annular space created by the penetration of a fire sprinkler is covered by a metal escutcheon plate in accordance with NFPA 13, “Installation of Sprinkler Systems.” 5) Unless specifically designed with a fire stop, fire dampers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the fire stop requirements of Sentences (1) to (3), provided the fire damper is installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives.” 3.3.1.5. 1) [described non-residential buildings that require two egress doors, in case one becomes blocked.] 2) Where 2 egress doorways are required by Sentence (1), they shall be placed at a distance from one another equal to or greater than one third of the maximum overall diagonal dimension of the area to be served, measured as the shortest distance that smoke would have to travel between the nearest required egress doors. Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads Limiting Distance and 10 Minute Response Time Changes to measurement of limiting distance and 10 minute response time • Meant to clarify intent of previous Code • Always existed in Part 3 • Now included in Part 9 • Construction requirement only • Only requires information from fire departments 3.2.3.1. [2006 BCBC] 3.2.3.1. [2012 BCBC] Changes to measurement of limiting distance and 10 minute response time • Meant to clarify intent of previous Code • Always existed in Part 3 • Now included in Part 9 • Construction requirement only • Only requires information from fire departments 2006 BCBC 2012 BCBC 2012 BCBC Changes to measurement of limiting distance and 10 minute response time • Meant to clarify intent of previous Code • Always existed in Part 3 • Now included in Part 9 • Construction requirement only • Only requires information from fire departments Changes to measurement of limiting distance and 10 minute response time • Inform building based on actual conditions • Similar to climate tables • Provides a clarity • Delayed implementation • Exists in other jurisdictions • Regulates construction, does not halt construction Changes to measurement of limiting distance and 10 minute response time • Meant to clarify intent of previous Code • Always existed in Part 3 • Now included in Part 9 • Construction requirement only • Only requires information from fire departments Where does this requirement come from? NRC Testing Facility NRC Fire Research • St. Lawrence Burns • High-Intensity Residential Fires Working Group • Testing • Fire Modeling • Based on time required for fire to reach flashover How do we determine “10 minute” response? A-3.2.3.1.(8) Intervention Time and Limiting Distance The total time from the start of a fire until fire suppression by the fire department depends on the time taken for a series of actions. Sentence 3.2.3.1.(8) is only concerned with the time from receipt of notification of a fire by the fire department until the arrival of the first fire department vehicle at the building. It specifies a 10min time limit which must be met in more than 90% of the calls to the building served by the fire department. This reliability level and provision for flexibility is essentially consistent with NFPA 1710, “Organization and Deployment of Fire Suppression Operations, Emergency Medical Operations, and Special Operations to the Public by Career Fire Departments.” Clause 4.1.2.1 of NFPA 1710 establishes “time objectives” for fire incidents as follows: 1 min (60 s) for turn-out of responders after receipt of notification of a fire, and 4 min (240 s) or less for arrival of the first arriving engine company at a fire suppression incident and/or 8 min (480 s) or less for the deployment of a full first alarm assignment at a fire suppression incident. The standard requires that the fire department establish a “performance objective” of not less than 90% for each response time objective. This reliability level is referred to in NFPA 1710 as a “performance objective.” Note: Appendix is for commentary only, and is not an enforceable part of the Building Code. Still confused? Ask the Building and Safety Standards Branch: “Response time” is measured from the fire department’s receipt of the emergency call until a properly manned fire truck arrives at the building. The response time should be “turn out” time plus travel time to the site of the proposed building. The Building & Safety Standards Branch plays no role in determining fire department response times. Calculations/judgments can only be based on what the present circumstances are, or perhaps those that are known to occur in the near future. The Code does not require the application of any NFPA standard for fire department performance objectives. NFPA 1710 is referenced in the Building Code’s appendix to provide context to the 90% reliability objective identified in the Code. We recommend actual times be used in calculation of response times and not performance objectives identified in NFPA standards. As mentioned above, response times will be unique from community to community dependent upon real life circumstances. What happens if we do not have 10 minute response in our community? 11 Minute fire department response means: • Greater limiting distance • Fewer windows on exposing building face • More likely to have sprinklers • Generally safer construction to mitigate the risk Changes to measurement of limiting distance and 10 minute response time • Meant to clarify intent of previous Code • Always existed in Part 3 • Now included in Part 9 • Construction requirement only • Only requires information from fire departments Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads Why? Where? When? What? How? Why the new requirements? 1. clarify application of code before: seismic was considered implicitly Why the new requirements? 1. clarify application of code 2. reduce risks http://www.earthquakesafety.com/_photo/earthquake-damaged-house.jpg now explicit and detailed requirements Where are the new requirements? Subsection 9.23.13. … and several in existing subsections in Section 9.23. structural design requirements in Part 9 seismic 9.4.1.1. Part 9 good engineerin g practice 9.23.13 . gravity Part 4 Canadian Wood Council “Engineering Guide for Wood Frame Construction” Part 9 9.23.13.4. to 9.23.13.7. + other cross-referenced provisions good engineerin g practice Part 4 Forces traditional constructi on 9.23.13.4. to 9.23.13.7. Part 4 good engineerin g practice Wind * Extreme optional 9.23.13. 3. High 9.23.13. 2. Low -Moderate q50 = 1.2 * Sa(0.2) = 1.2 * optional optional q50 = 0.8 Sa(0.2) = 0.7 optional optional optional 9.23.13. 1. Earthquake * different limits for heavy construction Sa(0.2) values can be found in Div. B Appendix C. 1.2 0.7 Earthqua ke Sa(0.2) Victoria , Langford, Sidney, Tofino, Ucluelet Cloverdale, Langley, Ladner, White Rock Ladysmith, Duncan, Crofton, Bamfield Sooke, Youbou, Surrey, Richmond New Westminster, Nanaimo, Port Renfrew Abbotsford, Jordan River, Haney Vancouver, Burnaby, Mission City West Vancouver, North Vancouver Sechelt, Tahsis, Parksville Qualicum Beach, Gold River Port Alberni, Chilliwack, Alberni, Kent Squamish Sandspit Agassiz, Whistler, Powell River Courtney, Sandspit Kelowna q50 0.8 Wind What are the new requirements? • concept • basic requirements • exceptions Concept figure from HPO Illustrated Guide for New Key Components: braced wall band braced wall panel Braced W all Band an imaginary continuous straight band extending vertically and horizontally through the building or part of the building, within which braced wall panels are constructed Braced W all P anel a portion of a wood-frame wall where bracing, sheathing, cladding or interior finish is designed and installed to provide the required resistance to lateral loads due to wind or earthquake figure from HPO Illustrated Guide for figure from HPO Illustrated Guide for main goal: strong stable overall frame fundamental requirement: adequate amount of properly constructed walls how to locate and size walls how to build and fasten walls Basic Requirements 9.23.13.4. Braced Wall Bands shall be full storey height be ≤ 1.2m wide lap at both ends with another BWB be aligned with BWBs on storeys above & below be spaced, at maximum, 10.6 m 7.6m where 1.0 ≤ Sa(0.2) ≤ 1.2 figure from HPO Illustrated Guide for Seismic Design of Houses Max 10.6 m (7.6 m) Max 1.2 m Max 1.2 m Max 10.6 m (7.6 m) Max 1.2 m 9.23.13.5. Braced Wall Panels shall be located within BWBs extend from top of supporting footing, slab or subfloor to underside of floor ceiling or roof framing above conform to max max min min limits on spacing distance from end of BWB length total length > 600 < 6 400 < 2 400 > 750 < 10 600 (or 7 600) Minimum Total Length of Braced Wall Panels in a braced wall band for light construction 25% 25% 25% 25% 25% 40% 75 % 1 storey 2 storeys 3 storeys 9.23.13.6. Materials in Braced Wall Panels Compliance panel-type cladding OR sheathing OR interior finish 9.27 Table 9.23.3.4. plywood, OSB, waferboard, or diagonal lumber sheathing 9.23.16. Table 9.23.13.6. fasteners 9.23.3.5 panel-type 9.29. (plywood, hardboard, OSB) (gypsum board) Table 9.23.13.6. Exceptions 9.23.13.5.( 3) porches & sun rooms • • • • ≤ 3.5m projection 1:2 plan dimensions no floor above integral with main roof or fastened to wall BWPs not required attached garages • • • • ≤ ≥ ≥ ≤ 7.6m between front and back 50% of back wall is BWPs 25% of side walls is BWPs 1 floor above 9.23.13.5.(4) and (5) BWPs not required in front setbacks setbacks 9.23.13.7.(1), (2), (3) additional requirements for adjacent interior braced wall band sheathed floor and roof at setback additional fastening in perpendicular walls figure from HPO Illustrated Guide for heavy construction heavy construction Forces traditional constructi on Extreme 9.23.13.4. to 9.23.13.7. Part 4 good engineerin g practice optional 9.23.13. 3. High 9.23.13. 2. Low -Moderate 9.23.13. 1. Sa(0.2) = 1.1 optional optional Sa(0.2) = 0.7 optional optional optional heavy construction 1.1 0.7 Earthqua ke Sa(0.2) Victoria , Langford, Sidney, Tofino, Ucluelet Cloverdale, Langley, Ladner, White Rock Ladysmith, Duncan, Crofton, Bamfield Sooke, Youbou, Surrey, Richmond New Westminster, Nanaimo, Port Renfrew Abbotsford, Jordan River, Haney Vancouver, Burnaby, Mission City West Vancouver, North Vancouver Sechelt, Tahsis, Parksville Qualicum Beach, Gold River Port Alberni, Chilliwack, Alberni, Kent Squamish Sandspit Agassiz, Whistler, Powell River Courtney, Sandspit Kelowna q50 0.8 Wind Minimum Total Length of Braced Wall Panels in a braced wall band 25% Light Construction 25% 25% 25% 25% 40% 75 % 1 storey Heavy Construction 2 storeys 25% 25% 40% 75 % 3 storeys impact on design
© Copyright 2026 Paperzz